McQuay PE046 Installation Manual

Page 1
Page 2
Page 3
Page 4
GENERAL
UNIT NAMEPLATE
The Model PE less condenser centrifugal water chiller has been factory assembled, checked and shipped with a holding charge of R-12 refrigerant. The purchase price of this equipment includes checkout of the unit and initial startup by a McQuay service technician. An integral part of the startup procedure includes instruc­tion of responsible personnel in the operation and maintenance of this water chilling unit.
It is most important that this equipment be properly operated and maintained if it is to perform the operating service it was designed and built to provide.
McQuay offers equipment maintenance and/or inspec­tion programs that can be tailored to fit individual job requirements. Information on the various service pro­grams is available through the McQuay Service De­partment or your local McQuay sales representative.

WARRANTY

The McQuay Model PE water chiller unit is covered by a standard published warranty which covers parts only. A complete published description of that warranty and its limitations is provided in a warranty certificate included with each unit.
First year warranty labor can be purchased separately, check your local McQuay sales representative to establish what additional coverage (if any) was pur­chased for your unit.
Whenever requesting information or assistance on the Model PE chiller, the unit model number, shop order number, and serial number should be copied from the unit nameplate. A reproduction of this nameplate is
shown in Figure 3.
HOLDING
CHARGE
ONLY
STYLE SERIAL S.O. NO. PE-5210
\
-~
lPE5210-GO1
5NAl234~0
FACTORY CHARGED
~
LBS. REFRIGERANT
LEAK TEST PRESSURE 100
MOTOR - COMPRESSOR CONTROLLER
AND OVERLOAD PROTECTION FIELD
SUPPLIED. SEE SPEC.
R12
PSIG
PE-D4
mccbuw k.
198PlMHOl A
MADE IN U S A
Note Typical Serial Number
l Prior to January 1, 1983 =
1,
l
After
January
1983
LZ1320
=5NA1234500

INSTALLATION

Information pertaining to the installation of Model PE
water chilling units is available in Installation Bulletin
number PE-L-Gl. A copy of this manual was included
in the envelope shipped with the unit.
MODEL CODE
PE
063J
AN 30 R G A 2 L
UNlT FA::::E-I 1
SPEED CODE
MOTOR CODE
COMPRESSOR MOTOR VOLTAGE
~k;;~~;~;::~R
TYPE OF CHILLER TUBING
CHILLER CODE
FIGURE 3. UNIT NAMEPLATE

OPERATING INFORMATION

OPERATOR’S RESPONSIBILITY
1.
Before operating the Model PE unit, become famil­iar with the machine and accessory equipment.
2.
If possible, arrange to attend a McQuay centrifugal operators school.
After the unit has been checked out and approved
3. for operation by a McQuay centrifugal service technician, work with him to learn how to prepare the system for startup. Start and stop the machine a number of times while observing the operation of the interlock function(s). The interlock circuit must
be satisfied before the compressor will run. After
operating the unit, place it in the shutdown mode.
Monitor operation and periodically inspect the
4. equipment, making routine adjustments where essa ry
nec-
Maintain a log of operating conditions on a daily
5.
basis. (Log sheets are available in pad form from
McQuay.
Page 5
PRE-START SYSTEM CHECKLIST
p&q
All of the following will have been checked out by the during the initial startup procedure. *Items should always be verified by the unit opera­tor on a routine basis during the operating season.
A. UNIT
"1.
All service valves are in the operating position. The control circuit is energized.
“2.
The oil heaters have been operating for a
“3.
minimum of 24 hours. Oil should be hot (approximately 130 to 140
“4.
The oil charge is visible in the sight glass. (Mark level on sight glass while machine is shut down, check level weekly).
Check control circuit, verify that all safety
“5.
switches interrupt compressor starter holding coil.
“6.
The water flow through the condenser is correct. (This can be checked from condenser water pressure drop curves available from
McQuay).
reduced by a plugged strainer which can
cause operating problems and nuisance outs. New systems are generally susceptible
to blocked water strainers from foreign mate-
rial washing out of the piping.
B. ELECTRICAL
McQuay
On any system, water flow can be
startup technician
F).
trip-
All load equipment is operative (main system
“3.
fans, pumps, etc.). Condenser fan(s) and controls are operative.
“4.
Condenser water bleed and water treatment
“5.
are adequate (if required).
STARTING
When the 115 volt AC control power supply is applied to the control panel for the first time or after a power failure has occurred, the following will take place.
1.
The oil sump heater(s) will be energized. The external failure light will glow and the external
2. “R9”)
alarm circuit (energized through Relay
activated. Push the RESET Button on the control panel. The
3.
external failure light will go out and the external alarm circuit will be reset (de-energized).
Set the compressor “ON-OFF” switch to “ON”, the
4. light in this switch will glow. The unit control circuit
has been re-established.
The unit safety circuits have now been reactivated
5. and the operating portion of the control circuit is
ready to function. (Before the operating portion of
the control circuit can function, the chilled water
pump will have to be running). The “LRT” (unit cycling thermostat) will, on a call
6.
for chiller operation;
Start the oil pump. (Providing 20 minutes have elapsed since the unit last stopped and the anti recycle time delay has timed out and closed its contacts).
will be
1.
The wire size is correct.
2.
The phase sequence is correct.
“3.
Voltage within plus or minus 10 percent of rated compressor nameplate voltage.
“4.
Phase voltage unbalance 3 percent or less.
5.
All wiring connections correct per the unit wiring diagram.
6.
All electrical connections are tight and made
with copper conductors and lugs.
“7.
All starter parts move freely and contacts meet evenly.
8.
Motor overloads correct size (filled with dash-
C.

SYSTEM

“1. The condenser pump is rotating in the right
direction.
“2. The condenser pump and motor are lubricat-
ed.
When the oil pump develops oil pressure ade­quate to close the oil differential pressure switch
“OD”
(50
psig above suction pressure), the
switch will close. A time delay relay “PLT” injects a 10 to 60
second time delay into the compressor starting control circuit and prevents this portion of the circuit from being energized while oil pressure is being developed. At the end of this delay, if the vane closed switch gized the condenser pump relay “CWR” the pump starter interlock contacts will close and energize relay “MCR” located in the unit starter. The compressor starter will now be energized and the compressor will start.
“VC”
has closed and ener-
OPERATING
1. With the compressor running, capacity is controlled by positioning variable inlet vane(s) located in the suction gas inlet to the compressor. Opening the vane(s) allows the compressor to pump more gas and, as a result, increases capacity. Closing the vane(s) reduces gas flow and reduces capacity. The
5
Page 6
capacity control system is capable of modulating the vane position to any capacity from 10 percent to 100 percent.
The inlet vane(s) are controlled by means of 3 different devices. The capacity will always be controlled by temperature unless the temperature control is overridden by Items “b” or “c” below.
a. A temperature sensor located in the leaving
chilled water translates temperature changes into an electrical signal and through the control module loads or unloads the compressor (opens or closes the vane(s).
b. The solid state control module in conjunction
with a current transformer and resistor located in
the compressor motor starter, senses and will limit current drawn by the compressor motor depending on the setting of the current limit control. This controller will override the tempera­ture control and will, whenever motor current exceeds its setting, open or close the compres­sor vane(s) in response to changes in current. Whenever the motor current is less than the
setting on the current limit controller, unit capacity control is returned to the temperature sensor. The current limit control can be set to limit current from 30 to 100 percent of name­plate full load current. The control is easily adjusted by a knob on the face of the control
module.
c. The low pressure override switch “LPO” built
into the unit control panel senses suction pres­sure and is set to open at 2 to 5 psig above the low pressure safety switch. Whenever the set­ting is reached, the override switch opens and in turn de-energizes relay
gizes
“SA” and de-energizes “SB” solenoids in the four way valve. Full oil pressure is applied to the unloader piston driving the vanes closed. This action will in most cases catch a momen­tary “sudden” drop in suction pressure such as
may be caused by a slow acting expansion
valve, a drop that without this unloading feature
would open the low pressure switch and stop
the compressor. The “LPO” pressure switch is
automatically reset, it will close when the pres­sure rises to a safe limit and return control of capacity to the temperature sensor.
During normal operation, the compressor will con­tinue to operate and unload to a minimum of 10 percent until the cycling thermostat is satisfied. When this occurs, the condenser relay the motor control relay “MCR” are de-energized and the compressor motor is stopped.
The unit oil pump will continue to run for a minimum of one minute after the compressor starter has been de-energized. This will assure
“R4”,
this in turn ener-
“CWR”
and
adequate lubrication for the compressor during the spin down period.
In addition, on the next call for cooling, the compressor capacity control vanes must be in a closed position before the compressor is allowed to restart. Contacts “VD” (auxiliary contacts located in the compressor starter) through relay
energize the unload portion of the unit capacity
control circuit. If the vanes were not fully closed
when the compressor was stopped, oil pressure
will continue to be applied to the unloading piston
through the “SA” portion of the four-way solenoid
valve. This pressure continues to drive the vanes to
the closed position while the oil pump is still running. This will permit the compressor with a minimum delay to start on the next call for cooling. (The compressor will not start until the vanes are in the closed position).
Rapid cycling of centrifugal compressor motors is not desirable. A time delay through relay “TDR” is built into the unit control circuit to prevent rapid cycling. Relay “TDR” will prevent the compressor from restarting for a period of 20 minutes after the
compressor is stopped unless the “automatic re­start after power failure with reduced timed off
cycle” accessory option is used.
In the event of a power interruption during unit
operation,
damage by an emergency oil reservoir and spring
loaded piston. During normal operation enough oil
is stored in the emergency cylinder to lubricate the
bearings during spindown. The oil is forced into the various passages by a spring loaded piston con­tained and compressed in the emergency oil cylin­der. ‘The spring is compressed by normal machine oil pressure while the compressor is running and on a loss of power is available along with the piston to act as an emergency oil pumping device.
CONTROL CENTER The control center contains all of the unit protective
controls and most of the operating devices. Table 1 “Control Summary” (on page control information including electrical diagram sym-
bol, control description, setting, reset information, location, signal light, and information on the control
function.
Eleven indicating lights are utilized on the unit control panel. Nine of these lights are normally out and only glow when a safety circuit has tripped.
Repeated tripping of a given control should be investi­gated by a competent air conditioning serviceman or by a
McQuay damage. Details of the control center are shown in Figure 5.
the compressor is protected against
15)
contains general
service technician to avoid costly
“R8”
Page 7
Page 8
Two important safety circuits incorporated in the control system are:
1.
GUARDISTOR positive motor protection against damage from motor overheating. Thermistors buried in the motor winding are super sensitive to changes in motor winding temperature. These thermistors have been calibrated to de-energize the “GDR” (guardistor
relay) whenever the motor winding exceeds the maximum allowable temperature.
The motor protection system, because it is sensing
internal motor winding temperature, provides posi-
tive protection against motor damage from such
heat causing problems as loss of motor cooling, low
voltage, etc. and, is in our opinion, the finest motor
protection system available. The guardistor control circuit is a manual reset
system which when actuated will require manual resetting by pushing the reset button on the unit control panel.
MOTOR PROTECTION - Provides
[-X-l
The control module, through the capacity control system, is capable of extremely close control of design
set point temperature. Dials provide for manual adjust­ment of the unit control set point and/or for limiting the current drawn by the compressor motor at any level between 30 and 100 percent of rated full load current.
The pulsing action built into the electronic control module, coupled with needle valve adjustment of the
hydraulic portion of vane control provides a very stable temperature control arrangement. During normal oper­ation, it will take approximately 3 to 5 minutes to move from minimum to maximum capacity and one minute to move from maximum to minimum capacity.
The water chilling unit can be applied to many different cooling applications and is adaptable to many different types of control systems. The particular control ar-
rangement used will be incorporated as a part of the
total job control system. Details on the total system
control should be available in the job file. The vane
control system is explained starting on page 11.
(1)
In the event of a power failure to the unit or control panel, the guardistor relay will trip and require manual resetting when power is restored.
2.
SURGEGARDTM- A surge or rotating stall is not a
normal operating condition for a centrifugal com­pressor. Under some abnormal unit operating con-
ditions, a compressor surge condition can develop and, if allowed to continue, can cause compressor damage. A surge is caused by many things, such as dirty condenser tubes, reduction in condenser water flow, increases in condenser water tempera­ture above design, or any other factor which can act to increase the pressure difference between
suction and discharge pressure (head).
The
McQuay against damage from surging by a unique protec­tion system which senses a surge condition, should
it occur,and shuts the
Whenever the machine has been stopped as a result of a surge condition, the cating
light on the control panel will glow.
SOLID STATE CAPACITY CONTROL
The solid state control module combines temperature and current limit control in a single solid state package. In addition, indicating lights on the module indicate whether the control is calling for the compressor to load or unload or whether the current override feature
is in control. By setting a switch, it is possible to place
the unit under manual or automatic control of un-
loading.
centrifugal compressor is protected
machine down
SurgeGardTMindi-
before

CONTROL MODULE CALIBRATION

The control module supplied as a standard part of the unit control center is a solid state electronic device which operates from a 24V A.C. power source. Except for its external sensor(s) and a 5 volt (full load) signal from a current transformer, and resistor located in the compressor motor starter, contained. The module can provide many features and functions, some of which are:
1.
Proportional temperature control (within k 0.5F of
set point).
2.
Current limit control (manually adjustable).
3.
A pulse rate adjustment which permits the module
response speed for loading or unloading to be varied to meet application requirements encounter­ed on different systems and/or applications.
4.
A “ramp-up” adjustment which can be utilized at compressor startup to control the time to load and the point at which the controlled loading begins. For example, this adjustment can be used to reduce the power that would be consumed by the unit if it were allowed to load the machine without a time restriction.
Indicating lights which glow when the controller is
5. calling for loading (green), unloading (red) or current override (amber).
A selector switch to permit manual or automatic
6. control of unit capacity.
A selector switch to permit manual control of
7.
loading or unloading. Can be adapted to accept a signal to reset the
8.
control point in response to a change occurring at
it is completely
self-
8
Page 9
another location, such as outside air, return chilled water or an energy management device.
Can be adapted to unload in response to a signal
9. from an energy management device used to shed electrical power loads. The compressor capacity can be reduced as a function of building entrance
power.
CALIBRATION
The control module is factory calibrated and should
not normally require field calibration. In the event calibration must be checked, a procedure covering the steps required for both current and temperature calibration is outlined in the following paragraphs.
CURRENT CALIBRATION
Equipment needed - an accurate
1.
ammeter. Start the unit and place the control module
2. selector switch in the manual position.
Open the starter door and place the
3. the power lead drawing the highest current on the load side of the starter.
4.
Remove the control module cover. Set current demand limit selector switch clock-
5. wise
(4)
against the stop (100%).
6.
Set the blue current limit calibration screw (located just to the left of the temperature control stem) to the full counterclockwise
7.
Check the compressor motor nameplate rated load amperes (RLA against the amperage reading on the
amprobe. amperes drawn by the motor match the motor rated load amperes.
When the nameplate and
8. are equal, turn the current limit calibration screw clockwise until the amber light just comes on and stop. This places the unit in current hold. The internal circuitry of the module will now insure that, should the current increase to 105 percent of
rated load amperes, the controller will unload the
compressor. To verify that the calibration is correct, manually
unload and then reload the compressor to the rated load ampere value and verify that the current override light glows. The current limit control portion of the module is now in calibration.
Check the knob setting, if it needs correcting snap
9. the top off the control knob, loosen the screw and
rotate the knob to indicate 100% of current.
Tighten screw and replace top.
Replace module cover, remove
IO.
starter door.
Manually adjust the load until the
(-1
position.
amprobe
amprobe
amprobe
amprobe
ampere values
and close
or
on
TEMPERATURE CONTROL CALIBRATION
Equipment required - accurate thermometer and
1. DC voltmeter.
Remove control module cover.
2. Allow unit to operate until leaving water tempera-
3. ture stabilizes. With the thermometer located in leaving chilled water, read the water temperature.
On the control module turn the temperature control
4. knob to a point where both the unload (red) and load (green) lights remain off. Move the knob to the midpoint between these points.
Check voltage between control module terminals
5. “IOM” and “COM” using the DC voltmeter. The voltage reading should be close to 7.5V
Read the leaving water temperature once more.
6.
Check this temperature against the temperature indicated by the pointer at the base of the tempera-
ture control stem. If they do not agree, hold the
stem and rotate the pointer until it indicates a temperature on the scale corresponding to the
thermometer reading.
Replace the control module cover. Check the
7.
temperature indicated by the knob against the cover temperature scale. If the reading is not correct, snap the top off the knob, loosen the screw and rotate the knob until it indicates the correct temperature. Tighten the screw and replace the top of the knob.
Remove the voltmeter and thermometer (if neces-
8.
sary). The temperature calibration is complete.
LUBRICATION SYSTEM A separate motor driven oil pump assembly supplies oil
at controlled temperature and pressure to all bearing surfaces and in addition is the source of hydraulic pressure for the capacity control and emergency oil
supply. The unit control system on a call for cooling will not
permit the compressor to start until oil pressure has been established for at least one minute. When the system controller is satisfied and stops the compres­sor, the oil pump runs for another minute to assure adequate lubrication during spindown. In addition, during this period the compressor is unloaded through the action of the vane closed switch “VC”. The compressor will then be ready to start unloaded on the
next call for cooling.
The oil pump is completely self-contained and located
in the oil sump. On Model SE046, 048 and 050 units, it is located inside the compressor housing, for model
SE063 units the oil pump is located in the oil pump assembly which is mounted at the rear of the unit adjacent to the condenser.
(
+
0.5V).
9
Page 10
FIGURE 5
In either case, it includes the pump, pump motor, oil heater and oil separator. The Model SE063 includes shut off valves for discharge, oil return and suction.
Oil is pumped through an externally adjustable oil relief valve which is factory adjusted to limit the discharge oil pressure from 100 to 110 psig above the operating suction pressure. After leaving the relief valve, oil flows through a refrigerant cooled oil cooler where the temperature is reduced to approximately 90 to 100 F. From the cooler it passes through a replaceable five
(5) micron oil filter located in the compressor casting. On Model SE046, 048 and 050 units the oil first passes through the oil filter and thrust pump before entering the oil cooler. Filtered oil is then distributed through internal passages in the compressor casting to the control system and before entering the bearings on Model SE063 units it passes into the thrust pump where the oil pressure to the bearings is boosted.
Oil leaving the compressor and motor bearings is re­leased under pressure into the low pressure gear hous­ing where some of this oil vaporizes. This oil vapor is used to lubricate the gearing. The remaining oil leaving
the bearings drops to the bottom of the gear housing where it is drained to the oil sump. On Model SE063
units oil from the gear housing and capacity control is dumped into the scavenger line and returned to the oil
sump. Oil as it circulates in the oil system (because of
the ability of oil and refrigerant to mix in all propor­tions) will always have some refrigerant mixed in it. Most of this refrigerant flashes from the oil as it enters the oil sump or is driven from the oil by the oil heater. This refrigerant gas as it is removed from the oil sump passes through a centrifugal oil separator located on top of the oil pump rotor.
10
The oil sump is vented to the suction side of the system just ahead of the compressor wheel eye. Gas flowing from the oil sump has to pass through the spinning oil separator where entrapped oil is removed by centrifugal force and is thrown back to the oil sump. The refrigerant gas flows on through to the compressor suction.
The main oil sump on all units is provided with an electric heater and, in addition, the Model SE063 units also include a heater in the gear housing.
THESE OIL HEATERS MUST REMAIN ON AT ALL TIMES THE COMPRESSOR
IS NOT RUNNING. SHOULD AN EX-
TENDED POWER LOSS OCCUR
(DE­ENERGIZING THE HEATERS) AND AL­LOWING THE OIL TO COOL, IT WILL BE NECESSARY WHEN POWER IS RE-
STORED TO KEEP THESE HEATERS
ENERGIZED FOR A MINIMUM OF 24 HOURS BEFORE ATTEMPTING TO RE-
START THE COMPRESSOR.
If conditions require the compressor to be restarted immediately, it will be necessary to drain the system oil and recharge the unit with new oil which is free of refrigerant.
The low oil temperature thermostat “LOT” (set for 120
F)
supplied as part of the unit safety controls will, if
adjusted properly, prevent the compressor from start-
ing with cold oil. This thermostat is a manual reset
type and when tripped will cause the oil temperature
light to glow. Quantities of oil required for Model SE units as well as
the recommended oil specifications are:
OIL CHARGE REQUIRED
MODELS PE046,048, and 050 1.75 gallons
MODEL PE063 . . . . . 8 gallons
RECOMMENDED OIL
SUNISO 4G/4GS
or TEXACO CAPELLA 68WF
EMERGENCY OIL SYSTEM An oil cylinder with a spring loaded piston is incorpo-
rated in the compressor casting to supply emergency lubrication for bearings in the event of a power loss. During normal operation, pressure from the oil pump fills the emergency oil cylinder and compresses the piston/spring assembly contained in the cylinder. On a loss of power (and as a result, a loss of oil pressure) oil is forced into the bearing lubrication passages as the spring behind the piston expands and forces oil from the emergency cylinder. The emergency oil system contains an adequate oil supply under pressure to assure adequate bearing lubrication during the spin down period.
Page 11
CAPACITY CONTROL
Capacity variation for the unit is accomplished by opening or closing vane(s) located in the suction inlet to the compressor. Vane movement is controlled by positioning a floating piston to which the inlet vane(s) are linked. The piston (and as a result the vane(s) are positioned by building up oil pressure on one side of the piston and draining or not draining the other side, depending on how far the piston must move to satisfy the capacity requirements of the system.
Figures 6, 7 and 8 schematically illustrate the control of
the floating piston.
CONTROL SATISFIED
When the system capacity control is satisfied, an electrical signal is sent to the control module calling for no change in capacity. Such a condition is illustrated in
Figure 6. The control module has de-energized both sections valve. With both sections de-energized, ports Cl and C2 are open and outlet port full pressure to both sides of the piston holding it in a stationary or satisfied position.
“SA” and “SB” of the four way solenoid
#3
is closed. This directs
riziq
COMPRESSOR UNLOADER CYLINDER
r
NOTE ADJUSTABLE
NEEDLE VALVES INTEGRAL WITH FOUR WAY SOLENOID VALVE ARE NOT SHOWN
IOPENlNG]
- OIL UNDER PRESSURE
-
FLOATING PISTON LINKED TO INLET VANES
-
OPENS VANES
-
CLOSES VANES
FIGURE 6
-LEGEND-
OIL SUMP PRESSURE
SECTION “SA” DE ENERGIZED
-
FROM OIL PUMP DISCHARGE VALVE
INCREASE CAPACITY
When the unit capacity is not high enough to satisfy the load (such a condition is illustrated in Figure
7),
a
signal from the control module will energize section
“SB” and de-energize section “SA”. This will drain oil
DRAIN FROM PISTON
--)
from the right hand side of the piston and allow it to
-
c
#3
OUTLET
0 c2
SECTION “SE” ENERGIZED
SECTION “SA’
DE~ENERGIZED
move to the right and open the vanes. Oil in the right
hand side of the piston will continue to drain through
the open port C2 and outlet
#3.
The piston will continue to move to the right until the control module de-energizes section that position.
“SB”
thus holding the piston at
FIGURE 7
TO OIL
I-
PUMP
SUMP
FROM OIL
*PUMP
DISCHARGE
DECREASE CAPACITY
When the unit has been running at a higher level of
capacity and the load falls off, the system is required to reduce compressor capacity. Such a condition is illustrated in Figure 8. The control module energizes section
“SA” and de-energizes section
“SB”.
This
permits oil to drain from the left side of the piston
through open port Cl to the outlet
#3.
With section “SB” de-energized, full oil pressure is applied to the right end of the compressor piston, moving it to the left. The piston can be stopped at any point in its leftward movement when the capacity is satisfied and the control module signals to de-energize “SA”.
The above descriptions are simplified versions of what
actually happens, neglecting the complicated control function provided by the control module as it pulses to control the action of solenoids
“SA” and ”SB”.
[CLOSlNGj
FIGURE 8
DISCHARGE VALVE
11
Page 12
METERING VALVES The hydraulic control system utilizes needle type
adjusting valves built into the four way solenoid valve. These valves are used to adjust the response time for the floating piston to move through its full length of travel. The valves are factory set and under normal operating conditions should not need to be reset. Attempts to reset the valves by unqualified personnel will result in very poor operation of the capacity control system.

MAINTENANCE

It is important that this unit and the air conditioning system it is part of receive adequate maintenance if full equipment life and all system benefits are to be realized.
On a new system, follow-up inspection of the system after 3 to 4 weeks of normal operation. Such an inspection is not part of the unit selling price. It can be provided by McQuay service at additional cost.
FACTORY MAINTENANCE SERVICE
McQuay offers a variety of maintenance services through its Nationwide Service Organization. These contract services include regular inspections and emer­gency service by factory trained technicians. Services
are available around the clock to keep your equipment running in top condition.
With a McQuay Assured Maintenance contract, all parts, labor and materials are furnished additional cost to the customer.
maintenance
should begin with a
. . .
with no
Model PE046, 046 and 050 units have an internal oil
pump and require that the system refrigerant charge be pumped into the condenser before attempting to change the filter. After the unit is pumped down, break the seal on the oil filter access cover and permit the pressure to bleed off before removing the cover. After replacing the filter, crack
open the condenser liquid valve and permit the
pressure to build up and purge the oil filter housing.
Replace the cover and check for leaks.
Model PE063 units have an external oil pump
assembly. Close the oil pump discharge valve.
Loosen the flair fitting feeding oil to the filter and bleed off the pressure by purging slowly. When the pressure has been relieved, remove the cover and replace the filter. When reassembling, vent as much air as possible from the oil lines before placing the compressor back into operation.
REFRIGERATION CYCLE Since the Model PE unit has a semi-hermetic compres-
sor and utilizes R-12 or R-500 refrigerant, normal system pressures, whether the system is operating or shut down, will always be above atmospheric.
Unit maintenance generally will consist of proper inspection and maintenance of an operating log. Visual inspection of oil level as shown in the sight glass and
noting operating suction, discharge and oil pressures will generally indicate if the unit operating characteris­tics are changing.

ELECTRICAL SYSTEM

It is widely recognized that a good maintenance program is the essential first step in controlling energy costs. And through McQuay’s Assured Maintenance and Energy Management Programs, the owner is assisted in establishing a comprehensive Energy Man­agement plan to meet his needs. For further informa­tion concerning the many services available, contact your local McQuay service representative.

LUBRICATION

Once the unit has been checked out and is placed in
service, no additional oil should be required. the oil
level in the oil sight glass should be marked when the
system is shut down and the level checked periodical-
ly.

OIL FILTER

The oil filter must be changed annually. We do not
recommend that untrained personnel attempt to re­place the filter. The filter is contained in a system under refrigerant as well as oil pressure. If proper care is not taken when changing the filter personal injury could occur. In addition air and/or moisture could enter the system and cause equipment problems.
Generally, maintenance of the electrical system only
involves keeping operating controls clean and electrical connections tight. In addition, the following items should be inspected;
1.
The compressor amperage (current) drawn should be compared to the nameplate rating. Normally, the current read will be less than nameplate since the nameplate value represents design full load current.
2.
Check that oil heaters are operative. Heaters are cartridge type and can be checked by an amperage reading. They should be energized whenever the compressor is not operating. When the compressor
runs,
energized.
Once a year all safety controls except compressor
3. overloads should be made to operate and the control operating point checked. Any control as it ages can shift its operating point and this should be detected.
Pump interlocks and flow switches should interrupt
the control circuit cleanly
switch can be a source of trouble as well as irritation.
the heater should be automatically
-
a chattering flow
de-
12
Page 13
4. Motor starter contacts should be inspected and cleaned annually. All terminal connections should be tightened.
AUXILIARY EQUIPMENT
It
is important that auxiliary equipment used in conjunction with the Model PE unit be adequately maintained. Malfunctions in this equipment often affect the operation of the condensing unit. For example; improperly maintained air filters in the system can restrict air flow to the cooling coils and as a result cause suction pressure to fall to a point where a nuisance trip out on the low suction pressure cutout could occur. Items such as the following should be checked and maintained.
1.
All filters must be cleaned or replaced. The fre­quency of this service will vary with different installations.
2.
If evaporative type condenser is used, keep con­denser pump water strainer clean. Inspect and service on a regular basis.
3.
Maintain condenser water treatment to limit buildup of scale in condenser tubes (if required).
4.
Inspect condenser, clean when required. If unit has a belt drive, change belts at least annually.
All fans and belts checked and adjusted.
5.
All condensate drains clean.
6.
7.
All motors lubricated.
8.
All electrical connections tight.
9.
All starter contacts are clean and mechanism moves freely.
SEASONAL SERVICING
At the end of the cooling season and before the unit is started in the spring, the following service procedures should be completed.
A.
Annual Shutdown
When the unit may be exposed to freezing tempera-
1.
tures, water piping should be disconnected from the supply and drained of all water. The chiller is not self-draining; If all water must be drained from the unit, remove the water heads and blow dry air through each tube.
When it is possible to have the unit and/or piping exposed to freezing temperatures, the only sure
method of protection is forced circulation of an
antifreeze solution through the water circuit.
When an evaporative condenser is used and the
2. water pump will be exposed to freezing, be sure to remove the pump drain plug and leave it out so that any accumulation of water will drain away.
3.
Take measures to prevent the water supply line shutoff valve from accidentally being turned on.
4.
Open the compressor disconnect switch and re­move the fusetrons. If a control circuit transformer is used for unit control power, the disconnect must remain on to supply power to the oil sump and gear housing oil heaters. Set the compressor “on-off” switch to “off”. To guard against the possibility of an accidental compressor start, remove relay “R7” from the control panel. (See Figure 4).
ANNUAL START UP
B.
Before commencing with the seasonal start up
1. procedures, we recommend that the compressor and oil pump motor resistance be checked. Annual checking and recording of this resistance will provide a record of deterioration in the motor winding insulation should it occur. All new units have a compressor megohms between any motor terminal and ground.
Whenever a marked change in resistance shows or uniform readings of less than 5 megohms are obtained, THE UNIT SHOULD NOT BE STARTED
SINCE MOTOR FAILURE WOULD BE PRACTI­CALLY CERTAIN. In all probability, the motor will have to be repaired or replaced. Your McQuay service representative should be called for recom­mendations and/or repair.
The unit control circuit should have been energized
2. at all times. If the control circuit has been shut off and the oil is cool, the machine should not be started until the heaters in the oil sump (and gear casing PE063 only) have been energized for a minimum of 24 hours. If it is necessary to start the machine without waiting 24 hours, then the oil in
stator
resistance well over 100
the unit should be drained and replaced with fresh
oil. Check and tighten all electrical connections.
3. Install fusetrons in the main disconnect switch
4. they have been removed).
Replace relay “R7” (if it was removed).
5. Replace drain plug in water pump if it had been
6. removed.
Reconnect water lines, turn on supply water and
7. check for leaks.
If evaporative type condenser is used, clean and
8.
flush the sump.
a. Make sure condenser bleed is adequate. b. Be sure water treatment is adequate to prevent a
buildup of solids in the condenser. Air circulated through the condenser contains many contami-
nants which are flushed out by the water sprays. The use of untreated water in most installations
(if
13
Page 14
can result in a reduction of heat transfer in the condenser tubes or damage to the tubes as a result of corrosion, erosion, sliming, scaling, or algae formation. (This section applies to systems with evaporative type condensers.)
RECOMMENDATION The service of a competent water treatment organi-
zation be obtained to determine what, if any, water treatment is required and their recommendations implemented.
Mcquay assumes no responsibility for operating
problems or damage occurring as a result of
untreated condenser water. Clean all surfaces and remove all litter. A clean well
9.
maintained unit is the sign of a good operator.
REPAIR OF THE SYSTEM
Information on pumping unit down, pressure testing, leak testing, evacuation and charging is contained in installation manual SE-Gl.
OPERATOR’S CHECKLIST
UNIT CHECKS
1. Suction, discharge and oil pressure normal.
2.
Oil level correct. Voltage within tolerance (plus or minus 10 percent
3. of compressor nameplate ratings). Phase unbalance does not exceed 3 percent.
4.
Motor amperage proper for load conditions.
Vanes open and close under manual and automatic
5. control.
Motor current limiting control operational.
6.
Safety interlocks interrupt compressor operation.
7.
Unit cycling thermostat set 3 to 5 degrees below
8.
unit control set point.
SYSTEM CHECKS
1.
All motors checked for voltage and running amperes.
All pumps and motors lubricated.
2.
Water strainer(s) clean.
3. All fans checked, belts tight, bearings lubricated.
4.
Air filters clean.
5.
All electrical connections tight, starter contacts
6.
clean, starter movement proper.
14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Loading...