Mersen, formerly Ferraz Shawmut TELECOMMUNICATIONS Catalog Page

TELECOMMUNICATIONS SPECIAL PURPOSE FUSES
Ferraz Shawmut telecommunications fuses are specially designed for the protection of telecommunications equipment which includes telephone switching equipment, rectifiers, distribution switching panels, battery back-up modules, power supplies and switching sub-stations.
The telecom fuses are available from 1 to 800 amperes rated at 170VDC with an interrupting rating of 100,000 amps to fulfill your circuit protection needs. The telecom fuses have high current limiting capabilities to provide a better degree of circuit protection to traditional tele­communications equipment. These fuses consist of a blue and white label for easy identification of their DC voltage capability.
Features/Benefits
All fuses rated 170VDC, 100kA I.R.
HIGHLIGHTS
DC Rated
Highly Current
Limiting Fast Acting
Rejection Style
Ratings
TGL: 70-800 A
170VDC, 100kA I.R.
TGN: 1-600 A
170VDC, 100kA I.R.
TGS: 1-70 A
170VDC, 100kA I.R.
APPLICATIONS:
Distribution Switching Panels
Battery Back-up Systems
Power Supplies
Switching Substations
Telephone Switching Rectifiers
Approvals
UL Recognized
Components
File #E60314
Extremely current limiting
Blue & white labels for easy identification
Various mounting configurations
Telecom Fuse Cross Reference
Competitor Part Number Ferraz Part Number
TPN TGN TPS TGS
TPL TGL
Recommended Fuse Holder
FUSE
TGL 70-250A P243D 300-800A P243G TGN 0-30 20306R 20308R 31-60 20606R 20608R 61-100 21036R 21038R 101-200 22001R 22003R 201-400 24001R 24003R 401-600 2631R 2633R TGS 0-70A 30656T 30658T
AMPERE 1 Pole 3 Pole
G 26G 26
TGS TELECOMMUNICATIONS/SPECIAL PURPOSE FUSES
Catalog Numbers, Standard Ampere Rating
Catalog Ampere Catalog Ampere
Number Rating Number Rating
TGS1 1A TGS20 20A
TGS2 2A TGS25 25A TGS3 3A TGS30 30A
TGS5 5A TGS40 40A TGS6 6A TGS50 50A TGS10 10A TGS60 60A TGS15 15A TGS70 70A
Peak Let - Thru Current Data
Dimensions
[22.35± .5mm]
.88 ± .02
Melting Time - Current Data
ø .566± .006
[14.3± .015mm]
Peak Let - thru Amperes
Maximum Instantaneous
Available DC Current in Amperes
G
Time in Seconds
(10 ms Time Constant )
Current in Amperes
G 29
G 29