MGE UPS Systems EX 7RT, EX 11RT, EX 5RT User Manual

Page 1
EX 5RT / EX 7RT/ EX 11RT System
Installation and User Manual
86-86000-00 A01
www.mgeups.com
Page 2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains important instructions for MGE UPS SYSTEMS, INC. products that must
be followed during operation and maintenance of the equipment.
WARNING Opening enclosures expose hazardous voltages. Always refer service to
ATTENTION L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous toujours
que le service ne soit fait que par des personnes qualifiees.
WARNUNG! Das öffnen der Gehäuse legen gefährliche Spannungen bloss. Service sollte immer
nur von qualifizierten Personal durchgeführt werden.
WARNING As standards, specifications, and designs are subject to change, please ask for con-
firmation of the information given in this publication.
ATTENTION Comme les normes, spécifications et produits peuvent changer, veuillez demander
confirmation des informations contenues dans cette publication.
WARNUNG! Normen, Spezifizierungen und Pläne unterliegen Anderungen. Bitte verlangen Sie
eine Bestätigung über alle Informationen, die in dieser Ausgabe gemacht wurden.
NOT E This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC rules. These limits are designed to pro­vide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user's own expense.
Certification Standards
IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability
FCC rules and regulations of Part 15, Subpart J, Class A
UL listed under 1778, Standards for Uninterruptible Power Supply Equipment
IEC 61000-4-2 (ESD) : level4.
IEC 61000-4-3 (Radiated field) : level 3.
IEC 61000-4-4 (EFT) : level4.
IEC 61000-4-5 (Fast transients) : level4.
IEEE-C6241 Category B (ring wave).
IEC 61000-4-6 (electromagnetic field).
IEC 61000-4-8 (conducted magnetic field).
EX 5/7/11 RT System
Important Safety Information and Standardsii 86-86000-00 A01
Page 3
Installation and User Manual
Safety of Persons
The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC power source.
The UPS must be properly grounded.
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed:
- Never burn the battery (risk of explosion).
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
- Comply with all applicable regulations for the disposal of the battery.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.
- Do not lay tools or metal parts on top of batteries.
Product Safety
A protection circuit breaker must be installed upstream and be easily accessible..
The UPS can be disconnected from the AC power source by opening the input circuit breaker.
UPS must be connected to a nearby power source that is easily accessible.
Never block the ventilation grates of the UPS.
The UPS must be installed in a controlled environment.
Special Precautions
The UPS connection instructions and operation described in the manual must be followed in the indicated order.
Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the UPS.
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
How to use this manual and Symbol Usage
This manual is designed for ease of use and easy location of information.
Typographical conventions use “< >” angle brackets in procedures to denote a prompt for User action:
For example:
1. After the selections are complete, click on the <Save> button.
This manual uses four icon symbols with text to convey important information and tips.
WARNING Indicates information provided to protect the user and service personnel against safety
hazards and/or possible equipment damage.
CAUTION Indicates information provided to protect the user and service personnel against possible
equipment damage.
IMPORTANT Indicates information provided as an operating instruction, or as an operating tip.
NOTE Indicates information provided as an operating tip or an equipment feature.
Safety of Persons iii86-86000-00 A01
Page 4
EX 5/7/11 RT System
CAUTION: Record all serial numbers!
CAUTION: Record All Serial Numbers!
RECORD ALL SERIAL NUMBERS FOR EX 5/7/11 RT AND ACCESSORIES.
THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.
KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL
NUMBERS IF SERVICE IS REQUIRED!
EX 5RT System EX 7RT System EX 11RT System
Power Module SERIAL NUMBER: ___________________________________________________
Battery Module SERIAL NUMBER: ____________________________________________________
Transformer SERIAL NUMBER: ______________________________________________________
ADDITIONAL MODULES SERIAL NUMBERS:
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
iv 86-86000-00 A01
Page 5
Installation and User Manual
v86-86000-00 A01
EX 5/7/11 RT System
Installation and User Manual
Revision History
EX 5RT / EX 7RT / EX 11RT System
Installation and User Manual
86-86000-00
Revision: A00 Initial Release 07/2004
Copyright © 2004 MGE UPS SYSTEMS, INC. All rights reserved. Printed in U.S.A.
MGE UPS SYSTEMS, INC.
1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636
For Service Call:
1 (800) 438-7373
Page 6
(This page left blank intentionally)
EX 5/7/11 RT System
vi
86-86000-00 A01
Page 7
Contents
Contents
c i86-86000-00 A01
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . .ii
Certification Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
Safety of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
How to use this manual and Symbol Usage . . . . . . . . . . . . . . . . . . . .iii
CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . . .iv
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
Section 1 Introduction
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1
1.1 System Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1.2 Standard Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1.2.1 Tower Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1.2.2 Rack Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5
1.3 Rear Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
1.3.1 Power Module EX 5/7/11 RT . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
1.3.2 Battery Module EXB 5/7/11 RT With Emergency
Power Off (EPO) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
1.3.3 EX RT Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
1.4 Display and Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
1.5 Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8
1.5.1 Power Module Rail Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8
1.5.2 Battery/ Transformer/CLA Module Rail Kit . . . . . . . . . . . . . . . . . .1 — 8
1.5.3 Battery Module with Remote Emergency
Power Off (REPO) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9
1.5.4 Battery Extension Cable Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9
1.5.5 Battery Integration Kit with Casters . . . . . . . . . . . . . . . . . . . . . .1 — 10
1.5.6 Input/Output Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10
1.5.7 Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 11
1.5.8 CLA Module (Long backup time charger) . . . . . . . . . . . . . . . .1 — 12
Page 8
EX 5/7/11 RT System
Contentsc ii 86-86000-00 A01
Section 2 Setup and Installation
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
2.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
2.1 Unpacking and Parts Check . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
2.2 Contents of EX 5/7/11 RT System . . . . . . . . . . . . . . . . . . . . . . .2 — 2
2.3 Installation in Tower Configuration . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
2.4 Installation in Rack Mounting Configuration . . . . . . . . . . . . . . . .2 — 5
2.4.1 Adjustment of Front Panel Logo and control panel for
Rack Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5
2.5 Prepare Battery Module for Rack Mounting . . . . . . . . . . . . . . . .2 — 6
2.6 Power or Battery Module Rack Mounting . . . . . . . . . . . . . . . . . .2 — 7
2.6.1 Rear Support Brackets Installation . . . . . . . . . . . . . . . . . . . . . . .2 — 8
2.6.2 Input/Output Box Bracket System Installation . . . . . . . . . . . . . . .2 — 8
2.7 Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 9
2.7.1 Connecting the RS232 Communication Port . . . . . . . . . . . . . . .2 — 9
2.7.2 Connecting the Dry (Relay) Contact Communication Port . . . .2 — 10
2.7.3 Installation of Optional Network Management Card . . . . . . . .2 — 10
2.7.4 Remote Emergency Power Off (REPO) Communication Port .2 — 12
2.8 Connecting the Input and Output Power Cables to the
Input/Output Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 13
2.8.1 Flexible Cordage and Conduit Installations . . . . . . . . . . . . . . .2 — 13
2.8.2 System Connections with Common Normal and
Bypass AC Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 15
2.8.3 Connecting EX RT Transformer . . . . . . . . . . . . . . . . . . . . . . . .2 — 16
2.8.4 System Connections with Separate Normal and
Bypass AC Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 17
2.8.5 System Connections as Frequency Converter
(without Bypass AC Source) . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 18
2.9 Connection of Battery Module, EXB . . . . . . . . . . . . . . . . . . . . .2 — 19
2.10 Connection of CLA Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 20
Section 3 Operation
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
3.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1
3.1 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1
3.2 UPS Personalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2
3.2.1 Accessing personalization with front panel buttons . . . . . . . . . .3 — 2
3.2.2 Accessing personalization through external software . . . . . . . . .3 — 4
3.2.3 Final startup sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4
3.3 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
3.3.1 Normal (double conversion) Mode . . . . . . . . . . . . . . . . . . . . . . .3 — 5
3.3.2 ECO Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
3.4 Operation on battery power . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7
3.4.1 Transfer to Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7
3.5 Return of Normal AC source . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8
3.6 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8
Page 9
Installation and User Manual
Section 4 Maintenance
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
4.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
4.1 Information Technology (IT) Network and Industrial
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
4.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2
4.3 Hot Swapping the Power Module . . . . . . . . . . . . . . . . . . . . . . . .4 — 4
4.4 Re-connecting the power module . . . . . . . . . . . . . . . . . . . . . . . .4 — 5
4.5 Hot Swapping the Battery Module . . . . . . . . . . . . . . . . . . . . . . . .4 — 6
4.5.1 Disconnecting the Battery Module . . . . . . . . . . . . . . . . . . . . . . .4 — 6
4.5.2 Re-connecting the Battery Module . . . . . . . . . . . . . . . . . . . . . . .4 — 6
Section 5 Appendix
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
5.0 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1
5.1 System Input/Output Power Ratings . . . . . . . . . . . . . . . . . . . . . .5 — 1
5.2 System Overload Characteristics . . . . . . . . . . . . . . . . . . . . . . . .5 — 1
5.3 System Backup Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1
5.4 System Short Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
5.5 Accessories Electrical Characteristics . . . . . . . . . . . . . . . . . . . . .5 — 2
5.6 Heat Rejection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
5.7 Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
MGE Warranty & Propriety Rights
MGE Warranty Proprietary Rights Statement
Warranty and Product Registration
User Information Product information Warranty Extension (Warranty+) not available on products
Technical Support and Field Service
MGE Service and Repair Who to Contact Scheduling Field Service Engineer Support Return for Repair (RMA)
Glossary G — 1
Reorder Form RO — 1
Contents c iii86-86000-00 A01
Page 10
Figures
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1: Tower Configurations with Power Module, Battery Module,
and optional Transformer Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1-2: Rack Configurations with Power Module, Battery Module, and
Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5
1-3: Rear panel of the Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
1-4: Rear Panel of the Battery Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
1-5: Rear Panel of the optional Transformer Module. (PN 86003) . . . . . . . . .1 — 7
1-6: View of typical control panel interface. . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
1-7: Power Module Rack Mounting Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8
1-8: Telescopic rails for the Battery/Transformer/CLA module
Rack mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8
1-9: Typical back-up time with multiple EXB’s at full load. . . . . . . . . . . . . . . . .1 — 9
1-10: Typical Battery Integration kit with casters setup. . . . . . . . . . . . . . . . . .1 — 10
1-11: Typical Transformer Module contents and connections. . . . . . . . . . . . .1 — 11
1-12: Connection for CLA Module and EX 5/7/11 RT. . . . . . . . . . . . . . . . . . .1 — 12
2-1: Contents of Standard HV EX 5RT (PN 86050)
/ EX 7RT (PN 86070) / EX 11RT (PN 86110) System. . . . . . . . . . . . . .2 — 3
2-2: Tower Configuration of Standard System and Optional
Transformer Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
2-3: Typical orientation of the logo and control panel.
(Power Module shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5
2-4: Accessing Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 6
2-6: Rack mounting of the power module onto the rails. . . . . . . . . . . . . . . . .2 — 7
2-7a: Rear Support Brackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8
2-7b: Input/Output Box Bracket System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8
2-8: RS232 Communication Cable Connection. . . . . . . . . . . . . . . . . . . . . . . .2 — 9
2-9: Relay Pin Connections for Communication Port. . . . . . . . . . . . . . . . . .2 — 10
2-10: Communication Card Slot with SNMP/Web Network
Management Card installed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 10
2-10a: Activation of remote power off function using a contact
normally open switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 12
2-10b: Activation of remote power off function using a contact
normally closed switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 12
2-12a: Step 1 & 2; Typical plastic and metal coupling installations. . . . . . . . . .2 — 13
2-12b: Step 3; Typical Straight Metal Conduit installation. . . . . . . . . . . . . . . .2 — 14
2-12c: I/O Box Terminal Block Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 14
2-13: Normal AC Input and Output Cables installation. . . . . . . . . . . . . . . . . .2 — 15
2-14: View of EX RT transformer connected downstream for
120/208/240 Vac outputs (shown with one EXB). . . . . . . . . . . . . . . . . .2 — 16
2-15: Normal AC Input, Bypass AC, and Output Cables Installation. . . . . . .2 — 17
2-16: Accessing Terminal Blocks for Input and Output power cables. . . . . . .2 — 18
2-17: Rear view of battery module cable connections. . . . . . . . . . . . . . . . . .2 — 19
2-18: Rear view of CLA module cable battery and AC input connections. . .2 — 20
EX 5/7/11 RT System
Contentsc iv 86-86000-00 A01
Page 11
Installation and User Manual
Figures (continued)
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
3-1: Initial Startup Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1
3-2: Control Panel with scroll up and down buttons. . . . . . . . . . . . . . . . . . . .3 — 2
3-3: Configuration used to provide full redundancy (2N) to critical loads. . . .3 — 3
3-4: Normal (double conversion) mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
3-5: ECO mode display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
3-6: Transfer, Threshold and End of backup time. . . . . . . . . . . . . . . . . . . . . .3 — 7
3-7: Shutdown display, circuit breaker, and AC source switch. . . . . . . . . . . .3 — 8
4-1: Disconnecting the power module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 4
4-2: Reconnect the power module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 5
4-3: Rear view of the battery module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 6
5-1: Power supplied as a function of input voltage (left), and
Permissible UPS overloads as a function of time (right). . . . . . . . . . . . . .5— 1
Tables
table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1: EX RT Model Descriptions and Contents . . . . . . . . . . . . . . . . . . . . . . . .1 — 2
2: Optional Accessories (See section 1.5 for description) . . . . . . . . . . . . .1 — 3
3: Power Module Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
4: Battery Module Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
5: Battery backup time chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 12
3-1: Local Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 3
3-2: Output features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 3
3-3: ON/OFF features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4
3-4: Battery features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4
4-1: Network and Industrial Modes of Operation. . . . . . . . . . . . . . . . . . . . . . .4 — 1
4-2: Troubleshooting not requiring MGE after-sales support. . . . . . . . . . . . . .4 — 2
4-3: Troubleshooting requiring MGE after-sales support. . . . . . . . . . . . . . . . .4 — 3
5-1: EX 5/7/11 RT Input and Output Characteristics. . . . . . . . . . . . . . . . . . . .5 — 1
5-2: Back-up Time ( in minutes). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1
5-3: Battery Recharge time to recover 90% of the rated backup time
after discharge at full load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
5-4: Full load heat rejection in BTU’s/hr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
Contents c v86-86000-00 A01
Page 12
(This page left blank intentionally)
EX 5/7/11 RT System
c vi
86-86000-00 A01
Page 13
Introduction
1.0 Scope
Thank you for selecting an MGE UPS SYSTEMS, INC. (MGE) product to protect your electrical equipment.
The product you selected is a part of the EX RT series. The EX RT series is a family of Uninterruptible Power Supply (UPS) designed to provide safe, and reliable AC power backup for sensitive electrical equipment. To discover the entire range of MGE products, we invite you to visit our website at www.mgeups.com or contact your representative at (800) 523-0142.
This manual describes the installation and operation of standard HV EX 5/7/11RT systems within the EX RT product family. For a complete description of the EX RT product family and its available options, please refer to the tables below:
1 Introduction
Introduction is a general description of system configurations of the EX 5/7/11 RT, and its mechanical ,electrical characteristics. Additionally there is an optional accessories section with important information on MGE products that will enhance the performance of the EX 5/7/11RT. Please contact your MGE representative for detailed information on these options.
2 Setup and Installation
Setup and Installation guides the user through tools and equipment required for connecting the EX 5/7/11 RT and battery installation or replacement. Included are assembly instructions, power cable connections with wire diagrams for configuring the product to hardware specifications.
3 Operation
Operation describes the EX 5/7/11RT system characteristics of indicators and controls, modes and specifications. The user procedures include performing software programming that will maintain optimal performance.
4 Maintenance
Maintenance includes a troubleshooting guide of symptoms and possible solutions, hot swapping the power module, battery module, and testing scenarios.
5 Appendix
Electrical and Mechanical specifications for the EX 5/7/11 RT.
A Glossary provides definitions of abbreviations and terms used in this manual.
1 — 186-86000-00 A01 Introduction
Page 14
Table 1: EX RT Model Descriptions and Contents
System Description Contents
Model Part Power Module Battery Module Transformer Power Module Battery Module SNMP/Web
Number 86055 86075 86115 86079 86119 Module Rail Kit 86001 Rail Kit 86002 Network
(120/208/240Vac) Mgt. Card
86003 66074
5kVA 86050 X X HV EX 5RT
5kVA 86052 X X X X X HV EX 5RT Network Pack
5kVA 86050-01 X X X LV EX 5RT
5kVA 86052-01 X X X X X (x2) X LV EX 5RT Network Pack
7kVA 86070 X X HV EX 7RT
7kVA 86072 X X X X X HV EX 7RT Network Pack
7kVA 86070-01 X X X LV EX 7RT
7kVA 86072-01 X X X X X (x2) X LV EX 7RT Network Pack
11kVA 86110 X X HV EX 11RT
11kVA 86112 X X X X X HV EX 11RT Network Pack
11kVA 86110-01 X X X LV EX 11RT
11kVA 86112-01 X X X X X (x2) X LV EX 11RT
Network Pack
EX 5/7/11 RT System
Introduction1 — 2 86-86000-00 A01
Page 15
Installation and User Manual
Table 2: Optional Accessories (See section 1.5 for description)
Part Number Description
86001 Rail Kit for Power Module EX 5/7/11 RT
86002 Rail Kit for Battery/Transformer/CLA Module
86005 Battery Integration Kit with Casters
86006 Battery Extension Cable Kit
86008 Battery Chassis Empty EXB RT W/EPO
86009 I/O Box 5/7kVA UL/US
86010 I/O Box 11kVA UL/US
86012 I/O Box Bracket System
86013 Rear Bracket Supports
Introduction 1 — 386-86000-00 A01
Page 16
1.1 System Electrical Characteristics
Table 3: Power Module Ratings
Part Number 86055 86075 86115
Apparent Power, kVA 5 7 10@ 200/208/250 VAC Output
11@ 220/230/240 VAC Output
Active Power, kW 4 4.9 8@ 200/208/250 VAC Output
7.3@ 220/230/240 VAC Output
Input Current, A 25/24/23/ 35/34/32 50/48/50/48/46/40
22/21/20 31/30/28
Input Voltage, VAC 200/208/220/ 200/208/220/ 200/208/220/230/240/250
230/240/250 230/240/250
Output Current, A 25/24/23/ 35/34/32 50/48/50/48/46/40
22/21/20 31/30/28
Output Voltage, VAC 200/208/220/ 200/208/220/ 200/208/220/230/240/250
230/240/250 230/240/250
CAUTION Power Module is factory configured at 208Vac, 60 Hz input and output.
Input and Output of the UPS must always be the same.
Table 4: Battery Module Ratings
Part Number 86079 86119
Battery Type 12VDC/7Ah 12VDC/9Ah
Battery Output Voltage 240VDC 240VDC
1.2 Standard Configurations
The EX 5/7/11 RT systems can be set up in tower and rack configurations.
1.2.1 Tower Configuration
Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.
EX 5/7/11 RT System
Introduction1 — 4 86-86000-00 A01
Standard Configuration Configuration with Transformer
POWER MODULE (EX 5/7/11 RT)
BATTERY MODULE (EXB 5/7/11 RT)
X
E
T
R
1
1
X
E
N O
F F
O
m co . s p
u e
g m . w
w w
T
R
B
m o c . s p
u e
g m . w
w w
EX RT Transformer
BATTERY MODULE
T
R
1
1
X
E
r
e
m
r
o
f
s
n
ra
T
T
R
X
E
F F O
eu
g m . w
w w
m o c
. ps u ge
m . w w
w
POWER MODULE
T
R
B
X
E
N O
m o
c . s p
u
ge m . w
w w
m o
c . s p
Page 17
Installation and User Manual
1.2.2 Rack Configuration
Figure 1-2: Rack Configurations with Power Module, Battery Module, and Transformer Module.
Introduction 1 — 586-86000-00 A01
Model Dimensions Weights
EX 5RT/7RT (3U) 5.16” x 17.49” x 25” 49.6 lbs (22.5 kg)
(131 x 444 x 635mm)
EX 11RT (3U) 5.16” x 17.49” x 25” 60.6 lbs (27.6 kg)
(131 x 444 x 635mm)
EXB 5 RT/ 7 RT (3U) 5.16” x 17.49” x 25” 142 lbs (64.5 kg)
(131 x 444 x 635mm)
EXB 11RT (3U) 5.16” x 17.49” x 25” 151 lbs (68.5 kg)
(131 x 444 x 635mm)
EX RT (3U) 5.16” x 17.49” x 25” 173 lbs (78.5 kg) Transformer (131 x 444 x 635mm)
Standard Configuration Configuration with Transformer
POWER MODULE (EX 5/7/11 RT)
former
Trans
EX RT
m o
c s. p
u e
g m .
w w w
T
EX 11 R
F F O
RT
XB
E
BATTERY MODULE (EXB 5/7/11 RT)
m o
c . s
p u
e g m
.
w w w
m o
c . s
p u
e g m
.
w w w
N
O
EX RT Transformer
POWER MODULE (EX 5/7/11 RT)
BATTERY MODULE (EXB 5/7/11 RT)
Page 18
1.3 Rear Panels
1.3.1 Power Module EX 5/7/11 RT
EX 5RT Power Module part number 86055 EX 7RT Power Module part number 86075 EX 11RT Power Module part number 86115
Figure 1-3: Rear panel of the Power Module.
1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function
Figure 1-4: Rear Panel of the Battery Module.
EX 5/7/11 RT System
Introduction1 — 6 86-86000-00 A01
Connectors for automatic detection of additional battery module(s) (to the UPS or to other battery modules).
Battery power connectors (to the UPS or to other battery modules).
Battery Circuit Breaker with Remote Emergency Power Off (REPO) shunt trip.
EXB 5RT with EPO part number 86079
EXB 7RT with EPO part number 86079
EXB 11RT with EPO part number 86119
14
13
12
Slot for optional communication cards.
Communication port by relays (Dry contacts).
Remote Emergency Power Off communication port (REPO).
Connectors for automatic detection of battery module(s).
RS232 communication port.
Battery/CLA module power connector.
Manual Bypass switch.
Normal AC source circuit breaker.
Knockout for entry of AC Output conduit.
Knockout for entry of Normal AC source conduit.
Knockout for entry of Bypass AC source conduit.
11
10
9
8
7
6
5
4
3
2
1
4
5
9
1
2
3
6
7
10
8
11
12
13
14
Page 19
Installation and User Manual
1.3.3 EX RT Transformer Module
Figure 1-5: Rear Panel of the optional Transformer Module. (PN 86003)
1.4 Display and Control Panel
Figure 1-6: View of typical control panel interface.
Introduction 1 — 786-86000-00 A01
Load
NEMA L
R
Load protected / On-line Operation LED.
Operation on battery LED.
Operation on bypass LED.
Fault LED.
Alphanumeric display.
UPS OFF button.
Function buttons (scroll up / scroll down).
UPS ON button (or function button in personalization mode).
23
2221
20
19
18
17
16
15
3: 1
6-30
Load 4: 4 NEMA 5-15/20R
Load 4 Circuit Breaker
AC Input
Transformer I/O Box
AC Output
Transformer Protect
Breaker
15 16
17 18
Load 2: 4 NEMA 5-15/20R
Load 3 Circuit Breaker
Load 2 Circuit Breaker
Main Output Circuit Breaker
Load 1 Circuit Breaker
Load 1: 1 NEMA L6-30R
E X 1 1 R T
OFF
20 21 22 23
ON
19
Page 20
1.5 Optional Accessories
Optional Accessories describes the options available for upgrades and enhancement of the EX 5/7/11RT system. Detailed installation of the unit is described in following sections.
To ensure a successful installation, all procedures should be followed in their correct sequence. Note that any unauthorized installation may cause damage to the UPS(s) and void the MGE warranty.
1.5.1 Power Module Rail Kit
(Part Number 86001)
This kit is for rack mounting the power module in a 19" enclosure. See section 2.6 for rack installation of power module.
Figure 1-7: Power Module Rack Mounting Kit.
Front mounting brackets.
Rear support brackets, part number
86013.
Telescopic rails, 695 mm to 1015 mm
length (27.36" to 39.96").
Input/Output Box bracket system, part
number 86012.
1.5.2 Battery/ Transformer/CLA Module Rail Kit
(Part number 86002)
This kit is for rack mounting of the battery/step-down transformer/CLA module in 19" enclosure. See section 2.6 for rack installation of power module.
Figure 1-8: Telescopic rails for the Battery/Transformer/CLA module Rack mounting.
Front mounting brackets.
Rear support brackets, part number
86013.
Telescopic rails, 695 mm to 1015 mm
length (27.36" to 39.96").
26
25
24
27
26
25
24
EX 5/7/11 RT System
Introduction1 — 8 86-86000-00 A01
24
25
27
26
24
25
26
Page 21
Installation and User Manual
1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function
(EXB 5/7 RT; PN 86079, EXB 11RT; PN 86119)
Standard HV EX 5/7/11RT system (one Power Module, EX 5/7/11 RT, and one Battery Module, EXB 5/7/11RT) offers a standard backup time of 5 to 12 minutes at full load.
To increase backup time, it is possible to connect up to 5 additional EXB 5/7/11 RT modules to the EX 5/7/11 RT module. See section 2.10 for connections between Power Module (EX 5/7/11 RT) and Battery Module (EXB 5/7/11 RT)
Figure 1-9: Typical back-up time with multiple EXB’s at full load.
See Appendix for additional Back-up time information.
1.5.4 Battery Extension Cable Kit
( 6 ft / 1.8 m, Part number 86006)
This extended battery cable kit will be used instead of the standard battery cable when battery modules (EXBs) are distant from each other (located in two different enclosures, for instance).
The battery extension cable kit includes a 6 ft long, straight connector battery power cable and a 6 ft. long battery detection cable.
Introduction 1 — 986-86000-00 A01
Opti
Standard
HV EX 5/7/11RT system
EX 5/7/11RT EXB 5/7/11RT
EXB 5 RT EXB 7 RT EXB 7 RT
+++
EXB 11 RT
5 kVA :
7 kVA :
11 kVA:
12 min 7 min
5 min
EXB 5 RT
/
30 min 55 min 20 min
14 min
/
EXB 11 RT
32 min
22 min
onal
Configurations
EXB 5 RT EXB 7 RT
/
EXB 11 RT
75 min 98 min 118 min 45 min
30 min
EXB 5 RT EXB 7 RT
+ +
/
EXB 11 RT
57 min
42 min
EXB 5 RT EXB 7 RT
/
EXB 11 RT
70 min
53 min
Page 22
1.5.5 Battery Integration Kit with Casters
(Part number 86005)
Battery Integration Kit is a cart, designed to hold up to 8 modules. It has swivel wheels with brakes, leveling feet, seismic floor mount panels, plates to lock modules and hardware included. Modules not included.
Figure 1-10: Typical Battery Integration kit with casters setup.
1.5.6 Input/Output Box
Shipped with ferrules for stranded wire application.
EX 5/7/11 RT System
Introduction1 — 10 86-86000-00 A01
TRANSFORMER MODULE (optional)
POWER MODULE
(Modules Not Included In Kit)
FF
O O
BATTERY MODULES (up to 6)
- I/O Box 5/7kVA Part number 86009
- I/O Box 11kVA Part number 86010
Page 23
Installation and User Manual
1.5.7 Transformer Module
This module provides isolated 120/208/240Vac output.
Figure 1-12: Typical Transformer Module contents and connections.
1 — 1186-86000-00 A01 Introduction
EX RT Transformer Module Contents
Transformer User Manual
r
rme o f
s n a
r
T
T
R
X
E
Tower Stand Expanders
Stabilizer Bracket
(4 screws included)
m o
.c
s p u
e
g m .
www
BATTERY MODULE EXB RT
POWER MODULE EX 5/7/11 RT
AC NORMAL
INPUT
TRANSFORMER MODULE EX RT
STEP-DOWN
TRANSFORMER
OUTPUT TO LOAD
Page 24
1.5.8 CLA Module (Long backup time charger)
(Part number 86004)
Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX 5/7/11RT via the CLA module.
IMPORTANT The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.
Figure 1-12: Connection for CLA Module and EX 5/7/11 RT.
Table 5: Battery backup time chart.
Battery Backup Time Recommended Batteries
EX 5RT EX 7RT EX 11RT
2 hours 50 Ah 65 Ah 100 Ah
4 hours 100 Ah 130 Ah 200 Ah
8 hours 200 Ah 200 Ah 400 Ah
Total battery voltage : 240 VDC (20 x 12VDC, one string).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization section 3.2.
EX 5/7/11 RT System
Introduction1 — 12 86-86000-00 A01
CLA Module Contents
Utility
AC Source
(cable not included)
~
(see section 2.10 for cable
connection information)
R
X
E
r o
sf
n
ra
T
T
m co .
s p
u e g m .
w w w
r e
m
CLA
Stabilizer Bracket
(4 screws included)
EX 5RT / EX 7RT / EX 11RT
(cable not included)
Tower Stand ExpandersCLA Documentation
Battery Power Cable
Battery Detection Cable
Typical High Power Battery Cabinet
(not included)
0A
5
Page 25
Setup and Installation
2.0 Scope
Installation guides the user through tools and equipment required for making input/output power and communica­tion cable connections, and battery installation and replacement. It provides assembly instructions, power cable connections with wire diagrams for configuring the product to hardware specifications.
2.1 Unpacking and Parts Check
Once the EX 5/7/11RT system has been inspected and received from the shipping courier, the unit should be moved to a position as close to the final installation location as possible. See Figures 2-1on page 2-3.
All Modules are shipped in separate boxes.
Prior to any installation, the following items should be observed upon receipt of the EX 5/7/11 RT.
1. Inspect shipment for any damage prior to receipt. Damage claims should be filed directly with the courier. Replacements for damaged components should be ordered through MGE Customer Support Services at 1-800-438-7373.
2. Remove wrapping and foam corners to verify that the equipment nameplate (located on the rear of the units) details a system that corresponds with the equipment ordered.
2 — 186-86000-00 A01 Installation
Page 26
EX 5/7/11 RT System
2 — 2 86-86000-00 A01
2.2 Contents of EX 5/7/11 RT System
Contents of Power Module: Contents of Battery Module:
EX 5RT /EX 7RT/ EX 11RT. Stabilizer Bracket and hardware.
Two sets of tower stands. EXB 5/7/11 RT.
RS232 communication cable. Tower stand expanders.
Product documentation. Battery Power cable.
Input/Output Box. (With 9 insulated ferrules for Battery/EX RT transformer/CLA
stranded wires.) module rack mounting kit, PN 86002.
(PN 86009 for EX 5/7RT; 86010 for EX 11RT)
Battery detection cable.
Solution-Pac CD. EXB Documentation.
Power Module rack mounting kit, PN 86001 Bezel hex drive.
(optional, but standard with Network Pack version).
SNMP/Web Network Management Card, PN 66074.
(optional, or standard with Network Pack version)
IMPORTANT Packaging must be destroyed according to waste management standards.
Recycling icons are displayed for easy selection.
37
4436
4335
42
4134
4033
3932
3831
2930
Installation
Page 27
Installation and User Manual
Figure 2-1: Contents of Standard HV EX 5RT (PN 86050) / EX 7RT (PN 86070) / EX 11RT (PN 86110) System.
Installation 2 — 386-86000-00 A01
- EX 5RT Power Module Part number 86055
- EX 7RT Power Module Part number 86075
- EX 11RT Power Module Part number 86115
30
T
R
1
1
X
E
31 32
33
(see 1.5.1)
36
Standard only with Network Pack option.
- EX 5RT network Pack Part number 86052-01
- EX 7RT network Pack Part number 86072-01
- EX 11RT network Pack Part number 86112-01
IP= MAC=00E0D8FF855E
1 2 ON
RS232 Download
34
FF
O O
35
- I/O Box 5/7kVA Part number 86009
- I/O Box 11kVA Part number 86010
37
Card Settings
100 10
UPS data
Reset
RS232
ETHERNET
66074
38
T
R
B
X
E
29
- EXB 5RT Battery Module Part number 86079
- EXB 7RT Battery Module Part number 86079
- EXB 11RT Battery Module Part number 86119
39 40 42
41
Standard only with Network Pack version. See 1.5.2.
43
(not to scale)
44
Page 28
2.3 Installation in Tower Configuration
Follow the numerical sequence to assemble tower stands and tower stand expanders, shown in Figure 2-2.
Figure 2-2: Tower Configuration of Standard System and Optional Transformer Module.
EX 5/7/11 RT System
Installation2 — 4 86-86000-00 A01
Tower Configuration with Standard System
5
T
R B X
E
T
R 1 1
X E
N O
F F O
m
o c . s p u
e g m
. w w w
m o c
. s p u e g
m . w w w
Battery Module
Power Module
3
4
4
3
4
4
2
1
2
1
Tower Configuration with Optional Transformer Module
5
T R B
X
E
T R 1
1 X E
N
O
F F O
Battery Modules
Power Module
m
o .c s p u
e g m .
w w w
m o c
. s p u e
g m . w w w
m o c . ps u e g
m . w w
w
Transformer Module
Use the same procedure for tower mounting multiple battery modules, if applicable.
3
4
4
3
4
4
2
1
2
1
Page 29
Installation and User Manual
2.4 Installation in Rack Mounting Configuration
2.4.1 Adjustment of Front Panel Logo and control panel for Rack Orientation.
NOTE If system includes the transformer module, we recommend to mount the battery module
on the bottom, then mount the power module above the battery module and mount the transformer on top for optimum stability.
To prepare the front panel logo and LCD display for rack orientation, of all modules. (including transformer or CLA module, if equipped).
Proceed as follows:
1. Unclip logo plate, and pull the LCD display from front panel.
2. Rotate them 90 degree counter clockwise as shown.
3. Place items back onto the panel.
Figure 2-3: Typical orientation of the logo and control panel. (Power Module shown)
Installation 2 — 586-86000-00 A01
E X
O F
1
F
1
R
w w w . m g e u p s. c o m
T
O N
T
R
1
1
X
E
N
O
F F
m o
c . s
p
u e g
m . w
w w
O
FINISHED PANEL (rack orientation)
E X
O F
1
F
1
R
1
1
w w w . m g e u p s . c o m
m o c .
s
p u e
g m .
w
ww
2
3
T
O N
T
R
1
1
X
E
N
O
F F O
2
3
Page 30
2.5 Prepare Battery Module for Rack Mounting
(optional rails required, part number: 86002)
The battery module is very heavy. To ease its rack mounting, we strongly recommend to remove the battery pack from the battery module, as explained below. See Section 1.2.2 for battery module weight.
Proceed as follows:
1. Unscrew the six screws securing front panel using Bezel Hex Driver .
2. Unscrew the brackets securing the battery connectors.
3. Disconnect Battery plugs.
4. Unscrew the brackets securing the battery pack. Remove battery bracket pack covers.
5. Pull the left and right battery packs out and set aside for reinstalling after the battery module cabinet has been rack mounted.
6. Mount battery module cabinet on rack.
7. Re-install the battery pack in reverse order.
Figure 2-4: Accessing Battery Pack.
44
EX 5/7/11 RT System
Installation2 — 6 86-86000-00 A01
3
2
2
m o c . s
p u e
g m . w
w w
T
R
B
X
E
3
4
4
x 6
1
1
1
44
(not to scale)
5
Page 31
Installation and User Manual
2.6 Power or Battery Module Rack Mounting
(optional rack mounting kits required, part number: 86001 and 86002)
The rails and necessary mounting hardware are supplied by MGE UPS SYSTEMS, INC.
Proceed as follows:
1. Attach both front mounting ear brackets to power module or battery module with supplied screws. (For this step, it is possible to adjust the position of both front mounting ears.)
2. Attach rails together and secure with wing nuts, and finger tighten.
3. Attach both rails to rear and front of rack chassis with supplied screws (as shown).
4. Use caution when sliding unit into rack mount, secure unit to rack with supplied screws. (For this step, it is possible to adjust the position of both front mounting brackets.)
Figure 2-6: Rack mounting of the power module onto the rails.
26
24
Installation 2 — 786-86000-00 A01
3
3
3
3
1
2
4
1
4
Page 32
2.6.1 Rear Support Brackets Installation
(Part number 86013, included with rack mounting kits, part numbers: 86001 and 86002)
These brackets prevent the power module from moving when the entire rack enclosure is moved.
Proceed as follows:
1. Attach the brackets to the I/O Box and power module.
2. Secure brackets to rails.
Figure 2-7a: Rear Support Brackets.
2.6.2 Input/Output Box Bracket System Installation
(Part number 86012 included with power module rack mounting kit, part numbers: 86001)
This bracket system keeps the I/O Box stationary while hot swapping the power module. It will then be easier to slide the replacement module into the connectors of the I/O Box.
NOTE: The rear support brackets must be removed prior to
installing I/O Box bracket system.
1. Secure small bracket to larger bracket from the underside .
2 & 3. Secure large bracket (with supplied screws) to rails at the rear of module.
4. Secure small attached bracket (with supplied screws) to the I/O Box.
Figure 2-7b: Input/Output Box Bracket System.
27
27
25
EX 5/7/11 RT System
Installation2 — 8 86-86000-00 A01
1
1
2
2
1
2
3
3
4
4
F F O
Page 33
Installation and User Manual
2.7 Communication Ports
EX 5/7/11RT provides 3 communication methods that can be used simultaneously:
The COM port provides RS232 communications using MGE Serial HID UPS Transfer (SHUT)protocol.
This COM Port is compatible with Personal Solution Pac (PSP) to shutdown one computer. Personal Solution Pac is included in the Solution Pac CD-Rom. For Network Management or multiple computer shutdowns an optional network card must be purchased.
The Dry Contact Port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly
AS400) and more.
The slot is compatible with any MGE UPS SYSTEMS, INC. communication card (check www.mgeups.com
web site for the complete list of compatible cards)
2.7.1 Connecting the RS232 Communication Port
1. Connect the RS 232 communications cable to the serial port on the computer.
2. Connect the other end of the communications cable to the RS 232 communications port on the EX 5/7/11 RT.
The EX 5/7/11 RT System can now communicate with Personal Solution Pac for power management. UPS config­uration settings are done by Personal Solution Pac for Windows.
Figure 2-8: RS232 Communication Cable Connection.
532
32
1
2
5
Installation 2 — 986-86000-00 A01
32
5
Page 34
2.7.2 Connecting the Dry (Relay) Contact Communication Port
The system status is indicated by the connection of common pin (Pin 5) to the appropriate pins. Refer to the pin explanations below for details.
Figure 2-9: Relay Pin Connections for Communication Port.
2.7.3 Installation of Optional Network Management Card
It is not necessary to shut down the UPS to install the optional communications card, except for USB card. Following is a typical installation of the Network Management Card, (PN 66074, standard with the network pack option.)
Proceed as follows:
1. Remove the slot cover secured by two screws.
2. Insert the card into the slot.
3. Secure the card with both screws.
Figure 2-10: Communication Card Slot with SNMP/Web Network Management Card installed.
37
2
EX 5/7/11 RT System
Installation2 — 10 86-86000-00 A01
Pin 1, 2: not used.
Pin 3: Remote Power Off signal (5 to 27 VDC, 10 mA max).
Pin 4: Operation on mains (not on battery). (48VDC, 2A max.)
Pin 5: User common.
Pin 6: Operation on automatic bypass.
Pin 7: Low battery.
Pin 8: Load protected
Pin 9: Operation on battery.
Legend:
NO: contact normally open.
NC: contact normally closed.
NO
common
45
123
6789
NONC NONO
37
Page 35
Installation and User Manual
A wide range of optional cards will allow your UPS to talk to nearly all equipment management systems, making integration faster and easier. All these cards can plug directly into the UPS, saving time and money on your next UPS project. (Meta UPS Card and U-Talk /Basic Acquisition Cards are used exclusively with Multi-slot.)
Dual U-Talk/Basic Card (66060)
Provides two communications ports that may be configured
for serial link or AS/400 type dry contacts.
ModBus Card (66061)
Interface your UPS with a Building Management System.
Dual COM Ports Card (66066)
This card has two independent RS232 communication ports on which it can be connected. One for connecting monitoring software (included) and one for remote control panel UPS control.
USB Card (66067)
Take advantage of the latest and fastest communication
protocol for Microsoft Windows 2000/XP or Mac OSX.
Dual Volt Free Contacts (66068)
The two ports are used to supply UPS status information
Card for AS/400 or one port can be used as a Remote Power Off (REPO) port.
Alarm Relay Card (66069)
Six output relays show UPS status and two status inputs are
used with the Galaxy 3000 UPS.
XML-Web Card (66073)
XML-Web Card acts as a web page for your UPS information.
Used along with XML-Client
TM
software, up to 50 servers or workstations will be protected and can monitor the UPS with a simple web browser. Security is handled with the SSL protocol, used by many websites to safeguard sensitive password information.
SNMP-Web Card (66074)
The SNMP/Web 10/100BT communications card is both an SNMP agent and an HTTP/Web server. Therefore, it enables UPS supervision from any Network Monitoring System using SNMP traps or simply from any web browser (Internet Explorer, Netscape Navigator, etc.) Orderly system shutdown of up to 32 protected servers can be established using MGE’s Solution-Pac/WAN software suite.
Installation 2 — 1186-86000-00 A01
Page 36
2.7.4 Remote Emergency Power Off (REPO) Communication Port
The end user is responsible for the installation of an emergency power off function. Installation must be carried out in compliance with local code regulations.
To shutdown the entire system completely in case of emergency:
Disconnect the AC input to the power module.
Turn off the circuit breaker of the battery module connecting to the power module.
Turn off the circuit breaker of the subsequent battery modules, if applicable.
All these steps above should be performed via a single device.
To simplify the last two steps above, the power module provides an RJ-45 connector on the back panel, called Remote Emergency Power Off (REPO) port. Upon applying a voltage source (5-27VDC, 10mA max.) to pins 2, 4 of this port, the power module will send a signal to trip off the shunt trip on each circuit breaker of all battery modules via the battery detection cable simultaneously. Refer to the diagram below for details.
Figure 2-10a: Activation of remote power off function using a contact normally open switch.
Figure 2-10b: Activation of remote power off function using a contact normally closed switch.
Signal:
Activation voltage: 5VDC to 27VDC
Current 10 mA (max)
NOTE Both AC and DC sources must be present for normal start-up of EX 5/7/11RT
system. If the system is configured for cold start, the AC and DC sources are required for initial start-up only.
3
EX 5/7/11 RT System
Installation2 — 12 86-86000-00 A01
RJ11
3
1
5432
6
RJ11
3
1
5432
6
Page 37
Installation and User Manual
2.8 Connecting the Input and Output Power Cables to the Input/Output Box
WARNING This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connections, check that battery circuit breaker is OFF and that the upstream protection devices (Normal and Bypass AC sources) are open (OFF).
EX 5/7/11 RT UPS always comes from factory with Normal and Bypass AC inputs already connected together, using a shunt.
2.8.1 Flexible Cordage and Conduit Installations
Figure 2-12a: Step 1 & 2; Typical plastic and metal coupling installations.
14
Installation 2 — 1386-86000-00 A01
1. Knockout die stamp circles.
NOTE Terminal cable capacity:
Max. 4 AWG (11kVA), 6 AWG (5/7kVA).
Knockout die stamp circles (on terminal block cover) have two sizes that fit
either plastic or metal
coupling. Plastic coupling is for
flexible cordage
and metal coupling is for solid wires. Knock out appropriate circle for your application.
2. Remove bottom cover plate as shown.
3. Typical plastic strain relief installation:
a) Secure strain relief body onto the
knockout plate.
b) Strip the jacket back to expose the
three wires. Strip the insulation of each wire back 1/2”. Insert the ferrules as shown to each wire.
CAUTION: Always connect the
earth ground wire first.
c) Slide the cordage into the strain relief
and secure the wires into the terminal blocks using the guide printed on bottom of I/O box.
d) Secure the cordage retainer nut.
4. Typical 90° metal conduit installation.
a) Secure strain relief body to knockout
plate as shown.
b) Insert three wires through flexible
conduit and bend 90°.
c) Strip the insulation back 1/2” to
expose solid wire and secure three wires into the terminal block using guide printed on bottom of I/O box.
CAUTION: Always connect the
earth ground wire first.
d) Install strain relief cover using two
screws.
F
F
O
I/O BOX
O
Terminal Block Cover
F F
O
O
2
3. Typical Flexible Cordage Installation
F F
O
O
(a)
NOTE: Place lug ring inside the terminal block cover. Screw coupling into lug ring.
4. Typical 90° Metal Conduit Installation
FF
O
O
(a)
NOTE: Place lug ring inside the terminal block cover. Screw coupling into lug ring.
1
Outer circle is for Plastic strain relief
Inner circle is for Metal strain relief
F F O 0
F F O
(b)
0
(c)
(d)
F F
O
O
(c)
(b)
(d)
Page 38
Figure 2-12b: Step 3; Typical Straight Metal Conduit installation.
Figure 2-12c: I/O Box Terminal Block Diagram.
EX 5/7/11 RT System
Installation2 — 14 86-86000-00 A01
5. Typical straight metal conduit Installation.
a) Secure strain relief onto the
terminal block cover as shown.
b) Insert three wire through flexible
conduit.
c) Strip the insulation of each wire
back 1/2” to expose solid wire.
CAUTION: Always connect the
earth ground wire first.
d) Secure three wires into the terminal
block using guide printed on bottom of I/O box.
e) Twist the conduit onto the coupling
body as shown.
5. Typical Straight Conduit Installation
F F
O
O
(a)
NOTE: Place lug ring inside the terminal block cover. Screw coupling into lug ring.
200/208/220/230/240Vac
Output
Normal AC Source
200/208/220/230/240Vac
F F O O
(d)
(c)
(e)
(b)
Bypass AC Source
200/208/220/230/240Vac
L6 L5 L2 L1 L1 L4 L3
Jumper
Page 39
2.8.2 System Connections with Common Normal and Bypass AC Sources
Figure 2-13: Normal AC Input and Output Cables installation.
NOTE: The power module factory default is for the common normal and bypass
AC source (single Main). AC input connections must be made to L1, L2, and terminals.
Installation and User Manual
Installation 2 — 1586-86000-00 A01
Proceed as follows:
1. Remove the I/O box from EX 5/7/11RT by loosening three screws. Knockout appro­priate circle for your wire style.
CAUTION: Always connect the
earth ground wire first.
1. See section 2.8.1 to install normal AC source and output wires per I/O Box Terminal diagram. Re-install the cover plate under the I/O Box.
2. Install the I/O Box with three screws.
F F O
O
1
2
F F
O
O
66074
Card Settings
data
UPS
ETHERNET
100 10
Reset
ON 1 2
RS232 Download
MAC=00E0D8FF855E
IP=
To Step-Down
Transformer
(if applicable)
Simplified Connection Diagram
UPSTREAM CIRCUIT
AC INPUT
BREAKER
(NOT SUPPLIED)
Bypass AC Normal AC
8
Load to Transformer Module
Page 40
2.8.3 Connecting EX RT Transformer
(Part number 86003)
This module is to provide isolated 120/208/240 VAC outputs to the protected loads.
Figure 2-14: View of EX RT transformer connected downstream for 120/208/240 Vac outputs (shown with one EXB).
EX 5/7/11 RT System
Installation2 — 16 86-86000-00 A01
POWER MODULE EX 5/7/11 RT
BATTERY MODULE EXB 5/7/11 RT
TRANSFORMER MODULE EX RT
AC NORMAL
INPUT
STEP-DOWN
TRANSFORMER
OUTPUT TO LOAD
Terminal Block Transformer Module Connection diagram (located on bottom of Transformer I/O Box)
L3 L2 L1 Lb Ld N Lc La
208Vac
240Vac
AC Input
120Vac
208Vac
240Vac
AC Output
Simplified Connection Diagram
Bypass AC
Normal AC
AC INPUT
UPSTREAM CIRCUIT BREAKER
(NOT SUPPLIED)
120Vac
Follow connection diagram for appropriate input/output voltages.
Terminal Block capability : AWG 4 solid or stranded wire.
Transformer Module
8
To Loa d
Page 41
Installation and User Manual
2.8.4 System Connections with Separate Normal and Bypass AC Sources
CAUTION: This installation requires 2 AC input source with Line, Neutral plus Ground,
(200-240VAC). Neutral points are connected together inside the UPS.
Figure 2-15: Normal AC Input, Bypass AC, and Output Cables Installation.
Installation 2 — 1786-86000-00 A01
Proceed as follows:
1. Remove the cover plate under the I/O Box. Loosen the terminal blocks L1 and L3, and remove the jumper.
CAUTION: Always connect the
earth ground wire first.
2. See section 2.8.1 and I/O Box terminal diagram for installation of Normal AC Input, Bypass AC source, and Output cable with different wire style.
3. Reinstall the cover plate under the I/O Box with four screws.
4. Secure the I/O Box to the power module using three screws.
See section 2.8.3 for connecting EX RT Transformer, if applicable.
L1
L3
F F O
O
1
F F O
O
2
Bypass
3
Output
Normal
4
F
F
O
O
66074
Card Settings
data
UPS
ETHERNET
100 10
Reset
ON
1 2
RS232 Download
MAC=00E0D8FF855E
IP=
To Step-Down
Transformer
(if applicable)
Page 42
2.8.5 System Connections as Frequency Converter (without Bypass AC Source)
Figure 2-16: Accessing Terminal Blocks for Input and Output power cables.
EX 5/7/11 RT System
Installation2 — 18 86-86000-00 A01
CAUTION: Always connect the
earth ground wire first.
1. Remove the cover plate under the I/O Box.
Remove the jumper connecting L3 and L1.
CAUTION: Do not connect anything to the
Bypass AC terminal block.
2. Refer to section 2.8.1 to install normal AC source and output wires per I/O Box Terminal diagram. Re­install the cover plate under the I/O Box.
3. Secure the I/O Box to power module with three screws.
See section 2.8.3 for connecting EX RT Transformer, if necessary.
F F O
O
1
F
OF
O
2
3
F
OF O
66074
Card Settings
data
UPS
ETHERNET
100 10
Reset
ON
1 2
RS232 Download
MAC=00E0D8FF855E
IP=
To Step-Down
Transformer
Page 43
Installation and User Manual
2.9 Connection of Battery Module, EXB
1. Check that the battery circuit breaker is OFF (“0”) position.
2. Connect the battery power cable to the connectors and of the power and battery modules.
3. Connect the battery detection cable between connectors and of the power and battery modules.
Figure 2-17: Rear view of battery module cable connections.
124
42
13640
14
Installation 2 — 1986-86000-00 A01
12
4
42
40
13
14
6
Page 44
2.10 Connection of CLA Module
1. Connect the battery power cable and battery detection cable (provided with the CLA module) between the power module and the CLA module.
2. Connect the DC Input of the CLA to high power battery cabinet.
DC Input Cable cross-section (not provided): maximum 4 AWG solid or stranded wire.
3. Connect the AC input cable of the CLA module to the utility AC input:
AC input cable cross-section (not provided): maximum 16 AWG solid or stranded wires.
Figure 2-18: Rear view of CLA module cable battery and AC input connections.
4240
EX 5/7/11 RT System
Installation2 — 20 86-86000-00 A01
Connection Diagram (inside CLA Module)
42
- +
DC INPUT
240Vdc
N L
(L2) (L1)
AC INPUT
156-280Vac
40
To High
Power Battery
Cabinet
Utility AC Source
Page 45
Operation
3.0 Scope
Operation describes EX 5/7/11RT system characteristics of indicators and controls, modes and specifications and theory of operating the EX 5/7/11RT. The user procedures include performing software programming that will maintain smooth performance. Refer to Figure 1.6 for descriptions of circled numbers.
3.1 Initial Startup
1. Check that the manual bypass switch is on Normal position.
2. Set the normal AC source circuit breaker to the ON position.
3. Set the battery circuit breaker to the ON position.
The load is powered via the bypass AC source, but not protected by the UPS.
Batteries are recharging, an eight-hour recharge period is necessary to get full backup time.
LED is ON.
Figure 3-1: Initial Startup Display.
17
14
8
7
3 — 186-86000-00 A01 Operation
OFF
17
ON
Page 46
3.2 UPS Personalization
IMPORTANT If specific settings are required, it is recommended to
enter the UPS personalization mode at this stage.
It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for Windows included in the MGE UPS SYSTEMS, INC. Solution­Pac power management suite CD-ROM.
3.2.1 Accessing personalization with front panel buttons
Press "scroll up" and "scroll down" function buttons together for more than 3 sec-
onds.
Press the function button placed under the “ENT” word to enter the set up mode and
follow the LCD messages using the buttons now defined as select keys. See Tables: 3-1, 3-2, 3-3, and 3-4 for settings.
Figure 3-2: Control Panel with scroll up and down buttons.
21
2120
EX 5/7/11 RT System
Operation3 — 2 86-86000-00 A01
UPS SET UP EXIT ENT
OFF
20 21
ON
Page 47
Installation and User Manual
Table 3-1: Local Settings.
Display Factory setting Options
Language English French, Spanish, German, Italian
Date / time format International format US format
(DD-MM-YYYY/HH:MM) (MM-DD-YYYY/HH:MM AM/PM)
Date / time change GMT (Greenwich Mean Time) MM-DD-YYYY/HH:MM adjustable
Audible alarm Quick beeps Slow beeps
Table 3-2: Output features.
Display Factory setting Options Comments
Output voltage 208 Volts AC 200/208/220/230/240/250
Frequency converter Disabled Enabled Bypass AC source disabled
Output frequency Auto ranging 50/60 Hz User selectable under
frequency converter mode
Eco mode Disabled Enabled See glossary
Hot standby Disabled Enabled Full redundancy (see Figure 3-3)
Operating mode IT Network Industrial (*) See Section 4.1
Bypass When bypass OK (**) When bypass NOK (**) (*) Transfer
Interrupt time 10 ms 10 to 200 ms Interrupt time calibration during
(by steps of 10 ms) during load transfer on
Bypass AC source out of tolerances
Overload level 102% 50/70%
(*) : - Select "IT Network" for computer loads.
- Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential
10 ms interrupt).
(**) UPS will switch to Bypass AC Source if it is within the set tolerances.
Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.
Operation 3 — 386-86000-00 A01
BYPASS AC
Full redundancy configuration
Protective Device
NORMAL AC
offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.
Utility
AC Source
Protective Device
NORMAL AC
LOAD
Page 48
Table 3-3: ON/OFF features.
Display Factory setting Options Comments
Cold start Disabled Enabled Start on battery.
Forced reboot Enabled Disabled Enables automatic restart of
the system even if normal AC source is restored before the end of the shutdown sequence.
Automatic restart Enabled Disabled UPS restarts automatically
when normal AC source is restored.
Sleep mode Disabled Enabled Automatic shutdown on battery
if output load level <10%
Remote Command Enabled Disabled Enables shutdown or restart
orders from software.
Table 3-4: Battery features.
Display Factory setting Options Comments
Battery test Every week No test/daily/monthly
Pre-Alarm 20% 0 to 100% Low battery signal;1% increment
Runtime choice UPS reads # and type From 65 to 400 Ah Requires EX 5/7/11RT CLA if
of battery using options (see section 1.5.4 modules connected. “Battery extensions cable kit”)
Battery deep discharge Enabled Disabled If disabled, loss of protection MGE UPS SYSTEMS,INC.
warranty.
3.2.2 Accessing personalization through external software
Insert the Solution-Pac CD ROM in your CD drive.
At the first Navigator Screen, select "Installation" and follow the instructions to install Personal
Solution-Pac for Windows.
If nothing appears, launch startup.exe
Then go to "Advanced settings" and "UPS settings".
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.
3.2.3 Final startup sequence
Press the <ON> button more than 3 seconds.
After UPS internal test sequence, the green LED goes on.
CAUTION During the restart, if the Bypass AC source is out of
tolerance, the UPS will generate an output calibrated 10 msec output interrupt.
15
EX 5/7/11 RT System
Operation3 — 4 86-86000-00 A01
Page 49
Installation and User Manual
3.3 Operating Modes
3.3.1 Normal (double conversion) Mode
Figure 3-4: Normal (double conversion) mode.
Operation 3 — 586-86000-00 A01
This is the standard operating mode, set by the factory.
Two possible cases.
1. If Normal AC source available:
LED is ON.
The load is protected by the UPS.
Scroll up and scroll down function buttons allow you to read the UPS measurements (Normal AC source voltage, Bypass AC source voltage, operating mode, battery capacity and UPS Serial Number).
2. If Normal AC source not available:
CAUTION: Do not operate the Manual Bypass switch
when the UPS is in Normal mode.
LED flashes.
LED is ON.
The audible alarm sounds intermittently.
The load is now powered by the UPS battery.
This display shows remaining back-up time.
16
15
2221
15
15
LOAD LEVEL 4kW / 5 kVA
OFF ON
15 16
REMAINING TIME
10 minutes
OFF ON
Page 50
3.3.2 ECO Modes
Figure 3-5: ECO mode display.
EX 5/7/11 RT System
Operation3 — 6 86-86000-00 A01
The main advantage of the ECO mode (see glossary) is that it reduces the consumption of electrical power.
Three possible cases:
1. If Bypass AC source available:
and LED are ON.
The load is supplied with AC power but not protected in ECO mode.
2. If Bypass AC source not available:
LED is ON.
The audio alarm sounds intermittently.
The load is automatically supplied in Normal mode via the Normal AC input.
3. Both Normal and Bypass AC sources not available or out of tolerance:
LED is ON.
LED is ON.
The audio alarm sounds intermittently.
The load is powered by the battery power from the UPS.
The display indicates the battery remaining backup time.
16
15
15
1715
15 17
OFF
15
15 16
OFF
ON
ON
OFF
ON
Page 51
Installation and User Manual
3.4 Operation on battery power
Figure 3-6: Transfer, Threshold and End of backup time.
Operation 3 — 786-86000-00 A01
3.4.1 Transfer to Battery Power
The load continues to be protected by the UPS when the Normal AC source is not available. Power is supplied by the battery.
There are three possible cases:
First Case:
LED is ON.
LED is ON.
The audio alarm beeps every 10 seconds.
This indicate the load is supplied by the battery.
The display indicates the battery remaining
backup time.
Second Case:
LED is ON.
LED is ON.
The audio alarm beeps every 3 seconds.
Low battery warning on display.There is very little
remaining battery backup time. Close all appli­cations because UPS automatic shutdown is pending.
Third Case:
LED is OFF.
LED is OFF.
The audio alarm is stopped.
The load is transferred to the Bypass AC source if
available. In this case:
LED is ON.
17
16
15
16
15
16
15
15 16
REMAINING TIME
10 minutes
OFF
ON
15 16
REMAINING TIME
2 minutes
OFF ON
15 16
SHUTDOWN DUE
TO DEPLETED BATTERY
OFF
17
ON
Page 52
3.5 Return of Normal AC source
After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled via UPS personalization).
3.6 Shutdown
Figure 3-7: Shutdown display, circuit breaker, and AC source switch.
EX 5/7/11 RT System
Operation3 — 8 86-86000-00 A01
1. Press the OFF button more than 3 seconds.
The load is no longer protected by the UPS. It is powered via the bypass AC source. If the UPS is set in frequency converter mode, the load will not be powered.
If the bypass AC source is out of tolerance, the UPS will generate a calibrated 10msec output interrupt.
2. Set the battery circuit breaker(s) to the
OFF position.
3. Set the Normal AC source circuit breaker
to the OFF position.
4. For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the OFF position.
8
14
19
OFF
19
14
17
ON
8
Page 53
Maintenance
4.0 Scope
Maintenance includes a troubleshooting guide of symptoms and possible solutions, Hot swapping the power module and Battery Module, and testing scenarios.
4.1 Information Technology (IT) Network and Industrial Operating Modes
Table 4-1: Network and Industrial Modes of Operation.
Symptoms IT network mode Industrial mode
Overload, and Bypass Load is transferred to Bypass AC source. Same as I/T network mode, but AC source in tolerance. UPS returns to normal mode if overload to the UPS does not return to
is removed. normal mode if overload
is removed.
Overload, and Bypass The UPS shuts down and load is not Load is transferred to Bypass AC source not in tolerance. transferred to Bypass AC source. AC source with 10 milli-
seconds output break. The UPS does not return to normal mode if overload
is removed. Output short circuit and Bypass The load remains powered by the UPS. Load is transferred to Bypass AC source in tolerance. The UPS shuts down after 3 minutes AC source, the UPS returns to
if the short circuit remains normal mode if the short circuit
is removed.
Output short circuit and Bypass The load remains powered by the UPS. The load is transferred to AC source not in tolerance. The UPS shuts down after 3 minutes Bypass AC source with
if the short circuit remains. 10 milliseconds output break.
The UPS does not return to
normal mode if the short circuit
is removed.
4 — 186-86000-00 A01 Maintenance
Page 54
4.2 Troubleshooting
If any of LED's or is on, there is an operating anomaly or an alarm.
Use "scroll up" or "scroll down" function button to reset the audible alarm.
Troubleshooting not requiring MGE UPS SYSTEMS, INC. after-sales support:
Table 4-2: Troubleshooting not requiring
MGE
after-sales support.
Symptom Indication Correction
LED is on, and Bypass AC AC source is not connected Rewire correctly the normal AC source is present to the correct terminals. source. the alphanumeric display shows BAD CONNECTION REWIRE AC NORMAL
LED is on, Load supplied by bypass AC source. Push the ON button for more than 3 the alphanumeric display shows: seconds. LOAD LEVEL XX kW / XX KVA
LED is on, and Bypass AC UPS overload Check if any device is shorted or failed. source is present the alphanumeric display shows: THERMAL OVERLOAD 1XX%
LED is on, Short circuit conditions on output Check if any device is shorted or
devices. failed.
the alphanumeric display shows: CURRENT OVERLOAD
LED is on, 180° degree phase shift between Check if bypass source is correctly
bypass and normal AC source. wired but the alphanumeric display shows: (in case of upstream transformer use). BYPASS REVERSE REWIRE BYPASS Audible alarm is on, Input/Output box not Check if the Input/Output box the alphanumeric display shows: installed correctly. is correctly installed. See section 2.8. I/O BOX REMOVED
15
18
17
17
17
1817
EX 5/7/11 RT System
Maintenance4 — 2 86-86000-00 A01
Page 55
Installation and User Manual
Table 4-3: Troubleshooting requiring
MGE
after-sales support.
Symptom Indication Correction
LED and are on, Internal fault Call the after sales support department. Bypass AC Source is present and transfer of load and audible alarm is on. on bypass AC source the alphanumeric display shows: xxx FAULT
LED is on, and audible alarm Battery fault during the battery test. Call the after sales support department. is on, the alphanumeric display shows BATTERY FAULT
LED is on, Static switch failure Call the after sales support department. the alphanumeric display shows: SHUTDOWN STATIC SW FAILED
Audible alarm is on, Batteries may have exceeded Follow the battery replacement procedure the alphanumeric display shows: their rated life period. Battery in section 4.5. END OF WARRANTY capacity is severely reduced.
NOTE: To reset the alarm permanently, press both function buttons and for more than 3 seconds.
2221
17
17
1817
Maintenance 4 — 386-86000-00 A01
Page 56
4.3 Hot Swapping the Power Module
This operation can be performed without interrupting the load.
Figure 4-1: Disconnecting the power module.
EX 5/7/11 RT System
Maintenance4 — 4 86-86000-00 A01
1. Stop the UPS with the OFF button (press more than 3 seconds).
Check if UPS is on bypass AC source:
LED is on (If LED is not on, do not turn the manual bypass and call the after sales support department).
2. Turn the manual bypass switch to the BYPASS position.
3. Switch the battery circuit breaker(s) to the OFF position.
CAUTION: Do not switch the Normal AC
source circuit-breaker to
the OFF position. Doing so
will disconnect power to the
load.
4. Loosen three screws to remove the Input/Output box.
5. Disconnect the battery cables and from the power module.
The power module can be replaced.
The connected equipment is powered by the Bypass AC source.
4240
8
14
7
1717
19
T
ower configuration
17
XXX FAULT
1CXXXXXXX
OFF ON
19
s ng i t t
e S d r
a
C
S UP
10
a
E
at
0
5
d
5
10
FF8
74
8
D
60
=
0
6
P
E
I
2
3
C=00
2
S
MA
R
et s
e
R
2
T
1
RNE
N
HE
O
T
E d a
nlo
ow
D
32
2 S R
42
40
7
φ
P
B
A
Y S S
8
12
Rack configuration
Page 57
Installation and User Manual
4.4 Re-connecting the power module
This operation can be performed without interrupting the load.
Figure 4-2: Reconnect the power module.
Maintenance 4 — 586-86000-00 A01
1. Secure the Input/Output junction box using the three screws.
2. Reconnect the cables and to the
power module.
3. Switch the battery circuit breaker(s) to the ON position.
4. Check if Normal AC source circuit breaker
is on the ON position.
5. Check that the LED is on.
6. Turn the manual bypass switch from the BYPASS to the NORMAL position.
7. Follow initial start up sequence (see section
3.1) in order to personalize the UPS.
8. Push the ON button for more than 3 seconds.
The green LED is on, and the connected equipment is now protected by the UPS.
15
22
17
8
14
4240
15
LOAD LEVEL
OFF
17
4 kW/ 5 kVA
ON
22
Page 58
4.5 Hot Swapping the Battery Module
Figure 4-3: Rear view of the battery module.
EX 5/7/11 RT System
Maintenance4 — 6 86-86000-00 A01
4.5.1 Disconnecting the Battery Module
1. Switch the battery circuit breaker(s) to the OFF position.
2. Disconnect the cables and from the
power module.
The battery module can be replaced.
The connected equipment is powered by the UPS, but not protected.
It is also possible to replace battery pack instead of battery module.
Contact your nearest after sales support service.
CAUTION: Always replace both battery
packs with new ones.
To remove battery pack:
1. First, switch the battery circuit breaker(s) to the OFF position.
See section 2.5 and follow instructions for battery pack replacement.
4.5.2 Re-connecting the Battery Module
1. Reconnect the battery cables and to the power module.
2. Switch the battery circuit breaker(s) to the ON position.
14
4240
4240
14
Battery Module Power Module
42
40
14
Page 59
Appendix
5.0 Electrical Specifications
5.1 System Input/Output Power Ratings
Table 5-1: EX 5/7/11 RT Input and Output Characteristics.
Source Voltage Frequency
Normal AC Source 208 to 240 Volts AC 40 to 70 Hz
Bypass AC Source 208 to 240 Volts AC* 48 to 52 Hz**
Load Output 120/240Vac Volts AC 50/60 Hz autoranging
(120/208/240Vac (or frequency converter) are possible with transformer module)
(*): depends on output voltage setting, can be modified by software. (**): set to +/- 4% by default, (1,2,4,8% are possible values), can be modified by software.
5.2 System Overload Characteristics
Figure 5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right).
5.3 System Backup Characteristics
Table 5-2: Back-up Time ( in minutes).
System Load Percentage
30% 50% 70% 100%
Standard 11kVA 25 14 9 5
Standard 11kVA + 1 EXB 61 30 20 14 Standard 11kVA + 2 EXB 96 53 34 22 Standard 11kVA + 3 EXB 135 84 51 30 Standard 11kVA + 4 EXB 172 102 67 42 Standard 11kVA + 5 EXB 201 113 87 53 Standard 7kVA 37 21 12 7 Standard 7kVA + 1 EXB 80 53 30 20 Standard 7kVA + 2 EXB 124 83 55 32 Standard 7kVA + 3 EXB 185 108 75 45 Standard 7kVA + 4 EXB 245 132 98 57 Standard 7kVA + 5 EXB 287 164 118 72 Standard 5kVA 37 31 21 12 Standard 5kVA + 1 EXB 90 70 53 30 Standard 5kVA + 2 EXB 140 112 83 55 Standard 5kVA + 3 EXB 185 156 108 75 Standard 5kVA + 4 EXB 255 207 132 98 Standard 5kVA + 5 EXB 306 260 164 118
Appendix 5 — 186-86000-00 A01
Load Percentage
100%
Load Percentage
1.5
70%
120VU160V 280V
1.25
1.1
1.02
0.5st30s
60s 120s
Page 60
Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.
Configuration for Configuration for Configuration for 2 hours backup time 4 hours backup time 8 hours backup time
EX 5 7 hours 15 hours 24 hours
EX 7 5 hours 12 hours 20 hours
EX 11 7 hours 15 hours 24 hours
5.4 System Short Circuit Protection
Short circuit current provided by EX 5/7/11RT in normal or battery mode: EX5/7 RT 110A for 80ms EX11 RT 190A for 80ms
5.5 Accessories Electrical Characteristics
EX RT Transformer
Nominal power 11 kVA Nominal current 63 A Input voltage 208-240Vac Output Voltage 120/208/240Vac Frequency 50/60 Hz (+/-10%) Isolation (EN 61558-1-2-4) 3.75 kV / 5 M ohms Operating temperature From 0° to +40°C Max. operating rel. humidity 95% Derating / altitude Pn-10% > 1000 m
Dimensions HxWxD (tower) 17.5 x 5.15 x 25 inches (444 x 131 x 635 mm) Dimensions HxWxD (rack 3U) 5.15 x 17.5 x 25 inches (131 x 444 x 635 mm) Weight 151 lbs. (68.5 kg)
EX RT CLA module
AC input voltage 156-280 Volts AC Input frequency 40-70 Hz Battery charge current 6 A DC
5.6 Heat Rejection
Table 5-4: Full load heat rejection in BTU’s/hr.
System Operation Mode
On-line On Battery
5kVA 1327 1944
7kVA 1858 2722
11kVA 2919 4278
5.7 Environmental Characteristics
The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C
range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.
The storage temperature : -20 to 40°C. Humidity : 5-95%, non condensing.
Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-
tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation due to the risk of thermal runaway.
Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.
EX 5/7/11 RT System
Appendix5 — 2 86-86000-00 A01
Page 61
MGE Warranty & Proprietary Rights for Single Phase Products
MGE Warranty
The liability of MGE UPS SYSTEMS, INC. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS, INC.’s factory or on the job site at MGE UPS SYSTEMS, INC.’s option, any part or parts which are defective, including labor, for a period of 24 months from the date of purchase. The MGE UPS SYSTEMS, INC. shall have the sole right to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to MGE UPS SYSTEMS, INC. for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, INC.’s Return Materials Authorization prior to returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, INC. will not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item, or for damage due to accident, abuse, or Act of God.
In no event shall the MGE UPS SYSTEMS, INC. be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS, INC. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. MGE UPS SYSTEMS, INC. is not liable for and Purchaser waives any right of action it has or may have against MGE UPS SYSTEMS, INC. for any consequential or special damages arising out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, INC. will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE UPS SYSTEMS, INC.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS SYSTEMS, INC. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the MGE UPS SYSTEMS, INC.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of the MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser but to no one else. Accessories supplied by MGE UPS SYSTEMS, INC., but manufactured by others, carry any warranty the manufacturers have made to MGE UPS SYSTEMS, INC. and which can be passed on to Purchaser.
MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent. Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to Purchaser’s specific design.
Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS SYSTEMS, INC. be responsible for consequential damages or for any damages except as expressly stated herein.
Proprietary Rights Statement
The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in which MGE UPS SYSTEMS, INC., retains any and all patent rights, including exclusive rights of use and/or manufac­ture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, INC.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.
Page 62
Warranty and Product Registration
Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality requirements. We are pleased to have you join our increasing family of users.
In order to maximize the value you receive from this product, and to ensure that you are kept informed of product or software updates, we recommend that you take a few minutes to register your new purchase. You may register online at the URL noted below. Should you not have Internet access, you may mail or fax this form back (attn: Warranty Registration) as indicated at the bottom of the page.
Register your UPS at: http://www.mgeups.com/email/warranty/menu.htm
Please be prepared with the following information to register and validate your UPS warranty, keep informed on software and product updates, and register your extension "Warranty+" if purchased with the UPS.
User Information
Last name ________________________________________
First name ________________________________________
Company name ________________________________________
Address ________________________________________
Zip code ________________________________________
City ________________________________________
State/Province ________________________________________
Country ________________________________________
Tel ________________________________________
Fax * ________________________________________
Email* ________________________________________
Product information
Model ________________________________________
Serial Number ________________________________________
Date of purchase ________________________________________
Warranty Extension (Warranty+) not available on products
I have purchased a warranty extension (Warranty+)
Reference: _____________________ Contract Number: _________________
Thank you from all of us at MGE.
MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA
Tel: 714-557-1636 Fax: 714-557-9788
41-000154-53 Rev B00 9/2003
Page 63
MGE Customer Care Center
Technical Support and Product Services
Technical questions? If you encounter a problem while following the instructions in
this manual, or have
questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS
SYSTEMS, INC.
Customer Care Center or visit our web site www.mgeups.com for complete service information.
To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial
number of the unit and include them in any discussions or correspondence.
Part Number: _____________________________________________________________________
Assembly Number: _____________________________________________________________________
Serial number: _____________________________________________________________________
Who To Contact
Customer Care Center:
1-800-
523-0142, extension 1113
(USA and Canada Only)
Field Service Engineer:
1-800-438-7373 (USA and Canada Only)
Customer FAQ or
International calls:
1-714-557-1636 (Ask for Technical Support Group, TSG)
Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that will
provide responses to any questions that you might have.
Scheduling Field Service Engineer Support
Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE toll free telephone number at
1-800-438-7373, to insure a safe installation and startup that will maintain
the MGE warranty and insure smooth performance
Return Policy for Repair (RMA)
Should you require factory service for your equipment, contact MGE’s Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RMA.
Date: ______________________________________________________
RMA Number: ______________________________________________________
Contact Name: ______________________________________________________
?
Page 64
(This page left blank intentionally)
EX 5/7/11 RT System
W—4
86-86000-00 A01
Page 65
Glossary
Term used Definition / Meaning
@ At.
/ And/or.
+/- Plus or Minus.
Equal to or less than.
# Number.
°C Degree Celsius.
°F Degree Fahrenheit.
Ø Phase angle.
Ohm; unit of resistance.
® Trade Mark.
2nd Second.
AC or ac Alternating current, also implies root-mean-square (rms).
Ambient Temp. Temperature of surrounding air.
Ambient noise Acoustical noise of surrounding environment.
ANSI American National Standard Institute.
AWG American Wire Gauge.
Breaker Electrical circuit interrupter.
BTU or Btu British thermal unit. Defined as the amount of heat required to raise the tempera-
ture of one pound of water by 1°F.
BYPASS See “Static Transfer switch”.
BYPASS mode See “off-line mode”.
Carrier The company or individual responsible for delivering goods from one location to another.
C Common.
CB Circuit breaker.
cm Centimeter.
dB Decibels.
DC Direct current.
Conduit A flexible or rigid tube enclosing electrical conductors.
C.S.S. Customer Support Service.
Glossary G — 186-86000-00 A01
Page 66
Current rating The maximum current that a conductor or equipment can carry reliably without damage.
dBA Decibel Adjusted.
dBrnC Decibel above reference noise.
DC or dc Direct current, or voltage.
Digital Meter The LCD display on the front panel of inverter system.
Earth ground A ground circuit that has contact with the earth.
ECO Mode Operating mode by which the load is supplied directly by the AC source if it is within the
tolerances defined by the user. This mode reduces the consumption of electrical power.
Electrician Refers to an installation electrician qualified to install heavy-duty electrical components in
accordance with local codes and regulations. Not necessarily qualified to maintain or repair electrical or electronic equipment.
FET Field effect transistor.
Freq. Frequency.
Frequency slew rate The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).
GND Ground (safety).
Hz Hertz, frequency measurement unit, 1Hz is one cycle per second.
Inverter mode See “on-line” mode.
I Current.
IEC International Electrotechnical Commission.
IEEE Institute of Electrical and Electronic Engineers.
Input branch circuit The input circuit from the building power panel to the equipment.
Inverter An electrical circuit that generates an AC voltage source from a DC voltage source.
IGBT Insulated gate bipolar transistors.
I/O Input/Output.
I/T or IT Information Technology.
kVA KiloVolt-Ampere; is equal to 1000 Volt-Ampere.
L Line.
LCD Liquid-Crystal Display unit.
LED Light Emitting Diode.
Mains or Mains 1 Main AC input source.
Mains 2 Bypass AC input source.
mA Milliampere.
MAX. Maximum.
MCM Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in
diameter. M is from Roman numerical system indicating 1000.
Module Refers to individual power inverter module.
N Neutral.
EX 5/7/11 RT System
GlossaryG — 2 86-86000-00 A01
Page 67
Glossary G — 386-86000-00 A01
NC Normally closed.
NO Normally open.
NEC National Electrical Code.
NFPA National Fire Protection Association.
PN Part number.
On-line mode Inverter output power is the primary energy source to load.
Off-line mode Inverter output is off, and the load connected at the inverter output receives power
from utility line via a static transfer switch or maintenance bypass relay.
OSHA Occupational Safety and Health Agency.
PCA Printed circuit assembly.
PCB Printed circuit board.
PWM Pulse Width Modulation.
SCR Silicon controlled rectifier.
Shipping damage Any damage done to an article while it is in transit.
SPDT Single Pole Double Throw.
Static Transfer An solid state switching mechanism electronically controlled to pass AC power
directly from the utility to an output load.
Technician Refers to an electronic technician qualified to maintain and repair electronic
equipment. Not necessarily qualified to install electrical wiring.
Test connector DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer
Support Service technician to access programmable and diagnostic features of the system.
V Volts
VA Volt amperes
VA Volt-amps, unit for apparent power measurement, equal V x I.
VAC or Vac Voltage of AC type.
VDC or Vdc Voltage of DC type.
ve Battery voltage.
Via By way of.
Installation and User Manual
Page 68
EX 5/7/11 RT System
G — 4
86-86000-00 A01
(This page left blank intentionally)
Page 69
Reorder Form
1660 Scenic Avenue
Costa Mesa, CA 92626
Use this form to report any errors, omissions, or other problems you have experienced, or to order additional hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Web site. Please contact your MGE UPS SYSTEMS,INC. Representative for assistance.
NAME _____________________________________________________________________________________
COMPANY ___________________________________________________________________________________
STREET ADDRESS ____________________________________________________________________________
CITY ________________________________________ STATE __________________ ZIP ___________________
I would like to order______ (quantity @ $75.00 each) additional copies of the:
EX 5/7/11 RT System
Installation and User Manual
86-86000-00 A01
I would like to report the following problems with this document:
Page 70
Page 71
Page 72
1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636
www.mgeups.com
Contact MGE
United States
MGE UPS SYSTEMS
1660 Scenic Ave. Costa Mesa, CA 92626
Tel: (714) 557-1636 (800) 523-0142 Fax: (714) 557-9788 email: info@mgeups.com www: mgeups.com
Canada
MGE UPS SYSTEMS
#9, 2789 Thamesgate Drive Mississauga, ON L4T 4E8
Tel: (905) 672-0990 (877) 672-0990 Fax: (905) 672-7667 email: info@mgeups.com www: mgeups.com