McQuay PFS-215B Installation Manual

Introduction

McQuay charged, tested and ready for installation. Each unit consists of a water-cooled condenser with integral subcooler, multiple accessible semi-hermetic single screw compressors. replaceable tube shell-and-tube evaporator. and complete refrigerant piping. Liquid line components included are manual liquid line sightglass/moisture heaters, and an advanced fully integrated microprocessor control system.
automatic operation. (the high and low pressure controls are external from the electrical control center). Compressors are protected by solid-state overload protection and over temperature protection.
StarGateTM
The electrical control center includes all safety and operating controls necessary for dependable
Field
water-cooled chillers are completely assembled. factory wired. evacuated.
shutoff valves. charging valves. filter-dryers. liquid line solenoid valves,
indicators. and electronic expansion valves. Other features include compressor
installed fused
disconnect Sw itch (furnished by
others) offers additional protection.

Receiving and Handling

Inspect the unit immediately after receipt for all claims for handling and shipping damage are shipping extreme care when rigging the equipment to prevent damage to the control center. or refrigerant piping. See Dimensional Data for the center
eyes are located (see Figure I ). Use spreader bars between the ri control center.
skid
in place until the unit is in final position. This will aid in handling the equipment. Use
Lift the unit
by
fastening the ri
gging
Figure I, Rigging Eyes
possible
of gravity of the
hooks to
damage.
the
responsibility
the
four corners of the evaporator where the rigging
The unit is shipped FOB factory and
of the
consignee. Leave the
unit.
gging lines to prevent damage to the
IM
663
Rigging eyes
Rigging eyes
3

Installation

Installation must be performed by qualified personnel who are familiar with local codes regulations, and experienced with this type of equipment
Start-up by
excluding Mexico. Two weeks prior notification of start-up is required. The contractor should obtain a copy of the Start-up Scheduled Request Form from the sales representative or from the nearest McQuayService office.
McQuayService
is included on all units sold for installation within North America

Location and Mounting

Mount the unit on a level concrete or steel base. Service clearance (at either end of the unit) is 14 feet for units with Evaporator and condenser tubes are rolled into the tube sheets to permit replacement. Clearance at all other points, including the top, is 3 feet.
Make certain the floor or structural support is adequate to support the full operating weight of the complete unit. Optional rubber-in-shear pads. or spring isolators can be ordered for use under each corner of the base members. although mounting holes are provided in the unit support at the four corners.
12-foot
long standard shells and 18 feet for units with
It is not necessary to bolt the unit to the mounting slab or frame work:
16-foot
long optional shells.

Compressor Condensation

Condensation occurs on the compressor surface when the temperature of the compressor surface is
lower than the ambient dew point temperature. Drain pans with drain connections are provided underneath each compressor to collect the condensate. The compressor motor housing extends past the drain pans. Install a floor drain close to the unit to collect condensate from motor housing and condensate pans.

Vibration Isolators

Vibration isolator pads are shipped with the unit for field installation. These pads provide minimal
isolation. Vibration isolators are recommended on all upper level installations where vibration transmission is a consideration. When vibration isolators are used. install springs under the main unit supports. Adjust spring so the upper housing clears lower housing by at least more than
Install vibration eliminators in water piping to reduce piping strain. vibration. and noise. Table
spring and rubber-in-shear isolators for all PFS unit sizes
4
1/2"
(1
3mm).
If hold-down bolts are not used. install a rubber anti-skid under isolators.
1/4"
(6mm) and not
l
lists
IM 663

Evaporator and Condenser Water Piping

PFS evaporators and condensers are equipped with either victaulic or flange connections. The installing contractor must provide matching connections.
Remove the solid-state temperature sensor and thermostat bulbs from the wells to prevent
damage to those components when welding on the victaulic or flange connections.
Connect the condenser with the inlet
condenser water will discharge from the top connection.
Support piping to reduce weight and strain on the fittings and connections. Be sure piping is adequately insulated.Install a cleanable piping. install enough without draining the complete system.
shutoff
valves
water
entering at the bottom to maximize subcooling. The
20-mesh
to permit draining water from the evaporator or condenser
water strainer in evaporator and condenser water
CAUllUN
Freeze Notice: Neither the evaporator nor the condenser is self-draining. Both must be blown out.
I
Include thermometers at the inlet and outlet connections and air vents at the high points of piping. The water heads can be interchanged (end for end) allowing water connections to be made at either end of the unit. Use new head gaskets when interchanging water heads. When water pump noise is objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration eliminator sections in the condenser inlet and outlet water lines are not normally required. Where noise and vibration are critical, and unit is mounted on spring isolators, flexible piping connections are necessary.

Water treatment

If unit is operating with a cooling tower, clean and flush cooling tower. or bleedoff is operating. Atmospheric air contains many contaminants which increases the need for water treatment. The use of untreated water may result in corrosion, erosion, sliming, scaling, or algae formation. A water treatment service is recommended. responsible for damage or faulty operation from untreated or improperly treated water.
McQuay
Make sure tower “blowdown”
International is not

Head pressure control, tower system

The minimum entering water temperature to the condenser must not be lower than 70°F (2 Use a three-way bypass valve around the tower to modulate the condenser water flow.Figure 6 shows a three-way pressure actuator water regulating valve used for cooling applications. This regulating valve will assure an adequate condensing pressure if the inlet condenser water temperature falls below 70°F). An optional valve or a varible speed condenser pump.
IM
663
AOX-4
board located in the
MicroTech
panel will control a cooling tower bypass
I _
1°C).
7

Head pressure control, well water system

When using city or well water for condensing refrigerant, install a normally closed direct acting water regulating valve in the outlet piping of the condenser. This regulating valve will assure an adequate condensing pressure if the inlet condenser water temperature falls below 70°F. The condenser service valve provides a pressure tap for the regulating valve. The valve can modulate in response to head pressure. On shutdown. the valve closes. preventing water from siphoning out of the condenser. Siphoning causes condenser waterside drying and accelerates fouling. If a valve is not used, Figure 7
illustrates the recommendation of a loop at the outlet. Size the loop height (H) to offset the negative
pressure caused by the siphoning effect. A vacuum breaker may be required.
Figure 6, Bypass valve
Figure 7, Well Water System
Loop required when no regulating valve is used
V-d
H
Kl-
r-
ld
f
To drain
/
T
Direct acting water regulating valve
Service valve
Y
From main
+ condenser
pump

Relief Valve Piping

Follow the requirements of ANSUASHRAE Standard 15- 1994 for relief valve piping. The condenser relief valve assembly consists of a tree valve and two relief valves. The tree valve must be fully front or back seated to ensure only one relief valve is available for discharge.
8
IM 663

Temperature and Water Flow Limitations

“F
(-8.9”C)
PFS units are designed to operate in conditions from temperature on the evaporator side and 70°F (2 I. 1 “C) to 95°F (35°C) entering water temperature on the condenser side.
Glycol in the evaporator is required on all applications below 40°F (4.4”C) leaving evaporator
fluid temperature. The maximum allowable water temperature to the cooler in a non-operating cycle
is
10j°F (40.6”(Z).
(46.1 “C). control. Flow rates above the maximum values will result in unacceptable pressure drops. excessive nozzle and tube erosion and possibly cause tube failure.
The non-operating leaving condenser water temperature maximum is 115°F
Flow rates below the minimum values may cause freeze-up problems, scaling and poor
2 1
to 55°F (1O’C) leaving water

Evaporator Freeze Protection

When freeze protection is a concern, do the following:
1. If the unit will not be operated during the winter. drain and flush the evaporator and chilled water
piping with glycol Drain and vent connections are provided on the evaporator.
2.
When using a cooling tower, add glycol solution to the chilled water system. Freeze point should
be approximately 10°F
Note: Freeze damage is not considered a warranty failure and is not the responsibility of McQuay
3.
International.
Insulate field water piping. especially on the chilled water side.
(5.6”C) below minimum design ambient temperature.

Condenser Protection and Design Considerations

If pond or river water is used as a condensing medium and the water valves leak, the condenser and liquid line refrigerant temperature could drop below the equipment room temperature on the cycle. This problem occurs when cold water continues to circulate through the condenser and the unit remains off due to satisfied cooling load.If this occurs:
1.
Cycle the condenser pump off with the unit.
2.
Verify the liquid line solenoid valves are operating properly.
“off

Chilled Water Thermostat

The PFS water-cooled chiller is equipped with the MicroTech leaving water controller. Be careful when working around the unit to avoid damaging lead wires and sensor cables. Check lead wires before running the unit. Avoid rubbing the lead wires on the frame or other components. Verify the
lead wires are firmly anchored. If the sensor is removed from the well for servicing. do not wipe off
the heat conducting compound supplied in the well.

Refrigerant Charge

All units are designed for use with HCFC-22 and are shipped with a full operating charge. The
operating charge for each unit is shown in the Physical Data Table.
IM
663
9
Loading...
+ 18 hidden pages