ONMARK International under a license granted by Echelon Corporation; Compliant Scroll
LONMARK, LonTalk, LONWORKS, and the LONMARK
Introduction
General Description
McQuay air-cooled water chillers are complete, self-contained automatic refrigerating units. Every
unit is completely assembled, factory wired, charged, and tested. Each unit consists of air-cooled
condensers, Copeland Compliant Scroll hermetic compressor, brazed plate-to-plate evaporator,
and complete refrigerant piping. Liquid line components include sight-glass/moisture indicator,
solenoid valve, and thermal expansion valve. Other features include a compressor heater, and
evaporator heater for chilled water freeze protection.
The electrical control center includes all equipment protection and operating controls necessary for
automatic operation. Condenser fan motors are three-phase (except single-phase on No. 1 fan with
SpeedTrol option) and started by their own contactors and have inherent overload protection. Each
compressor has solid-state motor protection for inherent thermal overload protection except Model
AGZ 010 that has internal line breakage.
Software Version
This manual is based on software version AGZSU0102D. The software version can be displayed by
pressing the Enter and Menu keys simultaneously. Exit by pressing Menu.
Inspection
Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report
shipping damage and file a claim with the carrier. Check the unit nameplate before unloading to be
sure it agrees with the power supply available. Units are shipped FOB factory and McQuay is not
responsible for physical damage after unit leaves the factory.
Note: Unit shipping and operating weights are listed on pages
Installation
Note: Installation must be performed by trained, experienced personnel who are familiar
with local codes and regulations, especially concerning refrigerant release to the
atmosphere.
Sharp edges and coil surfaces can cause personal injury. Avoid contact with them.
Handling
Be careful to avoid rough handling of the unit. Do not push or pull the unit from anything other than
the base. Block the pushing vehicle away from the unit to prevent damage to the sheet-metal cabinet
and end frame (see
Arrange spreader bars and cables to prevent damage to condenser coils or cabinet (see
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal
16 and 17.
!
WARNING
Figure 1). To lift the unit, lifting slots are provided in the base of the unit.
Figure 2).
HAZARD IDENTIFICATION INFORMATION
!
WARNING
injury, or death if not avoided.
!
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment
damage if not avoided.
IOMM AGZB1 AGZ 010B through 034B 3
Figure 1, Suggested Pushing Arrangement
BLOCKING REQUIRED
ACROSS FULL WIDTH
Figure 2, Suggested Lifting Arrangement
SPREADER BAR (2)
NOTE:: The fork lift slots can be used for
lifting by inserting sufficiently strong pipe
through them as shown in Figure 2.
Use the outboard slots on three-fan units
and the only two on two-fan units.
Location
Unit Placement
AGZ units are for outdoor applications and can be mounted on a roof or at ground level. Set units on
a solid and level foundation. For roof-mounted applications, install the unit on a steel channel or Ibeam frame to support the unit above the roof. For ground level applications, install the unit on a
substantial base that will not settle. A one-piece concrete slab with footings extended below the frost
line is recommended. Be sure the foundation is level (within 1/2” [13 mm] over its length and width).
The foundation must support the operating weights listed in the Physical Data Tables on pages
17. It is recommended that the unit be raised a few inches with a suitable support, located at least
under the mounting locations, to allow water to drain from under the unit and to facilitate cleaning
under it.
Since its operation is affected by wind, the unit should be located so that its length is parallel with the
prevailing wind. If this is not practical, use field fabricated wind deflectors.
Service Access
Each end of the unit must be accessible after installation for periodic service. Compressors, filterdriers, and liquid line solenoid valve are accessible from the end of the unit. High-pressure, lowpressure, and motor protector controls are on the compressor. Most operating, equipment protection,
and starting controls are located in the unit control box.
The fan deck with the condenser fans and motors can be removed from the top of the unit.
PIPE SLUNG THRU
OPENINGS IN LEGS (2)
16 and
4 AGZ 010B through 034B IOMM AGZB1
Clearances
The flow of air to and from the
condenser coil must not be limited.
Restricting airflow or allowing air
recirculation will result in a decrease in
unit performance and efficiency. There
must be no obstruction above the unit
that would deflect discharge air
downward where it could be
recirculated back to the inlet of the
condenser coil. The condenser fans are
propeller type and will not operate with
ductwork on the fan outlet.
Install the unit with enough side
clearance for air entrance to the coil and
for servicing. Provide service access to
the evaporator, compressors, electrical
control panel and piping components as
shown in Figure 3. Do not block access to
the unit with piping or conduit.
Do not allow debris to accumulate near the
unit. Air movement may draw debris into
the condenser coil causing air starvation.
Give special consideration to low ambient
operation where snow can accumulate.
Keep condenser coils and fan discharge free
of snow or other obstructions to permit
adequate airflow.
Sound Isolation
The low sound levels of the AGZ chiller are
suitable for most applications. When
additional sound reduction is necessary,
locate the unit away from sound sensitive
areas. Avoid locations beneath windows or
between structures where normal operating
sounds may be objectionable. Reduce
structurally transmitted sound by isolating
water lines, electrical conduit and the unit
itself. Use wall sleeves and rubber isolated
piping hangers to reduce transmission of
water or pump noise into occupied spaces.
Use flexible electrical conduit to isolate
sound through electrical conduit. Spring
isolators are effective in reducing the low
amplitude sound generated by the Discus
semi-hermetic compressors and for unit
isolation in sound-sensitive areas.
Figure 3, Clearance requirements
4 Ft. (1220mm)
Clearance for Air Inlet
4 Ft.
(1220mm)
Clearance for
Service Access
4 Ft. (1220mm)
Clearance for Air Inlet
The recommended minimum side clearance between two units
is 8 feet (2440mm).
The unit must not be installed in a pit or enclosure that is
deeper or taller than the height of the unit unless extra space
is provided. The minimum clearance on each side of the
unit is 6 feet (1828mm) when installed in a pit. The pit cannot
be deeper than the unit.
The minimum clearance to a side wall or building taller than
the unit height is 6 feet (1828mm) provided no solid wall
above 6 feet (1828mm) tall is closer than 12 feet (3658mm)
to the opposite side of the unit.
4 Ft.
(1220mm)
Clearance for
Service Access
Vibration Isolators
Vibration isolators are recommended
for all roof-mounted installations or wherever vibration transmission is a consideration.
IOMM AGZB1 AGZ 010B through 034B 5
The unit should be initially placed on shims or blocks at the listed free height. When all
piping, wiring, flushing, charging, etc. is completed, the springs are adjusted upward to loosen
the blocks or shims that are then removed.
A rubber anti-skid pad is part of the isolator. Installation of spring isolators requires flexible
piping connections and at least three feet of flexible conduit to avoid straining the piping and
transmitting vibration and noise. These units cannot be bolted to isolators.
Table 1, Recommended Vibration Isolators
Neoprene-in-Shear
AGZ Model RF LF RB LB
010, 013, 017
020, 025, 029, 034
RP-3 Red RP-3 Red RP-3 Red RP-3 Red 350014858
RP-3 Green RP-3 Green RP-3 Red RP-3 Red 350014857
Spring
AGZ Model RF LF RB LB
010
013, 017
020, 025
029
034
Note: See dimension drawing for location of isolators
CP 1-24 Brown CP 1-24 Brown CP 1-24 Brown CP 1-24 Brown 350014832
CP 1-25 Red CP 1-25 Red CP 1-25 Red CP 1-25 Red 350014834
CP1-26 Purple CP1-27 Orange CP 1-24 Brown CP 1-24 Brown 350014836
CP1-27 Orange CP1-27 Orange CP 1-25 Red CP 1-25 Red 350014838
CP1-27 Orange CP1-28 Green CP 1-25 Red CP 1-25 Red 350014840
CP-1, Spring Isolator RP-3 Neoprene-in-Shear Isolator
6 AGZ 010B through 034B IOMM AGZB1
Chilled Water System
Water Piping
Local authorities can supply the installer with the proper building and safety codes required
for proper installation.
Install piping with minimum bends and changes in elevation to minimize pressure drop.
Consider the following when installing water piping:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Install drains at
the lowest points in the system.
4. Maintaining adequate system water pressure (expansion tank or regulating valve).
5. Temperature and pressure indicators located at the unit to aid in unit servicing. Pressure
gauge taps must be installed in the chilled water inlet and outlet piping or as shown in
Figure 4.
6. A strainer or other means of removing foreign matter from the water before it enters the
pump. Place the strainer far enough upstream to prevent cavitation at the pump inlet
(consult pump manufacturer for recommendations). The use of a strainer can prolong
pump life and keep system performance up.
7. A 40-mesh strainer is requi red in the water line just before the inlet of the evaporator.
This will help prevent foreign material from entering and decreasing the performance of
the evaporator.
!
CAUTION
If a separate disconnect is used for the 110V supply to the evaporator heating cable,
mark the disconnect clearly so the disconnect is not accidentally shut off during cold
seasons. Failure to do so can cause a failure of the evaporator.
8. The brazed plate evaporator has a thermostat and heating cable to prevent freeze-up
down to -20F (-29C). The heating cable should be wired to a separate 110V supply
circuit. As shipped from the factory, the heating cable is wired to the control circuit.
Protect all water piping to the unit from freezing.
9. If the unit is used as a replacement chiller on a previously existing piping system, flush
the system thoroughly before unit installation. Perform regular water analysis and
chemical water treatment on the evaporator immediately at equipment start-up.
10. When glycol is added to the water system for freeze protection, the refrigerant suction
pressure will be lower, cooling performance less, and water side pressure drop greater.
If the percentage of glycol is high, or if propylene is used instead of ethylene glycol, the
added pressure drop and loss of performance could be substantial. Reset the freezestat
and low leaving water alarm temperatures. The freezestat is factory set to default at
38F (3.3C). Reset the freezestat setting to approximately 4 to 5 degrees F (2.3 to 2.8
degrees C) below the leaving chilled water setpoint temperature. See the section titled
“Glycol Solutions” on page
10 for additional information concerning glycol.
11. Perform a preliminary leak check before insulating the piping and filling the system.
12. Include a vapor barrier on the piping insulation to prevent condensation and possible
damage to the building structure.
IOMM AGZB1 AGZ 010B through 034B 7
Figure 4, Typical Field Evaporator Water Piping
Ai
r
Vent
Strainer
Inlet
P
Outlet
Drain
NOTES:
1. Chilled water piping within the unit enclosure must be insulated in the field.
2. Support piping independently of the unit and install per local codes.
Vibration
Eliminators
Flow
Switch
Isolation
Valves
System Volume
It is important to have adequate water volume in the system to provide an opportunity for
the chiller to sense a load change, adjust to the change and stabilize. As the expected load
change becomes more rapid, a greater water volume is needed. The system water volume is
the total amount of water in the evaporator, air handling products and associated piping. If
the water volume is too low, operational problems can occur, including rapid compressor
cycling, rapid loading and unloading of compressors, erratic refrigerant flow in the chiller,
improper motor cooling, shortened equipment life and other undesirable occurrences.
For normal comfort cooling applications, where the cooling load changes relatively slowly,
we recommend a minimum system volume of three to four times the flow rate (GPM). For
example, if the design chiller flow rate is 120 GPM, we recommend a minimum system
volume of 360 to 480 gallons.
Since there are many other factors that can influence performance, systems may
successfully operate below these suggestions. However, as the water volume decreases
below these suggestions, the possibility of problems increases.
Variable Chilled Water flow
Variable chilled water flow systems are not recommended for this class of equipment due to
limited unloading capability.
Flow Switch
Mount a water flow switch in the leaving water line to shut down the unit when water flow
is interrupted.
A flow switch is available from McQuay
(part number 017503300). It is a “paddle”
type switch and adaptable to pipe sizes
down to 1 1/4” (32mm) nominal. Certain
minimum flow rates are required to close
the switch and are listed in
Table 2. Install
the switch as shown in Figure 5. Connect
the normally open contacts of the flow
switch in the unit control center at
terminals 4 and 5. There is also a set of
normally closed contacts on the switch that
can be used for an indicator light or an
alarm to indicate when a “no-flow”
condition exists. Freeze protect any flow
switch that is installed outdoors. Follow
Figure 5, Flow Switch Installation
8 AGZ 010B through 034B IOMM AGZB1
installation instructions provided with the flow switch. Calibrate the flow switch to open at
one-half of nominal flow rate.
NOTE: Differential pressure switches are not recommended for outdoor
installation. They are subject to damage from freezing.
1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose.
2. Flow rates for a 2-inch paddle trimmed to fit the pipe.
3. Flow rates for a 3-inch paddle trimmed to fit the pipe.
4. Flow rates for a 3-inch paddle.
5. Flow rates for a 6-inch paddle.
Water Connections
The unit has 3-inch holes for the chilled water piping to enter the unit. The connections are
made to the evaporator water connections located within the unit. Chilled water piping
within the unit must be insulated.
All units are designed for R-22 or R-407C and are shipped with an operating charge. The
operating charge for each unit is shown in the Physical Data Tables on pages
Unit Component Location
Chilled Water
Inlet Connection
Chilled Water
Outlet Connection
Evaporator
16 and 17.
Control Panel
Tandem Scroll
Compressors
Charging Valve
Solenoid Valve, Expansion Val ve
Optional Hot Gas Bypass Valve Filter Drier
IOMM AGZB1 AGZ 010B through 034B 9
Glycol Solutions
The use of glycol antifreeze solutions will decrease unit capacity and increase the pressure
drop through the cooler. See Product Manual Catalog ACZAGZB1 for specific ratings and
correction factors.
!
CAUTION
Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive
antifreeze contains inhibitors that will cause plating on the copper tubes within the chiller
evaporator. The type, storage, disposal, and handling of glycol used must be consistent
with local codes.
Evaporator Water Flow and Pressure Drop
Evaporator flow rate must fall between the minimum and maximum values shown in the
evaporator pressure drop curve,
chilled water Delta-T outside the operating range of the controller.
Measure the chilled water pressure drop through the evaporator at field-installed pressure
taps. It is important not to include the effect of valves or strainers in these readings.
Do not vary the chilled water flow through the evaporator while the compressors are
operating.
Figure 6. Flow rates outside of these limits result in a
AGZ chillers are available with R-407C refrigerant as non-ARI certified units. R-407C is a
zeotropic blend of three compounds, and as such exhibits the characteristic of glide. It does not
behave as one substance like R-22 does. Glide is the difference (in degrees F) between the
beginning and end phase-change process in either the evaporator or condenser. During these
processes, different ratios of the refrigerant’s components change phase from the beginning to the
end of the process. The following functions, conditions and settings will differ from units charged
with R-22.
1. Different physical data and electrical data
2. Polyolester lubricants are used instead of mineral oil.
3. The saturated pressure/temperature relationship
4. Control and alarm settings
5. Charging procedures
1.Lubrication. The units are factory-charged with polyoester (POE) lubricant and one of the
following lubricants must be used if lubricant is to be added to the system:
POEs are very hygroscopic and will quickly absorb moisture if exposed to air. Pump the
lubricant into the unit through a closed transfer system. Avoid overcharging the unit.
Copeland Ultra 22 CC
Mobil EAL Arctic 22 CC
ICI EMKARATE RL RL 32CF
2.Pressure/temperature relationship. See
temperature chart. Due to refrigerant glide, use the following procedures for superheat and
subcooling measurement.
To determine superheat, only vapor must be present at the point of measurement, no liquid.
Use the temperature reading, the pressure reading and the Saturated P/T Chart. If the
pressure is measured at 78 psig, the chart shows the saturated vapor
50.6F. If the temperature is measured at 60F, the superheat is 9.4 degrees F.
To determine subcooling, only liquid must be present, no vapor. Use the temperature
reading, the pressure reading and the Saturated P/T Chart. If the pressure is measured at 250
psig, the chart shows the saturated liquid
measured at 98F, the subcooling is 10.2 degrees F.
The P/T relationship between R-407C and R-22 is similar enough to allow the use of R-22
expansion valves. The valves may be marked as “R-22’ or “R-22/R-407C”.
3.Control and alarm settings. The software that controls the operation of the unit is factory-
set for operation with R-407C, taking into account that the pressure/temperature relationship
differs from R-22. The software functionality is the same for either refrigerant.
4.Charging procedure. The units are factory-charged with R-407C. Use the following
procedure if recharging in the field is necessary:
Whether topping off a charge or replacing the circuit’s entire charge, always remove the
refrigerant from the charging vessel as a liquid. Many of the cylinders for the newer
refrigerants have a dip tube so that liquid is drawn off when the cylinder is in the upright
position. Do not vapor charge out of a cylinder unless the entire contents will be charged into
the system.
Table 3 on page 13 for the saturated pressure-
temperature to be
temperature to be 108.2F. If the temperature is
With the system in a 250-micron or lower vacuum, liquid can be charged into the high side.
Initially charge about 80 percent of the system total charge.
12 AGZ 010B through 034B IOMM AGZB1
Start the system and observe operation. Use standard charging procedures (liquid only) to
top off the charge.
It may be necessary to add refrigerant through the compressor suction. Because the
refrigerant leaving the cylinder must be a liquid, exercise care to avoid damage to the
compressor. A sight glass can be connected between the charging hose and the compressor.
It can be adjusted to have liquid leave the cylinder and vapor enter the compressor.
All electrical controls are enclosed in a weatherproof control center with tool-locked, hinged
access doors. The left-hand section contains the microprocessor controller and control input and
output terminals. All high-voltage components are located on the right side of the panel.
ON/OFF Switch
MicroTech II
Controller
SpeedTrol Location
Field Connection
Terminals
Start-up and Shutdown
Pre Start-up
1. The chilled-water system should be flushed and cleaned. Proper water treatment is required to
prevent corrosion and organic growth.
2. Open all electric disconnects and check all electric connections for tightness.
3. Inspect all water piping for flow direction and correct connections at the evaporator.
4. Verify thermostat water temperature sensor is installed in the leaving water line (supply to
building). On all AGZ units the sensor well and sensor are factory mounted.
5. Check compressor oil level. The oil level should be visible in the oil sight glass.
6. Check voltage of the unit power supply and make certain voltage is within 10% of nameplate
rating. Check unit power supply wiring for proper ampacity and a minimum insulation
temperature of 75C. Check for proper phasing using a phase sequence meter.
7. Verify all mechanical and electrical inspections have been completed according to local codes.
8. Open control stop switch S1(off). Turn on the main power and control disconnect switches.
This will energize crankcase heaters. Wait at least 24 hours before starting up unit.
9. Open all water flow valves and start the chilled water pump. Check all piping for leaks and
vent the air from the evaporator as well as from the system piping. Flush the evaporator and
system piping to obtain clean, noncorrosive water in the evaporator.
Control
Transformer
24-Volt Trans.
Non-Fused Disc.
or
Power Block
Fan
Contactors
Fan
Protection
Compressor Contactors
Start-up
1. Set temperature controller to the desired chilled water temperature. Set the chilled water
Delta-T.
2. Start auxiliary equipment by turning on the following: time clock (if present), ambient
thermostat and/or remote on/off switch, chilled water pump.
3. If the controller calls for cooling, the unit will begin the start-up sequence.
14 AGZ 010B through 034B IOMM AGZB1
4. After running the unit for a short time, check the oil level in the compressor (1/4 to 1/3
of the glass), rotation of fans, and flashing in refrigerant sight glass.
5. Verify superheat temperature is at the factory setting of 8 to 12 degrees F (4.4 to 6.7
degrees C).
6. After system performance has stabilized, complete the current AGZ Start-Up Form
(obtainable from the local McQuay sales office) to establish inception of warranty
benefits. Return the form to McQuay International through your sales representative.
Sequence of Operation
Start-Up
With the control circuit power on, 115V power is applied through the control circuit fuse F1
to the compressor crankcase heaters, the compressor motor protections and the primary of
the 24V control circuit transformer. The 24V transformer provides power to the
microprocessor controller.
When a remote time clock, manual switch, or the unit controller turns on the chilled water
pump, the flow switch closes and satisfies the flow requirement. If the chilled water
temperature is above the stage-on temperature, and all equipment protection devices are
closed, the unit will start. The controller will operate the unit in response to the leaving
chiller water temperature or reset signals that may be present.
Equipment Protection Alarms
The following conditions will shut down the unit and activate the alarm circuit:
No evaporator water flow Low evaporator pressure
High condenser pressure Motor protection system
Phase voltage protection (Optional) Outside ambient temperature
Evaporator freeze protection Sensor failures
The following alarms will limit unit operation:
Condenser pressure stage down, unloads unit at high discharge pressures
Low ambient lockout, shuts off unit at low ambient temperatures
Low evaporator pressure hold, holds stage #1 until pressure rises
Low evaporator pressure unload, shuts off stage #2
Unit Enable Selection
Enables unit operation from local keypad, digital input, or Building Automation System.
Unit Mode Selection
Selects standard cooling, ice, glycol, or test operation mode.
Condenser fan control
Control of condenser fans is provided by the MicroTech II controller. The control steps
condenser fans based on discharge pressure.
Shutdown
As the leaving water control is satisfied, it will stage off the lag compressor unloading the
unit. The second stage will de-energize the liquid line solenoid valve SV1 and shut off the
lead compressor. The compressor crankcase heaters will energize when the compressors
shut off, keeping the small amount of refrigerant in the plate heat exchanger from migrating
to the compressor. See page
IOMM AGZB1 AGZ 010B through 034B 15
56 for detailed explanation of compressor staging.
Physical Data
AGZ-BS, R-22/R-407C
Table 4, Physical Data, AGZ 010BS through 017BS, Packaged, R-22/R-407C
PHYSICAL DATA
BASIC DATA
Unit Capacity @ ARI Conditions (1), Tons (kW) 10.0 (36.2) 13.7 (48.2) 15.8 (55.6)
Number Of Refrigerant Circuits 1 1 1
Unit Operating Charge, R-22 and [R-407C], Lb. (kg) 22.0 (10.0) 24.0 (10.9) 31.0 (14.1)
Cabinet Dimensions, LxWxH, In. 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8
Cabinet Dimensions, LxWxH, (mm) (1869) x (1176) x (1289) (1869) x (1176) x (1289) (1869) x (1176) x (1289)
Unit Operating Weight, Lb. (kg) 1095 (498) 1190 (541) 1300 (591)
Unit Shipping Weight, Lb. (kg) 1085 (493) 1170 (532) 1280 (582)
Add'l Weight If Copper Finned Coils, Lb. (kg)
R-22 and [R-407C]
COMPRESSORS
Type Scroll Scroll Scroll
Nominal Horsepower 6.0 / 6.0 7.5 / 7.5 9.0 / 9.0
Oil Charge Per Compressor of a Tandem Set, oz. (g) 60 (1701) 85 (2410) 110 (3119)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DSPLACEMENT
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 30.3 (2.8) 30.3 (2.8) 30.3 (2.8)
Finned Height x Finned Length, In. 84 x 52 84 x 52 84 x 52
Finned Height x Finned Length, (mm) (2134) x (1321) (2134) x (1321) (2134) x (1321)
Fins Per Inch x Rows Deep: R-22 and [R-407C] 16 x 2 [16 x 2] 16 x 2 [16 x 2] 16 x 3 [16 x 3]
Pumpdown Capacity Lb. (kg) 35.3 (16.0) 35.3 (16.0) 52.9 (24.0)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 2 – 26 (660) 2 – 26 (660) 2 – 26 (660)
Number Of Motors - HP (kW) 2 – 1.0 (0.75) 2 – 1.0 (0.75) 2 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 13950 (6584) 13950 (6584) 12000 (5664)
DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Connection Size Victaulic, In. (mm) 2 (51) 2 (51) 2 (51)
Water Volume, Gallons (L) 0.9 (3.6) 1.7 (6.3) 2.0 (7.6)
Maximum Refrigerant Working Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103)
Maximum Water Pressure, psig (kPa) 350 (2413) 350 (2413) 350 (2413)
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range.
010B 013B 017B
176 (80.0)
[176 (80.0)]
AGZ MODEL NUMBER
176 (80.0)
[176 (80.0)]
264 (120.0)
[264 (120.0)]
16AGZ 010B through 034B IOMM AGZB1
Table 5, Physical Data, AGZ 020BS through 034BS, Packaged, R-22/R-407c
PHYSICAL DATA
BASIC DATA
Unit Capacity @ ARI Conditions (1), Tons (kW) 20.6 (72.4) 22.7 (79.8) 27.7 (97.5) 34.0 (119.5)
Number Of Refrigerant Circuits 1 1 1 1
Unit Operating Charge, R-22 and [R-407C],
Lb. (kg)
Cabinet Dimensions, LxWxH, In. 106.2x 46.3 x 50.8 106.2x 46.3 x 50.8 106.2x 46.3 x 58.8 106.2x 46.3 x 58.8
Cabinet Dimensions, LxWxH, (mm)
Unit Operating Weight, Lbs. (kg) 1590 (723) 1635 (743) 1830 (832) 2315 (1052)
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 49.0 (4.6) 49.0 (4.6) 58.3 (5.4) 58.3 (5.4)
Finned Height x Finned Length, In. 84 x 84 84 x 84 100 x 84 100 x 84
Finned Height x Finned Length, (mm) (2134) x (2134) (2134) x (2134) (2545 ) x (2134) (2545 ) x (2134)
Fins Per Inch x Rows Deep: R22 and [R407C]
Pumpdown Capacity, R-22 and [R-407C]
Lb. (kg)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 3 – 26 (660) 3 – 26 (660) 3 – 26 (660) 3 – 26 (660)
Number Of Motors - HP (kW) 3 – 1.0 (0.75) 3 – 1.0 (0.75) 3 – 1.0 (0.75) 3 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 20925 (9877) 20925 (9877) 19800 (9346) 19800 (9346)
DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Unit Capacity @ ARI Conditions (1), Tons (kW) 10.0 (36.2) 13.7 (48.2) 15.8 (55.6)
Number Of Refrigerant Circuits 1 1 1
Unit Operating Charge, R-22 and [R-407C], Lb. (kg) 13 (5.9) 14 (5.3) 17 (7.7)
Cabinet Dimensions, LxWxH, In. 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8
Cabinet Dimensions, LxWxH, (mm) (1869) x (1176) x (1289) (1869) x (1176) x (1289) (1869) x (1176) x (1289)
Unit Operating Weight, Lb. (kg) 950 (431) 1276 (579) 1278 (580)
Unit Shipping Weight, Lb. (kg) 1025 (465) 1350 (613) 1363 (619)
Add'l Weight If Copper Finned Coils, Lb. (kg)
R-22 and [R-407C]
COMPRESSORS
Type Scroll Scroll Scroll
Nominal Horsepower 6.0 / 6.0 7.5 / 7.5 9.0 / 9.0
Oil Charge Per Compressor of a Tandem Set, oz. (g) 60 (1701) 85 (2410) 110 (3119)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DSPLACEMENT
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 30.3 (2.8) 30.3 (2.8) 30.3 (2.8)
Finned Height x Finned Length, In. 84 x 52 84 x 52 84 x 52
Finned Height x Finned Length, (mm) (2134) x (1321) (2134) x (1321) (2134) x (1321)
Fins Per Inch x Rows Deep: R-22 and [R-407C] 16 x 2 [16 x 2] 16 x 2 [16 x 2] 16 x 3 [16 x 3]
Pumpdown Capacity Lb. (kg) 35.3 (16.0) 35.3 (16.0) 52.9 (24.0)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 2 – 26 (660) 2 – 26 (660) 2 – 26 (660)
Number Of Motors - HP (kW) 2 – 1.0 (0.75) 2 – 1.0 (0.75) 2 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 13950 (6584) 13950 (6584) 12000 (5664)
REMOTE DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Water Connection Size Victaulic, In. (mm) 2 (51) 2 (51) 2 (51)
Water Volume, Gallons (L) 0.9 (3.6) 1.7 (6.3) 2.0 (7.6)
Liquid Line Conn. Braze, inches 1.125 1.125 1.125
Suction Line Conn. Braze, Inches 2.125 2.125 2.125
Temperature Sensor Conn. NPT, Inches 0.75 0.75 0.75
Dry Weight, lbs (kg) 50 (22) 75 (34) 87 (39)
Operating Weight, lbs (kg) 58 (26) 88 (40) 109 (49)
Maximum Refrigerant Working Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103)
Maximum Water Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103)
Vent and Drain Conn. Field Field Field
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range and does not take field-installed lines into account.
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 49.0 (4.6) 49.0 (4.6) 58.3 (5.4) 58.3 (5.4)
Finned Height x Finned Length, In. 84 x 84 84 x 84 100 x 84 100 x 84
Finned Height x Finned Length, (mm) (2134) x (2134) (2134) x (2134) (2545 ) x (2134) (2545 ) x (2134)
Fins Per Inch x Rows Deep: R22 and [R407C]
Pumpdown Capacity, R-22 and [R-407C]
Lb. (kg)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 3 – 26 (660) 3 – 26 (660) 3 – 26 (660) 3 – 26 (660)
Number Of Motors - HP (kW) 3 – 1.0 (0.75) 3 – 1.0 (0.75) 3 – 1.0 (0.75) 3 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 20925 (9877) 20925 (9877) 19800 (9346) 19800 (9346)
REMOTE DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Connection Size Victaulic, In. (mm) 2 (51) 2 (51) 2 (51) 2 (51)
Water Volume, Gallons (L) 2.2 (8.2) 3.0 (11.5) 4. 0 (15.1) 5.6 (21.0)
Liquid Line Conn. Braze, inches 1.125 1.125 1.375 1.375
Suction Line Conn. Braze, Inches 2.125 2.125 2.125 2.125
Temperature Sensor Conn. NPT, Inches 0.75 0.75 0.75 0.75
Dry Weight, lbs (kg) 92 (42) 124 (56) 156 (71) 211 (96)
Operating Weight, lbs (kg) 110 (50) 148 (67) 188 (85) 255 (116)
Max. Refrigerant Working Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103) 450 (3103)
Maximum Water Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103) 450 (3103)
Drain and Vent Connections Field Field Field Field
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range and does not take field-installed lines into account.
020B 025B 029B 034B
34.0 (15.4)
[38.0 (17.3)]
(2697) x (1176) x
(1289)
284 (129)
[426 (194)]
110 (3119) 110 (3119) 110 (3119) 158 (4479)
16 x 2 [16 x 3] 16 x 3 [16 x 3] 16 x 3 [16 x 3] 16 x 3 [16 x 3]
56.9 (25.9)
[85.4 (38.8)]
AGZ MODEL NUMBER
42.0 (19.1) 47.0 (21.3) 50.0 (22.7)
(2697) x (1176) x
(1289)
426 (194)
[426 (194)]
85.4 (38.8) 101.6 (46.2) 101.6 (46.2)
(2697) x (1176) x
(1493)
508 (231)
[508 (231)]
(2697) x (1176) x
(1493)
508 (231)
[508 (231)]
IOMM AGZB1 AGZ 010B through 034B 19
Electrical Data
Field Wiring
Wiring must comply with all applicable codes and ordinances. Warranty is void if wiring is
not in accordance with specifications. Copper wire is required for all power lead
terminations at the unit.
AGZ 010A through AGZ 034A units have single point power connection. A single field
supplied fused disconnect is required. The control transformer is factory mounted.
If the evaporator heater is on a separate disconnect switch from the main unit power supply,
the unit may be shut down without defeating the freeze protection provided by the
evaporator heater.
R-22 data is located on pages 21 through 22, R-407C data in on pages 23 through 24.