McQuay AEQ-30 Installation Manual

Installation & Maintenance Data IM 502-3
Group: Unit Ventilator Part Number: 106196501 Date: April 2000
Model AED, AEQ AAF-HermanNelson® Classroom Unit Ventilator
©2000 AAF-HermanNelson IM 502-3 (Rev. 4/00)
Wall Sleeve
Receiving Shipment
Before signing the freight bill, be certain that all items have been received and that there is no visible damage. Note any shortages and any damage on all copies of the freight bill. Each Model AEQ unit has been carefully inspected and operated at the factory to verify proper performance. It has been packed in a sturdy carton, was checked by the carrier during loading for shipment, and should arrive in perfect condition. However, if there is damage or any shortages, the purchaser is responsible for filing the necessary claims with the carrier. Concealed damage which was not discovered until after unloading should be reported to the carrier within 15 days after receipt. To help avoid concealed damage, the air conditioners must be shipped, handled and stored right-side up. A formal claim for any shortage or damage must be filed with the carrier within nine (9) months after delivery.
Table 1. (See note below)
UNIT UNIT
MODEL DEPTH WT., LB. HEIGHT WIDTH AEQ-24, AEQ-30 AEQ-36, AEQ-42 AEQ-48, AEQ-54
28 103 31 885 28 84 28 103 31 975 28 96 28 115 31 1075 28 108
AB
Figure A.
A
IMPORTANT:
1. Move only one unit at a time.
2. Do not drop unit.
3. Store in a clean and dry environment.
4. Lift only from designated end.
5. May be stacked maximum of 2 high.
6. To remove unit from skid, follow instructions
under "Uncrating Unit" on page 3.
SHIP WALL SLEEVE
39"
B
See Table 1 for unit weights and dimensions. Forklift type vehicles may be used to unload and move the unit. When using a forklift, it is important that the unit remain banded to its skid and be lifted only from the end designated on the carton. See Figure A. Forks on forklift should be a minimum of 36" long. Move only one unit at a time. Do not drop unit.
Storage
If an air conditioner must be stored prior to installation, find a clean, dry, protected, preferably heated area for storage until the equipment is needed. Keep within the carton during storage or handling.
Preliminary Installation
The location and installation of each Model AEQ unit should be carefully arranged to ensure convenient service access for maintenance and, if necessary, removal of the unit. If the unit has been in storage in an unheated area, care must be taken that the refrigerant circuit has had time to reach proper ambient temperature before attempting operation. The unit consists of two major sections: (1) the unit proper and (2) the wall sleeve. The wall sleeve contains the unit main power disconnect switch located in the wall sleeve junction box. All field connections are made inside the wall sleeve junction box (see page 8). The Model AEQ unit is designed to be installed through an outside wall. Installation will require that the wall sleeve be removed from the unit and installed before the unit is installed. See "Uncrating Unit" section. On many jobs, the louver and wall sleeve are shipped ahead of the unit itself. Installation instructions for these compo­nents are shipped with the individual components, as well as being included in this publication.
Uncrating Unit (Figure A)
The unit should be moved to the location at which it is to be installed before uncrating. Check tagging on unit carton to confirm that the unit is correct for the location. The carton is imprinted with the AAF-HermanNelson trademark which is the "front" or room side of the unit. The end of the carton marked "Truck from this end" should be on the right-hand side when facing the front of the carton.
NOTE: All dimensions are approximate only and are subject to change
without notice. Refer to approved submittal prints for rough-in details and construction purposes and for recommended wall opening size.
Page 2 / IM 502
Wall Opening Preparation
An opening in the outside wall is required to accommodate the wall sleeve and louver. The wall opening must be of sufficient size to allow proper, yet snug, fit of the louver and will depend on the type of wall. If the louver is to be installed in a masonry wall, there should also be a lintel to support the wall above the wall sleeve and louver. The opening should be sleeved to prevent moisture from seeping into the wall interior. Refer to
approved submittal prints for recommended wall opening size.
Remodeling Existing Buildings
If the Model AEQ unit is to be installed in an existing class­room, an opening must be cut in the outside wall to accommo­date the wall sleeve and louver. This is accomplished as follows: First, the outside of the wall is cut with a carborundum or other suitable blade as shown in Figure B. This opening should be slightly larger than the size of the louver supplied with the unit.
Figure B.
The inside wall is then knocked out in the area cut for the wall sleeve as shown in Figure D. If the wall consists of concrete block with brick (or other) veneer, and the louver opening is smaller than the opening the wall sleeve (which is to be recessed), be careful not to knock out more veneer than is necessary.
Figure D.
The completed opening is shown in Figure E. After the open­ing is finished, a lintel must be installed above the opening in masonry walls to support the remaining block and brick.
Next, the inside of the wall is cut as shown in Figure C. If any portion of the wall sleeve is to be recessed into the wall, the opening must be large enough to accommodate the wall sleeve (see Table 1, page 2). It is also possible to have a wall opening smaller than the wall sleeve; in which case, the sleeve will be nonrecessed and all of the unit will remain in the room. Other variations are also possible such as dual louvers, etc.
Figure C.
Figure E.
New Buildings
In new construction, if any portion of the wall sleeve is to be recessed into the wall, the opening must be large enough to accommodate the wall sleeve (see Table 1, page 2). For smaller wall openings the wall sleeve will be nonrecessed and all of the unit will project into the room. In all cases the bottom of the wall opening must be at the same height as the floor line. A lintel must be installed above the opening in masonry walls to support the block and brick.
IM 502 / Page 3
Wall Sleeve Installation
a
a
a
a
a
General — The wall sleeve must be installed before the unit can be placed. The wall sleeve measures 85", 96" or 108"wide by 28" high and may be recessed into the wall up to 11 depth.* Consult the approved AAF-HermanNelson submittal drawings for the job to determine the proper amount of recess,if any, and recommended wall opening size.
The wall sleeve is attached to the unit chassis (weld studs) using 4-nuts and washers, see figure 1.
The AAF-HermanNelson wall sleeve and louver design is based on a "wet sleeve" concept. In brief, this means the design accommodates the penetration of some moisture into the rear section of the wall sleeve with the provision being made for containment and disposal of this moisture to the outdoors.
It is necessary for that portion of the opening between the wall sleeve and the louver to be completely enclosed by the installer to prevent air and water leaks into the building.
Recessed and Nonrecessed Applications
The installing contractor shall do the following:
1. Make sure there is a masonry lintel supporting the wall
above any masonry opening.
2. Frame and seal air- and watertight all openings not enclos-
ed by the wall sleeve.
3. Refer to relevant figures for details of required sealing:
Figure 2 for all applications.
Figures 3 and 4 for recessed wall sleeve applications.
Figures 5 and 6 for nonrecessed wall sleeve applications.
4. Seal watertight both ends and top of wall sleeve to building
at rear flange of wall sleeve.
5. Seal watertight bottom of wall sleeve at rear "D" seal to
building and pitch toward louver bottom channel. Also
fasten cross channel to floor through holes with fasteners
(by others). See Figure 2.
6. The louver must be installed with the drain notches
located at the bottom and the bird screen located on
the unit side. Openings between notches must be free
of mortar or other foreign material for water removal. Refer
to IM 449 for specific details regarding louver installation.
7. Apply rubber stripping or sealant material (by others)
across full length of wall sleeve splitters.
8. If the louver does not butt up against the wall sleeve:
a. Fabricate a horizontal air splitter from galvanized
steel, redwood or some other suitable weather resis­tant material. The width of the air splitters is determined by the width of the wall opening. The depth of the air splitters is determined by the distance between the louver horizontal splitter and the wall sleeve splitters.
b. The horizontal air splitters should have a 1" diameter
drain hole approximately 6" from each end.
c. Install the horizontal air splitters by fastening to the
wall sleeve splitters.
d. Apply rubber stripping or sealant material (by
others) across full length of horizontal air splitters to seal against louver.
9. Permanently seal any remaining air leaks so that, when
finished:
Figure 1.
Chassis
Wall Sleeve
3
8" in
a. There is an airtight separation between the condenser
inlet air, condenser discharge air and the outdoor air inlet;
b. There are no air leaks around the perimeter of the wall
sleeve where it adjoins the wall.
Recessed Applications (See Figures 3 and 4)
The installing contractor shall do the following:
1. Place the wall sleeve into the wall opening and recess it the amount shown on the approved AAF-HermanNelson submittal drawings.
2. Level the wall sleeve horizontally and plumb the wall sleeve vertically.
3. Fasten the wall sleeve securely in place using fasteners through the two knockouts provided on each end.
4. Caulk or seal any space between the wall sleeve and the wall on both the room side and the outdoor side.
Nonrecessed Applications (See Figures 5 and 6)
The installing contractor shall check the following before proceeding:
The wall behind the unit should be smooth and plumb. The seals on the rear of the unit will take up the small ir-
regularities of normal masonry construction.
Furring strips must be installed on irregular walls or walls
with mullions in order to provide a flush surface for the unit to seal against.
Any moldings at the floor/wall line should be omitted
behind the unit.
The installing contractor shall do the following:
1. Apply sealant (by others) to bottom edge at rear of unit top and both end flanges on rear of wall sleeve to provide watertight seal to interior wall of building.
2. Level the wall sleeve horizontally, and plumb the wall sleeve vertically.
3. Fasten the wall sleeve securely in place by: a. Securing it to the floor through the two (2)
holes in the turned out bottom flanges of the wall sleeve at each end, and/or:
b. Securing it to the wall through the two (2)
diameter holes in the turned out vertical flanges of the wall sleeve at each end.
4. a. Panel wall applications should have the wall opening
sleeved to prevent moisture from seeping into the wall interior.
b. If the panel wall is less than 2
should be installed flush to the interior wall and be allowed to extend to the outside as required.
5. Seals on rear of unit must be compressed to provide a watertight seal after installation is complete.
Figure 2. Cross Section Detail of Bottom of
Fasten cross channel to floor thru 1⁄4" holes with appropriate fasteners (by others.) 7 fasteners - AEQ 24, 30 8 fasteners - AEQ 36, 40 9 fasteners - AEQ 44, 48, 54
Wall Sleeve & Intake
A "D" shaped seal is provided at the bottom rear of the Wall Sleeve to provide a watertight seal to the bottom of the unit when installed.
Bottom of Wall Sleeve Cross Channel
1
⁄4" thick, the wall louver
3
⁄8" diameter
3
⁄8"
Seal both ends and top of Wall Sleeve to building, watertight at rear flange.
Bottom channel of Louver
3
⁄16"
Seal watertight bottom of Wall Sleeve at rear "D" seal to building and pitch toward bottom channel of louver as shown.
Page 4 / IM 502
*Unit may also be installed with the full 28" deep cabinet projecting into the room.
IMPORTANT: Opening under Louver must be free of foreign material for water removal.
CAUTION: Sleeves furnished for use with optional heated rear drain will have an electric cord installed along
the length of the wall sleeve splitter. Avoid screw penetration or drilling into this cord when installing the horizontal air splitter. (Model AEQ Only)
Figure 3. Rear View of Recessed Wall Sleeve With Horizontal Air Splitters.
By Others. Wall Sleeve must
be sealed watertight at top and both ends at location shown.
By Others. Seal Horizontal Air Splitters to building at both ends.
By Others. Seal both ends of opening between Wall Sleeve and Louver.
IMPORTANT NOTE: By Others: Attach Horizontal Air Splitters to Wall Sleeve
Splitters as shown. Splitters to have 1" dia. drain hole approx. 6" from each end.
Wall Sleeve Splitter(s) (See Caution Above)
"D" Seal
By Others. Wall Sleeve must be sealed watertight at bottom at location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver. (Figure 2.)
Seal Horizontal Air Splitter(s) to Louver. (By Others)
3
16" Under Intake must be free for water run-off. INTAKE MUST
STAND ON EMBOSSED FEET LOCATED ON BOTTOM.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
Condenser discharge
Condenser inlet
Outdoor air inlet
By Others. Louver must be sealed watertight at top and both ends.
Figure 4. Rear View of Recessed Wall Sleeve Without Horizontal Air Splitters.
By Others. Wall Sleeve must
be sealed watertight at top and both ends at location shown.
By Others. Seal Horizontal Air Splitters to building at both ends.
Wall Sleeve Splitter(s) (See Caution Above)
"D" Seal
By Others. Wall Sleeve must be sealed watertight at bottom at location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver. (Figure 2.)
IMPORTANT NOTE: By Others. Seal Louver to Wall Sleeve at top and bot­tom Wall Sleeve Splitters, and ends.
3
16" Under Intake must be free for water run-off. INTAKE MUST
STAND ON EMBOSSED FEET LOCATED ON BOTTOM.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
By Others. Louver must be sealed watertight at top and both ends.
IM 502 / Page 5
CAUTION: Sleeves furnished for use with optional heated rear drain will have an electric cord installed along
the length of the wall sleeve splitter. Avoid screw penetration or drilling into this cord when installing the horizontal air splitter. (Model AEQ Only)
Figure 5. Rear View of Nonrecessed Wall Sleeve With Horizontal Air Splitters.
By Others. Apply sealant (by others) to bottom edge of unit (not
shown) and to top flange and both end flanges of wall sleeve (as shown.) This must provide a watertight seal to the wall of the building.
By Others. Seal Horizontal Air Splitters to building at both ends.
By Others. Seal both ends of opening between Wall Sleeve and Louver.
IMPORTANT NOTE: By Others: Attach Horizontal Air Splitters to Wall Sleeve
Splitters as shown. Splitters to have 1" dia. drain hole approx. 6" from each end.
Wall Sleeve Splitter(s) (See Caution Above)
Seal Horizontal Air Splitter(s) to Louver.
"D" Seal
By Others. Wall Sleeve must be sealed watertight at bottom at location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver. (Figure 2.)
3
16" Under Intake must be free for water run-off. INTAKE MUST
STAND ON EMBOSSED FEET LOCATED ON BOTTOM.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
Condenser discharge
Condenser inlet
Outdoor air inlet
By Others. Louver must be sealed watertight at top and both ends.
Figure 6. Rear View of Nonrecessed Wall Sleeve Without Horizontal Air Splitters.
By Others. Apply sealant (by others) to bottom edge of unit (not
shown) and to top flange and both end flanges of wall sleeve (as shown.) This must provide a watertight seal to the wall of the building.
By Others. Seal both ends of opening between Wall Sleeve and Louver.
Wall Sleeve Splitter(s)
"D" Seal
By Others. Wall Sleeve must be sealed watertight at bottom at location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver. (Figure 2.)
IMPORTANT NOTE: By Others. Seal Louver to Wall Sleeve at top, Wall Sleeve Splitters and ends.
3
16" Under Intake must be free for water run-off. INTAKE MUST
STAND ON EMBOSSED FEET LOCATED ON BOTTOM.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
By Others. Louver must be sealed watertight at top and both ends.
Page 6 / IM 502
Figure 7.
Louver
Blade
Bottom
Flange
(Drain Holes)
Detail of Notches
Typical Wall Louver
Bird Screen
Fasteners
Demountable
Louver Section
Drain Notch At Bottom
Louver Installation
Factory Mounted
Bird Screen
Information
Labels
Frame
Optional Flanges
Splitter Lines Up With
Wall Sleeve Splitter
Optional Factory Mounted Exterior Grille
Mechanical Fasteners (Number Required Varies With Size of Louver)
28"
(711 mm)
14" ±1⁄8"
Wall Intake
Louver & Grille Detail
21⁄2"
(63.5 mm)
+
+
+
+
+
+
+
+
+
11⁄4"
Optional Flange
See Louver Dimensions
++
+
"W "
+
+
7
8"
The standard louver is an aluminum, vertical, divided blade design complete with bird screen. This louver is also available with flanges and/or with a heavy-duty exterior lattice grille.
1. Figure 7 shows a detail of a typical louver. Before installa­tion, carefully examine the louver and note the location of the bird screen and the notches (drain holes). The louver must be installed with the notches at the bottom and the bird screen toward the unit.
2. Measure the opening to be sure there is adequate clear­ance for the louver around the sides. Observe the opening in relation to the wall sleeve and unit. For proper unit operation, the louver must be centered left to right and top to bottom to the wall sleeve. If the louver is of such a dimension that it extends above, below, or beyond the wall sleeve, then these areas must be blocked off airtight (see Figure 8).
3. If the wall sleeve does not extend into the wall far enough to meet the louver, field fabricated splitter(s) must be provided. The splitter(s) need to extend far enough to engage the louver in order to form a proper seal.
4. Check to see if the horizontal divider on the louver is the same height as the horizontal splitter of the wall sleeve. The louver consists of a frame, which must be permanently mounted in the wall, a demountable center louver section to allow service access to the rear of the unit. To install the louver in the opening, the demountable center section must be in place. This will insure that the frame remains square during installation.
6. Before installing the louver in the opening, place a heavy bead of caulk along the top and two sides of the frame that come in contact with the walls of the opening. Use a flexible, waterproof caulk such as silicone.
7. Once the louver has been placed in the opening, further mechanical fastening may be desired or required. Fasten in a manner appropriate to the installation. Care must be taken if fasteners are to be placed in the frame. If this is necessary, remove the demountable center section by removing the screws that hold it in place. Drill holes in the desired locations and fasten with flat head screws. Be sure these screws do not interfere with the reinstallation of the demountable section. Shims must be placed between the frame and the wall so it won't be distorted. After the frame
Louver Dimensions
USED WITH QUANTITY OF LOUVER
AEQ UNIT SIZE LOUVERS/UNIT SIZE (H X W)
024 or 030 2 28" X 42"
036, 040 2 28" X 48"
044, 048, or 054 2 28" X 54"
024 or 030 1 28" X 84" 036 or 040 1 28" X 96"
044, 048 or 054 1 28" X 108"
Figure 8.
Exaggerated oversize louver or wall opening.
Unit Wall
Sleeve
Shaded area of louver must be blocked off & made air­and watertight, by install­ing contractor.
has been satisfactorily fastened, reinstall the demountable center section and secure with fasteners provided. Once the frame and louver assembly has been installed, run a bead of caulk around the outside perimeter of the frame to seal it watertight. Caution: Do not plug the weep
holes in the bottom of the louver.
Louvers With Flanges
1. If the louver is supplied with flanges, follow steps 1 through 6 above. Additionally, place a bead of caulk on the inside of the top and side flanges that come in contact with the building facade. Do not caulk the bottom flange.
2. Place the louver in the opening and push it tight against the building. Fasten it to the exterior of the building using appropriate fasteners for the installation.
3. Seal the top and two sides with waterproof caulk to make it weathertight. Do not seal the bottom flange. To do so may trap water behind the flange.
IM 502 / Page 7
Electrical Connections
All field wiring should be in accordance with the National Electric Code and applicable local codes. Refer to the wiring diagram furnished with the unit to deter­mine electrical connections required. Refer to Figure 9 for stub-up locations. Refer to pages 12 through 14 for main power connections and field wired con­trols, if any. Check nameplate to verify power supply is correct.
Figure 9. Wall Sleeve With Electric Stub-up From Bottom or Side.
Whenever the electric stub-up is brought in through the floor within the confines of the wall sleeve and any portion of the wall sleeve is recessed into the wall, the conduit must be flush with the floor to permit installation of the wall sleeve. Sufficient space must be left around the conduit to permit the attach­ment of continuing conduit after the wall sleeve is installed. For concrete slabs, it is recommended that this be accom­plished either by sleeving the conduit or by recessing a junction box into the slab.
2.5/1.75" Dia. Knockout
3.0/2.0" Dia. Knockout
Wall Sleeve
Conduit (by others)
Rear edge of wall sleeve
2.5/1.75" Dia. Knockout
3.0/2.0" Dia. Knockout Wall Sleeve
.875" Dia. Knockouts (3)
SW1-Main Power Nonfused “On-Off” Switch (AAF-HermanNelson)
Safety Precaution: Reverse this cover when unit is removed from wall sleeve to cover opening in the end of switch box.
Wall Sleeve Junction Box
5
/8" x 35/8" opening (for main power wiring from wall
sleeve to chassis). Field connection by others.
Control receptacle with plug-in disconnect (AAF­HermanNelson). Leads are provided for wire nut connection to all remote controls.
Stub-up from bottom must be confined in this area.
1
/4"
6
5"
51/2"
.875" Dia. Knockouts (3)
1
/2"
SW1-Main Power Nonfused “On-Off” Switch (AAF-HermanNelson)
Right End
Of Unit
Safety Precaution: Reverse this cover when unit is removed from wall sleeve to cover opening in the end of switch box.
Wall Sleeve Junction Box
Whenever the electric stub-up is brought in through the floor within the confines of the wall sleeve, and any portion of the wall sleeve is recessed into the wall, the conduit must be flush with the floor to permit installation of the wall sleeve. Sufficient space must be left around the conduit to permit the attachment of continuing conduit after the wall sleeve is installed. For concrete slabs, it is recommended that this be accomplished either by sleeving the conduit or by recessing a junction box into the slab.
Conduit (by others)
Rear edge of wall sleeve
Page 8 / IM 502
5
/8" x 35/8" opening (for main power wiring from wall
sleeve to chassis). Field connection by others.
16"
1"
9"
5"
Control receptacle with plug-in disconnect (AAF­HermanNelson). Leads are provided for wire nut connection to all remote controls.
Stub-up through side must be confined to this area: cut in field. Opening must be carefully prepared and gasketed for air tightness.
Right End
Of Unit
Note: These are general instructions. Refer to the AAF­HermanNelson submittal drawings for specific dimensions, unit arrangement, stub-up locations, recommended wall open­ing size, etc.
Unit Placement Before Moving Unit Up To Wall Opening:
1. Confirm unit is correct for the location.
2. Complete the installation of the wall sleeve and air intake louver in accordance with the instructions on pages 4 through 9.
3. For nonrecessed applications, inspect the field applied elastic tape to make sure it will seal tightly to prevent air leaks after unit is installed.
4. Check room air and condenser fan bearings to be sure they are secure (Figures 10 and 12).
5. Check room air and condenser fan shaft coupling set­screws to be sure they are tightened securely to both motor shaft and fan shaft.
6. Rotate the room air and condenser fans to be sure they rotate freely and quietly.
7 Check fan wheel setscrews for tightness.
8. Remove any debris from inside the unit.
Setting the Unit:
Slide the unit up to the wall sleeve aligning the four threaded studs (Figure 13) on the wall sleeve with the holes on each end of the unit. Sliding of this unit to the wall can be made easier with the assistance of Caster Kit P/N - 105629001. A piece of cardboard placed under the unit will make this job easier and prevent marring the floor. (Do not leave cardboard under unit after installation.) The wall sleeve mounting studs should slide through the holes in the unit. Place the washers over the threaded studs and tighten the mounting nuts. Do not draw the nuts up as tight as possible as they may distort the unit and loosen the caulking and wall sleeve from their position. If an adapter collar is used, make sure that the unit, adapter collar and wall sleeve all line up properly.
Figure 10.
ROOM AIR FAN
SHAFT BEARING
OIL CUP
Figure 11.
Oil Here
Caution:
Failure to follow these instructions may rack the unit which can cause the fan or unit to vibrate noisily on startup and appear to be in need of fan balancing. For quiet, smooth unit operation it is important that the unit be square, level and the base solidly supported by the floor, using shims where necessary due to uneven construction in order to prevent distortion of the cabinet. It is
Defrost Condenser Drain Piping It is strongly recommended that the condensate from the heating defrost cycle be disposed of into a building con­densate drain. See Figure 14, page 10 for details. If a building
condensate drain is not used, and the drain line is exposed to freezing temperatures, adequate freeze protection must be furnished.
Oiling
Do not attempt to operate the unit fans until the room air fan shaft bearing has been oiled. Use a high grade SAE 20 or 30 nondetergent oil. A few drops are sufficient. Do not over oil. Refer to Figure 10 for oil point. The fan motor does not require
Figure 12.
Figure 13.
CONDENSER
FAN SHAFT
BEARING
IM 502 / Page 9
Optional Internal Heating Condensate Disposal System (Drainless)
As an option, a "drainless" Model AED unit can be provided. This option has a built-in, automatically controlled internal condensate disposal system that eliminates the need for a condensate drain. This method of disposing of the heating condensate eliminates potential damage from freezing of
condensate and produces beneficial room humidification. If neither a floor drain (shown below) nor a "drainless" Model AED unit is used, AAF-HermanNelson assumes no respon-
sibility for any damage that may be caused from freezing condensate. Whenever the drain line is exposed to freezing
temperatures, adequate freeze protection must be furnished by others.
Figure 14. Heating Condensate Disposal into Building Drain System
Unit End
Compartment
Left End of Unit
(less end of panel)
ROOM DIMENSION DIMENSION
PROJECTION “A” “B”
IN. MM IN. MM IN. MM
165⁄8 422 1 25.4 2 50.8 195⁄8 498 4 102 5 127 217⁄8 556 61⁄4 159 71⁄4 184
28 711 123⁄8 314 133⁄8 340
From Wall To End of
(22.2 mm) O.D. Cooper
Drain Tube (by AAF)
Floor / Wall Line
"B"
7
/8"
1
8
/2"
(216 mm)
"A"
7
(194mm)
11
1
(292mm)
2
5
"
8
Drain tube by others. (Drain tube must not interfere with the damper linkage or caster. Tube must pitch down and must be kinked.
"
3
"
4
10
(264mm)
Building drain must be flush with floor in area shown to permit unit to be installed and removed.
Page 10 / IM 502
End Panel Assembly
The final step of unit installation is attaching the end panels. End panels are required unless the unit has adjoining match­ing cabinets.
1. Refer to Figure 15 for 1 " thick end panel. Attach two (2) Tinnerman nuts to the top edge of the end panel and two (2) to the bottom end of the unit. Align the end panel with the front and top edges of the unit. Attach end panel to the
5
unit using four (4)
⁄32" hex socket head fasteners provided.
2. Refer to Figure 15 for 6" thick end panel. a. Position bracket (YC1934) on wall so angle is 5" from
end of unit and near bottom.
Figure 15. 1" End Panel
b. Mark and drill required hole for device to fasten bracket
to wall (not included). c. Attach bracket to wall. d. Attach two (2) Tinnerman nuts to the top edge of the end
panel and one (1) to the bottom front of the end frame. e. Align the end panel with the front and top edges of the unit.
5
Attach end panel to the unit using three (3)
" hex socket
32
head fasteners provided. Bracket should prevent move-
ment of panel toward the unit when pressure is applied to
the end panel.
Figure 15. 6" End Panel
Bracket
YC 1934
End of Unit
IM 502 / Page 11
Field Wiring Controls, Maximum Outdoor Air Unit
Connector Located in Wall Sleeve Junction Box - Right End
YEL 36 37 BRN
Factory Wiring Furnished Only As Required
BLK WHT RED GRN ORG BLU PNK GRY
904A 910 911
For Further Information See Appropriate Field Wiring Detail
Remote Humidity Sensor Wiring
Day/Night Changeover Control
(Stand-Alone Units Only)
Control Receptacle In Wall Sleeve Junction Box
YEL 36 37
BRN BLK WHT RED GRN ORG
BLU PNK
GRY
Day/Night Changeover (4VA Inrush) Energize To Put Unit In Night Mode
Control Receptacle
Field Connection By Others (Not AAF-HermanNelson) To The Load Side Of SW-1. [(2) Wires Per Pole If Unit Has Electric Heat]
SW-1 - - Main Power “On - Off” Switch
Master/Slave Wiring
Attach Wires From Unit To Unit In Daisy Chain Fashion, In Any Order. See Chart 1 For Correct Wire/Line Voltage Combination. Shields Are To Be Grounded In Each Unit.
YEL 36
37 BRN BLK WHT RED GRN ORG BLU PNK GRY
Control Receptacle In Wall Sleeve Junction Box First Unit
BLU PNK GRY
Ground
1 2 3
SW-1
L1
Main Power Supply (Omit L3 For Single
L2
Phase Applications)
L3
Field Wiring
Network Wiring
Attach Wires From Unit To Unit In Daisy Chain Fashion. In Any Order, See Chart 2 For Correct Wire/Line V oltage Combination. Shields Are To Be Grounded In Each Unit.
YEL 36
37 BRN BLK WHT RED GRN ORG BLU PNK GRY
Control Receptacle In Wall Sleeve Junction Box First Unit
BLU PNK GRY
Ventilation Lockout Control
YEL 36 37
BRN
Control Receptacle In Wall Sleeve Junction Box
BLK WHT RED GRN ORG
BLU PNK
GRY
Exhaust Fan Interlock
YEL 36 37 BRN
Control Receptacle In Wall Sleeve Junction Box
BLK WHT RED GRN ORG BLU PNK GRY
Vent Lockout (4VA Inrush) Energize To Close The Outdoor Air Damper
Exhaust Fan Interlock (4VA Inrush) Energize To Open Outdoor Air Damper
Control Receptacle In Wall Sleeve Junction Box Additional Unit
Control Receptacle In Wall Sleeve Junction Box Last Unit
Chart 1
Wire Mfg.
Belden or
Equivalent
2-Wire 8761 9341
Page 12 / IM 502
BLU PNK GRY
Mfg.’s Wire No.
0-300V 301-600V
Chart 2
Wire Mfg.
Belden or
Equivalent
Control Receptacle In Wall Sleeve Junction Box Additional Unit
BLU PNK GRY
Control Receptacle In Wall Sleeve Junction Box Last Unit
2-Wire 8761 9341
To Local Master Panel
Mfg.’s Wire No.
0-300V 301-600V
Pneumatic Day/Night ChangeoverControl
(Stand-Alone Units Only)
YEL 36
Control Receptacle In Wall Sleeve Junction Box
37 BRN
Pneumatic/Electric
BLK
Switch.
WHT
Close Contacts To Put Unit In
RED
Night Mode. (24VAC,
GRN
Class II, 1 AMP)
ORG BLU
PNK GRY
Wall Mounted Room Air Sensor
Two (2) Mounting Screws (Furnished)
Sensor
American Standard Electrical Box (Not Furnished)
Control Receptacle in Wall Sleeve Junction Box
Main Power To 0 To 301 To
Shielded Wire Manufacturer
Manufacturer Wire No.
Belden
or Equiv.
Dearborn 4-Wire 1061804
4.50"
6.00"
.76"
22 AWG Stranded Wire BLK,WHT, GRN, ORG, BLU, RED)
YEL 36 37 BRN BLK BLK WHT WHT RED RED GRN GRN ORG ORG BLU BLU PINK GRY
Unit (Volts) 300V 600V
4-Wire 8729
2.75"
.280" Dia. (2)
1.38"
Set Point Adjustment
3.28"
Communications Port
Thermometer
.61"
Green LED
Tenant Override Switch
Note: All sensors have black (common) + white (thermistor sensor) + red (LED) wires. Orange and blue wires are provided for communications and a green wire for tenant override and set point adjustment.
`Wire Color Purpose
Black Common White Thermistor
Red LED
Green* Setpoint Adjustment and Tenant Override
Orange** Communications
Blue** Communications
Note:
* Connect this wire only if setpoint adjustment and tenant override
feature are used.
** Only connect these wires if a PC for troubleshooting the controller
from the sensor is used.
See IM 629 for specific sensor installation instruction.
IM 502 / Page 13
Product Warranty
McQuay International, hereinafter referred to as the "Com­pany," warrants that it will provide, at the Company's option, either free replacement parts or free repair of component parts in the event any product manufactured by the Company and used in the United States and Canada proves defective in material or workmanship within twelve (12) months from initial start-up or eighteen (18) months from the date shipped by the Company, whichever comes first. For additional consider­ation, the Company warrants that for four (4) years following the initial warranty period it will provide, at the Company's option, free replacement parts for the motor-compressor, or, free replacement for any integral component of the motor­compressor which proves defective in material or workman­ship. For an additional consideration, the Company warrants that for nine (9) years following the initial warranty period it will provide free replacement of the heat exchanger in gas-fired or oil-fired furnaces which proves defective in material and workmanship. (Extended warranties for motor-compressors and heat exchangers are not applicable unless separately purchased.)
To obtain assistance under this parts warranty, extended motor-compressor warranty, or extended heat exchanger warranty, simply contact the selling agency. To obtain infor­mation or to gain factory help for AAF-McQuay Incorporated, and AAF-HermanNelson brandnames, contact McQuay In­ternational, Warranty Claims Department, 4900 Technology Park Boulevard, Auburn, New York 13021-9030, telephone (315) 253-2771.
This warranty constitutes the buyer's sole remedy. It is given In lieu of all other warranties. There is no implied warranty merchantability or fitness for a particular pur-
pose. In no event and under no circumstances shall the Company be liable for incidental or consequential dam­ages, whether the theory be breach of this or any other warranty, negligence or strict tort.
This parts warranty and the optional extended warranties extend only to the original user. Of course, abuse, misuse, or alteration of the product in any manner voids the Company's warranty obligation. Neither the parts or extended warranty obligates the Company to pay any labor or service costs for removing or replacing parts, or any shipping charges. Refrig­erants, fluids, oils, and expendable items such as filters are not covered by this warranty.
The extended warranties apply only to integral components of the motor-compressor or heat exchanger, not to refrigerant controls, electrical controls, or mechanical controls, or to failures caused by failure of those controls.
Attached to this warranty is a requirement for equipment containing motor-compressors and/or furnaces to report start­up information. The registration form accompanying the prod­uct must be completed and returned to the Company within ten (10) days of original equipment start-up. If that is not done, the date of shipment shall be presumed to be the date of start­up and the warranty shall expire twelve (12) months from that date.
No person (including any agent, salesman, dealer or distribu­tor) has authority to expand the Company's obligation beyond the terms of this express warranty, or to state that the performance of the product is other than that published by the Company.
Page 14 / IM 502
NOTES
IM 502 / Page 15
AAF-HermanNelson 4900 Technology Park Boulevard, Auburn, NY 13021-9030 USA, (315) 253-2771
Printed on recycled paper containing at least 10% post-consumer material.
©2000 AAF-HermanNelson
Page 16 / IM 502-3 (Rev. 4/00)
Loading...