INC. l 13600 INDUSTRIAL PARK BLVD., P.O. BOX 1551, MINNEAPOLIS, MINNESOTA 55440
PHONE:
377-9750
AREA CODE: 612
Page 2
Page 3
Page 4
PRE-INSTALLATION
LOCATION
A.
Unit
is designed for indoor application and must
be located in an area where the surrounding ambient temperatures are 40 F or above. A good rule
of thumb is to place units where ambients are at
least 5 degrees above the leaving water tempera-
t
urc
B.
Because of the electric control devices, the units
should not be exposed to the weather. A plastic
cover over the control box is supplied as temporary
protection during transfer.
A reasonably level and sufficiently strong floor
c.
is all that is required for the Seasonpak Water
Chiller. If necessary,
bers should be provided to transfer the weight of
the unit to the nearest beams. Figures 1 and 2
indicate the base plan for the chiller. Refer to
310VING AND PLACING THE UNIT, Page
foundation information.
additional structural mem-
9,
for
INSPECTION
When the equipment is received, all items should
be carefully checked to make sure that all crates and
cartons have been received. All units should be
carefully
damage should be reported immediately to the carrier
and a claim filed for damage.
inspected for damage when received. All
HANDLING
Every model PWA Seasonpak with water cooled
condensers (Arrangement
refrigerant charge. A holding charge is supplied in
condenserless models (Arrangements 2
shipment, the charge is contained in the condenser
and is isolated by the manual condenser liquid
valve and the compressor discharge service valve.
Should the unit be damaged allowing the refrigerant
to escape, there may be danger of suffocation in
the equipment area since the refrigerant will displace the air. Care should be taken to avoid rough
handling or shock due to dropping the unit. NEVER
LIFT, PUSH OR PULL UNlT FROM ANYTHING
OTHER THAN THE BASE. Refer to MOVING AND
PLACING UNIT, Pages 7
and 4 for further information.
1)
is supplied with a full
& 3).
thru
9, and Figures 3
For
SPACE REQUIREMENTS FOR
CONNECTIONS AND SERVICING
Dimensions of the unit are given in Figures 1 and
A.
2.
The chilled water piping for all units enters and
B.
leaves the cooler from the rear. A clearance of
2-3 feet should be provided for this piping and for
replacing the filter-driers or servicing the solenoid
valves.
The condenser water piping enters and leaves the
C.
shell from the ends. Work space must be provided
in case water regulating valves are being used and
for general servicing.
It is desirable to leave a small walk area on the
D.
end opposite that used for replacement of a cooler
tube. Figures 1 and 2 indicate the requirements
for
tube
replacement. Clearance for removing a
length of tube is required on one end only. The
cooler
tube is longer than the condenser, therefore,
the condenser tube replacement area need not
be considered.
ELECTRICAL
Simple three lead connection is all that is required
to connect power to the Seasonpak. Wiring should
conform with all local and national codes. The system
nameplate
with the power supply available. Check Electrical
section,
should be checked to be sure that it agrees
Pages
12 to 18, for further information.
WATER TEMPERATURE LIMITS
A. The maximum allowable water temperature to the
cooler must not exceed
stance, such as change over from heating to cool-
ing.
B. These units must not be operated when the enter-
ing water temperature is in excess of 90” F.
140’
F under any circum-
Page
4
Page 5
Page 6
Page 7
MOVING ANDPLACING UNIT
MOVING THE UNIT
The light weight of the Seasonpak makes moving
A.
a simple matter. The
McQuay
Seasonpak is skidded
to protect the unit from being accidentally damaged
from any angle. Table 3 gives the approximate skid
dimens ions.
When moving the unit, dollies or simple pipe rollers
B.
can be used under the skid or under the base.
Always apply pressure to the base and not to the
piping or shells. A long bar helps move the unit
easily. Avoid dropping the unit at the end of the
roll.
The
4"
C.
channel base is arranged on the skid so
that the fork of a standard fork lift truck can be
slid easily under (See Figure
3).
The forks of the
fork lift truck must be across both the front and
rear channels before lifting. Always use a fork
lift truck on the side opposite the control panel to
avoid damaging the controls. Never put the weight
of the unit against the condensers.
If the unit must be hoisted, it is desirable to lift
D.
from the skid or from the base as indicated in
Figure 4, Page 8. A spreader bar must be used
to protect the control cabinet and other areas of
the chiller.
Do not attach slings to piping or equipment. Move
E
unit in the upright horizontal position at all times.
Let unit down gently when lowering from
or off
rollers.
TABLE 3
OVERALL SHIPPING
the truck
SKID DIMENSIONS
MODEL
PWA008
PWAOlO
PWAOlS
PWA020
PWA025
PWAOSO
PWA041 121
PWA050 128
PWA060 128
LENGTH WIDTH
98
98
98
121
121
121
39
39
39
34
34
38%
38%
40’/,
40’4
FIGURE 3
MOVING UNIT WITH FORK LIFT
THE CONTROLS.
Page 7
Page 8
MOVING AND PLACING UNIT
FIGURE 4
SUGGESTED RIGGING
Page
*--
PLACING THE UNIT
The small amount of vibration normally encountered
with the Seasonpak makes this unit particularly
able for basement or ground floor installations where
the unit can be bolted directly to the floor. The floor
construction should be such that the unit will not affect
the building structure, or transmit noise and
vibration into the structure. See VIBRATION ISOLATORS section for additional mounting information.
Hold down bolt locations are indicated in Figures 1
and 2, Page 5.
VIBRATION ISOLATORS AND
ELIMINATORS
A.
Rubber-in-shear or spring isolators can be fur- C
nished and field placed under each corner of the
package. It is recommended that a rubber-in-shear
8
desir-
NOTE: ALWAYS USE SPREADER
BARS TO PROTECT UNIT
FROM DAMAGE.
pad be used as the minimum isolation on all upper
level installations or areas in which vibration
transmission is a consideration.
B. Transfer the unit as indicated under MOVING THE
UNIT, or use the methods as indicated in Figures
3 and 4. In all cases, set the unit in place and
level with a spirit level. When spring type isolators
are required,
main side channels as shown in Figure 5. Foundation hold down bolt locations for vibration isolators
are given in Figure 6. A rubber-anti-skid pad should
be standard under isolators if hold down bolts are
not used.
Vibration eliminators in all water piping connected
to the Seasonpak are recommended to avoid straining the piping and transmitting vibration and noise.
install springs running under the
Page 9
Page 10
WATER
PIPING
GENERAL
A.
Piping practices
codes. local ordinances and established practices
govern the selection and installation of piping.
Local building and safety codes and ordinances
should be studied and complied with.
Shut off valves should bc provided at the unit so
B.
that normal servicing can be accomplished without
draining the system.
It is recommended that temperature and pressure
c
indicators be installed at the inlet and outlet of
the
shclls’to aid in the normal checking and
vicing
of the unit. Also. the installation of wire
mesh strainers at the pump suction will protect
the pump and shells from foreign matter.
A
preliminary leak check of the water piping should
D.
be made before filling the system.
Vibration eliminators are recommended in all lines
E.
connected to the Seasonpak.
vary considerably.
In most cases
CHILLED WATER PIPING
A.
Each cooler is provided with the connections as
indicated in Figures 1 and 2, Page 5. Also, a
NPT vent and S/4” NPT drain are provided.
Design
B.
the piping so that it has a minimum number
of changes in elevation. Include manual or automatic vent valves at the high points of the chilled
water piping, so that air can be vented from the
water circuit. System pressures can be maintained
by using an expansion tank or a combination pressure relief and reducing valve.
ser-
114”
C.
All chilled water piping should be insulated to
prevent the nuisance of water dripping from the
lines.
vapor barrier type,it should be covered with a
moisture seal. Do not insulate piping until it has
been tested for leaks and until all vent and drain
connections have been extended beyond the pro-
posed insulation thickness to make them
accessible.
The chilled water thermostat is mounted inside
D.
the control console, and the control bulb, capillary
tubing.and control bulb immersion well are attached to the unit with spring clips. The control
bulb well must be field inserted in the first tee
installed in the return water line as shown in
Figure 7. The bulb well is supplied with a
NPT male thread. Carefully unsnap the well from
the
and slowly remove the bulb from the well. Install
into piping as indicated in Figure
the bulb, carefully remove it from the well so as
to not wipe off the heat conducting compound supplied in the well. After installing the well, carefully insert the bulb and seal in with the excess
compound. Insert the retaining gasket and sealing
bushing and clip or tape the cap tube to the water
line. Care should be taken not to break or kink the
charged capillary tubing. Sufficient cap tube length
is provided for bulb insertion up to
unit; however, it is recommended that the bulb well
be placed as close to the cooler inlet as possible.
Insulate over thermostat well.
CAUTION: The thermostat bulb should not be
posed to water temperatwes above
will
If insulation is not of the self-contained
holding clips, remove the retaining bushing
7.
When installing
10
feet from the
140 F
since this
damage the control.
112”
ex-
Page 10
FIGURE 7 THERMOSTAT WELL
RETURN WATER
TO
COOLER
INSTALLATION
‘/I”
N.P.T.
BUSHING
(BY
OTHERS)
Page 11
Page 12
Page 13
ELECTRICAL
FIELD WIRING
Only three main power leads need be hooked up to
A.
the standard packaged water chiller. From the
power connection block to the motor, the unit is
factory wired ready for operation. Table 5, Page
18, gives the recommended lead wire size when
only three conductors are used in a raceway. Refer
to the National Electrical Code for other type wire
or special instructions.
Although there is no specific requirement, inter--
B.
locking of a flow switch and the condenser pump
starter (or air cooled condenser fan) is suggested
for the most dependable and economical system
operation. The cooler pump should operate continuously, even when the unit is not operating. The
condenser pump should be field interlocked by
connecting the pump starter coil to terminal 7 and
terminal 12 as shown on Schematic Wiring Diagrams
1 and 2, and terminals 8
matic Wiring Diagrams 3 and 4, Pages 14 thru 17.
This cycles the condenser pump (or air cooled
condenser fan) with the compressor.
Referring to Diagrams 1 thru 4, the flow switch
C.
is interlocked by removing jumpers between termi-
nals 13 and 14 for single units and 25 and 26 for
dual units, and wiring the switch contacts into
the system as is shown on the schematic wiring
diagrams. When so wired, the chilled water pump
must be operating before power can be applied to
start this system. Note that the crankcase heaters
will be energized regardless of water flow. The
flow switch is recommended and does not
the shortcomings of interlocking the cooler pump
starter. A
water temperature of
flow switch must be used for leaving
STARTING SEQUENCE
(Refer to Diagrams 1 thru
&
14 and 12 & 14 on Sche-
32 F and lower.
4).
have
compressors are not operating. The indicator
lights should show the heaters on. Power is
also supplied to the main system On-Off switch,
Sl.
Closing switch Sl energizes System No. 1 and
3.
System No. 2.
Referring to System No. 1, power at terminal
4.
2
indicates power to the system by lighting
the red “Power on” light.
Provided operating safety controls are closed
5
5.
(FSl, OPl,
overloads are used), power at terminal 3 will
energize safety light,
is ready to run.
Referring to the standard non-recycle,
6.
operation of the schematic wiring diagram,
relay R1
cannot reach compressor starter. Power can
reach
controlled by thermostat
pressor lead-lag switch (dual units only) and
the
pumpdown
When cooling is required. power is supplied to
7.
Terminal 4,
energizing relay
8.
When
close and open the liquid line solenoid valve
LLSl.
9.
If low pressure control
ing of
the low side building up pressure which will
close
Meanwhile, time delay TD 3
10.
second compressor. After the time delay closes,
power is fed to control system No. 2 and the
same sequence of starting for the second compressor is repeated.
HP1 and MPl or
and R3 are normally open, and power
starter only by energizing Rl which is
switch S3.
through water thermostat
Rl,
indicator light LT5.
Rl relay is energized, contact Rl will
LLSl
will allow refrigerant to flow into
LPl
and the compressor will start.
OLl
when external
indicating the system
TCl
through the com-
LPl
is open, the open-
is timing the
pumpdown
TC1
A. Variations or options in the control system will
change the basic wiring diagrams slightly, however,
the sequence of events will be similar.
B. The following starting sequence is for dual com-
pressor units. The sequence for single compressor
units is identical except for the obvious reference
to the second unit. Once the system ON-OFF
switch is pushed on the ON position, the unit will
operate completely automatically.
1. Check or throw to “auto” position switches
S3
and S4 (pumpdown switches). Switch is in
“auto” position during normal operation.
2. With main power on, power to the control circuit from
to terminal 25. The power from 25 is fed thru
NC contacts to relay
the compressor crankcase heaters, when the
Ll
and L2 is fed through fuse
R3
and R4 to energize
Fl
OFF
CYCLE
Referring to the schematic wiring diagrams, when
thermostat
terminal No. 4 (or No. 10 for second system), will be
broken opening relay
solenoid, and indicator light LT5. The compressor will
continue to operate through t.he contacts of R3 relay.
Note that
contacts and the compressor is on the pumpdown
cycle. When the compressor has pumped most of the
liquid refrigerant from the cooler, the low pressure
cut out,
This locks the compressor off the line until the thermostat
and Rl and closing
TCl
is satisfied, the electrical circuit to
Rl
de-energizing the liquid line
R3
relay is now energized through its own
LPl
will open and de-energize R3 relay.
TCl
calls for cooling again, energizing
LPl.
LLSl
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
START UP PROCEDURE
Do not start the Seasonpak until the following steps
have been completed.
A. Check all auxiliary components of the installation.
B. Open the compressor suction and discharge shut
off valves until back seated. Back seating the
valve closes the gauge ports and, if gauges are
provided,
toward the closed position.
caps.
Open the manual liquid line shut off valve at the
C.
condenser.
D.
If water regulating valves are provided, connect
their capillary to the manual valves provided on
the condensers and open the manual valves.
Check to see that the water temperature thermostat
E.
is installed in the entering water line, that the
thermostat well is full of heat conducting compound
and that the bulb is secured with the retaining
fitting.
close valve one turn from full open,
Always
replace seal
Check the compressor oil level. Prior to start-up,
F.
the oil level should be in the oil sight-glass.
Fill the water system. The cooler circuits should
G.
be filled with clean non-corrosive water.
Check the main system “on-off’ switch to see that
II.
it is in the
switches should be thrown to the “auto” position.
Check resets of all safety controls.
J.
K.
Throw the main power disconnect to “On”.
L. Start the auxiliary equipment for the installation.
M. Set the circuit breakers to “On”.
N.
Start the system by pushing the system “On-Off’
rocker switch to “On”.
“off’ position. The pump down
OPERATION
During full load operation, check the compressor oil
level. It should be at the center of the oil sight glass
during operation.
A. Check the refrigerant charge frequently at the
moisture/liquid indicator. A steady clear glass
of liquid refrigerant indicates sufficient charge.
A green colored button in the center of the moisture indicator indicates a dry system (should moisture enter the refrigerant, the color will turn yel-
low). The button was green before it left the
factory and should be green after period of operation on start up.
B. Check the temperature control thermostat by ob-
serving operation at reduced loads. The thermostat
is factory set for 44F leaving chilled water temperature when the entering temperature is 54F.
Refer to CHECKING CONTROLS section, Pages 20
and 21.
Check voltage and amperage of the compressor
C.
motor.
Adjust water regulating valve for discharge pres-
D.
sures between 200 and 230 psig for the most economical operating pressure.
Close gauge ports on valves when gauge readings
E.
are not required. This will prolong the gauge life.
Page
19
Page 20
CHECKING CONTROLS
All controls are checked and adjusted prior to
leaving the factory. However, after the unit has operated satisfactorily for a reasonable length of time, a
check of the operation and safety controls can be
made as indicated below:
A.
OIL PRESSURE SAFETY SWITCH - The oil failure pressure switch is activated by a low pressure
differential between the oil pressure and the crankcase pressure. Upon start up, the normally closed
pressure actuated contact of this control opens
when the pressure differential increases to about
I5 psig. If oil pressure does not reach this differen-
tial, the thermal time delay remains energized and
opens a bi-metallic safety contact, de-energizing
the complete control circuit. If pressure reaches
the prescribed differential within 120 seconds, the
thermal time delay is de-energized and the control
circuit remains closed. If during the operation,
the oil pressure differential falls below 10 psig,
the thermal time delay is again energized and the
control will shut down the compressor.
To check the control, jumper the Freezestat
terminals L
off position. Throw control circuit to “On” to
pull in contactor. The contactor should drop out
and the safety indicator light should go out after
approximately 120 seconds or less. After checking
the control, wait approximately 2 to 3 minutes and
then reset control manually. The compressor can
then be started. Repeated successive operations
of the control will require a longer period before
it can be reset, since the bi-metal will get hotter
and will take more time to cool.
& M
and trip the circuit breaker to the
the end of the
psig and automatically reset at approximately 60
psig. The control can be checked by throwing the
individual
tion and observing the cut-out point on the gauge.
FREEZESTAT
D.
control connected to the low side of the system
and is set to shut down the system when the pres-
sure drops low enough to be dangerous as far as
cooler freeze up is concerned. The control is factory set at 52 to 53 psig. When dropping to this
point,
the
tacts of this control will close, energizing a 220
volt heater. This causes the normally closed bi-
metallic relay switch of this control to open after
a delay of approximately 90 seconds, or less,
stopping
line so 1 en o id valve. The time delay prevents
nuisance trip out on momentary low suction pres-
sure and permits the operation of the system on a
“pumpdown cycle”.
The control must, be checked while the system
is operating. To check the control, install a volt
meter or
of the low pressure freeze control. There should
be a voltage indication or the test light will glow
indicating the contacts are opened. Throw the
pump down switch to the manual position and check
the pressure at which the test light goes out or
the volt meter goes to zero. In actual operation,
the compressor will shut down and the safety light
will go out. The control can be manually reset in
about 2 minutes.
pumpdown
pumpdown
-
The Freezestat is a pressure type
normally open pressure actuated con-
the
compressor and closing the liquid
220
volt light across terminal Tl and T2
cycle. It will open at 35
switches to the manual posi-
Page 20
B.
HlGH
PRESSURE CONTROL - The high pressure
switch will shut down the compressor and close
the liquid line solenoid valve when the compressor
discharge pressure reaches 270 psig for water
cooled units, or 360 psig for air cooled units. To
check the control, slowly throttle the condenser
inlet water or shut down the condenser fan. Ob-
serve the cut out point. During testing stand by
the System “On-Off’ switch to shut down the
unit should the safety device malfunction. Be sure
the gauges used are accurate.
The water cooled condensers are supplied with
a 300 psig relief valve and the discharge pressure
during the test must be kept below 270 psig. For
Aircooled Condenser operation the relief valve
will be set for 400 psig.
The control can be manually reset at approxi-
mately 70 psig below the cut out point.
LOW PRESSURE CONTROL
C
switch is connected to the low side of the system
and its purpose is to shut down the compressor at
-
This pressure
E. THERMOSTAT
packaged chillers are factory calibrated for use
in the return water line to the cooler inlet. The
thermostat bulb is installed in a well in the return water line in order to be more stable under
temperature changes due to load conditions. Figure
7. Page 10 illustrates the recommended method
of installing the bulb and well in the return water
line. The return water does not change temperature
as rapidly as the outlet because of the “fly wheel
effect” of the total water system. This results in a
stable, non-recycling control of the outlet water
temperature.
Normally the thermostat requires no adjustment
in the field other than the dial setting for the
required control point. The control is preset at the
factory to maintain a 44 F average leaving water
temperature throughout the loading and unloading
sequence of the unit based on a full load cooling
range of 10 F. It should be realized however, that
there will be a fluctuation in the leaving water
-
The thermostats supplied on all
Page 21
CHECKING CONTROLS
temperature as the unit cycles, unloads and loads.
The magnitude of fluctuation will decrease as the
number of capacity control
On a two stage thermostat, the dial setting indicates the average leaving water
that the control will maintain. At a 44 F setting
the high stage should actuate at approximately
51 F return water and 41 F leaving based on 10”
cooling range. The low stage will open at 46 F
return or 41 F leaving
As the water warms up, the low stage should
cut in at approximately 49 F which is the inlet
and outlet temperature with the unit off and the
high stage should operate at
leaving.
These settings may be checked by operating
the unit and slowly regulating the load from full
to minimum and return. It may then be necessary
to adjust the dial and/or differential between
switches to obtain
On a four stage thermostat, the dial setting
indicates
the cut out point of the low stage switch
these values.
steps
increases.
(5” TD
or 50% capacity).
54
F return or 49 F
temperature
which represents the average leaving water temperature desired. The high stage or
be
actuated at approximately 51 F return water
#3
temperature,
which is the dial
approximately 2 F higher than the cut out on each
switch.
These settings may be checked by operating
the unit and slowly reducing the load. The four
stage thermostat has a fixed switch
and fixed differential between switches. DO NOT
make
any
is a
preset
must
be
made using a screw driver in
gear
below
by turning the large numbered dial.
at 49 F, #2 at 47 F and #1 at 45 F
setting. The
adjustments other than the dial as this
precision control. This dial adjustment
the dial. Do not attempt the adjustment
#4
switch should
cut in point will be
differential
the
slotted
FIGURE 10
TWO STAGE FOUR STAGE
THERMOSTAT
BULB
THERMOSTATS
1
Page 21
Page 22
SYSTEM COMPONENTS
COMBINATION FILTER DRIER
A.
Each refrigerant circuit is furnished with a full
flow replaceable core type filter-drier. In the
drier installed in all Seasonpaks, the filters are
attached to the flange end cap
core assembly has a solid plate at the inlet end
and a plate with a gasket and fine mesh screen
at the outlet. During assembly, a spring at the
inlet end is compressed which holds the core in
place and exerts a force on the gasket at the outlet
end to prevent bypassing. CAUTION
refrigerant before removing end flange.
B. A condenser manual liquid line shut-off valve is
provided for isolating the charge in the condenser,
but also serves as the point from which the liquid
line can be pumped out. With the line free of liquid,
the filterdrier core can be easily replaced.
by
tie rods. The
LIQUID LINE SOLENOID
A.
Each refrigerant circuit is furnished with a liquid
line solenoid for automatic
All valves have epoxy-clad water proof coil as-
semblies for standard 220 volt AC
ice. The valve is completely serviceable without
removing valve body from the. line. The coils are
easily removed without “pumping-out” the liquid
line. All valves have a manual operation stem at
the side which allows you to open the valve and
operate the system in case of a coil malfunction.
Manual stem should be turned
clockwise to open bypass port.
CAUTION: Unit cannot be pumped down with valve
in manually opened position. Operator or
man should standby to shut unit off.
pumpdown
-
60 cycle
1/2
turn counter-
LIQUID SIGHT GLASS AND
MOISTURE INDICATOR
A. The color of the moisture indicator button is an
indication of the dryness of the system and is
extremely important when the system has been
serviced. Immediately after the system has been
opened for service, the element button may indicate
a chartreuse or yellow color. It is recommended
that the equipment operate for about 12 hours to
allow this system to reach equilibrium before
deciding if the system requires a change of drier
cores.
B. The following table is a guide to the moisture
content of the system.
Color Indication
Green
Chartreuse Caution
Yellow
C. Bubbles in the sight glass at constant full load
conditions indicate a shortage of refrigerant, a
Dry
Wet
filter-
-
Pump out
operation.
ser-
service-
plugged filter or a restriction in the liquid line.
However
sight glass during changing conditions.
it is not unusual to see bubbles in the
WATER FLOW SAFETY SWITCH
water flow safety switch is available as optional
A. A
equipment for all Model PWA chillers. The flow
switch must be field installed and wired into the
Scasonpak
ings
.
1. The flow switch should be installed in a horizontal run of piping as follows:
a. Adjust the flow switch paddle to the size
b. Apply pipe sealing compound to only the
c. Piping should provide for a straight length
2.
CAII’TION:
a.
b. The
control center as indicated on the draw-
of’ pipe in which it is to be used. (See Figure 11).
threads of the switch and screw unit into
a
D”
x D” x 1” reducing tee (See Figure 12).
The
flow arrow must be pointed in the cor-
rect direction.
before and after the flow switch of at least
5 times the pipe diameter.
Make
sure the
is pointed in the proper direction of flow.
flow
control voltage and should only be connected
according to the wiring diagram (See
Diagram inside control box door).
arrow
on the side of the switch
switch is designed to handle the
THERMAL EXPANSION VALVE
Each thermal expansion valve is adjusted for 8 to
A.
10 degrees superheat at the factory before shipment. The valve performs only one very simple
function; it keeps the evaporator supplied with
the proper amount of refrigerant to satisfy the
load conditions. Normal suction superheat will
be maintained by the expansion valve and it need
not be adjusted in the field.
The sensing bulb, of the thermal expansion valve
B.
is
installed
line from the cooler. The bulb is held on by two
clamps around the suction line to assure firm contact with the line. The line is then insulated to
remove the effect of surrounding ambients. In case
the bulb need be removed, simply slice the insulation on each side of the bulb, remove the clips
and then remove the capillary tubing that runs
along the suction line from the valve.
In the event the valve itself
C.
not necessary to remove the
line. All power assemblies
and
replaced.
in the closest straight run of suction
needs service, it is
valve body from the
are easily removed
Wiring
Page
22
Page 23
SYSTEM COMPONENTS
FIGURE 11
FLOW SWITCH
PADDLE
FS4-3 FLOW SWITCH
COMPRESSOR
FIGURE 12
FLOW DIRECTION
4
VIEW FROM END OF COOLER
STRAIGHT PIPE
FOR AT LEAST
TEE
Dv x
D” x
1”
A.
The reciprocating semi-hermetic compressor(s)
are complete with suction and discharge service
valves, integral force feed lubrication system, oil
sight glass,oil charging connection, crankcase
heater and initial oil charge.
The motor is of the hermetic induction type, 1750
B.
rpm, gas cooled, with inherent thermal protection
and supplementary overload protection, where required. The standard unit is wired for
across-theline starting. Part winding starting is available
as an option.
The compressor is pre-wired and ready to run.
C.
Suction and discharge service valves are closed
during shipment and must be opened. just prior
to start up. Gauge connections on suction and
discharge valves are closed when the valve stem
is back seated in the full open position. To increase the life of any gauges supplied, the suction
and discharge valve should be back seated except
when readings are required. Always replace valve
caps with gaskets in place.
The safety control piping connection to the com-
D.
pressor includes the oil failure switch-high pressure oil connection at the oil pump discharge; the
oil failure switch-low pressure connection at the
compressor crankcase: the high pressure safety
connection at the discharge manifold; and the low
pressure and freeze safety connection at the suction chamber on the motor end of the compressor.
Shut off valves are never installed in these control lines.
The compressor is pre-charged with sufficient oil
for normal operation. In case oil is required, or
if unit requires additional oil after installation
with a remote air cooled condenser, the compressor
may be pumped out on
pumpdown
cycle, valves
closed and oil charged through the filler plug
on the side of the compressor oil sump. The plug
must ‘be replaced with a sealer and leak checked
during operation.
A compressor crankcase heater, internal or external, is provided to minimize refrigerant accumu-
lation in the oil during the off-cycle of the compressor. Excessive refrigerant in the crankcase
dilutes the oil causing excessive foaming, oil loss,
and in extreme cases, bearing washout and pos-
sible failure. The heaters are energized at all
times when the unit is shut down. During prolonged
shut downs, when the electrical power may be shut
off, close the suction and discharge service valves
to prevent migration of the refrigerant to the oil
and reopen the valves just prior to start up.
Except for minor repairs, such as replacing a
suction or discharge reed valve, the compressor
is not generally repaired in the field. Exchange
compressors are stocked in warehouses throughout
the country and the damaged compressor is turned
in for credit.
Page
23
Page 24
SHELLS
SYSTEM COMPONENTS
A. Both the cooler and condenser shells are
constructed and stamped and are of the straight
through tube type with replaceable tubes.
ASME
WATER COOLER
A. The water cooler is of the direct expansion type
with removeable internally finned tubes and heavy
terneplate baffles. The copper tubes are individually rolled into heavy duty, steel tube sheets and
sealed by a cast steel refrigerant head.
B. The water nozzles which enter and leave the shell
are at the rear of the unit. No special attention
UNIT LESS CONDENSER
Seasonpaks supplied without condensers or with
mounted receivers require field piping to a remote
condenser of some type. As mentioned under the
REMOTE CONDENSER section of this manual, refrigerant piping should be sized and installed according to the Latest
-of refrigerant piping when using air cooled condensers
involves a number of considerations not commonly
associated with other types of condensing equipment.
The following discussion is intended for use as a
general guide to sound economical and trouble-free
piping of air cooled condensers.
A. On remote condenser applications having distances
of more than 20 feet between compressor or condenser, a discharge line muffler is recommended.
The muffler should be installed as close to the
compressor discharge as possible. If an oil separator is used, it will usually perform the same function as a muffler and will eliminate the need for
one. A muffler will reduce discharge line pulsations; particularly those which occur during unloaded compressor operation.
B. Discharge lines must be designed to handle oil
properly and to protect the compressor from damage
that may result from condensing liquid refrigerant
in the line during shut down. Total friction loss
for discharge lines of 3 psi is considered good
design. Careful consideration must be given to
sizing vertical risers to insure that gas velocities
are sufficient at all operating conditions to carry
oil. If the velocity in a vertical discharge riser
ASHRAE
Guide. The design
is required for the cooler except
tered
water should be supplied.
that clean,
CONDENSER
A.BThe condensers are of the shell
tube type with integral, externally finned copper
tubes, brazed into heavy-duty tube sheets. The
tube sheets are then epoxy coated on the water
side to protect the metal surfaces. Water heads
are rust-resistant, cast iron. Each condenser has
full refrigerant
with a purge valve and relief valve, according to
ASA-B9.
Each cooler and condenser is supplied with drain
and vent connections.
is too low, considerable oil may collect in the
riser and the horizontal header, causing the compressor to lose its oil and resultant damage due to
lack of lubrication.
Another danger is, when the compressor load is
C
increased, the oil that had collected during re-
duced loads may be carried as a slug through the
system and back to the evaporator, where a sudden
increase of oil concentration may cause
and damage to the compressor.
Any horizontal run of discharge piping should be
D
pitched away from the compressor approximately
li4”
gravity any oil lying in the header. Oil pockets
must be avoided as oil needed in the compressor
would collect at such points and the compressor
crankcase may become starved.
It is recommended
E
into a horizontal discharge header, rise above the
center line of the discharge header. This is necessary to prevent any oil or condensed liquid ‘from
draining to the top heads when the compressor is
not running.
F.
In designing liquid line, it is important that the
liquid reach the expansion valve with a minimum
of flash gas since this gas will reduce the capacity
of the valve. Because “flashing” can be caused
by a pressure drop in the liquid line, the pressure
1 code.
per ft. or more. This is necessary to move by
pumpdown
that
any discharge lines coming
capacity and is supplied
and replaceable
slopover
fil-
Page 24
Page 25
UNIT LESS CONDENSER
losses due to friction and changes in static head
should be kept to a minimum.
size
A good policy to follow is to
from the condenser to the receiver for sewer flow
operation. This allows any gas formed in the receiver to vent
bottled up in the receiver. Traps in this liquid
drain line should be avoided.
G
TYPlCAL ARRANGEMENTS
Page 26 illustrates a typical piping arrangement
involving a remote Aircon located at a higher
elevation than the compressor and receiver. This
arrangement is commonly encountered when the
Aircon is on a roof and the compressor and receiver are on grade level or in a basement equipment room.
In this case. the design of the discharge line is
very critical. If properly
dition. the gas velocity might he too low at reduced
loads to carry oil up through the discharge line
and condenser coil. Reducing the discharge line
size
would increase the gas velocity sufficiently
at reduced load conditions; however, when operating at full load, the
sized and thereby create an excessive refrigerant
pressure drop. This condition can
one of the two following ways:
1. The discharge line may
the desired pressure drop at full load condition
and an oil separator installed at the bottom of
the trap on the discharge line from the compressor.
2. A double riser discharge line may be used as
shown in Figure 14, Page 26. Line “A” should
be sized to carry the oil at minimum load con-
dition and line
at the full load condition both lines would
carry oil.
back to the condenser without being
sized
line
might be greatly under-
“B”
should be sized so that
the liquid line
-
Figure No. 13,
for full load con-
be
overcome in
be
properly sized for
unlike air cooled condensers or unequal piping is
used, the
drop may cause liquid to build up in one of the
condenser
capacity.
looped at the bottom and top of the vertical run.
This is done to prevent oil and condensed
erant from flowing back into
causing damage. The highest point in the
line should always be above the highest point
in the
a purging vent at this point to
s ihI< from
common
on
and
casrx
encountercxd
is
frccl
denser cx)i I to the receiver.
liquid buildup in the
common to this arrangement.
receiver is located as far below
outlet
of any
tal run:, they should be pitched down toward the
receiver.
common application where two or more separate
Aircons
Aircons
frigerant pressure drop through each unit is equal.
resultant unequal refrigerant pressure
coils, thereby
Notice
in all illustrations, the hot gas
cxondcnsrr coil; and it is advisable to include
the
system,
Figure
No.
15. Page> 26
application where the Aircon is located
cssc,ntialIy
rc~~civer.
is not
frcqucntly insuff’icic>nt
drai
To guard against gas binding in the receiver and
as possible. The liquid line should be free
traps
Figure No.
arc piped together on a single compressor.
First of all, it is very important that the two
have the same capacity so that the
the same
The dischargcl
t,oo
critical. The principal problem
with this arrangement is that
nag<>
of 1
or loops, and if
iqu
16,
Page 26 illustrates a third very
reducing
illustrates another very
lcvc~l
vertical
id rcfr
condenser
there
its effective
the compressor
discharge
rclcasc
as
lint
igclrant from
coil, which arc
noncondcIi-
the
comprcssoI
piping in this
distance
be certain
arc any horizon-
to allow
the
that the
the
condenser
line
rcfrig-
and
thcrc
co~i-
is
rc-
The above two points are particularly important
in applications where the refrigerant receiver is
directly beneath the air cooled condensers. If two
Secondly, the piping should be arranged so that
the lengths of run to and from each Aircon are
equal.
Page 25
Page 26
Page 27
Page 28
SERVICE INFORMATION
FIGURE 18
PROBLEM
lompressor
Compressor noisy or
vibrating.
High Discharge Pressure
will not run.
a) Main switch open.
Circuit breakers open.
b) Fuse Blown.
c)
Thermal overloads tripped or fuses
blown.
d) Defective contactor or coil.
e)
System shut down by safety de-
vices.
f)
No cooling required.
g) Liquid line solenoid will not open.
h)