McQuay Air-Cooled Global water chillers are complete, self-contained automatic refrigerating units.
Every unit is completely assembled, factory wired, charged, and tested. Each unit consists of twin
Air-Cooled condensers with integral subcooler sections, two reciprocating compressors, replaceable
tube dual circuit shell-and-tube evaporator, and complete refrigerant piping. Liquid line components
include manual liquid line shutoff valves, sight-glass/moisture indicators, solenoid valves, and double
diaphragm hydraulic element thermal expansion valves. Other features include compressor crankcase
heaters, an evaporator heater for chilled water freeze protection, limited recycling pumpdown during
“on” or “off” periods, compressor lead-lag switch to alternate the compressor starting sequence, and
sequenced starting of compressors.
The electrical control center includes all safety and operating controls necessary for dependable
automatic operation. Condenser fan motors are fused in all three phases and started by their own
three-pole contactors. Compressors are not fused but may be protected by optional circuit breakers.
Inspection
Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report
shipping damage and file a claim with the carrier. Check the unit name plate before unloading,
making certain it agrees with the power supply available. McQuay is not responsible for physical
damage after unit leaves the factory.
Note: Unit shipping and operating weights are available in the Physical Data tables
beginning on page 13.
IOMM AGR-1AGR 070A through 100A3
Installation
Note: Installation is to be performed by qualified personnel who are familiar with local codes
and regulations.
WARNING
Sharp edges and coil surfaces are a potential hazard. Avoid contact with them.
Handling
Be careful to avoid rough handling of the unit. Do not push or pull the unit from anything other t han
the base. Block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet
and end frame (see Figure 1).
To lift the unit, 2 1/2" (64mm) diameter lifting holes are provided in the base of the unit. Arrange
spreader bars and cables to prevent damage to the condenser coils or cabinet (see Figure 2).
Figure 1, Suggested Pushing Arrangement
Blocking is required
across full width
Figure 2, Suggested Lifting Arrangement
Number of fans may vary
Spreader Bars
recommended
(use caution)
4AGR 070A through 100AIOMM AGR-1
from this diagram. The
lifting method will remain
the same
These rigging holes
must be used.
Location
Unit Placement
AGR units are for outdoor applications and can be mounted on a roof or ground level. Set units on a
solid and level foundation. For roof mounted applications, install the unit on a steel channel or Ibeam frame to support the unit above the roof. For ground level applications, install the unit on a
substantial base that will not settle. A one piece concrete slab with footings extended below the frost
line is recommended. Be sure the foundation is level (within 1/2” [13mm] over its length and width).
The foundation must support the operating weights listed in the Physical Data tables beginning on
page 13.
On ground level applications protect fins agai nst vandalism using the optional coil guard s or by
erecting a screen fence. The fence must allow free flow of air to the condenser coil for proper unit
operation.
Clearances
The flow of air to and from the condenser coil must not be limited. Restricting air flow or allowing
air recirculation will result in a decrease in unit performance and efficiency. There must be no
obstruction above the unit that would deflect discharge air downward where it could be recirculated
back to the inlet of the condenser coil. The condenser fans are propeller type and will not operate
with ductwork on the fan outlet.
Install the unit with enough si de clearance for air entranc e to the coil and for servicing. Provide
service access to the evaporator, compressors, electrical control panel and piping components as
shown in Figure 3.
Do not allow debris to accumulate near the unit. Air movement may draw debris into the condenser
coil causing air starvation. Give special consideration to low ambient operation where snow can
accumulate. Keep condenser coils and fan discharge free of snow or other obstructions to permit
adequate airflow.
Sound Isolation
The ultra-low sound levels of the AGR chiller is suitable for most applications. When additional
sound reduction is necessary, locate the unit away from sound sensitive areas. Avoid locations
beneath windows or between structures where normal operating sounds may be objectionable.
Reduce structurally transmitted sound by isolating water lines, electrical conduit and the unit itself.
Use wall sleeves and rubber isolated piping hangers to reduce transmission of water or pump noise
into occupied spaces. Use flexible electrical conduit to isolate sound through electrical conduit.
Spring isolators are effective in reducing the low amplitude sound generated by reciprocating
compressors and for unit isolation in sound sensitive areas.
Service Access and Clearances
Each end of the unit must be accessible after installation for periodic service. Compressors, filterdriers, and manual liquid line shutoff valves are accessible. The high pressure control is located in the
control panel when using the Global UNT controller, and on the compressor when using the
MicroTech controller. Low pressure, and motor protector controls are on the compressor. Most other
operational, safety and starting controls are located in the unit control box.
The condenser fan and motors can be removed from the top of the unit.
IOMM AGR-1AGR 070A through 100A5
Figure 3, Clearance Requirements
A
A
A
A
AIR FLOW
AIR
DISCHARGE
AIR FLOW
10 FT.
The recommended min imu m side clear ance betwe en tw o units is 10 feet (304 8m m) .
Distance less than 10 feet (3048mm) can result in air recirculation.
AIR
DISCHARGE
AIR FLOW
The unit must not be installed in a pit or enclosure tha t is deeper
Or taller than the height of the unit unless extra space is provided ,
(consult factory) the minimum clearanc e on each side of the unit is
8 feet (2438mm) when installed in a pit.
AIR
IR FLOW
8 FT.
The minimum clearance to a side wall or building taller than the
Unit height is 6 feet (1828mm) provided no solid wall above 6 feet
(1830mm) tall is closer than 8 feet (243 8mm ) to the opposite
Side of the unit. (consult factory for special situations.)
DISCHARGE
AIR
DISCHARGE
IR FLOW
IR FLOW
Do not block the flow of air to
and from the condenser coil.
Restricting airflow or allowing
air recirculation will result in a
decrease in unit performance
IR FLOW
and efficiency because
discharge pressures are
increased. There must be no
obstruction above the unit that
would deflect discharge air
downward where it could be
recirculated back to the inlet of
the condenser coil. The
condenser fans are propeller
type and will not operate with
ductwork on the fan outlet.
Install the unit with enough sid e
clearance for air entrance to the
coil and for servicing. Provide
service access to the evaporator,
compressors, electrical control
panel and piping components.
Do not allow debris to
accumulate near the unit. Air
movement may draw debri s into
the condenser coil causing coil
starvation. Give special
consideration to low ambient
operation where snow can
accumulate. Keep condenser
coils and fan discharge free of
snow or other obstructions to
permit adequate airflow for
proper unit operation.
6AGR 070A through 100AIOMM AGR-1
Vibration Isolators
Vibration isolators are recommended for all roof mounted installations or wherever vibration
transmission is a consideration.
See Dimensional Data for dimensions required to secure each isolator to the mounting surface.
The spring flex isolators are white type CP2-32, McQuay kit number 350014821, includes four spring
isolators assemblies.
Figure 4, Isolator Locations (4 and 6 fan units)Spring Isolator
Table 1, Isolator Loads at each Mounting Location with Aluminum Fins
UnitControl Box LeftControl Box RightOpposite End LeftOpposite End Right
Sizelbkglbkglbkglbkg
070107148611935419524321060481
0751491676163374111375161245565
0801542699174579211515221302591
0851561708182282611715311367620
0901675760185083912645731396633
0951678761185384112665741398634
1001678761185384112665741398634
Table 2, Isolator Loads at each Mounting Location with Copper Fins
UnitControl Box LeftControl Box RightOpposite End LeftOpposite End Right
Sizelbkglbkglbkglbkg
0701279580142464611375161266574
0751828829200290813946321526692
0801877851212396314006351584719
08518898572206100114176431654750
09020129132222100815186891677761
09520159142225100915206891679762
10020159142225100915206891679762
IOMM AGR-1AGR 070A through 100A7
Water Piping
Local authorities can supply the installer with the proper building and safety codes required for safe
and proper installation.
Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the
following when installing water piping:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Install drains at the lowest
points in the system.
4. A means of maintaining adequate system water pressure (expansion tank or r egulating valve).
5. Temperature and pressure indicators located at the unit to aid in unit servicing.
6. A strainer or other means of removing foreign matter from the water before it enters the pump.
Place the strainer far enough upstream to prevent cavitation at the p ump inlet (consult p ump
manufacturer for recommendations). The use of a strainer will prolong pump life and keep
system performance up.
7. Place a strainer in the water line just before the inlet of the evaporator. This will help prevent
foreign material from entering and decreasing the performance of the evaporator.
CAUTION
If separate disconnect is used f or the 115V supply to the evaporator heating cable, m ark the
disconnect clearly to ensure disconnect is not accidentally shut off during cold seasons.
8. The shell-and-tube evaporator has a thermostat and heating cable to prevent freeze-up down to 20°F (-29°C). It is suggested that the heating cable be wired to a separate 110V supply circui t .
As shipped from the factory, the heating cable is wired to the control circuit. All water piping to
the unit must also be protected to prevent freezing.
9. If the unit is used as a replacement chiller on a previously existing piping system, flush the
system thoroughly before unit installation. Regul ar water analysis and chemica l wate r treatment
for the evaporator loop is recommended immediately at equipment start-up.
10. The total water volume in the system should be sufficient to prevent frequent “on-off” cycling.
Turnover rate should not be less than 15 minutes for normal variable cooling loads. Turnover
rate for process cooling or a constant load, should not be less than 6 minutes.
11. When glycol is added to the water system for freeze protection, the refrigerant suction pressure
will be lower, cooling performance less, and water side pressure drop greater. If the percentage
of glycol is high, or if propylene is used instead of ethylene glycol, the added pressure drop and
loss of performance could be substantial. Reset the freezestat and low leaving water alarm
temperatures. The freezestat is factory set to default at 36°F (2.2°C). Reset the freezestat setting
to approximately 4 to 5 degrees F (2.3 to 2.8 degrees C) below the leaving chilled water setpoint
temperature. See the section titled “Glycol Solutions” for additional information concerning
glycol.
12. Perform a preliminary leak check before insulating the piping and filling the system.
13. Piping insulation should include a vapor barrier to prevent condensation and possible damage to
the building structure.
8AGR 070A through 100AIOMM AGR-1
Figure 5, Typica l field evaporator water piping
Flow Switch
Mount a water flow switch in either the entering or leaving (recommended) water line to shut down
the unit when water flow is interrupted.
A flow switch is available from McQuay (part number 0017503300). It is a “paddle” type switch and
adaptable to any pipe size from 3” (76mm) to 8” (203mm) nominal. Certain minimum flow rates are
required to close the switch and are listed in Table 3. Installation should be as shown in Figure 6.
Connect the normally open contacts of the flow switch in the unit control center at terminals 5 and 6.
There is also a set of normally closed contacts on the switch that can be used for an indicator light or
an alarm to indicate when a “no flow” condition exists. Freeze protect any flow switch that is
installed outdoors.
NOTE: Differential pressure switches are not recommended for outdoor installation.
Bring water piping to the evapor ator through the side, between the verti cal supports.
Refrigerant Charge
All units are designed for use with R-22 and other refrigerants. See nameplate for specific refrigerant
used. Units are shipped with an operating charge and ready for operation. The operating charge
(using R-22) for each unit is shown in the Physical Data tables beginning on page 13.
IOMM AGR-1AGR 070A through 100A9
Figure 7, Refrigerant Piping (Some Components Are Optional)
Note: The procedure
does not specify the
type of glycol. Use
the derate factors
found in Table 4 for
corrections when
using ethylene glycol
and those in Table 5
for propylene glycol.
Glycol Solutions
The system glycol capacity, glycol solution flow rate in GPM, and pressure drop through the cooler
may be calculated using the following formulas and data from Table 4 or Table 5.
1. Capacity -- Find the reduced capacity by multiplying the chiller’s capacity with water by the
capacity correction factor.
2. Flow -- To determine evaporator gpm (or Delta-T) knowing Delta-T (or gpm) and capacity:
)(24
GPM GlycoltionFlowCorrec
×
=
For Metric Applications -- To determine evaporator L/s (or Delta-T) knowing Delta-T (or L/s)
and kW:
L/s GlycoltionFlowCorrec
=
Pressure drop -- To determine pressure drop through the eva porator, when using glycol, enter
3.
kW
18.4
the water pressure drop curve on page 12 at the water flow rate. Multiply the water pressure drop
by PD correction factor from Table 4 or Table 5 to obtain corrected glycol pressure drop.
To determine the unit's power consumption when using glycol, multiply the water system kW by
4.
factor kW.
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service
stations) to determine the freezing point. Obtain percent glycol from the freezing point table below.
On glycol applications it is normally recommended by the supplier that a minimum of 25% solution
by weight be used for protection against corrosion.
glycolcapacity
TDelta
−
×
TDelta
−×
×
table)(from
table)(from
10AGR 070A through 100AIOMM AGR-1
CAUTION
Do not use an automotive grade antifreeze. Industrial grade glycols must be used.
Automotive antifreeze contains inhibitors which will cause plating on the copper tubes within
the chiller evaporator. The type and handling of glycol used must be consistent with local
codes.
Evaporator flow rate must fall between the minimum and maximum values shown in the evaporator
pressure drop table on page 12. Varying chilled water flow through the evaporator while the
compressor(s) are operating is not recommended.
Figure 8, Pressure Drop Curve
090 - 100
070
Unit
Size
(ft) of Water(gpm)(lps)(ft) of Water(gpm)(lps)(ft) of Water(gpm)(lps)
070AS11.216210.2228.127017.034.81016.39
075AS8.917210.8522.528718.093.81086.78
080AS10.318711.8025.931219.664.41177.37
085AS11.820212.7429.733721.245.01267.97
090AS10.520813.1226.334721.874.51308.20
095AS12.022414.1330.037323.555.21408.83
100AS13.423815.0233.639725.025.71499.38
Minimum and maximum flows are established to ensure the Delta-T for each unit size falls within the 6 - 16°F range for proper
unit control. Contact factory for unit operation outside of minimum and maximum flows shown.
Unit Capacity @ ARI Conditions (1), Tons (kW)67.5 (237.6)70.1 (246.7)77.9 (273.9)84.7 (298.1)
Number Of Refrigerant Circuits2222
Unit Operating Charge, R-22, lbs. (kg)60 (27.2)84 (38.1)84 (38.1) 86 (39.9) 86 (39.9)86 (39.9) 86 (39.9)86 (39.9)
Unit Operating Charge, R-134a, , lbs. (kg)63 (28.6) 88 (40.0)88 (40.0) 90 (41.9)90 (41.9) 90 (41.9)90 (41.9) 90 (41.9)
Cabinet Dimensions, LxWxH, In.94.0 x 88.2 x 96.2136.4 x 88.2 x 96.2136.4 x 88.2 x 96.2136.4 x 88.2 x 96.2
Cabinet Dimensions, LxWxH, (mm)2388 x 2241 x 24443463 x 2241 x 24443463 x 2241 x 24443463 x 2241 x 2444
Unit Operating Weight, Lbs. (kg)4276(5506)5506(2497)5740(2604)5921(2686)
Unit Shipping Weight, Lbs. (kg)4169(5359)5359(2431)5593(2537)5774(2619)
Add'l Weight If Copper Finned Coils, Lbs. (kg)830(375)1245(565)1245(565)1245(565)
COMPRESSORS
TypeSemi-HermeticSemi-HermeticSemi-HermeticSemi-Hermetic
Nominal Horsepower3540404040505050
Number Of Cylinders Per Compressor66666888
Oil Charge Per Compressor, oz.140255255255255255255255
Oil Charge Per Compressor, (g)(3969)(7229)(7229)(7229)(7229)(7229)(7229)(7229)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT
Standard Staging - Circuit #1 in Lead0-16-33-49-670-17-33-50-670-15-42-58-730-25-50-63-75
Standard Staging - Circuit #2 in Lead0-17-33-51-670-17-33-50-670-27-42-56-710-25-50-63-75
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, sq. ft.5858878787878787
Coil Face Area, (m2)(5.4)(5.4)(8.1)(8.1)(8.1)(8.1)(8.1)(8.1)
Finned Height x Finned Length, In.100x 83.5 100x 83.5 100x125.3 100x125.3 100x125.3 100x125.3 100x125.3 100x125.3
Finned Height x Finned Length, (mm)
Fins Per Inch x Rows Deep16 x 316 x 316 x 316 x 316 x 316 x 316 x 316 x 3
Number Of Fans - Fan Diameter, In. (mm)4 - 28 (712)6 - 28 (712)6 - 28 (712)6 - 28 (712)
Number Of Motors - HP (kW)4 - 2.0 (1.5)6 - 2.0 (1.5)6 - 2.0 (1.5)6 - 2.0 (1.5)
Fan And Motor RPM, 60Hz1140114011401140
60 Hz Fan Tip Speed, fpm (m/Sec)8357 (35.4)8357 (35.4)8357 (35.4)8357 (35.4)
60 Hz Total Unit Airflow, cfm (m3/sec)40800 (19.3)61200 (28.9)61200 (28.9)61200 (28.9)
DIRECT EXPANSION EVAPORATOR - BAFFLED SHELL AND THRU-TUBE
Diameter, in. - Length, ft.12.75- 412.75 - 5.512.75 - 5.512.75 - 5.5
Diameter, (mm) – Length, (mm)324 - 1220324 - 1676324 - 1676324 - 1676
Water Volume, gallons, (l)12.8 (48.5)17.6 (66.6)17.6 (66.6)17.6 (66.6)
Maximum Water Pressure, psig (kPa)175 (1207)175 (1207)175 (1207)175 (1207)
Maximum Refrigerant Working Pressure, psig (kPa)225 (1552)225 (1552)225 (1552)225 (1552)
Water Inlet / Outlet Victaulic Connections, In. (mm)5 (141.3)5 (141.3)5 (141.3)5 (141.3)
Drain - NPT int, In. (mm).375 (9.5).375 (9.5).375 (9.5).375 (9.5)
Vent - NPT int, In. (mm).375 (9.5).375 (9.5).375 (9.5).375 (9.5)
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range.
070AS075AS080AS085AS
-83-100-83-100-86-100-88-100
-84-100-83-100-85-100-88-100
2032 x
2121
2032 x
2121
AGR MODEL NUMBER
2540 x
3183
2540 x
3183
2540 x
3183
2540 x
3183
2540 x
3183
2540 x
3183
IOMM AGR-1AGR 070A through 100A13
Table 8, AGR 090A – AGR 100A
PHYSICAL DATAAGR MODEL NUMBER
STANDARD EFFICIENCY090AS095AS100AS
BASIC DATACkt.1Ckt.2Ckt.1Ckt.2Ckt.1Ckt.2
Unit Capacity @ ARI Conditions (1), Tons (kW)86.5 (304.1) 93.4 (328.4)99.3 (349.1)
Number Of Refrigerant Circuits222
Unit Operating Charge, R-22, lb.909090909292
Unit Operating Charge, R-22, (kg)(40.8)(40.8)(40.8)(40.8)(41.7)(41.7)
Cabinet Dimensions, LxWxH, In.136.4 x 88.2 x 96.2136.4 x 88.2 x 96.2136.4 x 88.2 x 96.2
Cabinet Dimensions, LxWxH, (mm)3463 x 2241 x 24443463 x 2241 x 24443463 x 2241 x 2444
Unit Operating Weight, Lbs. (kg)6184(2805)6194(2810)6194(2810)
Unit Shipping Weight, Lbs. (kg)6008(2725)6018(2730)6018(2730)
Add'l Weight If Copper Finned Coils, Lbs. (kg)1245(565)1245(565)1245(565)
COMPRESSORS
TypeSemi-HermeticSemi-HermeticSemi-Hermetic
Nominal Horsepower505050606060
Number Of Cylinders Per Compressor888888
Oil Charge Per Compressor, Oz.255255255255255255
Oil Charge Per Compressor, (g)(7229)(7229)(7229)(7229)(7229)(7229)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT
Standard Staging - Circuit #1 in Lead0-25-50-63-75-
Standard Staging - Circuit #2 in Lead0-25-50-63-75-
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, Sq. Ft.878787878787
Coil Face Area, (M2)(8.1)(8.1)(8.1)(8.1)(8.1)(8.1)
Finned Height x Finned Length, In.100x125.3 100x125.3 100x125.3 100x125.3 100x125.3 100x125.3
Finned Height x Finned Length, (mm)2540 x
Fins Per Inch x Rows Deep16 x 316 x 316 x 316 x 316 x 316 x 3
Maximum Relief Valve Pressure Setting, psig (kPa)450 (3103) 450 (3103) 450 (3103) 450 (3103) 450 (3103) 450 (3103)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm)6 - 28 (712)6 - 28 (712)6 - 28 (712)
Number Of Motors - HP (kW)6 - 2.0 (1.5)6 - 2.0 (1.5)6 - 2.0 (1.5)
Fan And Motor RPM, 60Hz114011401140
60 Hz Fan Tip Speed, FPM (M/Sec)8357 (35.4)8357 (35.4)8357 (35.4)
60 Hz Total Unit Airflow, CFM (M3/sec)61200 (28.9)61200 (28.9)61200 (28.9)
DIRECT EXPANSION EVAPORATOR - BAFFLED SHELL AND THRU-TUBE
Diameter, in. - Length, Ft.14 - 5.514 - 5.514 - 5.5
Diameter, (mm) - Length, (mm)356 - 1676356 - 1676356 - 1676
Water Volume, Gallons, (L)21.2(80.3)21.2(80.3)21.2(80.3)
Maximum Water Pressure, psig (kPa)175 (1207)175 (1207)175 (1207)
Maximum Refrigerant Working Pressure, psig (kPa)225 (1552)225 (1552)225 (1552)
Water Inlet / Outlet Victaulic Connections, In. (mm)5 (141.3)5 (141.3)5 (141.3)
Drain - NPT int, In. (mm).375 (9.5).375 (9.5).375 (9.5)
Vent - NPT int, In. (mm).375 (9.5).375 (9.5).375 (9.5)
NOTE:
1. Nominal capacity based on 95°F ambient air and 54°F/44°F water range.
3183
88-100
88-100
2540 x
3183
0-23-50-61-75
88-100
0-27-50-61-75-
88-100
2540 x
3183
2540 x
3183
0-25-50-63-75
88-100
0-25-50-63-75-
88-100
2540 x
3183
2540 x
3183
14AGR 070A through 100AIOMM AGR-1
Electrical Data
Field Wiring
Internal power wiring to the compressors for single and multiple point option are differ ent.
Field wiring must be installed according to unit wiring diagram.
Wiring must comply with all applicable codes and ordinances. Warranty is void if wiring is not in
accordance with specifications. Copper wire is required for all power lead terminations at the unit.
Aluminum or copper can be used for all other wiring.
Standard AGR units have internal power wiring for single point power connection. A single large
power terminal block is provided and wiring within the unit is sized in accordance with the National
Electrical Code. A single field supplied fused disconnect is required. The control transformer with
fuses is factory installed.
If the evaporator heater is on a separate disconnect switch from the main unit power supply, the unit
may be shut down without defeating the freeze protection (115V, 420W heat tape) provided by the
cooler heater.
CAUTION
IOMM AGR-1AGR 070A through 100A15
Table 9, 60 Hz, Single Point Power Electrical Data
1. Unit wire size ampacity (MCA) is equal to 125% of the largest compressor-motor RLA plus
100% of RLA of all other loads in the circuit including the control transformer.
If the control transformer option is furnished, a separate 115v power is not required.
2.
If a separate 115V power supply is used for the control circuit, then the wire sizing amps is 10
3.
amps for all unit sizes.
Recommended power lead wire sizes for 3 conductors per conduit are based on 100% conductor
4.
ampacity in accordance with NEC. Nominal voltage drop has been included. It is recommended
that power leads be kept short. All terminal block connections must be made with copper (type
THW) wire.
“Recommended Fuse Sizes or HACR breaker size” is selected at approximately 150% to 175%
5.
of the largest compressor RLA, plus 100% of all other loads in the circuit.
“Maximum Fuse or HACR breaker size” is selected based on 225% of the largest compressor
6.
RLA, plus 100% of all other loads in the circuit.
The recommended power lead wire sizes are based on an ambient temperature of 86°F (30°C).
7.
Ampacity correction factors must be applied for other ambient temperatures. Refer to the
National Electrical Code Handbook.
Must be electrically grounded according to national and local electrical codes.
8.
9.
The MCA may vary slightly due to motor options such as SpeedTrol, TEFC.
Voltage Limitations:
Within ± 10 percent of unit nameplate rating.
Notes for “Compressor and Condenser Fan Amp Draw”:
1. Compressor RLA values are for wiring sizing purposes o nly and may be higher than nominal
operating current draw at rated capacity.
If unit is equipped with SpeedTrol condenser fan motors, the first motor on each refrigerant
2.
circuit is a single phase, 1hp motor, with a FLA of 2.8 amps at 460 volts, 5.6 amps at 208, 230,
and 575 volts.
Compressor LRA for reduced inrush start are for the first winding of part-winding start only.
3.
4.
If the unit is equipped with SpeedTrol motors, the first motor is a single phase, 1 hp motor, with a
LRA of 7.3 amps at 460 volts, 14.5 amps at 208, 230, and 575 volts.
Notes for “Field Wiring Data”:
1. The standard unit requires a single disconnect to supply electrical power to the unit. Power
supply must either be fused or use an HACR type circuit breaker.
Multiple point power connection for field wiring is available as an option. Two power terminal
2.
blocks are supplied in the unit, one for each system in the unit. Each power terminal block
supplies both compressor and fan motor power for each system. If the control transformer option
is furnished, it is connected to the system #1 power terminal block.
All field wiring to unit power block or optional non-fused disconnect switch must be copper.
3.
4.
All field wire size values given in table apply to 75°C rated wire per NEC. Following NEC
guidelines for other wire ratings such as 90°C.
IOMM AGR-1AGR 070A through 100A19
Figure 9, Typical Field Wiring with Global UNT Controller
20AGR 070A through 100AIOMM AGR-1
Figure 10, Typical Field Wiring Diagram with Mi croTech Controller
IOMM AGR-1AGR 070A through 100A21
Figure 11, Standard Single-Point Connection with FanTrol
22AGR 070A through 100AIOMM AGR-1
Figure 12, Standard Single-Point Connection with Optional SpeedTrol
IOMM AGR-1AGR 070A through 100A23
Figure 13, Unit Control Schematic (2 compressor UNT)