SJ SERIES 600 VOLT/FUSE BLOCKS
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com
SPACE-SAVING FUSE BLOCKS
Ferraz Shawmut expands its popular “SJ” series fuse
blocks to now include a 100A version in addition to
the existing 30A design. These blocks occupy up
to 25% less mounting space than standard Class J
fuse blocks. A patented built-in DIN rail adapter on
the 30A SJ block adds further design versatility. A
choice of box, screw, or pressure plate connectors
fit a wide range of stranded, solid copper, or aluminum wire for the 30A design, while the 100A design
features a box connector. Insulators are glass-filled
polycarbonate with verified dielectric strength in
excess of 2500V. Both the 30A and 100A SJ blocks
feature a unique adder block which can be snapped
onto 1-, 2-, or 3-pole blocks to form multi-pole segmented blocks of as many poles as desired. All fuse
clips are spring reinforced, made of high conductivity tin-plated copper.
RECOMMENDED FUSE USAGE
Class J Blocks (600V) . . . . . . . . use with AJT, A4J, HSJ
Clip & Connector Types
30A CLIP
SPRING
REINFORCED
30A CONNECTORS
SPRING
REINFORCED:
BOX
SCREW
PRESSURE
PLATE
100A CONNECTORS
TERMINAL
Ratings
600VAC:
➤
30A, 100A
Short Circuit Current
➤
Rating: 200kA
Approvals
All fuse blocks meet
➤
the requirements of
UL 512
UL Listed,
➤
Guide IZLT, File E52283
CSA Certified
➤
Class 6225, File 32169
H
H
H 13
H 13
SJ SERIES 600 VOLT/FUSE BLOCKS
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · sales@grossautomation.com
Recommended mounting
screws for 30A fuse blocks:
1/4” (.250” dia.)
Figure 6
Figure 2
Figure 3
Figure 7 Figure 8
Figure 4
Figure 1
Figure 5
600 Volt, 30A Class J Fuse blocks
CONNECTOR CONNECTOR
AMPERE WIRE CATALOG FIG. TORQUE
RATING POLES TYPE RANGE NUMBER In - lb
ADDER 60305SJ 1
1 BOX Al/Cu 60306SJ 2 35
2 #2-14 60307SJ 3
3 60308SJ 4
ADDER 60315SJ 1
30 1 SCREW Cu 60316SJ 2 20
GFPC 2 #10-14 60317SJ 3
INSULATOR 3 60318SJ 4
ADDER 60325SJ 1
1 PRESSURE Cu 60326SJ 2 20
2 PLATE #10-14 60327SJ 3
3 60328SJ 4
ADDER 60355SJ 1
1 BOX Cu* 60356SJ 2 35
2 #4-14 60357SJ 3
3 60358SJ 4
100 ADDER 61005SJ 5 100 (AL WIRE)
GFPC 1 BOX AI/Cu 61006SJ 6 60 (CU WIRE)
INSULTOR 2 SIDE CLIP 2/0#6 61007SJ 7
3 61008SJ 8
Note: To convert 30A “SJ” adder pole to single pole, use end barrier #U09372.
* Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the
same coefficient of expansion as copper wire for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
H 14