McQuay PE046 Installation Manual

GENERAL
UNIT NAMEPLATE
The Model PE less condenser centrifugal water chiller has been factory assembled, checked and shipped with a holding charge of R-12 refrigerant. The purchase price of this equipment includes checkout of the unit and initial startup by a McQuay service technician. An integral part of the startup procedure includes instruc­tion of responsible personnel in the operation and maintenance of this water chilling unit.
It is most important that this equipment be properly operated and maintained if it is to perform the operating service it was designed and built to provide.
McQuay offers equipment maintenance and/or inspec­tion programs that can be tailored to fit individual job requirements. Information on the various service pro­grams is available through the McQuay Service De­partment or your local McQuay sales representative.

WARRANTY

The McQuay Model PE water chiller unit is covered by a standard published warranty which covers parts only. A complete published description of that warranty and its limitations is provided in a warranty certificate included with each unit.
First year warranty labor can be purchased separately, check your local McQuay sales representative to establish what additional coverage (if any) was pur­chased for your unit.
Whenever requesting information or assistance on the Model PE chiller, the unit model number, shop order number, and serial number should be copied from the unit nameplate. A reproduction of this nameplate is
shown in Figure 3.
HOLDING
CHARGE
ONLY
STYLE SERIAL S.O. NO. PE-5210
\
-~
lPE5210-GO1
5NAl234~0
FACTORY CHARGED
~
LBS. REFRIGERANT
LEAK TEST PRESSURE 100
MOTOR - COMPRESSOR CONTROLLER
AND OVERLOAD PROTECTION FIELD
SUPPLIED. SEE SPEC.
R12
PSIG
PE-D4
mccbuw k.
198PlMHOl A
MADE IN U S A
Note Typical Serial Number
l Prior to January 1, 1983 =
1,
l
After
January
1983
LZ1320
=5NA1234500

INSTALLATION

Information pertaining to the installation of Model PE
water chilling units is available in Installation Bulletin
number PE-L-Gl. A copy of this manual was included
in the envelope shipped with the unit.
MODEL CODE
PE
063J
AN 30 R G A 2 L
UNlT FA::::E-I 1
SPEED CODE
MOTOR CODE
COMPRESSOR MOTOR VOLTAGE
~k;;~~;~;::~R
TYPE OF CHILLER TUBING
CHILLER CODE
FIGURE 3. UNIT NAMEPLATE

OPERATING INFORMATION

OPERATOR’S RESPONSIBILITY
1.
Before operating the Model PE unit, become famil­iar with the machine and accessory equipment.
2.
If possible, arrange to attend a McQuay centrifugal operators school.
After the unit has been checked out and approved
3. for operation by a McQuay centrifugal service technician, work with him to learn how to prepare the system for startup. Start and stop the machine a number of times while observing the operation of the interlock function(s). The interlock circuit must
be satisfied before the compressor will run. After
operating the unit, place it in the shutdown mode.
Monitor operation and periodically inspect the
4. equipment, making routine adjustments where essa ry
nec-
Maintain a log of operating conditions on a daily
5.
basis. (Log sheets are available in pad form from
McQuay.
PRE-START SYSTEM CHECKLIST
p&q
All of the following will have been checked out by the during the initial startup procedure. *Items should always be verified by the unit opera­tor on a routine basis during the operating season.
A. UNIT
"1.
All service valves are in the operating position. The control circuit is energized.
“2.
The oil heaters have been operating for a
“3.
minimum of 24 hours. Oil should be hot (approximately 130 to 140
“4.
The oil charge is visible in the sight glass. (Mark level on sight glass while machine is shut down, check level weekly).
Check control circuit, verify that all safety
“5.
switches interrupt compressor starter holding coil.
“6.
The water flow through the condenser is correct. (This can be checked from condenser water pressure drop curves available from
McQuay).
reduced by a plugged strainer which can
cause operating problems and nuisance outs. New systems are generally susceptible
to blocked water strainers from foreign mate-
rial washing out of the piping.
B. ELECTRICAL
McQuay
On any system, water flow can be
startup technician
F).
trip-
All load equipment is operative (main system
“3.
fans, pumps, etc.). Condenser fan(s) and controls are operative.
“4.
Condenser water bleed and water treatment
“5.
are adequate (if required).
STARTING
When the 115 volt AC control power supply is applied to the control panel for the first time or after a power failure has occurred, the following will take place.
1.
The oil sump heater(s) will be energized. The external failure light will glow and the external
2. “R9”)
alarm circuit (energized through Relay
activated. Push the RESET Button on the control panel. The
3.
external failure light will go out and the external alarm circuit will be reset (de-energized).
Set the compressor “ON-OFF” switch to “ON”, the
4. light in this switch will glow. The unit control circuit
has been re-established.
The unit safety circuits have now been reactivated
5. and the operating portion of the control circuit is
ready to function. (Before the operating portion of
the control circuit can function, the chilled water
pump will have to be running). The “LRT” (unit cycling thermostat) will, on a call
6.
for chiller operation;
Start the oil pump. (Providing 20 minutes have elapsed since the unit last stopped and the anti recycle time delay has timed out and closed its contacts).
will be
1.
The wire size is correct.
2.
The phase sequence is correct.
“3.
Voltage within plus or minus 10 percent of rated compressor nameplate voltage.
“4.
Phase voltage unbalance 3 percent or less.
5.
All wiring connections correct per the unit wiring diagram.
6.
All electrical connections are tight and made
with copper conductors and lugs.
“7.
All starter parts move freely and contacts meet evenly.
8.
Motor overloads correct size (filled with dash-
C.

SYSTEM

“1. The condenser pump is rotating in the right
direction.
“2. The condenser pump and motor are lubricat-
ed.
When the oil pump develops oil pressure ade­quate to close the oil differential pressure switch
“OD”
(50
psig above suction pressure), the
switch will close. A time delay relay “PLT” injects a 10 to 60
second time delay into the compressor starting control circuit and prevents this portion of the circuit from being energized while oil pressure is being developed. At the end of this delay, if the vane closed switch gized the condenser pump relay “CWR” the pump starter interlock contacts will close and energize relay “MCR” located in the unit starter. The compressor starter will now be energized and the compressor will start.
“VC”
has closed and ener-
OPERATING
1. With the compressor running, capacity is controlled by positioning variable inlet vane(s) located in the suction gas inlet to the compressor. Opening the vane(s) allows the compressor to pump more gas and, as a result, increases capacity. Closing the vane(s) reduces gas flow and reduces capacity. The
5
capacity control system is capable of modulating the vane position to any capacity from 10 percent to 100 percent.
The inlet vane(s) are controlled by means of 3 different devices. The capacity will always be controlled by temperature unless the temperature control is overridden by Items “b” or “c” below.
a. A temperature sensor located in the leaving
chilled water translates temperature changes into an electrical signal and through the control module loads or unloads the compressor (opens or closes the vane(s).
b. The solid state control module in conjunction
with a current transformer and resistor located in
the compressor motor starter, senses and will limit current drawn by the compressor motor depending on the setting of the current limit control. This controller will override the tempera­ture control and will, whenever motor current exceeds its setting, open or close the compres­sor vane(s) in response to changes in current. Whenever the motor current is less than the
setting on the current limit controller, unit capacity control is returned to the temperature sensor. The current limit control can be set to limit current from 30 to 100 percent of name­plate full load current. The control is easily adjusted by a knob on the face of the control
module.
c. The low pressure override switch “LPO” built
into the unit control panel senses suction pres­sure and is set to open at 2 to 5 psig above the low pressure safety switch. Whenever the set­ting is reached, the override switch opens and in turn de-energizes relay
gizes
“SA” and de-energizes “SB” solenoids in the four way valve. Full oil pressure is applied to the unloader piston driving the vanes closed. This action will in most cases catch a momen­tary “sudden” drop in suction pressure such as
may be caused by a slow acting expansion
valve, a drop that without this unloading feature
would open the low pressure switch and stop
the compressor. The “LPO” pressure switch is
automatically reset, it will close when the pres­sure rises to a safe limit and return control of capacity to the temperature sensor.
During normal operation, the compressor will con­tinue to operate and unload to a minimum of 10 percent until the cycling thermostat is satisfied. When this occurs, the condenser relay the motor control relay “MCR” are de-energized and the compressor motor is stopped.
The unit oil pump will continue to run for a minimum of one minute after the compressor starter has been de-energized. This will assure
“R4”,
this in turn ener-
“CWR”
and
adequate lubrication for the compressor during the spin down period.
In addition, on the next call for cooling, the compressor capacity control vanes must be in a closed position before the compressor is allowed to restart. Contacts “VD” (auxiliary contacts located in the compressor starter) through relay
energize the unload portion of the unit capacity
control circuit. If the vanes were not fully closed
when the compressor was stopped, oil pressure
will continue to be applied to the unloading piston
through the “SA” portion of the four-way solenoid
valve. This pressure continues to drive the vanes to
the closed position while the oil pump is still running. This will permit the compressor with a minimum delay to start on the next call for cooling. (The compressor will not start until the vanes are in the closed position).
Rapid cycling of centrifugal compressor motors is not desirable. A time delay through relay “TDR” is built into the unit control circuit to prevent rapid cycling. Relay “TDR” will prevent the compressor from restarting for a period of 20 minutes after the
compressor is stopped unless the “automatic re­start after power failure with reduced timed off
cycle” accessory option is used.
In the event of a power interruption during unit
operation,
damage by an emergency oil reservoir and spring
loaded piston. During normal operation enough oil
is stored in the emergency cylinder to lubricate the
bearings during spindown. The oil is forced into the various passages by a spring loaded piston con­tained and compressed in the emergency oil cylin­der. ‘The spring is compressed by normal machine oil pressure while the compressor is running and on a loss of power is available along with the piston to act as an emergency oil pumping device.
CONTROL CENTER The control center contains all of the unit protective
controls and most of the operating devices. Table 1 “Control Summary” (on page control information including electrical diagram sym-
bol, control description, setting, reset information, location, signal light, and information on the control
function.
Eleven indicating lights are utilized on the unit control panel. Nine of these lights are normally out and only glow when a safety circuit has tripped.
Repeated tripping of a given control should be investi­gated by a competent air conditioning serviceman or by a
McQuay damage. Details of the control center are shown in Figure 5.
the compressor is protected against
15)
contains general
service technician to avoid costly
“R8”
Loading...
+ 14 hidden pages