Installation & Maintenance Data
AAF–McQuay Suite™ With Top Mounted Heat Section
Wall Sleeve Installation
Wall Opening Requirements
Before installing the unit, check the wall opening to be sure the
wall sleeve will slide into the opening unobstructed. For masonry
walls, a lintel must be used to provide support over each opening.
Figure 1.
IM 426-1
Group: PTAC
P art No.: 106018741
Date: May 1999
1
The rough opening should measure 16
opening must be a minimum of 4" above the finished floor (including
carpeting).
/4" high X 421/4" wide. The
42"
(1069mm)
5"
(127mm)
Wall Sleeve
52" (1320mm)
Removable Cabinet
Front Panel
Note: Electrical rough-in should be located behind kickplate
(removable front) and below wall sleeve.
11⁄2"
(38mm)
191⁄2"
(495mm)
3"
(76mm) Min.
3"
(76mm)
52" (1320mm)
Wall Space For Piping Rough-in
(Typ. R.H. & L.H.)
Kickplate (Removable
Front)
31⁄2" (89mm)
1
⁄2" (13mm)
11⁄4" (32mm)
(Architectural)
Cabinet
Floor Space
For Piping
Rough-in (Typ.
R.H. & L.H.)
2" (51mm)
7
⁄8"
(22mm)
51⁄2"
(140mm)
15⁄16"
(33mm)
11/4" RECESS FOR ARCHITECTURAL LOUVER
“A”
ROOM CABINET
173/4"
163/4"
153/4"
143/4"
133/4"
123/4"
113/4"
103/4"
103/4"
103/4"
103/4"
103/4"
“B”
WALL SLEEVE
133/4"
133/4"
133/4"
133/4"
133/4"
133/4"
133/4"
133/4"
143/4"
153/4"
163/4"
173/4"
WALL THICKNESS
53/4" to 63/4"
63/4" to 73/4"
73/4" to 83/4"
83/4" to 93/4"
93/4" to 103/4"
103/4" to 113/4"
113/4" to 123/4"
123/4" to 133/4"
133/4" to 143/4"
143/4" to 153/4"
153/4" to 163/4"
163/4" to 173/4"
Standard Size Wall Sleeve
Wall
Thickness
“A”
91⁄8"
(232mm)
15⁄8"
(41mm)
“C”
27⁄8" (67mm)
“B”
3" (76mm) Min.
Kickplate Height
11⁄4" (32mm)
16"
(406mm)
7
⁄8" (22mm)
“C”
Anchoring
Figures 3 through 5 on the following pages illustrate typical wall
sleeve installations. After the wall sleeve has been set in place
anchor it in the opening as shown in Figure 2. It is recommended
that rubber isolation washers be used with the fasteners to minimize sound transmission from the equipment to the wall, at the
point of contact.
Level w all sleeve in all directions and anchor with appropriate
fasteners (as shown in Figure 2). A
side, 2" down from the top and 2" in from the rear of the wall
sleeve. It may be necessary to drill additional holes in the wall
sleeve to firmly secure it. CAUTION: Do not drill holes in the base
of the wall sleeve . Use shims between the wall and the wall sleev e
to prevent wall sleeve distortion during anchoring.
5
/16" hole is provided on each
©1999 AAF–McQuay Incorporated IM 426-1 / Page 1 (Rev. 5/99)
Figure 2.
Wall Sleeve Installation – Thin Wall Construction
The standard wall sleeve is designed to be easily installed in a
variety of wall constructions. For panel wall and thin wall construction, it is recommended that the optional top angle be used
wall sleeve. If a subbase is not used, field support must be
provided up to the center of gravity. This support can be metal,
wood or concrete.
and the wall sleeve be supplied with a turned down flange
(see Figure 3).
The recommended procedure for installing units in panel wall
and thin wall construction is as follows:
3. Level wall sleeve in all directions and anchor with appropriate
fasteners. Use holes provided (see Figure 2, page 1) or drill
additional holes as required to secure firmly . Caution: Do not
drill holes in the base of the wall and the wall sleeve to
1. Clean the opening of all debris that may interfere with
prevent wall sleeve distortion during anchoring.
installation.
4. Caulk the wall sleeve to the wall opening on both the inside
2. Recess the wall sleeve so that the louver is flush with the
exterior of the building (refer to Figure 3). The center of grav-
and outside perimeter. This can be done from the inside of
the building. Be careful not to plug the weep holes.
ity is approximately 10 3/4" from the rear face of the standard
Figure 3. Wall Sleeve Installation Using Top Angle & Factory Supplied Louver
131⁄4"
(337mm)
42"
(1069mm)
Optional
Top Angle
Wall
Sleeve
11⁄4" (38mm)
Optional
Top Angel
C**
Outside
Louver
16"
(406mm)
Y*
Optional
Subbase
3"
(76mm)
Min .
Notes:
** See Figure 1, page 1, for dimensions “B” and “C”.
* Dimension “Y” is field determined or specified. Angle is factory welded at
101⁄2"
(267mm)
Max.
1"
(25mm)
given dimension when option is designated.
Turndown
Flange
(See Detail)
Outside
Edge of
Sleeve
Fininish Floor
Including Carpet
Turndown
Flange
16"
(406mm)
37⁄8" (98mm)
Min.
B**
Wall Sleeve
Support
By Others
(2 Req’d).
Caulk
IM 426-1 / Page 2 (Rev. 5/99)