TELECOMMUNICATIONS SPECIAL PURPOSE FUSES
Ferraz Shawmut telecommunications fuses are specially
designed for the protection of telecommunications
equipment which includes telephone switching
equipment, rectifiers, distribution switching panels,
battery back-up modules, power supplies and
switching sub-stations.
The telecom fuses are available from 1 to 800 amperes
rated at 170VDC with an interrupting rating of 100,000
amps to fulfill your circuit protection needs. The telecom
fuses have high current limiting capabilities to provide
a better degree of circuit protection to traditional telecommunications equipment. These fuses consist of a
blue and white label for easy identification of their DC
voltage capability.
Features/Benefits
All fuses rated 170VDC, 100kA I.R.
➤
HIGHLIGHTS
DC Rated
➤
Highly Current
➤
Limiting
Fast Acting
➤
Rejection Style
➤
Ratings
TGL: 70-800 A
➤
170VDC,
100kA I.R.
TGN: 1-600 A
➤
170VDC,
100kA I.R.
TGS: 1-70 A
➤
170VDC,
100kA I.R.
APPLICATIONS:
Distribution Switching Panels
➤
Battery Back-up Systems
➤
Power Supplies
➤
Switching Substations
➤
Telephone Switching Rectifiers
➤
Approvals
UL Recognized
➤
Components
File #E60314
➤
Extremely current limiting
➤
Blue & white labels for easy identification
➤
Various mounting configurations
➤
Telecom Fuse Cross Reference
Competitor Part Number Ferraz Part Number
TPN TGN
TPS TGS
TPL TGL
Recommended Fuse Holder
FUSE
TGL 70-250A P243D
300-800A P243G
TGN 0-30 20306R 20308R
31-60 20606R 20608R
61-100 21036R 21038R
101-200 22001R 22003R
201-400 24001R 24003R
401-600 2631R 2633R
TGS 0-70A 30656T 30658T
AMPERE 1 Pole 3 Pole
G 26G 26
TGS TELECOMMUNICATIONS/SPECIAL PURPOSE FUSES
Catalog Numbers, Standard Ampere Rating
Catalog Ampere Catalog Ampere
Number Rating Number Rating
TGS1 1A TGS20 20A
TGS2 2A TGS25 25A
TGS3 3A TGS30 30A
TGS5 5A TGS40 40A
TGS6 6A TGS50 50A
TGS10 10A TGS60 60A
TGS15 15A TGS70 70A
Peak Let - Thru Current Data
Dimensions
[22.35± .5mm]
.88 ± .02
Melting Time - Current Data
ø .566± .006
[14.3± .015mm]
Peak Let - thru Amperes
Maximum Instantaneous
Available DC Current in Amperes
G
Time in Seconds
(10 ms Time Constant )
Current in Amperes
G 29