Wall Sleeve
Receiving Shipment
Before signing the freight bill, be certain that all items have
been received and that there is no visible damage. Note any
shortages and any damage on all copies of the freight bill.
Each Model AEQ unit has been carefully inspected and
operated at the factory to verify proper performance. It has
been packed in a sturdy carton, was checked by the carrier
during loading for shipment, and should arrive in perfect
condition. However, if there is damage or any shortages, the
purchaser is responsible for filing the necessary claims with
the carrier. Concealed damage which was not discovered
until after unloading should be reported to the carrier within 15
days after receipt. To help avoid concealed damage, the air
conditioners must be shipped, handled and stored right-side
up. A formal claim for any shortage or damage must be filed
with the carrier within nine (9) months after delivery.
Table 1. (See note below)
UNIT UNIT
MODEL DEPTH WT., LB. HEIGHT WIDTH
AEQ-24, AEQ-30
AEQ-36, AEQ-42
AEQ-48, AEQ-54
28 103 31 885 28 84
28 103 31 975 28 96
28 115 31 1075 28 108
AB
Figure A.
A
IMPORTANT:
1. Move only one unit at a time.
2. Do not drop unit.
3. Store in a clean and dry environment.
4. Lift only from designated end.
5. May be stacked maximum of 2 high.
6. To remove unit from skid, follow instructions
under "Uncrating Unit" on page 3.
SHIP WALL SLEEVE
39"
B
See Table 1 for unit weights and dimensions. Forklift type
vehicles may be used to unload and move the unit. When
using a forklift, it is important that the unit remain banded to
its skid and be lifted only from the end designated on the
carton. See Figure A. Forks on forklift should be a minimum of
36" long. Move only one unit at a time. Do not drop unit.
Storage
If an air conditioner must be stored prior to installation, find a
clean, dry, protected, preferably heated area for storage until
the equipment is needed. Keep within the carton during
storage or handling.
Preliminary Installation
The location and installation of each Model AEQ unit should
be carefully arranged to ensure convenient service access for
maintenance and, if necessary, removal of the unit.
If the unit has been in storage in an unheated area, care must
be taken that the refrigerant circuit has had time to reach
proper ambient temperature before attempting operation.
The unit consists of two major sections: (1) the unit proper and
(2) the wall sleeve. The wall sleeve contains the unit main
power disconnect switch located in the wall sleeve junction
box. All field connections are made inside the wall sleeve
junction box (see page 8).
The Model AEQ unit is designed to be installed through an
outside wall. Installation will require that the wall sleeve be
removed from the unit and installed before the unit is installed.
See "Uncrating Unit" section.
On many jobs, the louver and wall sleeve are shipped ahead
of the unit itself. Installation instructions for these components are shipped with the individual components, as well as
being included in this publication.
Uncrating Unit (Figure A)
The unit should be moved to the location at which it is to be
installed before uncrating. Check tagging on unit carton to
confirm that the unit is correct for the location. The carton is
imprinted with the AAF-HermanNelson trademark which is the
"front" or room side of the unit. The end of the carton marked
"Truck from this end" should be on the right-hand side when
facing the front of the carton.
NOTE: All dimensions are approximate only and are subject to change
without notice. Refer to approved submittal prints for rough-in details
and construction purposes and for recommended wall opening size.
Page 2 / IM 502
Wall Opening Preparation
An opening in the outside wall is required to accommodate the
wall sleeve and louver. The wall opening must be of sufficient
size to allow proper, yet snug, fit of the louver and will depend
on the type of wall. If the louver is to be installed in a masonry
wall, there should also be a lintel to support the wall above the
wall sleeve and louver. The opening should be sleeved to
prevent moisture from seeping into the wall interior. Refer to
approved submittal prints for recommended wall opening
size.
Remodeling Existing Buildings
If the Model AEQ unit is to be installed in an existing classroom, an opening must be cut in the outside wall to accommodate the wall sleeve and louver. This is accomplished as follows:
First, the outside of the wall is cut with a carborundum or other
suitable blade as shown in Figure B. This opening should be
slightly larger than the size of the louver supplied with the unit.
Figure B.
The inside wall is then knocked out in the area cut for the wall
sleeve as shown in Figure D. If the wall consists of concrete
block with brick (or other) veneer, and the louver opening is
smaller than the opening the wall sleeve (which is to be
recessed), be careful not to knock out more veneer than is
necessary.
Figure D.
The completed opening is shown in Figure E. After the opening is finished, a lintel must be installed above the opening in
masonry walls to support the remaining block and brick.
Next, the inside of the wall is cut as shown in Figure C. If any
portion of the wall sleeve is to be recessed into the wall, the
opening must be large enough to accommodate the wall
sleeve (see Table 1, page 2). It is also possible to have a wall
opening smaller than the wall sleeve; in which case, the sleeve
will be nonrecessed and all of the unit will remain in the room.
Other variations are also possible such as dual louvers, etc.
Figure C.
Figure E.
New Buildings
In new construction, if any portion of the wall sleeve is to be
recessed into the wall, the opening must be large enough to
accommodate the wall sleeve (see Table 1, page 2). For
smaller wall openings the wall sleeve will be nonrecessed and
all of the unit will project into the room. In all cases the bottom
of the wall opening must be at the same height as the floor line.
A lintel must be installed above the opening in masonry walls
to support the block and brick.
IM 502 / Page 3
Wall Sleeve Installation
General — The wall sleeve must be installed before the unit
can be placed. The wall sleeve measures 85", 96" or 108"wide
by 28" high and may be recessed into the wall up to 11
depth.* Consult the approved AAF-HermanNelson submittal
drawings for the job to determine the proper amount of
recess,if any, and recommended wall opening size.
The wall sleeve is attached to the unit chassis (weld studs)
using 4-nuts and washers, see figure 1.
The AAF-HermanNelson wall sleeve and louver design is
based on a "wet sleeve" concept. In brief, this means the
design accommodates the penetration of some moisture into
the rear section of the wall sleeve with the provision being
made for containment and disposal of this moisture to the
outdoors.
It is necessary for that portion of the opening between the
wall sleeve and the louver to be completely enclosed by the
installer to prevent air and water leaks into the building.
Recessed and Nonrecessed Applications
The installing contractor shall do the following:
1. Make sure there is a masonry lintel supporting the wall
above any masonry opening.
2. Frame and seal air- and watertight all openings not enclos-
ed by the wall sleeve.
3. Refer to relevant figures for details of required sealing:
Figure 2 for all applications.
Figures 3 and 4 for recessed wall sleeve applications.
Figures 5 and 6 for nonrecessed wall sleeve applications.
4. Seal watertight both ends and top of wall sleeve to building
at rear flange of wall sleeve.
5. Seal watertight bottom of wall sleeve at rear "D" seal to
building and pitch toward louver bottom channel. Also
fasten cross channel to floor through holes with fasteners
(by others). See Figure 2.
6. The louver must be installed with the drain notches
located at the bottom and the bird screen located on
the unit side. Openings between notches must be free
of mortar or other foreign material for water removal. Refer
to IM 449 for specific details regarding louver installation.
7. Apply rubber stripping or sealant material (by others)
across full length of wall sleeve splitters.
8. If the louver does not butt up against the wall sleeve:
a. Fabricate a horizontal air splitter from galvanized
steel, redwood or some other suitable weather resistant material. The width of the air splitters is determined
by the width of the wall opening. The depth of the air
splitters is determined by the distance between the
louver horizontal splitter and the wall sleeve splitters.
b. The horizontal air splitters should have a 1" diameter
drain hole approximately 6" from each end.
c. Install the horizontal air splitters by fastening to the
wall sleeve splitters.
d. Apply rubber stripping or sealant material (by
others) across full length of horizontal air splitters
to seal against louver.
9. Permanently seal any remaining air leaks so that, when
finished:
Figure 1.
Chassis
Wall Sleeve
3
⁄8" in
a. There is an airtight separation between the condenser
inlet air, condenser discharge air and the outdoor air
inlet;
b. There are no air leaks around the perimeter of the wall
sleeve where it adjoins the wall.
Recessed Applications (See Figures 3 and 4)
The installing contractor shall do the following:
1. Place the wall sleeve into the wall opening and recess it
the amount shown on the approved AAF-HermanNelson
submittal drawings.
2. Level the wall sleeve horizontally and plumb the wall sleeve
vertically.
3. Fasten the wall sleeve securely in place using fasteners
through the two knockouts provided on each end.
4. Caulk or seal any space between the wall sleeve and the
wall on both the room side and the outdoor side.
Nonrecessed Applications (See Figures 5 and 6)
The installing contractor shall check the following before
proceeding:
The wall behind the unit should be smooth and plumb.
The seals on the rear of the unit will take up the small ir-
regularities of normal masonry construction.
Furring strips must be installed on irregular walls or walls
with mullions in order to provide a flush surface for the unit
to seal against.
Any moldings at the floor/wall line should be omitted
behind the unit.
The installing contractor shall do the following:
1. Apply sealant (by others) to bottom edge at rear of unit
top and both end flanges on rear of wall sleeve to provide
watertight seal to interior wall of building.
2. Level the wall sleeve horizontally, and plumb the wall
sleeve vertically.
3. Fasten the wall sleeve securely in place by:
a. Securing it to the floor through the two (2)
holes in the turned out bottom flanges of the wall
sleeve at each end, and/or:
b. Securing it to the wall through the two (2)
diameter holes in the turned out vertical flanges of the
wall sleeve at each end.
4. a. Panel wall applications should have the wall opening
sleeved to prevent moisture from seeping into the wall
interior.
b. If the panel wall is less than 2
should be installed flush to the interior wall and be
allowed to extend to the outside as required.
5. Seals on rear of unit must be compressed to provide a
watertight seal after installation is complete.
Figure 2. Cross Section Detail of Bottom of
Fasten cross channel to floor
thru 1⁄4" holes with appropriate
fasteners (by others.)
7 fasteners - AEQ 24, 30
8 fasteners - AEQ 36, 40
9 fasteners - AEQ 44, 48, 54
Wall Sleeve & Intake
A "D" shaped seal is
provided at the bottom
rear of the Wall Sleeve
to provide a watertight
seal to the bottom of
the unit when installed.
Bottom of Wall Sleeve
Cross Channel
1
⁄4" thick, the wall louver
3
⁄8" diameter
3
⁄8"
Seal both ends and top of
Wall Sleeve to building,
watertight at rear flange.
Bottom channel
of Louver
3
⁄16"
Seal watertight bottom of Wall Sleeve at rear "D" seal
to building and pitch toward bottom channel of louver
as shown.
Page 4 / IM 502
*Unit may also be installed with the full 28" deep cabinet projecting into the room.
IMPORTANT: Opening under Louver must be
free of foreign material for water removal.
CAUTION: Sleeves furnished for use with optional heated rear drain will have an electric cord installed along
the length of the wall sleeve splitter. Avoid screw penetration or drilling into this cord when
installing the horizontal air splitter. (Model AEQ Only)
Figure 3. Rear View of Recessed Wall Sleeve With Horizontal Air Splitters.
By Others. Wall Sleeve must
be sealed watertight at top and
both ends at location shown.
By Others. Seal Horizontal
Air Splitters to building at
both ends.
By Others. Seal both ends of
opening between Wall Sleeve
and Louver.
IMPORTANT NOTE:
By Others: Attach Horizontal Air Splitters to Wall Sleeve
Splitters as shown. Splitters to have 1" dia. drain hole
approx. 6" from each end.
Wall Sleeve Splitter(s)
(See Caution Above)
"D" Seal
By Others. Wall Sleeve must be sealed
watertight at bottom at location shown.
Refer to cross section detail of bottom
of Wall Sleeve and Louver.
(Figure 2.)
Seal Horizontal Air Splitter(s)
to Louver. (By Others)
3
⁄16" Under Intake must be free for water run-off. INTAKE MUST
STAND ON EMBOSSED FEET LOCATED ON BOTTOM.
By Others. Building must be sealed between Wall
Sleeve and under Louver for water run-off. Pitch
toward Louver.
Condenser discharge
Condenser inlet
Outdoor air inlet
By Others. Louver must be sealed
watertight at top and both ends.
Figure 4. Rear View of Recessed Wall Sleeve Without Horizontal Air Splitters.
By Others. Wall Sleeve must
be sealed watertight at top and
both ends at location shown.
By Others. Seal Horizontal
Air Splitters to building at
both ends.
Wall Sleeve Splitter(s)
(See Caution Above)
"D" Seal
By Others. Wall Sleeve must be sealed
watertight at bottom at location shown.
Refer to cross section detail of bottom
of Wall Sleeve and Louver.
(Figure 2.)
IMPORTANT NOTE: By Others. Seal
Louver to Wall Sleeve at top and bottom Wall Sleeve Splitters, and ends.
3
⁄16" Under Intake must be free for water run-off. INTAKE MUST
STAND ON EMBOSSED FEET LOCATED ON BOTTOM.
By Others. Building must be sealed between Wall
Sleeve and under Louver for water run-off. Pitch
toward Louver.
By Others. Louver must be sealed
watertight at top and both ends.
IM 502 / Page 5