McQuay PTAC Installation Manual

Installation & Maintenance Data
16" x 42" x 133/4" Deep BWS Wall Sleeves
Single wall sleeve - PN/107026401, 15 Pack - PN/107026415
Remove protective film (if provided) before sleeve installation.
IM 825
Group: PTAC Part No.: 107028201 Date: January 2006
Wall opening requirement
Before installing the unit, check that the cabinet/wall sleeve slides into the rough opening unobstructed. A lintel must be used in masonry walls to provide support over the opening. The rough
1
opening must measure 16
/4" high x 42 1/4" wide (413mm x 1023mm), see Note 5 in Figure 2. If a subbase is not used, the opening should be a minimum of 3" (76mm) off the floor. The subbase is available in 3" (76mm) or 4" (102mm) heights. For units with hydronic heat,
1
the subbase is 8
/4" high (210mm). Subbases have leveling legs that
provide 1" (25mm) of additional height.
Attaching cabinet wall sleeve to subbase
After the subbase is set in place and the plumbing and/or electrical
rough-in is complete, install the cabinet/wall sleeve.
1. Install cabinet/wall sleeve as described on pages 2 through 4.
2. Attach the subbase to the cabinet/wall sleeve using the clips
provided.
3. Secure the two sections by installing the clip screws supplied
with the hardware bag.
4. Caulk indoor/outdoor perimeter of the cabinet/wall sleeve with
resilient caulk such as silicone.
5. Complete all electrical and/or plumbing connections.
Figure 2. Unit with Subbase
3/
8" (Stamped) Louver
11/8" (Architectural) Louver
42" (1067mm)
Top View
43" (1092mm)
133/4"
(349mm)
81/4" (210mm)
Figure 1. Wall Sleeve
Tinnerman clip locations
Note: Wall sleeve shown with insulation installed.
Notes:
1. Subbase Side Dimension: Electric: 4 Hydronic: 0" to 133/4" (0mm to 349mm)
2. Subbase Height Dimension: Electric: 3" to 4" (76mm to 102mm) with 0" to 1" (0mm to 25m) leveling screw Hydronic: 8" (203mm) with
3. Unit pictured with subbase installed. Subbase is optional on 208V and 230V units. Subbase is standard on all 265V units and units with hydronic heat. Hydronic subbase is flush with the front of the cabinet. Electric subbase is flush with wall sleeve.
4. Subbase extends to front edge of unit when furnished with hydronic heat.
5. Opening needs to be 16 frame.
6. Subbase side channels are adjustable from 4
3
/8" to 133/4" (111mm to 349mm)
1
/4" (6mm) to 11/4" (32mm) leveling bolts
5
/8" x 425/8" (422mm x 1083mm) when using a louver
1" (25mm)
3
/8" to 133/4" (111mm to 349mm).
Front View
411/2" (1054mm)
See Note 2
17"
(432mm)
3/
4" (19mm)
22°
Side
View
1/
4
8
(210mm)
©2006 McQuay International IM 825 / Page 1 of 5
See
"
Note 1
22" (559mm)
16"
(406mm)
Wall sleeve installation – frame and brick
A corrosion resistant cabinet/wall sleeve is provided for each unit. The cabinet/wall sleeve is shipped in a separate carton, in a multipack of 15 or in a single carton with the heating/cooling chassis.
The standard cabinet/wall sleeve is designed to be installed easily into a variety of wall constructions. Note: The center of gravity is 10 (260mm) from the rear face of the wall sleeve. Be sure to insert the wall sleeve into the wall at least 10
1
/4" (260mm), or other support must be employed. A factory supplied subbase is available to support the wall sleeve. Follow the installation procedures as described below.
1.
Clean debris from the rough opening that may interfere with installation.
Remove protective film (if provided) before sleeve installation.
2. If the unit is supplied with a subbase, install it before installing
the cabinet/wall sleeve (see IM 419 or IM 420).
3. If the unit is provided with a drain kit (optional), refer to IM 430-
4 for installation procedure.
4. Place a thin pad of soft mortar on the bottom plate of the rough
opening and slide the cabinet/wall sleeve into the opening. The cabinet/wall sleeve must be recessed enough from the outside face of the building to accommodate the outside louver. This recess is
3
/8" (9.5mm) for stamped louvers and 11/4" (32mm) for
architectural louvers. The louver must be flush to the exterior surface after it is attached to the cabinet/wall sleeve. Note: The wall sleeve is not intended to replace the lintel.
5. Level the cabinet/wall sleeve in both directions and secure it by
anchoring with appropriate fasteners. A
5
/16" (8mm) hole is provided on each side, 2" (51 mm) down from the top and 2" (51mm) in from the rear of the cabinet/wall sleeve. If additional holes are required to secure the cabinet/wall sleeve, see Caution below.
CAUTION
!
Do not drill holes in the base of the cabinet/wall sleeve. Where a subbase is used, secure wall sleeve to subbase with clips provided.
1
/4"
6. Caulk the cabinet/wall sleeve along the wall opening on the inside and outside perimeter. Do not plug the weep holes with caulk. Caulk should be resilient, non-hardening such as silicone.
Figure 4. Frame and brick with cord connection
STEEL LINTEL (BY OTHERS)
OUTDOOR
LOUVER
3
/4"
13
(349mm)
17"
(432mm)
3" MIN. (76mm)
FINISHED
FLOOR OR
CARPET
81/4"
(209mm)
ROOM
CABINET
16"
(406mm)
WALL SLEEVE
WALL
RECEPTACLE
BY OTHERS
MOUNTING
SCREWS BY
INSTALLER
CAULK PERIMETER
Figure 5. Frame and brick with hydronic subbase
Figure 3. Frame and brick with standard electrical subbase
STEEL LINTEL BY OTHERS
43/8"
(111mm)
133/4"
(349mm)
17"
(432mm)
SEE NOTE
FINISHED
FLOOR OR
TOP OF
CARPET
81/4"
(209mm)
16"
(406mm)
ROOM
CABINET
SUBBASE
LEVELING LEG
POWER SUPPLY CONNECT
(ALTERNATE ENTRY)
WALL SLEEVE
Note: Standard subbase is available in 3" or 4" (76 mm or 102 mm) height. Leveling legs provide adjustment of 1" (25 mm).
OUTSIDE
LOUVER
MOUNTING
HOLES BY
INSTALLER
CAULK PERIMETER BOTH INDOORS & OUTDOORS BEFORE INSTALLING LOUVER
17"
(432mm)
HYDRONIC HEATING COIL
81/4"
(209mm)
FINISHED FLOOR OR CARPET
LEVELING LEG
81/4"
(209mm)
ROOM
CABINET
ELECTRICAL
CONNECTIONS
STEEL LINTEL (BY OTHERS)
1" MIN. (25mm)
16" (406mm)
ALTERNATE
133/4"
(349mm)
WALL SLEEVE
OUTDOOR
LOUVER
MOUNTING
SCREWS BY
INSTALLER
CAULK PERIMETER BOTH INDOORS & OUTDOORS BEFORE INSTALLING LOUVER
SUBBASE SIDE
CHANNEL
IM 825 / Page 2 of 5