McQuay PE046W Installation Manual

USED ON ALL PE, PH. PJ, PG
TPE, TPF, TPH, TPJ MODELS
THROUGH DECEMBER
31,1982
USED ON ALL
AND PF UNITS SINGLE AND DUAL
MODELS THROUGH DECEMBER
PE046W-06OW
GENERAL
Prior to January 1, 1982 a number of different control panels were utilized on the model PE and PF centri­fugal water chilling units. None of these panels are now in production, this bulletin will provide general information on these superseded panels to assist ser­vice personnel in understanding the operating se­quence as well as providing control settings and functions.
Each unit control oanel contained necessarv
operating
and
1.
Leaving Water Cycling Thermostat (CT or LRT)
2.
Guardistor Motor Protection High Pressure Cutout (HP)
3.
4.
Low Pressure Cutout
5.
Oil Pressure Differential Switch (OD)
6.
High Oil Temperature Thermostat (OT or HOT)
7.
Vane Closed Switch (VD)
8.
Low Pressure Override Switch
9.
Oil Pump Time Delay Relay (OTD)
10.
Oil Pump Motor Capacitor
11.
Oil Pump Motor Contactor Oil Pump Motor Overload Relays (OL)
12. Electronic Control Module (Temperature and
13. Current)
Generally, control item identifications and identifying
symbols on wiring diagrams were maintained the same from panel to panel; however, there were cases where a control with the same function did carry a different symbol than had been used on similar panes of an
earlier design. The table of operating and safety con­trols starting on page 14 will identify controls and also show where differences did exist.
Notes
1.
2.
3.
-
The information following is of a general nature and applies to all control panels illustrated on pages 4 through 6, except for the temperature/ motor load control modules. Details on the dif­ferent control modules which were used are pre­sented starting on page 7.
When functions covered by a specific control panel differ from the write-up below, these differences will be covered with the control panel details on
pages 4 through 6.
A control summary table is presented starting on
page 14, the summary contains the control identifi­cations and other details of protection and operat­ing controls used in the panels.
controls.
All panels basically included:
(GR)
(LP)
(LPO)
(1
M)
protective
OPERATING SEQUENCE
The following operating sequence generally applies to control panels built through January 1, 1982. Informa-
/l/82
tion on panels utilized after 1 rent product manuals.
Assuming all interconnecting control and power wiring connections to the panel are complete and the off” switch is in the “on” position, the operating
controls will be allowed to call for unit operation.
is contained in cur-
“on-
NOTE
If power to the control panel is supplied by a separate transformer, it should be rated 2KVA with an inrush rating of The disconnect switch in the power lines supplying this transformer must be marked to prevent the switch from being opened and de-energizing the control circuit. Oil heaters are required whenever the unit is shut down. It is most important that power is available to the heaters at all times the unit is not operating.
An open section in the control circuit has been provided for connection of chilled and condenser water pump starter interlocks and flow switches. The purpose of these interlocks is to prevent the compressor from starting unless both chilled and condenser water pumps are running and flow has been established.
The cycling thermostat with its control bulb located in the leaving chilled water line will, when cooling is re­quired, close its contacts and energize the starting sequence built into the control panel (assuming the chilled water pump is running and flow has been estab­lished) closing of the cycling thermostat contacts will first call for oil pump operation by energizing the pump motor contactor and the oil cooler solenoid valve through the clutch coil contacts on the oil time delay relay (OTD).
Once the oil pump is running, two switches and a timing relay must be satisfied before the compressor will be allowed to start.
1.
The oil pressure differential switch will close when
the oil/suction pressure difference is 50 psig or
greater. If adequate oil pressure is not developed,
this switch will not close and the compressor will be
prevented from starting.
Before the compressor can start, the inlet guide vanes must be closed. The vane closed position is sensed by a pressure switch which is activated when the unloader piston has moved the guide vanes to the fully closed position capacity). Until the vanes are in the minimum
load position, the compressor starting position in
the control circuit will not be energized. The control circuit also incorporates a timing relay
(OPT) which will stop the oil pump if adequate oil pressure is not developed or the compressor does not start within 60 seconds from the closing of the cycling thermostat.
Once adequate oil pressure has been developed and the oil differential and vane closed switches have
closed, the condenser pump will be energized by the condenser pump relay contacts (HWR). The con­denser pump must cycle with the compressor. A
second set of condenser pump relay contacts com-
plete a circuit to the motor control relay(s) (MCR), energizing it or them and as a result energizing the compressor motor starter to bring the compressor on line.
Once the compressor is running, the temperature control module will direct the opening or closing of the compressor suction inlet guide vanes as require­ments for more or less cooling are relayed by the sensor located in the leaving chilled water line.
12KVA.
(10
percent
2
In addition to temperature, the current section of the control module is constantly monitoring the amount of current being drawn by the compressor motor. The current limit is manually set for the required current limit level (percent of rated load amperes). Regardless of demands for added cooling capacity, the current sensing section of the module will not permit the compressor vanes to open beyond the point where added capacity will require a value of motor current which would exceed the current limit setting.
When load conditions change and the need for less cooling is relayed to the temperature control section through the sensor in the leaving chilled water, com­pressor capacity will be reduced as the building load drops. When the compressor has been unloaded to 10 percent and the load continues to fall, leaving chilled water temperature will also drop until the setting of the cycling thermostat is reached
below design leaving water temperature), at this point the contacts in the cycling thermostat will open and the following sequence will take place:
1.
The condenser pump relay will be de-energized and the condenser pump will stop.
The motor control relay will be de-energized,
2. opening the compressor starter contacts and stopp­ing the compressor.
The oil pump will continue to run for an additional
3. 30 seconds after the cycling thermostat contacts open. Keeping the oil pump running after the com­pressor has stopped will accomplish the following:
a. Bearing lubrication is assured during the spin-
down period.
b. If the compressor cycled off before the vanes
were at minimum load position, the unloading piston will be driven toward the minimum load
position. (The vanes must be at the minimum load position before the compressor can start on the next call for cooling.
4.
The compressor and oil sump heaters are energized and stay on until the compressor starts again.
5.
A timing relay is incorporated into the control cir­cuit to limit compressor starts to not more than one every 40 minutes (timed from start). If the com-
pressor operating period prior to shutdown was
less than the time setting, it will be necessary for the time remaining on the timer to elapse before the compressor will be permitted to restart. If the
running time prior to shutdown was equal to or greater than the time setting, the compressor will be permitted to restart any time the cycling thermo­stat calls for cooling. A second type of relay was used on later units where a 20 minute interval from
stop to start was utilized.
In
the event of a power failure during compressor operation, the compressor bearings will be protected by oil stored in the emergency cylinder. The spring loaded piston in this cylinder will force oil into the
various lubrication passages and assure that all bear-
ings are lubricated during the
The exception to the above paragraph is the
through 135W units. These units utilized a solenoid valve “SD” and condensing pressure to force oil
from the supply line,oil filter and oil cooler into
the compressor bearings.
GUARDISTOR
The compressor motor is protected by the Guardistor
MOTOR PROTECTION
)
spindown
period.
(3’F
PE095W
motor protection circuit. This circuit utilizes ther­mistors buried in the motor winding to sense tem­perature changes. At a preset temperature the resis­tance of the thermistor increases rapidly, this increase in resistance and the resulting voltage drop causes the guardistor relay to open and in turn to de-energize relay
“Rl”
which opens the operating circuit and
energizes motor control relay (MCR). The Guardistor circuit, once opened, requires manual
resetting before the compressor can be restarted. If power to the control panel is interrupted for any reason, the circuit will open and will have to be
manually reset once power is restored to the control panel.

CAPACITY CONTROL MODULE

The capacity control module, regardless of the type
incorporated in the control panel, will perform the
functions described below. Where a given control
performs in a different manner, the differences will
be covered with details for that particular module
starting on page 7. The control module is powered from a 5 volt supply
(through a current transformer and resistor located in the compressor starter).
The control in response to signals relayed from a sen-
sor located in the leaving chilled water will regulate
compressor capacity by opening and/or closing two
solenoid valves “SA” (unload) and “SB” (load).
Opening and/or closing these valves permits oil pres-
sure to build up or drain from opposite ends of a
cylinder containing a floating piston. The compressor
suction inlet guide vanes are linked to the piston and
are positioned by moving it in one direction or the
other until the vane opening is adequate to satisfy
the load requirements.
The temperature control module on a call for increased
cooling capacity can continue to open the suction inlet
vanes until current drawn by the motor reaches the
setting of the current limit control. Once this current value is reached, the current limit section of the control will not permit additional loading of the compressor.
The current limit is adjustable from 40 to 100 percent
of rated load current.
The temperature controller can increase or decrease
compressor capacity through solenoid valves
and “SB”.
follows.
Loading Unloading Holding
Some older units included solenoid valve “SC”, this
valve was actuated by a low pressure switch and was
utilized to override the normal control and unload the
compressor on a sudden drop in suction pressure,
such as might be caused by a slow opening or sticking
expansion valve. On later units the “SC” valve was
eliminated and the low pressure override switch
actuated valve “SA” directly.
Most of the later panels included a service switch to permit override of the capacity control and allow manual control of compressor load level. This switch
has been included as a tool for the service mechanic and should not be utilized for any other purpose.
3
The valve action to load or unload is as
-
SB energized, SA de-energized
-
SA energized, SB de-energized
-
SA and SB de-energized
de-
“SA”
Control Panels Used on Models
Through December
SOLID STATE
TEMPERATURE/CURRENT
LIMIT CONTROLLER
SEE PAGE 8
_,
PE063,079,100
31,1982
During the production life of this control panel improvements were made. Among these improvements were a number of different temperature/current limit control modules. The different modules used are shown below with page references for
\
AND 126
ial
information.
TUBE TYPE TEMPERATURE/ CURRENT LIMIT
CONTROLLER
SEE PAGE 7
NOTE
*%mii
I
SOLID STATE
TEMPERATURE/CURRENT
LIMIT CONTROLLER
SEE PAGE 11
1.
Panel power supply - l-60-1 15V
2. Disconnect switch in power supply to the control panel must be on at all times. The oil heaters receive power through this panel.
3. If panel power is supplied through a transformer, it must have a minimum rating of 2 KVA with an inrush of 12 KVA.
4. All panels incorporate a timer to limit starts to a maximum of three (3) in a two hour period. (40 minutes between starts). Later panels 20 minutes between stop and start.
5. Earlier versions of this panel included a high discharge temperature cutout (“HDT”).
SOLID STATE TEMPERATURE/CURRENT LIMIT CONTROLLER
SEE PAGE 9
6. Later versions included a low oil temperature cutout (“LOT”).
7. Later versions included a system monitor relay and indicating light. The system monitor was utilized to indicate a problem in the system external to the unit control box. For example, the compressor starter open because its overload relays have tripped.
8. Protection against damage caused by compressor surging was added and a lockout relay and indica­ting light was incorporated on later versions of the panel. This was labeled “Surg Gard”.
4
This Control Panel was used on all models PE075W through 135W units produced.
SOLID STATE TEMPERATURE/ CURRENT LIMIT CONTROLLER
SEE PAGE 11 THIS CONTROL
MODULE IS USED AS A RETROFIT DEVICE TO
REPLACE THE ORIGINAL TUBE TYPE WHICH IS NO LONGER AVAILABLE.
1. Panel power supply - 1-60-l
15V
2. The disconnect switch in the power supply to the control panel must be on at all times. The oil
heaters receive power through this panel.
3. If panel power is supplied through a transformer,
it must have a minimum rating of 2 KVA with an inrush of 12 KVA.
4. The control panel includes a time delay relay limit compressor motor starts to a maximum of three (3) in a two hour period. (40 minutes between starts.
)
to
5. Panel includes a compressor start time delay relay (CTD) which is set for 5 seconds. This permits oil pressure to build up and bearings to be lubricated prior to having the compressor start.
6. The compressor is protected during
spindown after a power Failure by solenoid valve “SD”. This is a normally open valve when its coil is de-energized with this valve open condenser gas pressure forces oil from the oil supply line and compressor oil passages to assure bearing lubri­cation.
5
Loading...
+ 11 hidden pages