in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from
ASHRAE;
LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license gr anted by
Echelon Corporation; Compliant Scroll from Copeland Corporation; E l ectroFin from AST ElectroFin Inc.; Modbus from Schneider Electric;
FanTrol, MicroTech II, Open Choices, and SpeedTrol from McQuay International
2 IMM AGSD3
Introduction
General Description
McQuay AGS air-cooled water chillers are complete, self-contained automatic refrigerating units
that include the latest in engineered components arranged to provide a compact and efficient unit.
Each unit is completely assembled, (except remote evaporator applications) factory wired,
evacuated, charged, tested and comes complete and ready for installation. Each unit consists of
two air-cooled condenser sections with integral subcooler sections, two semi-hermetic, singlescrew compressors with solid-state starters, a two-circuit shell-and-tube direct expansion
evaporator, and complete refrigerant piping. Each compressor has an independent refrigeration
circuit. Liquid line components included are manual liquid line shutoff valves, charging ports,
filter-driers, sight-glass/moisture indicators, solenoid valves and electronic expansion valves. A
discharge shutoff valve is included and a compressor suction shutoff valve is optional. Other
features include compressor heaters, evaporator heaters for freeze protection, automatic one-time
pumpdown of each refrigerant circuit upon circuit shutdown, and an advanced fully integrated
microprocessor control system.
AGS units are available as standard efficiency (model DS) and high efficiency units (DE). The
high efficiency units have certain larger components to improve efficiency.
The units are optionally available with the evaporator shipped separately for remote mounting
indoors.
Information on the operation of the unit MicroTech II controller is in the OM AGSD3 manual.
Nomenclature
A G S - XXX D S
Rotary Screw Compressor
Air-Cooled
Global
Nominal Tons
S=Standard Efficiency, Packaged Unit
M=Standard Efficiency, Remote Evaporator
E= High Efficiency, Packaged Unit
F= High Efficiency, Remote Evaporator.
Design Vi ntage
Inspection
When the equipment is received, carefully check all items against the bill of lading to check for a
complete shipment. Check all units for damage upon arrival. All shipping damage must be reported
to the carrier and a claim must be filed with the carrier. Check the unit’s serial plate before
unloading the unit to be sure that it agrees with the power supply available. Physical damage to
unit after acceptance is not the responsibility of McQuay International.
Note: Unit shipping and operating weights are shown on page
23.
IMM AGSD3 3
Installation and Start-up
Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Note: Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.
Start-up by McQuayService is included on all units sold for installation within the USA and
Canada and must be performed by them to initiate the standard limited product warranty.
Two-week prior notification of start-up is required. The contractor should obtain a copy of
the Start-up Scheduled Request Form from the sales representative or from the nearest office
of McQuayService.
Escaping refrigerant can displace air and cause suffocation. Immediately evacuate and
ventilate the equipment area. If the unit is damaged, follow Environmental Protection Agency
(EPA) requirements. Do not expose sparks, arcing equipment, open flame or other ignition
source to the refrigerant.
Handling
Avoid rough handling shock due to impact or dropping the unit. Do not push or pull the unit.
!
WARNING
!
WARNING
Never allow any part of the unit to fall during unloading or moving, as this can result in
serious damage.
To lift the unit, lifting tabs with 2½" (64 mm) diameter holes are provided on the base of the
unit. All lifting holes must be used when lifting the unit. Spreader bars and cables should be
arranged to prevent damage to the condenser coils or unit cabinet (see
!
DANGER
Improper lifting or moving unit can result in property damage, severe personal injury or
death. Follow rigging and moving instructions carefully
Figure 1).
Figure 1, Required Lifting Method
NOTES:
1. All rigging points on a unit must be used.
See location and weights at lifting points
beginning on page
unit.
2. Crosswise and lengthwise spreader bars
must be used to avoid damage to unit.
Lifting cables from the unit mounting
holes up must be vertical.
3. The number of condenser sections, and
fans can vary from this diagram.
23 for a specific size
4 IMM AGSD3
Location
Locate the unit carefully to provide proper airflow to the condenser. (See Figure 2on page 6
for required clearances).
Due to the shape of the condenser coils on the AGS chillers, it is recommended that the unit
be oriented so that prevailing winds blow parallel to the unit length, thus minimizing the
wind effect on condensing pressure and performance. If low ambient temperature operation
is expected, optional louvers should be installed if the unit has no protection against
prevailing winds.
Using less clearance than shown in
condenser and could have a significant detrimental effect on unit performance.
See Restricted Airflow beginning on page
For pad-mounted units, it is recommended that the unit be raised a few inches with suitable
supports, located at least under the mounting locations, to allow water to drain from under
the unit and to facilitate cleaning under it
Figure 2 can cause discharge air recirculation to the
7 for further information.
Service Access
Compressors, filter-driers, and manual liquid line shutoff valves are accessible on each side or end
of the unit. The evaporator heater is located on the barrel.
The control panels are located on the end of the chiller. The left-hand control box contains the unit
and circuit microprocessors as well as transformers, fuses and terminal. The right-hand panel
contains a circuit breaker and solid state starter for each compressor plus fuses, fan VFD (optional)
and fan contactors. A minimum of four feet of clearance is required in front of the panels.
The side clearance required for airflow provides sufficient service clearance.
On all AGS units, the condenser fans and motors can be removed from the top of the unit. The
complete fan/motor assembly can be removed for service. The fan blade must be removed for
access to wiring terminals at the top of the motor.
!
WARNING
Disconnect, lockout and tag all power to the unit before servicing condenser fan motors or
compressors. Failure to do so can cause bodily injury or death.
Do not block access to the sides or ends of the unit with piping or conduit. These areas must be
open for service access. Do not block any access to the control panels with a field-mounted
disconnect switches.
IMM AGSD3 5
Clearance Requirements
Figure 2, Clearance Requirements
5ft (1.5m)if open fence or 50% open wall
6ft (1.8m)
4ft (1.2m)
For electric
panel access
if solid wall (see note 3 for pit)
No obstructions.
Recommended area
required for unit
operation, air flow
and maintenance
access.
5ft (1.5m)if open fence or 50% open wall
6ft (1.8m)
if solid wall (see note 3 for pit)
See notes 2 & 4
concerning wall
height at unit sides.
No obstructions allowed
above unit at any height
Air Flow
3ft (1m) for service
See Note 5
Wall or
Fence
Notes:
1. Minimum side clearance between two units is 12 feet (3.7 meters).
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit unless
extra clearance is provided per note 4.
3. Minimum clearance on each side is 8 feet (2.4 meters) when installed in a pit no deeper than the unit
height.
4. Minimum side clearance to a side wall or building taller than the unit height is 6 feet (1.8 meters),
provided no solid wall above 6 feet (1.8 meters) is closer than 12 feet (3.7 meters) to the opposite side
of the unit.
5. Do not mount electrical conduits where they can block service access to compressor controls, refrigerant
driers or valves.
6. There must be no obstruction of the fan discharge.
7. Field installed switches must not interfere with service access or airflow.
8. The evaporator can be removed from the side of the unit and may require the temporary removal of a
coil section support post. See dimension drawings beginning on page
9. If the airflow clearances cannot be met, see the following pages on Restricted Airflow.
25 for details.
6 IMM AGSD3
Restricted Airflow
General
The clearances required for design operation of AGS air-cooled condensers are described in the
previous section. Occasionally, these clearances cannot be maintained due to site restrictions such
as units being too close together or a fence or wall restricting airflow, or both.
The McQuay AGS chillers have several features that can mitigate the problems attributable to
restricted airflow.
• The shape of the condenser section allows inlet air for these coils to come in from both sides
and the bottom. All the coils on one side serve one compressor. Every compressor always has
its own independent refrigerant circuit.
• The MicroTech II™ control is proactive in response to off-design conditions. In the case of
single or compounded influences restricting airflow to the unit, the microprocessor will act to
keep the compressor(s) running (at reduced capacity) as long as possible, rather than allowing
a shut-off on high discharge pressure.
Figure 3, Coil and Fan Arrangement
The following sections discuss the most common situations of condenser air restriction and give
capacity and power adjustment factors for each. Note that in unusually severe conditions, the
MicroTech II controller will adjust the unit operation to remain online until a less severe condition
is reached.
IMM AGSD3 7
Case 1, Building or Wall on One Side of One Unit
The existence of a screening wall, or the wall of a building, in close proximity to an air-cooled
chiller is common in both rooftop and ground level applications. Hot air recirculation on the coils
adjoining the wall will increase compressor discharge pressure, decreasing capacity and increasing
power consumption.
When close to a wall, it is desirable to place chillers on the north or east side of them. It is also
desirable to have prevailing winds blowing parallel to the unit’s long axis. The worst case is to
have wind blowing hot discharge air into the wall.
Figure 4, Unit Adjacent to Wall
D
H
Figure 5, Adjustment Factors
5 ft.
(1.5m)
6 ft.
(1.8m)
5 ft.
(1.5m)
6 ft.
(1.8m)
8 IMM AGSD3
Case 2, Two Units Side By Side
Two or more units sited side by side are common. If spaced closer than 12 feet (3.7 meters), or 8 feet (2.5
meters), depending on size, it is necessary to adjust the performance of each unit. Circuits adjoining each
other are affected. NOTE: This case applies only to two units side by side. See Case 3 for three or more
parallel units. If one of the two units also has a wall adjoining it, see Case 1. Add the two adjustment
factors together and apply to the unit located between the wall and the other unit.
Mounting units end to end will not necessitate adjusting performance. Depending on the actual
arrangement, sufficient space must be left between the units for access to the control panel door opening
and/or evaporator tube removal. See “Clearance” section of this guide for requirements for specific units.
Figure 6, Two Units Side by Side
Figure 7, Adjustment Factor
3.0
2.0
1.0
0
9
(2.7)
10
(3.0)
11
(3.3)
12
(3.6)
6.0
4.0
2.0
0
9
(2.7)
10
(3.0)
11
(3.3)
12
(3.6)
IMM AGSD3 9
Case 3, Three or More Units Side By Side
When three or more units are side by side, the outside units (chillers 1 and 3 in this case) are influenced by
the middle unit only on their inside circuits. Their adjustment factors will be the same as Case 2. All inside
units (only chiller 2 in this case) are influenced on both sides and must be adjusted by the factors shown
below.
Figure 8, Three or More Units
Chiller 1Chiller 2Chiller 3
Figure 9, Adjustment Factor
4.0
3.0
2.0
1.0
0
15
(4.6)
16
(4.9)
17
(5.2)
18
(5.5)
8.0
6.0
4.0
2.0
0
15
(4.6)
16
(4.9)
17
(5.2)
18
(5.5)
10 IMM AGSD3
Case 4, Open Screening Walls
Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop. These
walls should be designed such that the combination of their open area and distance from the unit do not
require performance adjustment. It is assumed that the wall height is equal to or less than the unit height
when mounted on its base support. This is usually satisfactory for concealment. If the wall height is greater
than the unit height, see Case 5, Pit Installation.
The distance from the ends of the unit to the end walls must be sufficient for service, opening control panel
doors, and pulling evaporator tubes, as applicable.
If each side wall is a different distance from the unit, the distances can be averaged, providing either wall is
not less than 8 feet (2.4 meters) from the unit. For example, do not average 4 feet and 20 feet to equal 12
feet.
Figure 10, Open Screening Walls
Figure 11, Wall Free Area vs. Distance
IMM AGSD3 11
Case 5, Pit/Solid Wall Installation
Pit installations can cause operating problems and great care must be exercised if they are to be
used on an installation. Recirculation and restriction can both occur. A solid wall surrounding a
unit is substantially the same as a pit and the data presented in this case should be used.
Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit. The
grating material and installation design must be strong enough to prevent such accidents, yet
provide abundant open area or serious recirculation problems will occur. Have any pit installation
reviewed by the McQuay sales office prior to installation to discuss whether it has sufficient
airflow characteristics. The installation design engineer must approve the work and is responsible
for design criteria.
Figure 12, Pit Installation
Figure 13, Adjustment Factor
12 IMM AGSD3
Vibration Isolator Location
Spring-Flex Locations
NOTE: See dimension drawings for mounting point location.
Table 1, Standard Efficiency with Aluminum Fin Condensers
Unit
Size
140DS to
170DS
190DS to
210DS
M1 M2 M3 M4 M5 M6
CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
White White White White Gray Gray
CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
White White White White White White
Table 2, High Efficiency with Aluminum Fin Condensers
Unit
Size
149DE to
190DE
M1 M2 M3 M4 M5 M6
CP-2 CP-2 CP-2 CP-2 CP-2 CP-2
White White White White Gray Gray
Table 3, Standard Efficiency with Copper Fin Condensers
Unit
Size
140DS to
210DS
M1
CP-4 CP-4 CP-4 CP-4 CP-4 CP-4
Orange Orange Orange Orange Orange Orange
M2
Mounting Location
Mounting Location
Mounting Locations
M3 M4 M5 M6
Spring Kit
Number
330904106
330904126
Spring Kit
Number
330904126
Spring Kit
Number
330904127
Table 4, High Efficiency with Copper Fin Condensers
Unit
Size
140DE to
210DE
M1 M2 M3 M4 M5 M6
CP-4 CP-4 CP-4 CP-4 CP-4 CP-4
Orange Orange Orange Orange Orange Orange
Mounting Locations
Spring Kit
Number
330904127
IMM AGSD3 13
R-I-S Locations
NOTE: See dimension drawings for mounting point location.
Table 5, Standard Efficiency with Aluminum Fin Condensers
Unit
Size
140DS to
210DS
1 2 3 4 5
RP-4 330904133 RP-4 RP-4 RP-4
Green Green Green Green Red
Table 6, High Efficiency with Aluminum Fin Condensers
Unit
Size
140DE to
190DE
1
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Red Red
2
Table 7, Standard Efficiency with Copper Fin Condensers
Unit
Size
170DS to
210DS
1 2 3 4 5 6
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Green Green
R-I-S Mountings
R-I-S Mountings
3 4 5 6
R-I-S Mountings
6
RP-4
Red
R-I-S Kit
Number
330904133
R-I-S Kit
Number
330904133
R-I-S Kit
Number
330904125
Table 8, High Efficiency with Copper Fin Condensers
Unit
Size
170DE to
190DE
1 2 3 4 5 6
RP-4 RP-4 RP-4 RP-4 RP-4 RP-4
Green Green Green Green Green Green
R-I-S Mountings
R-I-S Kit
Number
330904125
14 IMM AGSD3
Figure 14,CP-4 Spring Flex Mounting Figure 15, RP-4 Rubber-in-Shear
Mounting
IMM AGSD3 15
Chilled Water Pump
It is recommended that the chilled water pumps' starters be wired to, and controlled by, the chiller's
microprocessor. The controller will energize the pump whenever at least one circuit on the chiller
is enabled to run, whether there is a call for cooling or not. Wiring connection points are shown in
Figure 22 on page 38.
Water Piping
Due to the variety of piping practices, follow the recommendations of local authorities. They can
supply the installer with the proper building and safety codes required for a proper installation.
Design the piping with a minimum number of bends and changes in elevation to keep system cost
down and performance up. It should contain:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system and drains at the low parts
in the system. The evaporator should not be the highest point in the piping system.
4. Some means of maintaining adequate system water pressure (i.e., expansion tank or regulating
valve).
5. Water temperature and pressure indicators located at the evaporator inlet and outlet to aid in
unit servicing. Any connections should be made prior to filling the system with water.
6. A strainer to remove foreign matter from the water before it enters the pump. Place the strainer
far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for
recommendations). The use of a strainer will prolong pump life and help maintain high system
performance levels.
NOTE: A 20 mesh strainer must also be placed in the supply water line just prior to the inlet
of the evaporator. This will aid in preventing foreign material from entering the evaporator and
causing damage or decreasing its performance. Care must also be exercised if welding pipe or
flanges to the evaporator connections to prevent any weld slag from entering the vessel.
7. Any water piping to the unit must be protected to prevent freeze-up if below freezing
temperatures are expected.
!
CAUTION
If a separate disconnect is used for the 115V supply to the unit, it should power the entire
control circuit, not just the evaporator heaters. It should be clearly marked so that it is not
accidentally shut off during cold seasons. Freeze damage to the evaporator could result. If
the evaporator is drained for winter freeze protection, the heaters must be de-energized to
prevent burnout.
8. If the unit is used as a replacement chiller on a previously existing piping system, flush the
system thoroughly prior to unit installation. Perform regular chilled water analysis and
chemical water treatment immediately at equipment start-up.
16 IMM AGSD3
9. In the event glycol is added to the water system as a late addition for freeze protection,
recognize that the refrigerant suction pressure will be lower, cooling performance less, and
water side pressure drop greater. If the percentage of glycol is large, or if propylene is
employed in lieu of ethylene glycol, the added pressure drop and loss of performance could be
substantial.
10. For ice making or low temperature glycol operation, a different freezestat pressure value is
usually required. The freezestat setting can be manually changed through the MicroTech II
controller.
Make a preliminary leak check prior to insulating the water piping and filling the system.
Include a vapor barrier with the piping insulation to prevent moisture condensation and possible
damage to the building structure. It is important to have the vapor barrier on the outside of the
insulation to prevent condensation within the insulation on the cold surface of the pipe.
System Water Volume
All chilled water systems need adequate time to recognize a load change, respond to that load
change and stabilize, without undesirable short cycling of the compressors or loss of control. In air
conditioning systems, the potential for short cycling usually exists when the building load falls
below the minimum chiller plant capacity or on close-coupled systems with very small water
volumes.
Some of the things the designer should consider when looking at water volume are the minimum
cooling load, the minimum chiller plant capacity during the low load period and the desired cycle
time for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown,
a rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow
rate” is often used.
A properly designed storage tank should be added if the system components do not provide
sufficient water volume.
Variable Speed Pumping
Variable water flow involves reducing the water flow through the evaporator as the load decreases.
McQuay chillers are designed for this duty, provided that the rate of change in water flow is slow,
and the minimum and maximum flow rates for the vessel are not exceeded.
The recommended maximum change in water flow is 10 percent of the change per minute.
The water flow through the vessel must remain between the minimum and maximum values listed
on page
occur. If the flow exceeds the maximum rate, excessive pressure drop and tube erosion can occur.
22. If flow drops below the minimum allowable, large reductions in heat transfer can
IMM AGSD3 17
Evaporator Freeze Protection
AGS chillers are equipped with thermostatically controlled evaporator heaters that help protect
against freeze-up down to -20°F (-28°C).
NOTE: The heaters come from the factory connected to the control power circuit. The control
power can be rewired in the field to a separate 115V supply (do not wire directly to the heater). See
the field wiring diagram on page
accidental deactivation of the heater during freezing temperatures. Exposed chilled water piping
also requires protection.
For additional protection, at least one of the following procedures should be used during periods of
sub-freezing temperatures:
1. Adding of a concentration of a glycol anti-freeze with a freeze point 10 degrees F below
the lowest expected temperature. This will result in decreased capacity and increased
pressure drop.
Note: Do not use automotive grade antifreezes as they contain inhibitors harmful to chilled
water systems. Use only glycols specifically designated for use in building cooling systems.
2. Draining the water from outdoor equipment and piping and blowing the chiller tubes dry
from the chiller. Do not
38. If this is done, mark the disconnect switch clearly to avoid
energize the chiller heater when water is drained from the vessel.
!
CAUTION
If fluid is absent from the evaporator, the evaporator heater must be de-energized to avoid
burning out the heater and causing damage from the high temperatures.
3. Providing operation of the chilled water pump, circulating water through the chilled water
system and through the evaporator.
Table 9, Freeze Protection
Temperature
°F (°C)
20 (6.7) 16 18 11 12
10 (-12.2) 25 29 17 20
0 (-17.8) 33 36 22 24
-10 (-23.3) 39 42 26 28
-20 (-28.9) 44 46 30 30
-30 (-34.4) 48 50 30 33
-40 (-40.0) 52 54 30 35
-50 (-45.6) 56 57 30 35
-60 (-51.1) 60 60 30 35
Notes:
1. These figures are examples only and cannot be appropriate to every situation. Generally, for an extended margin of
protection, select a temperature at least 15°F lower than the expected lowest ambient temperature. Inhibitor levels
should be adjusted for solutions less than 25% glycol.
2. Glycol of less than 25% concentration is not recommended because of the potential for bacterial growth and loss of
heat transfer efficiency.
Maximum standby ambient temperature, 130°F (55°C)
Maximum operating ambient temperature, 125°F (51.7°C)
Minimum operating ambient temperature (standard), 35°F (2°C)
Minimum operating ambient temperature (optional low-ambient control), 0°F (-18°C)
Leaving chilled water temperature, 40°F to 60°F (4°C to 16°C)
Leaving chilled fluid range (with anti-freeze), 20°F to 60°F (-7°C to 16°C). Unloading is not
permitted with fluid leaving temperatures below 30°F (-1°C).
Operating Delta-T range, 6 degrees F to 16 degrees F (10.8 C to 28.8 C)
Maximum operating inlet fluid temperature, 76°F (24°C)
Maximum startup inlet fluid temperature, 90°F (32°C)
Maximum non-operating inlet fluid temperature, 100°F (38°C) NOTE: Contact the local McQuay sales office for operation outside any of these limits.
Two series of units are available with the AGS-D chillers.
Standard Efficiency,
model number following the “D” vintage designation (i.e. AGS 200DS
designated by a "S" (or “M” with remote evaporator) as the last digit in the
or AGS 200DM) are
designed to meet ASHRAE 90.1 efficiency standard. They provide the lowest dollar per ton price.
High Efficiency,
model number (i.e. AGS 200DE
designated by an "E" (or “F” with remote evaporator) as the last digit in the
or AGS 200DF) are designed for high efficiency operation. The
high efficiency models have larger components, and/or more fans than the comparable standard
efficiency models. This results in improved efficiency and the ability to operate at higher ambient
air temperatures.
Flow Switch
A flow switch must be included in the
chilled water system to prove that there is
Figure 16, Flow Switch
Flow direction
adequate water flow to the evaporator
before the unit can start. It also serves to
shut down the unit in the event that water
flow is interrupted in order to guard against
1" (25mm) NPT flow
switch connection
Tee
evaporator freeze-up.
A solid state flow switch that is factory-
mounted and wired in the chiller leaving
water nozzle is available as an option.
A flow switch for field mounting and
1 1/4" (32mm) pipe
dia. min. before
switch
1 1/4" (32mm)
pipe dia. min.
wiring in the leaving chilled water is also
available as an option from McQuay under
ordering number 017503300. It is a paddletype switch and adaptable to any pipe size
from 1" (25mm) to 8" (203mm) nominal.
Certain minimum flow rates are required to close the switch and are listed in
should be as shown in
Figure 17.
Table 10. Installation
Electrical connections in the unit control center should be made at terminals 60 and 67 from switch
terminals Y and R. The normally open contacts of the flow switch should be wired between these
IMM AGSD3 19
two terminals. Flow switch contact quality must be suitable for 24 VAC, low current (16ma). Flow
A
switch wire must be in separate conduit from any high voltage conductors (115 VAC and higher)
and have an insulation rating of 600 volts.
Table 10, Flow Switch Flow Rates
(NOTE)
Min.
Adjst.
Max.
Adjst.
Flow
Flow Lpm 11.4 22.9 35.9 38.6
Flow
Flow Lpm 27.7 53.4 81.8 90.8
NOTES:
1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose.
1. Connections for vent and drain fittings are located on the top and bottom of the evaporator.
2. Piping must be supported to avoid putting strain on the evaporator nozzles.
In
Vibration
Eliminator
Valved
Pressure
Gauge
Flow
Switch
Vibration
Eliminator
Balancing
Valve
Water
Strainer
Gate
Valve
Flow
Gate
Valve
Protect All Field Piping
Flow
gainst Freezing
Refrigerant Charge
All packaged units are designed for use with R-134a and are shipped with a full operating charge.
The operating charge for each unit is shown in the Physical Data Tables beginning on page
packaged units, and page
53 for remote evaporator models. Model AGS-CM/CB with remote
23 for
evaporators are shipped with a full unit charge. Refrigerant must be added in the field for the
evaporator and for the refrigerant lines.
Glycol Solutions
When using glycol anti-freeze solutions the chiller's capacity, glycol solution flow rate, and
pressure drop through the evaporator can be calculated using the following formulas and tables.
Note: The procedure below does not specify the type of glycol. Use the derate factors found in
Table 11 for corrections when using propylene glycol and those in Table 12 for ethylene glycol.
1. Capacity - Cooling capacity is reduced from that with plain water. To find the reduced value,
multiply the chiller’s water system tonnage by the capacity correction factor to find the
chiller’s capacity when using glycol.
2. Flow - To determine flow (or Delta-T) knowing Delta-T (or flow) and capacity:
20 IMM AGSD3
(
GPM
24
()( )
=
factorflowtons
)
−
TDelta
3. Pressure drop - To determine pressure drop through the evaporator when using glycol, enter
the water pressure drop curve at the water flow rate. Multiply the water pressure drop found
there by the "PD" factor to obtain corrected glycol pressure drop.
4. Power - To determine glycol system kW, multiply the water sy stem kW by the factor
designated "Power".
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service
stations) to determine the freezing point. Obtain percent glycol from the freezing point table below.
On glycol applications, the supplier normally recommends that a minimum of 25% solution by
weight be used for protection against corrosion or that additional inhibitors should be employed.
NOTE: Do not use automotive antifreeze. Industrial glycols must be used. Automotive antifreeze
contains inhibitors that will cause plating on the copper tubes within the chiller evaporator. The
type and handling of glycol used must be consistent with local codes.
Table 11, Ethylene Glycol Factors
Freeze
%
E.G.
Point
oF o
26 -3.3 0.996 0.998 1.036 1.097
10
18 -7.8 0.988 0.994 1.061 1.219
20
7 -13.9 0.979 0.991 1.092 1.352
30
-7 -21.7 0.969 0.986 1.132 1.532
40
-28 -33.3 0.958 0.981 1.182 1.748
50
Capacity Power Flow PD
C
Water Flow and Pressure Drop
Adjust the chilled water flow through the evaporator to meet specified conditions. The flow rates
must fall between the minimum and maximum values shown in the table on the following page.
Flow rates below the minimum values shown will result in laminar flow that will reduce efficiency,
cause erratic operation of the electronic expansion valve and could cause low temperature cutouts.
On the other hand, flow rates exceeding the maximum values shown can cause erosion on the
evaporator water connections and tubes.
Measure the chilled water pressure drop through the evaporator at field-installed pressure taps. It is
important not to include valve or strainer pressure drops in these readings.
No. of Fans/Circuit – 30 in. Fan Dia. 5 5 5 5 5 5
Fan Motor hp (kW) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8950 (45.5) 8950 (45.5) 8950 (45.5)
60 Hz Total Unit Airflow, cfm (l/s) 108630 (51280) 108630 (51280) 108630 (51280)
No. of Fans/Circuit – 30 in. Fan Dia 6 6 6 6 6 6
Fan Motor -- hp (kW) 2.0 (1.5) 2.0 (1.5) 2.5 (1.9)
Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm (m/s) 8950 (45.5) 8950 (45.5) 8950 (45.5)
60 Hz Total Unit Airflow, cfm (l/s) 130360 (61530) 130360 (61530) 137328 (64819)