Mersen, formerly Ferraz Shawmut PCS SERIES Catalog Page

PCS SERIES
PC MOUNT FUSES
SEMICONDUCTOR PROTECTION FUSES FOR DIRECT MOUNTING ON PRINTED CIRCUIT BOARDS
Ferraz Shawmut’s new PCS series of extremely fast-acting, direct-mountable fuses addresses the increasing need for electrical protection at the PC board as current and voltage requirements push higher. These fuses help printed circuit board manufacturers reduce parts by eliminating clips and fuse blocks and allowing automated assembly. PCS fuses are AC and DC rated and are extremely current-limiting. They will protect semiconductors, main frame boards, circuit breakers
2
with low interrupting rating and other critical components. PCS fuses bring I voltage and interrupting ratings to the board itself and are UL Component Recognized.
t protection, higher
HIGHLIGHTS:
Extremely Fast Acting
PC Board Mount
Three Mounting Styles
APPLICATIONS:
Protection of
semiconductors, circuit breakers, critical components
Peak Let-Thru Current Data
Availalbe Current in RMS Symetrical Amperes
Maximum Instaneous Peak Let-Thru Amperes
Ratings
AC: 5 to 40A 600VAC,
200kA I.R.
DC: 5 to 40A
600VDC, 100kA I.R. L/R < 10 ms
Approvals
UL Recognized
Components FILE E60314
Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER
Slot Mount 5 PCS5-R 20 PCS20-R
8 PCS8-R 25 PCS25-R 10 PCS10-R 30 PCS30-R 12 PCS12-R 35 PCS35-R 15 PCS15-R 40 PCS40-R
Double Hole Mount 5 PCS5-H 20 PCS20-H
8 PCS8-H 25 PCS25-H 10 PCS10-H 30 PCS30-H 12 PCS12-H 35 PCS35-H 15 PCS15-H 40 PCS40-H
Surface Mount 5 PCS5-S 20 PCS20-S
8 PCS8-S 25 PCS25-S 10 PCS10-S 30 PCS30-S 12 PCS12-S 35 PCS35-S 15 PCS15-S 40 PCS40-S
C 26
C 26
Dimensions of the PCS Series are found on page C 29
PCS SERIES
PC MOUNT FUSES
I2t at 600VDC,100kA, L/R = 10 ms
AMPERE RATING (A2s)
5 40
8 42 10 70 12 90
15 110 20 200 25 260 30 520 35 780 40 1100
CLEARING I2t
Peak Let-Thru Current Data – PCS5 to 30-R, H or S, 600 Volts AC
I2t at 600VAC, 100kA
AMPERE MELTING RATING (A2s) (A2s)
5 5 60 8 6.5 70 10 10 110 12 17 150 15 26 180 20 41 330 25 69 440 30 132 860 35 197 1300 40 276 1800
I2t CLEARING I2t
Watts Loss Data
AMPERE WATTS LOSS @ WATTS LOSS @
5 0.5 0.7
10 0.9 1.5 15 1.9 3.0 20 2.6 4.4 25 2.9 5.3 30 3.0 5.8 35 3.3 6.4 40 3.6 7.0
RATING 80% RATING (w) 100%RATING (w)
C
C
Time in Seconds
Current in Amperes
C 27
C 27
Loading...
+ 1 hidden pages