Configuring the RFT9739 Field-Mount Transmitter for Commercial Trade
Introduction
Securing the transmitter configuration
These instructions explain how to configure a Version 3 field-mount RFT9739 transmitter for use in custody transfer and other commercial trade applications.
For commercial trade applications, the transmitter has security switches and an optional lockout clamp.
• Security switches enable the user to write-protect all configuration and calibration parameters and/or disable flowmeter zeroing and resetting of totalizers.
• The lockout clamp prevents access to the transmitter's wiring terminals and electronics module.
Before securing the transmitter configuration or installing the lockout clamp, make sure the transmitter has been properly installed and the flowmeter has been zeroed, according to the appropriate sections in the instruction manual that is shipped with the transmitter.
A Version 3 field-mount RFT9739 has three security switches.
• To access switches, unscre w the cov er fro m the base of th e transm itter , then unlatch the hinged cover of the electronics module.
Figure 1 illustrates the switches, which are labeled SECURE 1, SECURE 2, and SECURE 3.
Figure 1. Switches
Switches 1 through 10 at left are shown in the OFF position.
Security modes
Table 1. Security modes
Switches 1, 2, and 3 enable the user to disable flowmeter zeroing, disable resetting of totalizers, and write-protect all configuration and calibration parameters.
Switch settings enable any of eight possible security modes. Different modes determine which functions are disabled and whether configuration and calibration parameters are write-protected. The following functions can be disabled:
• Flowmeter zeroing using digital communications
• Flowmeter zeroing using the zero button and, if the transmitter has a display, the Scroll and Reset knobs
• Totalizer reset, with flow, using digital communications
• Totalizer reset, with flow, using the Scroll and Reset knobs, if the transmitter has a display
• Totalizer control, with zero flow, using digital communications
• Totalizer control, with zero flow, using the Scroll and Reset knobs, if the transmitter has a display
Table 1 lists the parameters that are write-protected and functions that are disabled for each security mode. Security modes 1 through 7 are entered immediately when switches 1 through 3 are set.
For information about security mode 8, see page 3.
Switch settings
Switch 1 Switch 2 Switch 3
Function/ parameter
Flowmeter zeroing
Totalize r control, no flow
Totalize r control, with flow
Configuration and calibration parameters
(1)
Changing the settings of switches 1, 2, and 3 does not immediately implement security m ode 8. For more information about
security mode 8, see page 3.
Performed with
Zero but t on or Reset knob
HART or Modbus
Scroll and Reset knobs
HART or Modbus
Scroll and Reset knobs
HART or Modbus
Mode
1
OFF OFF OFF
Mode
1
Mode
2
OFF OFF
ON
Mode
2
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Mode
3
OFF
ON
OFF
Mode
3
Disabled Disabled Disabled Disabled
Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled
Write-
protected
Mode
4
OFF
ON ON
Mode
4
Write-
protected
Mode
5
ON OFF OFF
Mode
5
Write-
protected
Mode
6
ON
OFF
ON
Mode
6
Write-
protected
Mode
7
ON ON
OFF
Mode
7
Write-
protected
protected
Mode
(1)
8
ON ON ON
Mode
8
Write-
2