Voltage
C = 208V, 60Hz, 1Ø
D = 208V, 60Hz, 3Ø
G = 230V, 60Hz, 1Ø
H = 230V, 60Hz, 3Ø
K = 460V, 60Hz, 3Ø
Cooling Coil Options
G = Direct Expansion
H = Direct Expansion with Refrigerant Relief Valve
Heating Options
00 = None
12 = Low Electric Heat, 3-Element
13 = High Electric Heat, 6-Element
65 = 1 Row Hot Water
66 = 2 Row Hot Water
68 = Steam, Low Capacity
69 = Steam, High Capacity
Color
I = Antique Ivory
W = Off White
B = Putty Beige
G = Soft Gray
Power Connection
G = Box with Switch
Return Air/Outdoor Air
22 = Return Air Front,
Outdoor Air Rear
Discharge
AL = 16 5/8" Top Bar
Control Options (continued)
E1 = Expanded Stand-Alone w/o TC
E2 = Expanded Stand-Alone Master w/o TC
E3 = Expanded Stand-Alone Slave w/o TC
E4 = Expanded BACnet MS/TP w/o TC
E5 = Expanded LonMark SCC w/o TC
E6 = Expanded Metasys N2 Open w/o TC
E7 = Expanded Stand-Alone w/ TC
E8 = Expanded Stand-Alone Master w/ TC
E9 = Expanded Stand-Alone w/o TC w/CO2
EA = Expanded Stand-Alone Master w/o TC w/CO2
EB = Expanded Stand-Alone Slave w/o TC w/CO2
EC = Expanded BACnet MS/TP w/o TC w/CO2
ED = Expanded LonMark SCC w/o TC w/CO2
EE = Expanded Metasys N2 Open w/o TC w/CO2
EF = Expanded Stand-Alone w/ TC w/CO2
EG = Expanded Stand-Alone Master w/ TC w/CO2
L1 = Leading Stand-Alone w/o TC
L2 = Leading Stand-Alone Master w/o TC
L3 = Leading Stand-Alone Slave w/o TC
L4 = Leading BACnet MS/TP w/o TC
L5 = Leading LonMark SCC w/o TC
L6 = Leading Metasys N2 Open w/o TC
L7 = Leading Stand-Alone w/ TC
L8 = Leading Stand-Alone Master w/ TC
L9 = Leading Stand-Alone w/o TC w/CO2
LA = Leading Stand-Alone Master w/o TC w/CO2
LB = Leading Stand-Alone Slave w/o TC w/CO2
LC = Leading BACnet MS/TP w/o TC w/CO2
LD = Leading LonMark SCC w/o TC w/CO2
LE = Leading Metasys N2 Open w/o TC w/CO2
LF = Leading Stand-Alone w/ TC w/CO2
LG = Leading Stand-Alone Master w/ TC w/CO2
44 = Electromech w/2-Pos Damper for Remote T'Sta
45 = Electromech w/2-Pos Damper w/Unit Mtd. ACO
46 = Electromech w/2-Pos Damper w/Unit Mtd. MCO
Grille Unit
AAF-HermanNelson Model AZ Unit Ventilators3
Introduction
AAF-HermanNelson Classroom Unit Ventilators
For more than 89 years, schools have relied on
AAF-HermanNelson unit ventilators to keep classrooms
comfortable. Students learn more readily in a quiet, wellventilated environment. That’s why Herman Nelson
invented the unit ventilator and why we remain
committed to meeting the changing requirements of
schools with the highest quality products available.
We realize that keeping expenditures down is a high
iority for school administrators and school boards.
r
p
AAF-HermanNelson unit ventilators are inexpensive to
install and operate, and they are designed and built to
provide decades of trouble-free service.
Built To Last
Our proven institutional design can withstand the rigors
of the classroom environment. It features an extra-sturdy
chassis and double-wall damper on the inside; scuffresistant finishes and tamper prevention features on the
outside. In fact, many units installed over 30 years ago
continue to provide quiet, reliable classroom comfort.
Heavy Duty Frame Construction
AAF-HermanNelson’s exclusive, unitized welded frame
is far superior to the fastener-type construction used by
other manufacturers. Loosened fasteners can cause
vibration, rattles and sagging panels.
Other design features that promote trouble-free
per
ation and long life include:
o
• A corrosion-resistant, galvanized-steel frame.
• Extra-strength, steel-bar disc
• Heavy-gauge-metal cabinet access panels and doors.
• An extra-str
ength pipe tunnel that stiffens the structure
while adding aerodynamic air flow within the unit.
• Hidden reinforcement that provides additional built-in
ort for the top section as well as better support for
supp
the fan deck assembly.
harge grille.
igid exterior that is strong enough to support
• A r
main
tenance personnel without fear of damaging the
unit.
Rugged Exterior Finish
The superior finish of the unit ventilator cabinet fosters
long-lasting beauty as well as resistance to abuse and
corrosion. We apply the very highest standards at every
step of the finishing process to provide lasting quality:
• Exter
ior cabinet panels are fabricated from high-
qua
lity, furniture grade steel with no sharp edges.
• A specially formulated, environmentally friendly,
ermosetting urethane powder is applied
th
electrostatically to the exterior panels. This film is
oven-cured to provide correct chemical cross-linking
and to obtain maximum scuff- and mar-resistance.
he top of the unit is finished with a textured, non-glare
• T
and
scuff-resistant, charcoal bronze electrost atic pa int.
End and front panels are available in a pleasing array
of architectural colors.
he Oxford brown steel kickplate is coated and baked
• T
with a
thermosetting urethane powder paint to blend
with floor moldings and provide years of trouble-free
service.
h unit is painstakingly inspected before
• Eac
then encapsulated in a clear plastic bag, surrounded
by an extra-heavy-duty cardboard box and secured to
a skid to help provide damage-free shipment.
MicroTech II Control For Superior
Performance, Easy Integration
AAF-HermanNelson unit ventilators can be equipped
with MicroTech II™ unit controllers for superior
performance. Factory integrated and tested controller,
sensor, actuator and unit options promote quick, reliable
start-up and minimize costly field commissioning. Our
Protocol Selectability feature provides easy, low-cost
integration into most building automation systems. Select
BACnet
communications to communicate control and monitoring
information to your BAS, without the need for costly
gateways. Unit controllers are L
the optional L
®
, LonTalk® or Metasys® N2 Open
ONWORKS
®
communication module.
ONMARK
®
certified with
boxing,
4McQuay Catalog 1620
Introduction
The Model AZ Floor Unit
Our Model AZ is a vertical, floor-standing unit that utilizes
refrigerant for cooling, and hot water, steam or electric
heat for heating. The Model AZ also can be supplied as a
cooling/ventilating unit only.
11
13
1
10
12
2
4
8
6
The Model AZ is just right for new construction and for
etrofit applications. Older buildings with baseboard
r
radiant heat or other hydronic heating systems can be
easily adapted to work efficiently with Model AZ units.
The major features of this model are shown below and
described in more detail on the following pages.
7
3
5
9
16
17
15
1 Welded One-Piece Chassis offers
superior strength, durability, and
vibration reduction.
2 Unique Draw-Thru Design provides
uniform air distribution across the coil
for even discharge air temperatures.
3 Quiet, Aerodynamic Fans utilize
GentleFlo technology for
exceptionally quiet unit operation.
4 Modular Fan Section improves
balance, alignment and simplifies
maintenance.
5
Fan Motor Located Out Of Air
Stream
and away from heating coil
reduces heat exposure to prolong life.
6 Outside Air/Return Air Damper &
Linkage Provides superior mixture of
outdoor air and room air for precise
temperature control.
7 MicroTech II Controls provide
superior comfort control and easy
integration into the building
automation system of your choice.
8 Advanced Heat Transfer Coil
design provides extra capacity.
9 Sturdy Cabinet Construction
includes hidden reinforcement, a
non-glare textured surface, and a
tough, scuff- and mar-resistant finish
to make the top sturdy enough to
support maintenance personnel.
10 Sectionalized Front Access Panels
provide easy access to unit interior.
Panels are easily removed by a
single person. Front side panels can
be removed while unit is running.
14
11 Two Hinged To p Access Doors
provide easy access to the motor,
electrical, and refrigeration
components..
12 Sampling Chamber for unit-
mounted sensor provides accurate
sensing of room temperature.
13 Optional Adjustable Caster (Left
and Right Ends).
14 Insulated Double-Wall Outdoor Air
Damper seals tightly without
twisting.
15 Full-leng t h Air Filt er is efficient and
easy to replace. All air delivered to
classroom is filtered.
16 Corrosion Proof Sloped Drain Pan.
17 Tamper Resistant Fasteners on
Access Panels
AAF-HermanNelson Model AZ Unit Ventilators5
Features & Benefits
Features & Benefits
GentleFlo Delivery
AAF-HermanNelson unit ventilators are engineered and
manufactured to deliver quiet, continuous comfort. We
developed our GentleFlo™ air moving syst em to
minimize operating sound levels—even as demands for
more fresh air require units to operate longer and work
harder. GentleFlo featur es include:
wheels are large, wide and rotate at a low speed
• Fan
to red
uce fan sound levels. They are impact-resistant
and carefully balanced to provide consistent
performance.
fset, aerodynamic fan wheel blades move air
• Of
ef
ficiently (Figure 1).
• Precision tolerances help reduce flow and pr es su re
turbulence, resulting
in lower sound levels.
• Fan housings incorporate the latest logarithmic-
ansion technology for smoother, quieter air flow
exp
(Figure 2).
Figure 1. GentleFlo Fan Technology
Expanded discharge air
opening
• A large, expanded discharge opening minimizes air
resistance, further lowering sound levels.
• Modular fan construction contributes to equal outlet
locities and promotes quiet operation.
ve
• Fan shafts are of ground and polish ed steel to
ize deflections and provide consistent, long-term
minim
operation.
• Fan assemblies are balanced before unit assembly,
en tested after assembly (and rebalanced if
th
necessary) to provide stable, quiet operation.
Figure 2. GentleFlo Reduces Turbulence
Minimal
Offset aerodynamic blades
Logarithmic expansion housing
Precision Tolerances
6McQuay Catalog 1620
GentleFlo fan blade design
turbulence
Typical fan blade design
High turbulence
Features & Benefits
The Right Amount of Fresh Air and
Cooling
AAF-HermanNelson unit ventilators deliver required
amounts of fresh air to meet ventilation requirement s and
added cooling capacity to maintain consistent comfort for
students and teachers. Our Economizer Operation,
Demand Control Ventilation (DCV) and Part Load,
Variable Air options allow you to mat ch cla ssr oo m
comfort requirements even more closely, and reduce
operating costs.
at your school is
This means that you can be confiden
meeting ventilation standards for Indoor Air Quality and
that your students are receiving adequate air to be
attentive to instruction. At the same time, you are saving
money in early morning hours, between classes or after
hours when classrooms are heated and cooled but not
always fully occupied.
Economizer Operation
It is well recognized that cooling, not heating, is the main
thermal challenge in school classrooms. The typical
classroom is cooled by outdoor air over half the time,
even in cold climates. It is therefore essential that unit
ventilators efficiently deliver outdoor air when classroom
conditions call for “free” or economizer cooling.
With AAF-HermanNelson unit ventilators, you can have
tdoor air whenever it is needed. Economize r operatio n
u
o
is facilitated by the outdoor air damper, which
automatically adjusts the above-minimum outside air
position to provide free cooling when the outdoor air
temperature is appropriate (Figure 3). On unit s equippe d
with MicroTech II controls, three levels of economizer
rol are available (see See “Economizer Modes” on
t
con
page 14).
Figure 3. Full Economizer Mode
100% Outdoor Air Into Classroom
Condenser
Section
Face &
Bypass
Damper
Room Air
Damper
t th
Filter
Outdoor Air
Damper
Outdoor Air
Part-Load Variable Air Control
Part Load Variable Air control can be used in conjunction
with face and bypass damper temperature control to
automatically adjust the unit ventilator fan speed based
upon the room load and the room temperat ure. This
MicroTech II control option provides higher latent cooling
capabilities and quieter operation during non-peak load
periods by basing indoor fan speed upon room load.
Lower fan speeds in conjunction with our GentleFlo fan
technology contributes to a very quiet classroom
environment.
Room-temperature PI control loops determine the speed
e fan, wh
of th
also provides a built-in delay to prevent overshooting for
better comfort control. The outdoor air damper’s
minimum-air position is adjusted with the fan speed to
bring in a constant amount of fresh air.
ich varies according to the room load. It
Precise Temperature and
Dehumidification Control
AAF-HermanNelson unit ventilators provide precise
temperature and dehumidification control to keep
students and teachers comfortable while making
maximum use of “free” outdoor-air cooling to reduce
operating costs. They utilize a draw-thru fan design that
contributes to even heat transfer and provides uniform
discharge air temperatures into the classroom.
MicroTech II active dehumidification control strategies
and 2-stage compressor operation, provide precise
control of temperature and humidity levels under both
part-load and full-load conditions.
Draw-Thru Design For Even Discharge
Temperatures
The AAF-HermanNelson Draw-Thru design sets our unit
ventilators apart from most competitive models. With this
system, fans draw air through the entire heat transfer
element (Figure 4) rather than blowing it through highly
concentrated areas of the coil element. The result is
o
re uniform discharge air temperatures into the
m
classroom and more efficient unit ventilator operation.
AAF-HermanNelson Model AZ Unit Ventilators7
Features & Benefits
Figure 4. Draw-Thru Design Provides Even Discharge Air
Uniform Discharge Air (Shaded)
Motor
Fans
Condenser
Face & Bypass Design For Better
Temperature Control
When coupled with our draw-thru design, face and
bypass damper air control offers optimal temperature
control in heating. That’s because indoor and out d oo r air
streams can be separated until it is optimal to mix them.
Figure 5. Draw-Thru Vs. Blow-Thru Design
Coil
Filter
RA/OA
Divider
Room Air
Outdoor Air
Blow-Thru Design
Face &
Bypass
Damper
Room Air
Damper
Room Air
AAF-HermanNelson
Draw-Thru Design
Coil
Outdoor
Air Damper
Outdoor Air
Active Dehumidification (Reheat)
In high-humidity applications where valve-controlled,
reheat units are used, the Active Dehumidification
Control (ADC) sequence should be considered. With the
Leading Edge Microtech II controls, an inside humiditst at
compares indoor humidity (enthalpy) with outdoor
humidity to determine the economizer position.
During excessive humidity conditions
, a humidity
sensor
directs the unit to continue cooling p ast the room setpoint
to remove moisture. Hydronic heat or electric heat is
then used to reheat the discharge air to maintain
acceptable room temperatures.
Increased Coil Freeze Protection
AAF-HermanNelson units equipped with face and
bypass damper control, provide extra protection from coil
freeze-up, because there is a constant flow of hot water
through the coil, and water that is flowing typically does
not freeze. Additionally, all AAF-HermanNelson units
feature a double-walled, insulated outdoor air damper
with airtight mohair seals to prevent unwanted coil air
from entering the unit.
Furthermore, a low-temperature freezestat is factory
inst
alled on
all units with hydronic coils. Its serpentine
capillary tube senses temperatures across the leaving air
side of the coil, allowing the unit controller to react
quickly to low-temperature conditions.
Figure 6. Freezestat
Freezestat
Capillary Tube
Low Installation Costs
Perfect For Both New & Retrofit
Applications
New construction installations are easily accomplished
with AAF-HermanNelson unit ventilators because they
avoid the added cost and space required for expensive
duct work. Further savings can be realized because
piping installations use less space than duct systems.
This is important in existing buildings and also in new
construction where floor-to-floor heights can be reduced,
saving on overall building costs.
Retrofit installations are economical because new units
pically
ty
Using AAF-HermanNelson unit ventilators, central
equipment, such as chillers, can be sized smaller using
building diversity. This results in a low capital-cost
system.
Built In Flexibility
AAF-HermanNelson unit ventilators include features that
make them easy to set up and reconfigure as needed to
meet special requirements. These features include:
• Built-In Wire Race A built-in meta
fit the same space occupied by existing ones.
l wire race runs from
one end of the unit to the other to provide extra
protection for wires and protect them from unit air.
8McQuay Catalog 1620
Features & Benefits
Figure 7.
Condenser casters ease
installation. Optional indoor
casters can be adjusted.
Condenser Casters and Optional Unit Casters
Controls Flexibility
Multiple control options—including MicroTech II controls
with our Protocol Selectability feature—provide easy , low
cost integration of AAF-HermanNelson unit ventilators
into the building automation system of your choice (See
“MicroTech II Controls” on page 13) . You can also
operate these units individually or in a master-servant
t
rol configuration.
con
With MicroTech II controls, you can select BACnet,
alk or Metasys N2 communications to communicate
LonT
control and monitoring information to your BAS, without
need for costly gateways. Unit controllers are
the
ONMARK certified with the optional LONWORKS
L
communication module.
Then consider how AAF-HermanNelson unit ventilators,
locate
d in each classroom, take advantage of these
realities to lower operating costs:
• They provide individual classroom control and comfort.
• They can be cycled on
when the room is occupied and
cycled off when it is not.
• They bring in fresh air from directly outside the
ssroom for high indoor air quality.
cla
• During most of the school year, they use outdoor air to
ep classrooms comfortable without the expense of
ke
mechanical cooling.
MicroTech II Control Options Further
Reduce Operating Costs
Many of the MicroTech III control options available with
AAF-HermanNelson unit ventilators can further reduce
operating costs. For example:
• Economizer Operation Econ
automatically adjusts the above-minimum outside air
position to provide free cooling when the outdoor air
temperature is appropriate.
• Demand Control Ventilation By usin
monitor the actual occupancy pattern in a room, the
system can allow code-specific levels of outdoor air to
be delivered when needed without costly overventilation during periods of low or intermittent
occupancy (Figure 8).
omizer operation
g CO
levels to
2
Low Operating Costs
Schools consume more than 10% of the total energy
expended in the United States for comfort heating and
cooling of buildings. As energy costs increase, educators
are placed in a difficult position: caught between rising
costs, lower budgets and the requirements to raise
educational standards.
e system exists for
Fortunately, the technology an
schools to take control of their energy expenditures wh ile
providing a comfortable environment for learning. And
that system is the AAF-HermanNelson unit ventilator.
Consider these realities of school environments:
• Most
heating energy in schools is expended to heat
un
occupied spaces. Because lights, computers and
students give off considerable heat, occupied spaces
require little supplemental heat.
• The
removal
of heat is usually required in occupied
classrooms, even when outside temperatures are
moderately cold (i.e., 35-40°F).
d th
Figure 8. Energy Savings with Demand Control Ventilation
100%
Energy Savings
with DCV
Unoccupied
20%
DCV's fresh air for indoor air quality
6:008:00 10:00 12:00 2:004:00 6:008:00 10:00
School Hours
Cleaning
After Hours
Unoccupied
• Occupancy Mode Operation Units can be
programmed to operate only sparingly during
unoccupied periods and at night to conserve energy.
Two Stage Compressor
Air conditioning units are usually sized for worse case
conditions. During high load requirement the unit will
operate in high fan speed and high compressor capacity.
Most of the time there is not a full load on the
compressor. Operation in lower load will be at medium or
AAF-HermanNelson Model AZ Unit Ventilators9
Features & Benefits
low fan speeds which will be at the lower displacement
compressor stage. The two stage compressor will remain
at low speed until more cooling is required. With the twostage compressor, these units will run on lower fan
speeds most of the time improving comfort through
better humidity control and quieter operation, while
minimizing issues with over-sizing.
ors operate at
Other units utilizing single stage compres
full compressor capacity all of the time regardless of fan
speed.
s
Easy To Maintain
Fan Deck
The fan deck’s rotating element has one large, selfaligning, oilable end bearing for smoother operation.
Figure 9. Long-Life Bearings
Long Life Bearing
Even “permanently” lubricated motors are supplied with
recommended lubrication charts calling for lubrication
every seven years. Maintenance instructions of the
motor manufacturer should be followed clo sely.
Heavy-Duty Discharge Grille
The discharge grille on the top of the unit is made from
extra-strength steel bar stock, promoting long life
(Figure 10). It can be removed to facilitate cleaning
fans and fan housings.
Figure 10. Heavy-Duty Steel Discharge Grille
of
Internal Fan Deck Components
Unlike with many competitive models, the motor in
AAF-HermanNelson unit ventilators is separate from the
fan assembly and is located out of the airstream at the
end of the fan shaft—away from the hot coil—for easier
maintenance and removal. Locating the motor away from
the coil (Figure 11) has the added benefit of extending
motor life. Our direct-coupled motor and self-aligning
r mount facilitate motor change-out. The motor
to
mo
comes with a molex plug that fits all sizes and further
simplifies removal.
Figure 11. Fan Deck
Aerodynamic Fans
Modular
Fan Deck
Heavy-Duty
Discharge Grille
Motor Located
Out of Airstream
Filter
10McQuay Catalog 1620
Features & Benefits
Tamper-Resistant Fasteners
Front panels and top access doors are held in place by
tamper-resistant, positive-positioning fasteners. They are
quickly removed or opened with the proper tool, but deter
unauthorized access to the unit’s interior (Figure 12).
Sectionalized Access Panels And Doors
All units have three separate front panels and hinged top
access doors, sized for convenient handling by a single
person (Figure 12). The result is easy , t argeted access to
the component that needs servicing:
wo end panels provide easy access to piping,
• T
te
mperature control components and the fan switch.
Unlike units with full-length front panels, these can be
removed without disturbing the normal operation of the
unit.
ged top access doors provide easy access into the
• Hin
end c
ompartments to facilitate convenient servicing of
the motor, electrical, and refrigeration components.
• Center front panel provides easy access to the filter
d fan shaft bearing (size 048 only).
an
Filter
Three filter types are offered:
• Units come standard with a single-use filter which is
de
signed to be used once and discarded.
• Optional, permanent metal filters are available and can
removed for cleaning and reused numerous times.
be
• Renewable media filters, which consist of a heavy-
uty, painted-metal structural frame and renewable
d
media.
Figure 12. Easy Access With Tamper-Resistant Fasteners
Tamper Resistant
Fasteners
Tamper Resistant
Fasteners
Discharge
Grille
Tamper Resistant
Fasteners
Tamper Resistant
Fasteners
Removeable
Filter
AAF-HermanNelson Model AZ Unit Ventilators11
Features & Benefits
Built To Last
Durable, Energy Efficient Fan Motors
AAF-HermanNelson unit ventilators are equipped with
1 15/60/1 NEMA motors that feature low operating curr ent
and wattage (Figure 13).
Figure 13.
Additional features of these motors include:
• Split-capacitor (PSC) design with au
thermal-overload protection.
• No brushes, contacts or centrifugal starting switches—
the mo
• A built-in, decoupled isolation system to reduce
tran
• A multi-tap, auto-transformer (Fi
multiple fan motor speed control through the speed
switch. The
which allows stocking of one motor (school districtwide) for various voltage applications.
a twist-free
reinforced aluminum construction for durability.
Aluminum is used because it is lightweight and
noncorrosive, resulting in low torque and easy
movement.
e
• Outdoor air dampers ar
made of galvanized steel to
inhibit corrosion, with double-wall welded construction
for rigidity and encapsulated insulation (Figure 15).
Additional insulation is provided on the exterior of the
d
oor air damper blade and on the outdoor air entry
out
portion of the unit.
Figure 15.
Wool Mohair
End Seal
Outdoor Damper Seals Out Cold Weather
Turned Metal
Damper Blade
Turned Metal
Damper Stop
Full-Length
Wool Mohair Damper
Additional
Insulation
Wool Mohair End
Seal
• Room air dampers are free-floating and designed to
prevent intermittent gusts of cold air from blowing
directly into the classroom on windy days (Figure 16).
They are constructed of aluminum with built-in rigidity.
metal forming technique that is employed resists
The
twisting and incorporates a full-length counter weight
for easy rotation. The simple principle of an area
exposed to a force is used to automatically close the
damper, rather than open it, when gusts of cold air
occur.
Figure 16.
Room Air Damper Auto-Closed By Wind Gusts
Wind
Gust
Durable Damper Design
All dampers in AAF-HermanNelson Unit Ventilators use
the turned-metal principle on their long closing edges
(Figure 15). Positive sealing is provided by embedding
a
the edge into wool mohair (no met
There are no plastic gaskets to become brittle with time,
sag with heat or age, or require a difficult slot fit to seal.
12McQuay Catalog 1620
l to metal contact).
MicroTech II Controls
MicroTech II Controls
MicroTech II Controls For Superior Performance, Easy Integration
AAF-HermanNelson unit
ventilators equipped with
MicroTech II unit controllers can
ovide superior performance
pr
and easy integration into your
building automation system of
choice. MicroTech II benefits
include:
actory integrated and tested
• F
controller, sensor, actuator and unit options promote
quick, reliable start-up and minimize costly field
commissioning.
h-performance features and advanced control
• Hig
options can quickly pay for themselves in saved energy
costs and more comfortable classrooms.
• Select
from three control levels: stand-alone, master-
servant or network control.
network control applications, our Protocol
• For
Selectability feature provides easy, low-cost integration
of AAF-HermanNelson unit ventilators into most
building automation systems.
• Flexible BAS
network communication options guard
against controls obsolescence, keeping MicroTech II
controls viable for the life of your AAF-HermanNelson
equipment.
Three Control Levels
MicroTech II unit controllers provide the flexibility to
operate AAF-HermanNelson unit ventilators on any of
three levels:
• As st
• I
• Co
Stand-Alone Control
When operating in stand-alone mode, the MicroTech II
controller performs complete room temperature and
ventilation control. Units can be operated in occupied,
unoccupied, stand-by, or bypass (tenant override)
modes. Occupied/unoccupied changeover can be
accomplished:
• Man
• Automa
and-alone units, with control either at the unit or
from a wall sensor.
n a master-servant relationship, where serv an t un its
follow the master unit for some or all functions.
ntrolled as part of a network using a centralized
building automation system.
ually by a unit-mounted occupied/unoccupied
switch.
tically by a unit-mounted occupied/unoccupied
time clock.
tomatically by a remote-mounted time clock that
• Au
operates unit-mounted day/night relays.
If a school has more than one zone, separate, remote
time clocks ar
e used to regulate each zone. In this case,
the remote-mounted time clock energizes or deenergizes an external, 24-volt or 120-volt control circuit
which operates the unit-mounted day/night relays in that
zone.
Master-Servant Control
Designate the master and servant units and we will
factory configure and install the controllers so they are
set up for a local peer-to-peer network between units
(leaving only the network wiring between these units to
be field installed).
Servant units can be field-configured to be dependent or
ependent as follows:
ind
pendent servant units follow the master unit
• De
completely. They are ideal for large spaces that have
even loads across the space (such as some libraries).
dependent servant units (default) use master
• In
setpoints and servant sensors. The servant follows the
master unit modes, such as heat or cool, but has the
flexibility to provide the conditioning required for its
area within the space. Independent servant units
perform better in spaces where loads vary from one
area of the space to the other (such as stairwells or
cafeterias).
Network Control
MicroTech II unit controllers provide easy integration into
your building automation system of choice. All factoryinstalled options are handled by the unit controller. This
simplifies the transmission of monitoring and setpoint
data to the building automation system.
You select BACnet, LonTalk or Metasys N2 Open
unications to communicate control and monitoring
comm
information to your BAS, without the need for costly
gateways (see “Optional Communication Modules” on
page 19). Unit controllers are L
optional L
ONWORKS communication module.
ONMARK certified with the
Flexible network communication options via our Protocol
tability feature help you avoid control obsolescence
Selec
over the life of your AAF-HermanNelson equipment.
AAF-HermanNelson Model AZ Unit Ventilators13
MicroTech II Controls
Control Modes and Functions
AAF-HermanNelson unit ventilators equipped with
MicroTech II unit controllers can be programmed to
perate in a variety of modes based on the current
o
situation in the room and the status of the unit ventilator.
Changes in mode can be triggered manually, via network
signals, by sensor readings, or by date and time.
External inputs and outputs can be used to change
modes, communicate data to network contr ols or change
the functional operation of the unit.
Occupancy Modes
MicroTech II unit controllers can be set up to change
modes based on room occupancy. Four different
occupancy modes are provided, as described below.
Occupied Mode
This is the normal daytime operation mode. The
controller maintains a room set point using the out side air
capability and other functions.
Note: For non-school applications, the unit can also be
configured to cycle the fan in response to the room load.
In this case, the fan would normally be in the Off Mode
until heating or cooling is required. The outside air
damper is always closed when the fan is off. When the
fan starts, the outside air damper opens to the required
position, usually minimum position.
Economizer Modes
Economizer operation is facilitated by the outdoor air
damper, which automa tically adjust s the above-minimum
outside air position to provide free cooling when the
outdoor air temperature is appropriate. Three levels of
economizer control are available:
Basic Economizer Operation: The MicroTech II
controller compares the inside and outs ide temperatures.
If the temperature comparison is satisfactory, then freeair economizer operation is used to cool the space.
Reheat units also come configured with an indoor
humidity sensor.
Expanded Economizer Operation: In addition to
comparing inside and outside temperatures, outdoor
relative humidity is measured to calculate outside air
enthalpy. Free economizer operation is used to cool the
space. This helps to minimize the entrance of humid
outside air.
Leading-Edge Economizer Operation: The MicroTech II
controller compares both indoor and outdoor
temperatures and indoor and outdoor relative humidities
to determine if free economizer operation can cool the
space with non-humid outside air. This is a true enthalpy
economizer.
Unoccupied Mode
This is the night setback operating mode, in which the
unit responds to a new room set point and cycles to
maintain the condition. The fan comes on when heating
or cooling is needed and runs until the load is satisfied.
The outdoor air damper is closed during this mode.
When a cooling load is satisfied by a refrigerant system,
the compressor is de-energized and the unit ventilator
indoor fan continues to run for a fixed period of time to
remove coldness from the evaporator coil.
Stand By Mode
In this mode, the unit maintains the occupied mode set
point temperature with the outdoor air damper closed.
The fan runs continuously unless it is configured to cycle
in response to the load.
Bypass Mode
This is a tenant override operating mode in which the unit
is placed back into the Occupied Mode for a
predetermined time. The default is 120 minutes. Settings
can be made in 1-minute increments from 1 minute to
240 minutes through ServiceTools™ (see page 23) or a
network.
Night Purge Mode
Under this mode, the unit is configured to purge the room
space for one hour for various reasons (odor or fume
removal, drying, etc.).During Night Purge the outside air
damper is open full and the fan is run on high speed. No
“normal” heating or cooling takes place (the emergency
heat set point is maintained) and the exhaust fan, if the
room is so equipped, is signaled to turn on.
Freeze Prevention Mode
This mode helps protect the unit ventilator from freezing
air conditions. Control functions vary depending on the
type of temperature control used by the unit, as follows:
Face and Bypass Control Units
Upon sensing a potential freezing air tempera tu re
condition leaving the heating coil, the unit will protect
itself by shutting the outside air damper and opening the
EOC valve. The fan continues to run to remove the cold
air. Once accomp lished, the freezestat is reset, the
outside air damper opens to the minimum position and
the unit commences its normal mode of operation.
14McQuay Catalog 1620
MicroTech II Controls
Valve Control Units
Upon sensing a potential freezing air temperature
condition leaving the heating coil, the unit will
automatically protect itself by shutting the outside air
damper and opening the hot water valve to a mini mum of
50% (more if required to heat the room). The fan speed
will be staged down to low speed and then turned off.
When the freezestat is reset, the outside air damper
opens to the minimum position and the fan runs at low
speed for a minimum of 10 minutes. It then will stage up
if needed to satisfy the room set point. This reduces the
potential to overheat a room recovering from a potential
freeze condition.
Note: Valve selection and coil sizing is critical for proper
operation. Face and bypass control is recommended for
proper freeze protection.
Emergency Heat Mode
If the unit is left in a mode that does not normally allow
heating (such as Off, Fan Only, Cool, or Night Purge)
and the room temperature falls below 55°F, the unit will
heat the space to above 55°F and then return to the
previously set mode of operation. This mode of operation
can be field configured and/or be disabled.
External Input Functions
The unit ventilator controller is provided with three (3)
binary inputs that allow a single set of dry contacts to be
used as a signal to it. Input signal choices are described
below. Multiple units can be connected to a single set of
dry contacts.
Note: Not all of the functions listed can be used at the same
time. The unit ventilator controller is provided with
configuration parameters that can be adjusted to select
which function will be used for these inputs where
multiple functions are indicated below. For wiring
examples see installation manual IM 747: MicroTech II
Unit V
entilator Controller.
Unoccupied Input Signal
This input signals the unit ventilator controller to go into
unoccupied or occupied mode. When the contact s close,
the unit ventilator controller goes into unoccupied mode;
when the contacts open, it goes into occupied mode.
Additional variables can affect occupancy mode and
override this binary input. See “Occupancy Modes” on
page 14.
Dewpoint/Humidity Input Signal (Optional)
This input signals the unit ventilator controller to go into
active dehumidification mode. When the contacts close
(high humidity) the controller will go into active
dehumidification; when the contacts open (low hu midity)
it will stop active dehumidification.
Remote Shutdown Input Signal
This input signals the unit ventilator controller to go into
shutdown mode. When the contact s close, the controller
goes into shutdown mode; when the contacts open, it
returns to normal operation.
Ventilation Lockout Input Signal
This input signals the unit ventilator controller to close
the outdoor air damper. When the contacts close
(ventilation lockout signal) the controller closes the
outdoor damper; when the contacts open, it returns to
normal outdoor damper operation.
Exhaust Interlock Input Signal
This input signals the unit ventilator controller that an
exhaust fan within the space has been energized. The
controller then repositions the outdoor air damper to a
user-adjustable minimum position. When the contacts
close (exhaust fan on signal) the controller uses the
value defined by the Exhaust Interlock OA Damper Min
Position Setpoint as the new minimum outdoor air
damper position regardless of the indoor air fan speed.
When the contacts open, it returns to normal outdoor
damper operation.
External Output Functions
The unit ventilator controller is provided with three (3)
binary outputs to perform the functions described below.
These are relay type outputs that are intended to be
used with signal level voltages only (24 VAC max).
Note: Not all of the functions listed can be used at the same
time. The unit ventilator controller is provided with
configuration parameters that can be adjusted to select
which function will be used for these outputs when
multiple functions are indicated below. For wiring
examples, see installation manual IM 747: MicroTech II
Uni
t Ventilator Controller.
Lights On/Off Signal
This relay output provides one set of NO dry contacts
that can be used to signal the operation of the room
lights. When the unit ventilator controller is in occupied,
standby or bypass occupancy modes, the relay output
will signal the lights on (contacts closed); when the
controller is in unoccupied occupancy mode the relay
output will signal the lights off (contacts open).
AAF-HermanNelson Model AZ Unit Ventilators15
MicroTech II Controls
Fault Signal
This relay output provides NO, NC, and Common
connections that can be used to signal a fault condition.
When a fault exists, the unit ventilator controller
energizes this relay output. When the fault or faults are
cleared, it de-energizes this relay output.
Exhaust Fan On/Off Signal
This relay output provides one set of NO dry contacts
that can be used to signal the operation of an exhaust
fan. When the outdoor air damper opens more than the
Energize Exhaust Fan OA Damper Setpoint, the relay
output will signal the exhaust fan on (contacts closed).
When the outdoor damper closes below this setpoint, th e
relay output will signal the exhaust fan off (contacts
open).
Auxiliary Heat Signal
This relay output provides one set of NO dry contacts
that can be used to operate an auxiliary heat device. The
unit ventilator controller by default is configured to
operate a NO auxiliary heat device (de-energize when
heat is required) such as a wet heat valve actuator with a
spring setup to open upon power failure. However, the
Auxiliary Heat Configuration variable can be used to set
the controller to use an NC auxiliary heat device
(energize when heat is required) such as electric heat.
fan operation under normal operating conditions, in
conjunction with our GentleFlo fan technology
contributes to a very quiet classroom environment.
Demand-Controlled Ventilation (Optional)
AAF-HermanNelson unit ventilators can be equipped to
use input from a CO
based on actual occupancy instead of a fixed design
occupancy. This Demand Controlled Ventilation (DCV)
system monitors the amount of CO
students and teachers so that enough fresh o utdoor air is
introduced to maintain good air quality. The system is
designed to achieve a target ventilation rate (e.g., 15
cfm/person) based on actual occupancy.
By using DCV to monitor the actual occup a ncy pattern in
oom, the system can allow code-specific levels of
a r
outdoor air to be delivered when needed. Unnecessary
over-ventilation is avoided during periods of low or
intermittent occupancy.
With DCV you can be confident that your school is
eting ventilation standards for Indoor Air Quality and
me
that your students are receiving adequate air to be
attentive to instruction. At the same time, you are saving
money in early morning hours, in between classes, or
after hours when classrooms are heated and cooled but
not always fully occupied.
Acceptance By Codes And Standards
controller to ventilate the space
2
produced by
2
Advanced Control Options
MicroTech II controls make possible a number of
advanced control options that can quickly pay for
themselves in saved energy costs and more comforta ble
classrooms, as described below .
Part Load Variable Air Control
Part Load Variable Air control can be used in conjunction
with face and bypass damper temperature control to
automatically adjust the unit ventilator fa n spee d ba se d
upon the room load and the room-temperature PI control
loop. This MicroTech II control option provides higher
latent cooling capabilities and quieter operation during
non-peak load periods by basing indoor fan speed upon
room load.
During low-load or normal operation (about 60% of the
time) the fan will operate
increases to an intermediate demand, the fan will
automatically shift to the medium-speed setting. Under
near-design or design-load conditions, the fan will
operate on high speed. A built-in, 10-minute delay helps
minimize awareness of fan speed changes. Low-speed
on low speed. When the load
ASHRAE Standard 62-2004 Ventilation for Indoor Air
Quality recognizes CO
controlling ventilation based on occupancy. The
ASHRAE standard has been referenced or adopted by
most regional and local building codes. This standard
references ventilation on a per-person basis.
Using CO
amount of outside air delivered into a room but will
maintain the per-person rate. For example, if a
classroom is designed for 30 students, the ventilation
rate is 450 cfm (30 students X 15 cfm/student) . However,
when there are only ten students in the classroom, the
CO
2
X 15 cfm/student). A minimum base ventilation rate
(typically 20% of design levels) is provided when in the
occupied mode. This provides outdoor air to offset any
interior source contamination while allowing for proper
space pressurization.
control will sometimes lower the absolute
2
control will adjust ventilation to 150 cfm (10 students
based DCV as a means of
2
Active Dehumidification Control (Reheat)
In high-humidity applications where valve-controlled,
reheat units are used, the Active Dehumidification
Control (ADC) sequence should be considered. During
16McQuay Catalog 1620
MicroTech II Controls
excessive humidity conditions, a humidity sensor directs
the unit to continue cooling past the room setpoint to
remove excess moisture. Hydronic heat or electric heat
is then used to reheat the discharge air to maintain
acceptable room temperatures.
MicroTech II controls minimize th
e amount of reheat
needed to maintain relative humidity below a preset limit.
Reheat is used only when required and in the most
energy-efficient manner possible.
Active Dehumidification comes standard on units
quipped with MicroTech II controls, a reheat
e
figuration and valve-control temperature modulation.
con
The MicroTech ADC humidity sensor is unit-mounted. It
issues a signal proportional to the classroom’s humidity
level (unlike humidistats which issue an open-close
signal). This enables a control sequence that manages
both the temperature and the relative humidity.
When the relative humidity exceeds a preset value, the
efrigerant cooling activates to dehumidify the mixture of
r
outdoor and return air entering the cooling coil. The
reheat modulating water valve then opens, or electric
heat is engaged, to reheat the air leaving the cooling coil,
as required to maintain the classroom setpoint.
Active dehumidification starts when the indoor relative
umidity exceeds the preset relative humidity upper
h
setpoint and continues until the room humidity falls 5%
below the endpoint. During active dehumidification,
economizer operation is disabled (and the outdoor air
damper is reset to its minimum position) unless the
outdoor air temperature is below 55°F. It is maintained
until dehumidification is completed. When the indoor
humidity level is satisfied, the MicroTech II controller
reverts to its normal sequences to satisfy the classroom
temperature setpoint.
DX System Control
The unit ventilator controller is configured to operate the
compressor as secondary (mechanical) cooling when
economizer cooling is available, and as primary cooling
when economizer cooling is not available. Additional DX
control features include:
Compressor Envelope: This helps protect the
compressor from adverse operating conditions that can
cause damage and or shortened compressor life. It ends
compressor operation if coil temperatures exceed the
defined operating envelope.
Compressor Cooling Lockout: The unit ventilator
controller is configured to lock out compressor cooling
when the outdoor air temperature falls below the
compressor cooling lock out setpoint. Below this
temperature setpoint only economizer cooling will be
available.
Minimum On And Off Time: The unit ventilator controller
is provided with minimum-on and minimum-off timers to
prevent adverse compressor cycling (3-minutes default).
Compressor Start Delay Variable: This variable is
intended to be adjusted as part of the start-up procedure
for each unit. It is used to prevent multiple unit
compressors from starting at the same time af ter a power
failure or after an unoccupied-to-occupied changeover.
Each unit should be configured at start-up with a slightly
different (random) delay, or groups of units should be
provided with different delays.
AAF-HermanNelson Model AZ Unit Ventilators17
MicroTech II Controls
System Components
The main components of the MicroTech II system are:
• The Unit Ventilator Controller (UVC)
• The Local User Interface (LUI)
• Optional plug-in network communication modules
In ad
dition, unit ventilators equipped with MicroTech II
rollers feature factory-mounted sensors and
cont
actuators for system control and feedback.
Unit Ventilator Controller
The MicroTech II UVC is a DDC, microprocessor-based
controller designed to provide sophisticated comfort
control of an economizer-equipped AAF-HermanNelson
unit ventilator. In addition to normal operating control, it
provides alarm monitoring and alarm-specific component
shutdown if critical system conditions occur. Each UVC is
factory wired, factory programmed and factory run-tested
for the specific unit ventilator model and configuration
ordered by the customer.
Figure 17. MicroTech II Control Board
Terminal Connections
Plug-In Control Module
Figure 18. User Interface To uc h Pad
The User Interface has individual touch-sensitive printed
circuit board mounted buttons, and comes with a built-in
menu structure (Hidden Key and Password Protected) to
change many of the common operating variables.
Four Operating Mode States
Four different user operating mode st ates can be chosen
on the LUI:
Heat: Heating and economizer operation only.
Cool: Cooling and economizer operation only.
Fan Only: Fan only operation.
Local User Interface
A built-in LUI touch pad with digital LED Display is
located in the right hand compartment below the top rig ht
access door. In addition to the Operating Mode States
and Fan Functions, the Touch Pad will digitally display:
he room set point temperature.
• T
• The current room temperature.
• Any fault code for quick diagnostics at the unit.
Auto: The unit automatically switches between heating,
cooling and economizer operation to satisfy the room
load conditions. The current unit state is also displayed.
Four Fan States
Four fan states are provided on all units: high, medium
low and Auto speed modulation. The Auto speed
function (part load, variable air) varies the fan speed
automatically to meet the room load whether the unit is in
heating, cooling or economizer mode.
All this is accomplished with
NEMA frame motor. A built-i n 10-minute delay helps
minimize awareness of speed changes. During low-load
or normal operation (about 60% of the time) the fan will
operate at low speed. The low speed operation, along
with GentleFlo fan technology, contributes to a very quiet
classroom environment.
When the load increases to an intermediate demand, the
cally shifts to the medium speed setting. At
fan automat
near-design or design-load conditions the fan will
operate on high speed.
With four fan states and GentleFlo fan technology, there
n
o need to oversize units or worry about
is
uncomfortable conditions.
i
a standard, single-speed
18McQuay Catalog 1620
MicroTech II Controls
Optional Communication Modules
Optional communication modules provide control and
monitoring information to your building automation
system without the need for costly gateways. Available
communication protocols include BACnet, LonTalk and
Metasys N2 Open. The communication modules for each
are described below.
Figure 19. Typical 2" x 4" Communication Module
BACnet MS/TP Communication Module
This module allows the UVC to inter-operate with
systems that use the BACnet (MS/TP) protocol with a
conformance level of 3. It meets the requirements of the
ANSI/ASHRAE 135-1995 standard for BACnet systems.
LONWORKS SCC Communication Module
This module supports the LONWORKS SCC (Space
Comfort Communication) profile number 8500-10. Unit
controllers are LonMark certified with this optional
ONWORKS communication module.
L
Metasys™ N2 Communication Module
This module provides N2 Open network communication
capability to the UVC for communication with Johnson
Metasys systems.
Sensors
The UVC is configured to use passive Positive
Temperature Coefficient (PTC) unit-mounted and wallmounted sensors. These sensors vary their input
resistance to the UVC as the sensed temperature
changes.
Figure 20. Wall-Mounted Temperature Sensors
StandardExpanded
Standard Sensor: This sensor has no remote setpoint
adjustment capability.
Expanded Sensor: This sensor has a remote room
setpoint adjustment of ±3°F (±1.5°C) from the room
setpoint established on the unit ventilator’s local user
interface touch pad. Five temperature settings are
provided on each side of center.
Humidity Sensors
On units equipped with humidity sensors, the UVC is
configured to use a 0-100% RH, 0 VDC, capacitive
humidity se
nsor. Humidity sensors are available as unitmounted only. The humidity sensors are used with units
capable of active dehumidification, or with units using an
outdoor enthalpy economizer or an indoor/outdoor
enthalpy economizer.
CO2 Sensor for Demand Controlled Ventilation
On units equipped for Demand Controlled Ventilation
(DCV) the UVC is configured to use a 0-2000 PPM, 0-10
VDC, single beam absorption infrared gas sensor. CO
2
sensors are available as unit mounted only. An air
collection probe (pitot tube and filter) is installed in the
return air of the unit.
Figure 21. CO2 Sensor For Demand Control Ventilation
Remote Wall-Mounted Temperature Sensors
MicroTech II unit ventilators offer three choices for
remote wall-mounted room sensors (Figure 20). Each
has a tenant override capability and comes with an
international, quick-
AAF-HermanNelson Model AZ Unit Ventilators19
fastening connection capability.
MicroTech II Controls
MicroTech II Sensor and Component Locations
Figure 22. MicroTech II Sensor and Component Locations
14
4
5
13
12
11
16
20
1 MicroTech II Unit Ventilator Controller (UVC):
(Located Beneath the Local User Interface Panel).
Factory mounted and run tested, microprocessorbased DDC control device capable of complete,
Stand-alone unit control, Master/Slave control, or
incorporated into a building-wide network using an
optional plug-in communication module. The UVC
supports up to 6 analog inputs, 12 binary inputs, and 9
binary outputs. The UVC expansion board supports
up to 4 additional analog inputs and 8 additional
binary outputs. Master/Slave units have the controller
factory configured for a local peer-to-peer network
between these units (network wiring between thes e
units needs to be field installed). Optional network
17
3
9
19
18
21
2
15
10
6
communication is provided via plug-in communication
modules that connect directly to the UVC.
2 Communication Modules (optional): (Lo
Beneath the Local User Interface Panel). Plug -in
network communication module that is attached to the
UVC via a 12-pin header and 4 locking standoffs.
Available communication modules:
ing Automation and Control Netw
• Build
net™) Master Slave/Token Passing
ork (BAC-
(MS/TP) Allows the UVC to inter-operate with systems that
use the BACnet (MS/TP) protocol with a conformance level of 3. Meets the requirements of ANSI/
AE 135-1995 s
ASHR
tandard for BACnet systems.
1
ated
c
7
20McQuay Catalog 1620
MicroTech II Controls
• LONWORKS™ compliant Space Comfort Controller
(SCC) – Supports the L
ONWORKS SCC profile num-
ber 8500-10.
etasys™ N2 Open – Provides N2 Open network
• M
communication capability to the UVC.
3 Local User Interface (LUI):
The LUI provides a unit
mounted interface which indicates the current unit
operating state and can be used to adjust the unit
ventilator operating parameters (operating mode,
temperature set points, fan speed, and occupancy
mode). The LUI features a 2-digit display, 7 keys (1
key is hidden), and 9 individual LED indicators.
4 Tenant Override Switch Pr
ovides a contact closure
that causes the unit to enter the “Occupied” operating
mode for a set time period (default = 120 minutes).
5Time Clock (
optional on stand-alone units only)
Factory mounted 7 day/24 hour, digital time clock with
up to 20 programs to sequence the unit ventilator
through occupied and unoccupied modes in
accordance with a user programmed time schedule.
6 External Signal Connection Plugs: (L
ocated
Beneath the Local User Interface Panel). Three multipin plugs are factory provided and pre-wired with amp
plug connections that plug into the wall sleeve.
Provided for field wiring of :
ote Wall Mounted Temperature Sensor
• Rem
(optional accessory).
rnal Input Signals (by others): unoccupied,
• Exte
remote shutdown, ventilation lockout, dew point/
humidity (night time operation) or exhaust interlock
signals.
rnal Output Options (by others): lights on/off,
• Exte
fault indication signal, exhaust fan on/off or au xiliary
heat signal.
Note: Not all external signal options can be used
simultaneously and may not be available on all software
models. Refer to the “UVC Input and Output Tables” in
IM 747 for available options.
7 Motor Speed Transformer: (Located Beneath the
Local User Interface Panel). Multi-tap autotransformer provides multiple fan motor speed control
through the LUI.
8 Unit Main Power “On-Off” Switch (not shown):
Shipped
with the wall sleeve accessory, the “On-Off”
switch disconnects the main power to the unit for
servicing or when the unit is to be shut down for an
extended period of time.
9 Fuse(s) - Fa
n motor and controls have the hot line(s)
protected by factory installed cartridge type fuse(s).
10 Control Transformer - (L
ocated Beneath the Local
User Interface Panel). 75 VA 24-volt NEC Class 2
transformer for 24 volt power supply.
11 Outdoor Air/Return Air Damper Actuator -
Direct
coupled, floating point (tristate) actuator that spring
returns the outdoor air damper to the closed position
upon a loss of power.
12 Face and Bypass Damper Actuator - Direc
t
coupled, floating point (tristate) actuator that is nonspring returned (Model AZQ only , other unit s are valve
control).
13 Hydronic Coil Low Air T
emperature Limit (T6
freezestat) – Factory installed on all units with
hydronic (water) coils. The T6 freezestat cuts out at
38ºF (+/- 3ºF) and automatically resets at 45ºF (+/3ºF).
14 Indoor, Direct Expansion (DX) Coil Refrigerant
emperature Sensor – The sensor is installed on the
T
unit ventilator’s indoor refrigerant coil on the right
hand side of the coil “u-bend”. It is used to sense low
refrigerant temperatures on the indoor coil.
15 Outdoor, Direct Expansion (DX) Coil Refrigerant
emperature Sensor - The sensor is installed on the
T
unit ventilator’s outdoor refrigerant coil on the right
hand side of the coil “u-bend”. It is used to sense the
refrigerant temperature on the outdoor coil.
16 Room Temperature Sensor - Th
e unit mounted
sensor is located in the sampling chamber (front,
center section) where room air is continuously drawn
through for prompt response to temperature changes
in the room. A remote wall mounted temperature
sensor is available for remote room temperature
sensing. (optional).
17 Discharge Air Temperature Sensor – The
sensor is
located on the second fan from the right to sense
discharge air temperatures.
18 Outdoor Air Temperature Sensor –
The sensor is
located in the outdoor air section of the unit before the
outdoor air damper. With network applications, the
unit mounted sensor can be overridden by a remote
sensor through the network.
19 Outdoor Air Humidity Sensor (o
ptional, standard
with expanded and leading edge controls) - Unit
mounted humidity sensor for units using expanded
outdoor enthalpy economizer or Le ad ing Edge in doo r/
outdoor, true enthalpy comparison economizer. The
sensor is located in the outdoor air section of the unit
before the outdoor air damper. With network
applications, the unit mounted sensor can be
overridden by a remote sensor through the network.
AAF-HermanNelson Model AZ Unit Ventilators21
MicroTech II Controls
20 Room Humidity Sensor (optional, standard with
expanded controls) – Unit mounted humidity sensor
for units capable of passive or active dehumidification
(Reheat) or with units using Leading Edge indoor/
outdoor, true enthalpy comparison economizer. The
sensor is located in the sampling chamber (front,
center panel) where room air is continuously drawn
through for fast response to humidity changes in the
room. With network applications, the unit mounted
sensor can be overridden by a remote sensor thro ugh
the network.
(
21 CO2 Sensor
optional) – Unit mounted, single beam
absorption infrared gas sensor with a sensing range
of 0 – 2000 ppm and voltage output of 0 to 10 VDC
(100 ohm output impedance). The pitot tube sensing
device is located in the unit ventilator's return air
stream. The optional CO2 sensor is used with the
UVC's Demand Control Ventilation feature to vary the
amount of outside air based on actual room
occupancy. With network applications, the unit
mounted sensor can be overridden by a re mote
sensor through the network.
ot
22 Control Valve(s) (n
shown) – Optional accessory
valve(s) may be either 2-position "End of Cycle"
(model AZQ) or modulating (model AZU and AZR), to
control the quantity of water through the coil. Available
in 2-way or 3-way configurations. Spring return
actuators are required for all hot water and steam
heating valves. All heating valves are normally open.
Outdoor Air/Return Air Damper (OAD) Actuator
The UVC is configured to operate a floating-point (tristate) direct-coupled actuator for the outdoor air damper.
This actuator provides spring-return operation upon loss
of power for positive close-off of the outdoor air damper.
To determine damper position, the UVC uses a separate,
factory-preset, configurable setting for each actuator's
stroke time.
On units equipped with 2-way or 3-way, end-of-cycle
(EOC) valves, the UVC is configured to operate 2position End-Of-Cycle (EOC) valve actuators
(Figure 25). Spring return actuator s are used fo r all End
of Cycle (EOC) valves. All wet heat EOC valves are
o
rmally open.
n
Figure 25. End of Cycle Valve Actuator
Actuators
Face & Bypass Damper Actuator
On units equipped with face & bypass damper control,
the UVC is configured to operate a floating-point (tristate), direct-coupled, face & bypass damper actuato r . To
determine the modulating damper position, the controller
uses a separate, factory-preset, configurable setting for
each actuator's stroke time.
Figure 23. Face & Bypass Damper Actuator
22McQuay Catalog 1620
MicroTech II Controls
Modulating Valve Actuators (Optional)
On units equipped with modulating valves, the UVC is
configured to operate floating-point (tri-state) actuators
for modulating 2- way and 3-way valves (Figure 26).
Figure 26. Modulating Valve Actuator
2-Way Valve3-Way Valve
s
Spring return actuators are used for all modulating
valves. All wet heat valves are normally open.
To determine modulating valve position
the UVC uses a
separate factory preset, configurable setting for each
actuator's stroke time. For accuracy of actuator
positioning, the UVC is provided with an overdrive
feature for the 0% and 100% positions and a periodic
(12-hour) auto-zero PI control loop for each modulating
actuator.
Optional Time Clock For Stand-Alone Units
As an option, stand-alone, non-servant un it ventilators
can be factory-equipped with a unit-mount ed, di g ital, 24hour/7-day time clock with 20 programs (Figure 27). The
clock is factory-wired to automatically
o
ccupied or unoccupied mode based upon its schedule.
Features of this clock include:
• Large keys with circular programming for easy
hedule setup
sc
• An LCD disp
lay
• Manual 3-way override (On/Auto/Off)
• Capacitor backup to retain pr ogram memory during
po
wer outages.
place the unit into
Figure 27. Optional Time Clock
ServiceTools™
ServiceTools for MicroT ech II Unit Ventilators is a CD
containing software for operation on a personal
computer. This software provides a visual schematic of
the unit, a pictorial representation of the sequence of
operation and enables the service technician to:
onitor equipment operation.
• M
• Configure network communications.
• Diagnose unit operating problems.
• Download application code and configure the unit.
Th
is software is a purchased tool for service technicians
and will run
on PCs with Windows
2000 (SP2), and NT4.0 (SP6) and XP (SP1) operating
systems. This tool is highly recommended for startup and
servicing. (It may be required for startup and/or servicing,
depending upon unit integration and other requirement s.)
It has no BAS functions, such as scheduling or trending,
and it cannot serve as a Work Station Monitoring
package.
ServiceTools comes with a service cable having two
rface conn
inte
ections:
• A 12-pin connection to the main control board.
• A 3-pin connection to the optional communication
ules.
mod
®
98 (Second Edition),
AAF-HermanNelson Model AZ Unit Ventilators23
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.