McQuay AGZ 030CB Installation Manual

Operation Manual
Air-Cooled Scroll Compressor Chiller
AGZ 030CH through 190CH, Packaged
AGZ 030CB through 190CB, Remote Evaporator
60 Hertz, R-410A
Software Version AGZDU0102G
OM AGZC-1
Group: Chiller
Part Number: 331376301
Effective: February 2010
Supercedes: April 2009
Table of Contents
Introduction........................................3
General Description..................................... 3
Nomenclature .............................................. 3
Ambient Air Temperature Limitations......... 4
Water Flow Limitations ............................... 4
System Water Volume Considerations ......... 5
Glycol Solutions .......................................... 5
Operating/Standby Limits............................ 9
Pressure Drop Curves........................9
oTech II Controller ..................13
Micr
Controller Section Table of Contents ........ 13
Overview ................................................... 14
General Description................................... 14
Setpoints .................................................... 16
Dynamic Defaults...................................... 18
Security...................................................... 19
Control Functions...................................... 19
Unit Enable................................................ 20
Unit Mode Selection.................................. 21
Unit State................................................... 22
Power Up Start Delay................................ 23
Ice Mode Start Delay................................. 23
Low Ambient Lockout............................... 23
Evaporator Water Pump State.................... 23
Leaving Water Temperature (LWT) Reset. 24
Maximum LWT Rate................................. 24
Unit Capacity Overrides ............................ 24
Circuit Capacity Overrides – Limits of Operation
................................................................... 25
Low Ambient Starts ................................... 26
Compressor Sequencing ............................ 26
Manual Compressor Control ..................... 27
Normal Circuit Shutdown.......................... 28
Rapid Circuit Shutdown ............................ 28
Cycle Timers.............................................. 28
Liquid Line Solenoid................................. 28
Hot Gas Bypass Solenoid .......................... 28
EXV Control.............................................. 28
Condenser Fan Control.............................. 29
Alarms and Events.......................... 31
Unit Stop Alarms........................................31
Circuit Stop Alarms....................................31
Circuit Events.............................................33
Clearing Alarms .........................................34
4x20 Display & Keypad.................. 35
Layout ........................................................35
Keys ...........................................................37
Navigation..................................................37
Editing........................................................39
Screen Definitions – MENU......................39
Screen Definitions – VIEW .......................40
Screen Definitions – ALARM/EVENT .....44
Screen Definitions – SET...........................44
Screen Definitions – TEST ........................51
Building Automation System Interface
........................................................... 52
Protocols Supported...................................52
Available Parameters..................................52
Parameter Details....................................... 53
Optional Low Ambient VFD.......... 55
Startup.............................................. 66
Operation......................................... 68
Hot Gas Bypass (Optional) ........................68
VFD Low Ambient Control (Optional)......69
Filter-Driers................................................69
System Adjustment ....................................69
Liquid Line Sight Glass .............................69
Refrigerant Charging .................................69
Thermostatic Expansion Valve...................69
Crankcase Heaters......................................70
Evaporator..................................................70
Phase Voltage Monitor (Optional) .............70
*
©2007 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; L
ONMARK International under a license granted by Echelon Corporation; Compliant Scroll from Copeland Corporation; ElectroFin from AST
ElectroFin Inc.; Modbus from Schneider Electric; FanTrol, MicroTech II, Open Choices, and SpeedTrol from McQuay International. *Unit Controllers are L
2 AGZ 030C through 190C OM AGZC-1
ONMARK certified with an optional LONWORKS communication module.
Our facility is ISO Certified
LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by

Introduction

General Description

McQuay Air-Cooled Global Water Chillers are complete, self-contained automatic refrigerating units. Every unit is completely assembled, factory wired, charged, and tested (except remote evaporator option). Each unit consists of twin air-cooled condensers with integral subcooler sections, two tandem or triple scroll compressors, brazed-plate or replaceable tube, dual circuit shell-and-tube evaporator, and complete refrigerant piping. Liquid line components include manual liquid line shutoff valves, sight-glass/moisture indicators, solenoid valves, and thermal expansion valves. Other features include compressor crankcase heaters, an evaporator heater for chilled water freeze protection,
BOOT Version 3.0F
limited pumpdown during “on” or “off” periods, automatic compressor lead-lag to alternate the compressor starting sequence, and sequenced starting of compressors.
The electrical control center includes all equipment protection and operating controls necessary for dependable automatic operation. Condenser fan motors are protected in all three phases and started by their own three-pole contactors.
This manual covers units with Software Version AGZDU0102G. Installation, maintenance and service information is in IMM AGZC (or current, latest dash number) manual.
BIOS Version 3.62
Scroll Compressor
Air-Cooled
Global

Nomenclature

A G Z - XXX C H
Application H= Packaged Chiller B= Chiller with Remote Evap.
Design Vintage
Model Size (Nominal Tons)
OM AGZC-1 AGZ 030C through 190C 3

Ambient Air Temperature Limitations

Standard/High Ambient Panels

The AGZ-C units for high ambient operation (105F to 125F maximum) require the addition of the High Ambient Control Panel Option, which includes the addition of a small fan with a filter in the air intake to cool the control panel.
Table 1, Panel Ratings
All units with the optional VFD low ambient fan control automatically include the High Ambient Control Panel Option. Operation of the VFD generates a quantity of panel heat best removed by use of a control panel fan.
Voltage
208-230
240
380-460
575
Standard
Standard Options
Optional
Panel
35 5 120 120 35 5 100 100 35 5 65 65
5 5 25 25
VFD

Water Flow Limitations

The evaporator flow rates and pressure drops shown on page 9 (and following) are for full load design purposes in order to m proper unit control. The maximum flow rate and pressure drop are based on a 6 degree temperature drop. Avoid higher flow rates with resulting lower temperature drops to prevent potential control problems resulting from very small control bands and limited start up/shut off temperature changes.

Variable Speed Pumping

Variable water flow involves changing the water flow through the evaporator as the load changes. McQuay chillers are designed for this duty provided that the rate of change in water flow is slow and the minimum and maximum flow rates for the vessel are not exceeded.
The recommended maximum change in water flow is 10 percent of the change per minute.
aintain
High Short Circuit
Panel (kA)
The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16 degrees. Evaporator flow rates below the minimum values can result in laminar flow causing freeze-up problems, scaling and poor control. Flow rates above the maximum values will result in unacceptable pressure drops and can cause excessive erosion, potentially leading to failure.
When units are operated with flow rates less than nominal (see Table 8), the “Evap Delta T” setpoint m match the minimum operating flow rate. The “Delta T” setting should be increased by the same percentage as the flow reduction is from the nominal rating in order to prevent short cycling. This will require reevaluation of “Cool LWT”, “Startup Delta T”, and “Stop Delta T” settings as well.
ust be changed proportionally to
High Interrupt Panel w/
Disconnect Swt. (kA)
4 AGZ 030C through 190C OM AGZC-1
System Water Volume
T
Considerations
All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes.
Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow rate” is often used.
A properly designed storage tank should be added if the system components do not provide sufficient water volume.

Glycol Solutions

The use of a glycol/water mixture in the evaporator to prevent freezing will reduce system capacity and efficiency, as well as increase pressure drop. The system capacity, required glycol solution flow rate, and pressure drop with glycol may be calculated using the following formulas and tables.
1. Capacity – Multiply the capacity based on
water by the Capacity correction factor from Table 2 through Table 5.
2. Flow – Multiply
by the Flow correction factor from Table 2 through Table 5 to determine the increased evaporator flow due to gly
If the flow is unknown, it can be calculated from the following equation:
the water evaporator flow
col.
glycolCapacityTons
)(×24
=(gpm) Flow Glycol
TDelta
×
FactorCorrectionFlow
For Metric Applications
– Use the following equation:
(l/s) Flow Glycol
3. Pressure drop -- Multiply the water
pressure drop from page 10 by Pr
essure
Drop correction factor from Table 2
through Table 5. High concentrations of
lene glycol at low temperatures can
propy cause unacceptably high pressure drops.
4. Power -- Multiply the water system power
by Power correction factor from Table 2 ­Table 5.
est coolant with a clean, accurate glycol
T
CapacitykW
Delta
18.4
service stations) to determine the freezing point. Obtain percent glycol from the freezing point tables below. It is recommended that a minimum of 25% solution by weight be used for protection against corrosion or that additional compatible inhibitors be added.
Concentrations above 35 % do not provide any additional burst protection and should be carefully considered before using.
FactorCorrectionFlow
solution hydrometer (similar to that found in
!
WARNING
Do not use an automotive grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze
contains inhibitors which will cause plating on the copper tubes within the chiller evaporator. The type
and handling of glycol used must be consistent with local codes
OM AGZC-1 AGZ 030C through 190C 5
Loading...
+ 9 hidden pages