McQuay AEQ024 User Manual

AAF®-HermanNelson® Self-Contained Air Source Heat Pump Unit Ventilator
Model AEQ Size 024 (2 Ton) to 054 (4.5 Ton) R-410A Refrigerant, MicroTech II™ (“F” V intage)
C
Contents
Introduction
Nomenclature ...............................................................................3
AAF-HermanNelson Self-Contained Air Source Heat Pump
Classroom Unit Ventilator .............................................................4
Model AEQ Air Source Heat Pump Self-Contained Unit Ventilato
.....................................................................................................5
Features & Benets
GentleFlo Delivery ........................................................................6
The Right Amount of Fresh Air and Cooling .................................7
Precise Temperature and Dehumidication Control .....................7
Low Installation Costs ..................................................................8
Low Operating Costs ....................................................................9
Easy To Maintain ........................................................................10
Built To Last ................................................................................12
MicroTech II Controls
MicroTech II Controls For Superior Performance,
Easy Integration ................................................................... 13-18
MicroTech II Sensors & Control Component Locations ........ 19-21
Accessories
Time Clock ..................................................................................22
ServiceTools ...............................................................................22
Wall Louvers & Grilles ................................................................23
VentiMatic Shutter Room Exhaust Ventilation ...................... 24-25
Storage Cabinets, Sink & Bubbler ........................................ 26-27
End Panels .................................................................................27
Unit Selection
Quick Selection Procedure ................................................... 40-43
Selection Procedure ...................................................................44
Engineering Data .................................................................. 45-46
Electrical Data - Size 024 and 036 .............................................45
Electrical Data - Size 044 and 054 .............................................46
General Unit Data - Model AEQ .................................................46
Details & Dimensions
Unit Size 024 ..............................................................................47
Unit Size 036 ..............................................................................48
Unit Sizes 044 & 054 ..................................................................49
End Panels .................................................................................50
Wall Intake Louvers & Grilles .....................................................51
VentiMatic Shutter Assembly ......................................................52
Sink & Bubbler Cabinet ..............................................................53
Utility Compartment & Filler Sections ........................................54
Wiring Diagrams
MicroTech II Wiring - Typical.......................................................55
Typical Wall Senors ....................................................................56
External Input Wiring ..................................................................56
External Output Wiring-Single Unit .............................................57
External Output Wiring-Multiple Units ........................................57
Guide Specications
AAF-HermanNelson Self-Contained Air Source Heat Pump Unit
Ventilator Model AEQ Guide Specications ......................... 58-61
Applications Considerations
Why Classrooms Overheat .................................................. 28-31
Meeting IBC Seismic Requirements ...........................................32
ASHRAE Cycle II ........................................................................33
Unit Installation Considerations ............................................ 34-36
Wall Sleeve Arrangements ................................................... 37-39
C
McQuay is a registered trademark and MicroTech II, Digital Ready, GentleFlo, ServiceTools,
Microsoft is a registered trademark and Windows is a trademark of Microsoft Corporation.
and Protocol Selectability are trademarks of McQuay International.
Copyright © 2010 McQuay International. All rights reserved throughout the world.
Introduction
Nomenclature
U AEQ 6 024 C G 12 Z B1 AL 22 G B B 1
Unit Type
U = Unit Ventilator
Product Identier
AEQ = SC - a/c Air Source Heat Pump, Ultra Quiet
Design Series
6 = F Design
Nominal Capacity, cubic feet/minute (cfm)
024 = 24,000 Btuh 036 = 36000 Btuh (Replacement Only) 044 = 44,000 Btuh (Replacement Only) 054 = 54,000 Btuh (Replacement Only)
Voltage
C = 208-60-1 D = 208-60-3 G = 230-60-1 H = 230-60-3 K = 460-60-3
Cooling Options
G = Direct Expansion (DX) H = Direct Expansion (DX) with refrigerant relief valve
Heating Options
12 = Low Electric Heat, 3-Element 13 = High Electric Heat, 6-Element
Hand Orientation [Right (RH) Left (LH)]
Z = Not applicable
Controls (TC = Time Clock, CO2 = CO2 Sensor)
B1 = Basic Stand-Alone w/o TC B2 = Basic Stand-Alone Master w/o TC B3 = Basic Stand-Alone Slave w/o TC B4 = Basic BACnet MS/TP w/o TC B5 = Basic LonMark SCC w/o TC B6 = Basic Metasys N2 Open w/o TC B7 = Basic Stand-Alone w/ TC B8 = Basic Stand-Alone Master w/ TC B9 = Basic Stand-Alone w/o TC w/CO2 BA = Basic Stand-Alone Master w/o TC w/CO2 BB = Basic Stand-Alone Slave w/o TC w/CO2 BC = Basic BACnet MS/TP w/o TC w/CO2 BD = Basic LonMark SCC w/o TC w/CO2 BE = Basic Metasys N2 Open w/o TC w/CO2 BF = Basic Stand-Alone w/ TC w/CO2 BG = Basic Stand-Alone Master w/ TC w/CO2 E1 = Expanded Stand-Alone w/o TC E2 = Expanded Stand-Alone Master w/o TC E3 = Expanded Stand-Alone Slave w/o TC E4 = Expanded BACnet MS/TP w/o TC E5 = Expanded LonMark SCC w/o TC E6 = Expanded Metasys N2 Open w/o TC E7 = Expanded Stand-Alone w/ TC E8 = Expanded Stand-Alone Master w/ TC
Product Styles
1 = Product Style 1
Warranty
A = Standard E = Extended X = Special
SKU
B = Standard Delivery C = Ext. Delivery
Power Connection
G = Box w/Switch
Return Air
22 = RA Bottom Front / OA Rear Duct Collar
Discharge
AL = 16-5/8" Unit, Top Bar Grille Discharge
E9 = Expanded Stand-Alone w/o TC w/CO2 EA = Expanded Stand-Alone Master w/o TC w/CO2 EB = Expanded Stand-Alone Slave w/o TC w/CO2 EC = Expanded BACnet MS/TP w/o TC w/CO2 ED = Expanded LonMark SCC w/o TC w/CO2 EE = Expanded Metasys N2 Open w/o TC w/CO2 EF = Expanded Stand-Alone w/ TC w/CO2 EG = Expanded Stand-Alone Master w/ TC w/CO2 L1 = Leading Stand-Alone w/o TC L2 = Leading Stand-Alone Master w/o TC L3 = Leading Stand-Alone Slave w/o TC L4 = Leading BACnet MS/TP w/o TC L5 = Leading LonMark SCC w/o TC L6 = Leading Metasys N2 Open w/o TC L7 = Leading Stand-Alone w/ TC L8 = Leading Stand-Alone Master w/ TC L9 = Leading Stand-Alone w/o TC w/CO2 LA = Leading Stand-Alone Master w/o TC w/CO LB = Leading Stand-Alone Slave w/o TC w/CO LC = Leading BACnet MS/TP w/o TC w/CO LD = Leading LonMark SCC w/o TC w/CO LE = Leading Metasys N2 Open w/o TC w CO LF = Leading Stand-Alone w/ TC w/CO LG = Leading Stand-Alone Master w/ TC w/CO 44 = Electromech w/2-Pos Damper for Remote T'Stat 45 = Electromech w/2-Pos Damper w/Unit Mtd. ACO 46 = Electromech w/2-Pos Damper w/Unit Mtd. MCO
2
2
2
2
2
2
2
AAF-HermanNelson Model AEQ Unit Ventilator 3
Introduction
AAF-HermanNelson Self-Contained Air Source Heat Pump Unit Ventilator
For more than 89 years, schools have relied on AAF­HermanNelson unit ventilators to keep classrooms comfortable. Students learn more readily in a quiet, well-ventilated environment. That’s why Herman Nelson invented the unit ventilator and why we remain committed to meeting the changing requirements of schools with the highest quality products available.
We realize that keeping expenditures down is a high priority for school administrators and school boards. AAF-HermanNelson unit ventilators are inexpensive to install and operate, and they are designed and built to provide decades of trouble-free service.
Built To Last
Our proven institutional design can withstand the rigors of the classroom environment. It features an extra sturdy chassis and double-wall damper on the inside;
scuff resistant nishes and tamper prevention features
on the outside. In fact, many units installed over 30 years ago continue to provide quiet, reliable classroom comfort.
Heavy Duty Frame Construction
AAF-HermanNelson’s exclusive, unitized welded frame is far superior to the fastener-type construction used by other manufacturers. Loosened fasteners can cause vibration, rattles and sagging panels.
Other design features that promote trouble-free operation and long life include:
A corrosion-resistant, galvanized-steel frame.
Extra-strength, steel-bar discharge grille.
Heavy-gauge-metal cabinet access panels and
doors.
An extra-strength pipe tunnel that stiffens the struc-
ture while adding aerodynamic air ow within the
unit.
Hidden reinforcement that provides additional built-in support for the top section as well as better support for the fan deck assembly.
A rigid exterior that is strong enough to support maintenance personnel without fear of damaging the unit.
Rugged Exterior Finish
The superior nish of the unit ventilator cabinet fosters
long-lasting beauty as well as resistance to abuse and corrosion. We apply the very highest standards at every
step of the nishing process to provide lasting quality:
Exterior cabinet panels are fabricated from high-
quality, furniture grade steel with no sharp edges.
A specially formulated, environmentally friendly, thermosetting urethane powder is applied electro-
statically to the exterior panels. This lm is oven-
cured to provide correct chemical cross-linking and to obtain maximum scuff- and mar-resistance.
The top of the unit is nished with a textured, non-
glare and scuff-resistant, charcoal bronze electro­static paint. End and front panels are available in a pleasing array of architectural colors.
The Oxford brown steel kickplate is coated and baked with a thermosetting urethane powder paint
to blend with oor moldings and provide years of
trouble-free service.
Each unit is painstakingly inspected before box­ing, then encapsulated in a clear plastic bag, surrounded by an extra-heavy-duty cardboard box and secured to a skid to help provide damage-free shipment.
MicroTech II Control For Superior Performance, Easy Integration
AAF-HermanNelson unit ventilators can be equipped with MicroTech II™ unit controllers for superior performance. Factory integrated and tested controller, sensor, actuator and unit options promote quick, reliable
start-up and minimize costly eld commissioning. Our
Protocol Selectability feature provides easy, low-cost integration into most building automation systems. Select BACnet®, LonTalk® or Metasys® N2 Open communications to communicate control and monitoring information to your BAS, without the need for costly
gateways. Unit controllers are LONMARK® certied
with the optional LonWorks® communication module.
R-410A Refrigerant
4 AAF-HermanNelson Model AEQ Unit Ventilator
Introduction
Models AEQ Air Source Heat Pump Self-Contained Unit Ventilator
Our model AEQ is a vertical, oor standing unit that
utilizes refrigerant for cooling and heating. The model AEQ, size 024 is just right for new construction and for
retrot applications. Unit sizes 036, 044 and 054 are for
replacement applications only, not to be installed in new construction projects in accordance with ASHRAE 90.1
Older buildings with baseboard radiant heat or other hydronic heating systems can be easily adapted to work
efciently with the model AEQ unit. The major features
of this model are shown below and described in more detail on the following pages.
1 Welded One-Piece Chassis offers
superior strength, durability, and vibration reduction.
2 Unique Draw-Thru Design provides
uniform air distribution across the coil for even discharge air temperatures.
3 Quiet, Aerodynamic Fans utilize
GentleFlo technology for exception­ally quiet unit operation.
4 Modular Fan Section improves
balance, alignment and simplies
maintenance.
5 Fan Motor Located Out of Air
Stream and away from heating coil
reduces heat exposure to prolong life.
6 Outside Air/Return Air Damper &
Linkage Provides superior mixture of
outdoor air and room air for precise temperature control.
7 MicroTech II Controls provide
superior comfort control and easy integration into the building automa­tion system of your choice.
8 Advanced Heat Transfer Coil de-
sign provides extra capacity.
9 Sturdy Cabinet Construction
includes hidden reinforcement, a non-glare textured surface, and a
tough, scuff- and mar-resistant nish
to stand up to the abuses of a class­room environment.
10 Sectionalized Front Access Pan-
els provide easy access to unit inte-
rior. Panels are easily removed by a single person. Front side panels can be removed while unit is running.
11 Two Hinged Top Access Doors
provide easy access to the motor, electrical, and refrigeration
components.
12 Sampling Chamber for unit-
mounted sensor provides accurate sensing of room temperature.
13 Optional Adjustable Caster (Left
and Right Ends).
14 Insulated Double-Wall Outdoor
Air Damper seals tightly without
twisting.
15 Full-length Air Filter is efcient
and easy to replace. All air deliv-
ered to classroom is ltered.
16 Corrosion Proof Sloped Drain
Pan
17 Tamper Resistant Fasteners on
Access Panels
AAF-HermanNelson Model AEQ Unit Ventilator 5
Features and Benets
GentleFlo Delivery
AAF-HermanNelson unit ventilators are engineered and manufactured to deliver quiet, continuous comfort. We developed our GentleFlo™ air moving system to minimize operating sound levels – even as demands for more fresh air require units to operate longer and work harder. GentleFlo features include:
Fan wheels are large, wide and rotate at a low speed to reduce fan sound levels. They are impact­resistant and carefully balanced to provide consis­tent performance.
Offset, aerodynamic fan wheel blades move air
efciently (Figure 1).
Precision tolerances help reduce ow and pressure
turbulence, resulting in lower sound levels.
Figure 1: GentleFlo Fan Technology
Expanded Discharge Air Opening
Fan housings incorporate the latest logarithmic-
expansion technology for smoother, quieter air ow
(Figure 2).
A large, expanded discharge opening minimizes air resistance, further lowering sound levels.
Modular fan construction contributes to equal outlet velocities and promotes quiet operation.
Fan shafts are of ground and polished steel to mini-
mize deections and provide consistent, long-term
operation.
Fan assemblies are balanced before unit assembly, then tested after assembly (and rebalanced if nec­essary) to provide stable, quiet operation.
Offset Aerodynamic Blades
Logrithmic Expansion Housing
Precision T olerances
Figure 2: GentleFlo Reduces Turbulence
High Minimal Turbulence
Offset Aerodynamic Blades
GentleFlo Fan Blade Design Typical Fan Blade Design
Turbulence
6 AAF-HermanNelson Model AEQ Unit Ventilator
Features and Benets
The Right Amount of Fresh Air and Cooling
AAF-HermanNelson unit ventilators deliver required amounts of fresh air to meet ventilation requirements and added cooling capacity to maintain consistent comfort for students and teachers. Our Economizer Operation, Demand Control Ventilation (DCV) and Part Load, Variable Air options allow you to match classroom comfort requirements even more closely, and reduce operating costs.
This means that you can be condent that your school
is meeting ventilation standards for Indoor Air Quality and that your students are receiving adequate air to be attentive to instruction. At the same time, you are saving money in early morning hours, between classes or after hours when classrooms are heated and cooled but not always fully occupied.
Economizer Operation
It is well recognized that cooling, not heating, is the main thermal challenge in school classrooms. The typical classroom is cooled by outdoor air over half the time, even in cold climates. It is therefore essential
that unit ventilators efciently deliver outdoor air when
classroom conditions call for “free” or economizer cooling.
With AAF-HermanNelson unit ventilators, you can have outdoor air whenever it is needed. Economizer operation is facilitated by the outdoor air damper, which automatically adjusts the above-minimum outside air position to provide free cooling when the outdoor air temperature is appropriate (Figure 3). On units equipped with MicroTech II controls, three levels of economizer control are available (see See “Economizer Modes” on page 14).
Figure 3: Full Economizer Mode
100% Outdoor Air Into Classroom
Part-Load Variable Air Control
Part Load Variable Air control can be used in conjunction with face and bypass damper temperature control to automatically adjust the unit ventilator fan speed based upon the room load and the room temperature. This MicroTech II control option provides higher latent cooling capabilities and quieter operation during non-peak load periods by basing indoor fan speed upon room load. Lower fan speeds in conjunction with our GentleFlo fan technology contributes to a very quiet classroom environment.
Room-temperature PI control loops determine the speed of the fan, which varies according to the room load. It also provides a built-in delay to prevent overshooting for better comfort control. The outdoor air damper’s minimum-air position is adjusted with the fan speed to bring in a constant amount of fresh air.
Precise Temperature and Dehumidi­cation Control
AAF-HermanNelson unit ventilators provide precise
temperature and dehumidication control to keep
students and teachers comfortable while making maximum use of “free” outdoor-air cooling to reduce operating costs. They utilize a draw-thru fan design that contributes to even heat transfer and provides uniform discharge air temperatures into the classroom. MicroTech II control strategies and 2-stage compressor operation, provide precise control of temperature and humidity levels under both part-load and full-load conditions.
Draw-Thru Design For Even Discharge Temperatures
The AAF-HermanNelson Draw-Thru design sets our unit ventilators apart from most competitive models. With this system, fans draw air through the entire heat trans­fer element (Figure 4) rather than blowing it through highly concentrated areas of the coil element. The result is more uniform discharge air temperatures into the
classroom and more efcient unit ventilator operation.
Figure 4: Draw-Thru Design Provides Even Discharge Air
Uniform Discharge Air (Shaded)
Motor
Filter
Room Air Damper
AAF-HermanNelson Model AEQ Unit Ventilator 7
Outdoor Air Damper
Outdoor Air
Fans
Condenser
Features and Benets
Figure 5: Draw-Thru Vs. Blow-Thru Design
Coil
Coil
Room Air Damper
Room Air
AAF-HermanNelson Draw-Thru Design
Outdoor Air Damper
Outside Air
Filter
RA/OA Divider
Room Air
Outside Air
Blow-Thru Design
Low Installation Costs
Perfect For Both New Construction (Size
024) & Retrot Applications
New construction installations are easily accomplished with the AAF-HermanNelson AEQ size 024 air source heat pump unit ventilator because of the avoided added cost and space required for expensive duct work. This is important in existing buildings and also in new construc-
tion where oor-to-oor heights can be reduced, saving
on overall building costs. Further savings can be real­ized because air source heat pump self-contained unit installations use less space than units that require water supply and return piping.
Retrot installations are economical because new units typically t the same space occupied by existing ones.
Built In Flexibility
AAF-HermanNelson unit ventilators include features
that make them easy to set up and recongure as
needed to meet special requirements. These features include:
Built-In Wire Race A built-in metal wire race runs from one end of the unit to the other to provide extra protection for wires and protect them from unit air.
Figure 6: Optional Unit Casters
Left Caster
Counter-clockwise to lower
Clockwise to raise
Casters can be adjusted
Figure 7: Condenser Casters
Condenser casters ease installaiton. Optional unit casters can be adjusted.
Right Caster
Controls Flexibility
Multiple control options—including MicroTech II controls with our Protocol Selectability feature—provide easy, low cost integration of AAF-HermanNelson unit ventila­tors into the building automation system of your choice (See “MicroTech II Controls” on page 13). You can also operate these units individually or in a master-servant
control conguration.
With MicroTech II controls, you can select BACnet, Lon­Talk or Metasys N2 communications to communicate control and monitoring information to your BAS, without the need for costly gateways. Unit controllers are LON­MARK certied with the optional LonWorks communica- tion module.
8 AAF-HermanNelson Model AEQ Unit Ventilator
Features and Benets
Low Operating Costs
Schools consume more than 10% of the total energy expended in the United States for comfort heating and cooling of buildings. As energy costs increase, educa­tors are placed in a difcult position: caught between ris­ing costs, lower budgets and the requirements to raise educational standards.
Fortunately, the technology and the system exists for schools to take control of their energy expenditures while providing a comfortable environment for learning. And that system is the AAF-HermanNelson unit ventilator.
Consider these realities of school environments:
Most heating energy in schools is expended to heat unoccupied spaces. Because lights, computers and students give off considerable heat, occupied spaces require little supplemental heat.
The removal of heat is usually required in occupied classrooms, even when outside temperatures are moderately cold (i.e., 35 to 40°F).
Then consider how AAF-HermanNelson unit ventila­tors, located in each classroom, take advantage of these realities to lower operating costs:
They provide individual classroom control and comfort.
They can be cycled on when the room is occupied and cycled off when it is not.
They bring in fresh air from directly outside the classroom for high indoor air quality.
During most of the school year, they use outdoor air to keep classrooms comfortable without the ex­pense of mechanical cooling.
Figure 8: Energy Savings with Demand Control Ventilation
100%
Energy Savings
with DCV
20%
Unoccupied
DCV's fresh air for indoor air quality
6:00 8:00 10:00 12:00 2:00 4:00 6:00 8:00
School Hours
Cleaning
Unoccupied
After Hours
Occupancy Mode Operation Units can be pro- grammed to operate only sparingly during unoccu­pied periods and at night to conserve energy.
Two-Stage Compressor
Air conditioning units are usually sized for worse case conditions. During high load requirement the unit will operate in high fan speed and high compressor capacity. Most of the time there is not a full load on the compressor. Operation in lower load will be at medium or low fan speeds which will be at the lower displacement compressor stage. The two stage compressor will remain at low speed until more cooling is required. With the two-stage compressor, the unit will run on lower fan speeds most of the time improving comfort through better humidity control and quieter operation, while minimizing issues with over-sizing.
Other units utilizing single stage compressors operate at full compressor capacity all of the time regardless of fan speed.
MicroTech II Control Options Further Reduce Operating Costs
Many of the MicroTech II control options available with AAF-HermanNelson unit ventilators can further reduce operating costs. For example:
Economizer Operation Economizer operation au­tomatically adjusts the above-minimum outside air position to provide free cooling when the outdoor air temperature is appropriate.
Demand Control Ventilation By using CO2 levels to monitor the actual occupancy pattern in a room, the system can allow code-specic levels of out­door air to be delivered when needed without costly over-ventilation during periods of low or intermittent occupancy (Figure 8).
AAF-HermanNelson Model AEQ Unit Ventilator 9
Features and Benets
Easy To Maintain
Fan Deck
The fan deck’s rotating element has one large, self­aligning, oilable end bearing for smoother operation.
Figure 9: Long-Life Bearings
Long Life Bearing
Even “permanently” lubricated motors are supplied with recommended lubrication charts calling for lubrication every seven years. Maintenance instructions of the motor manufacturer should be followed closely.
Figure 11: Fan Deck
Heavy-Duty Discharge Grille
The discharge grille on the top of the unit is made from extra-strength steel bar stock, promoting long life (Figure 10). It can be removed to facilitate cleaning of fans and fan housings.
Figure 10: Heavy-Duty Steel Discharge Grille
Internal Fan Deck Components
Unlike with many competitive models, the motor in AAF-HermanNelson unit ventilators is separate from the fan assembly and is located out of the airstream at the end of the fan shaft—away from the hot coil—for easier maintenance and removal. Locating the motor
away from the coil (Figure 11) has the added benet of
extending motor life. Our direct-coupled motor and self­aligning motor mount facilitate motor change-out. The
motor comes with a molex plug that ts all sizes and further simplies removal.
Aerodynamic Fans
Modular Fan Deck
1/4" Mesh Screens Protects Against Objects Dropping into Fan Housings
Heavy-Duty Discharge Grille
Motor Located Out of Airstream
Filter
10 AAF-HermanNelson Model AEQ Unit Ventilator
Features and Benets
Tamper-Resistant Fasteners
Front panels and top access doors are held in place by tamper-resistant, positive-positioning fasteners. They are quickly removed or opened with the proper tool, but deter unauthorized access to the unit’s interior (Figure
12).
Sectionalized Access Panels and Doors
All units have three separate front panels and hinged top access doors, sized for convenient handling by a single person (Figure 12). The result is easy, targeted access to the component that needs servicing:
Two end panels provide easy access to piping,
temperature control components and the fan switch. Unlike units with full-length front panels, these can be removed without disturbing the normal operation of the unit.
Hinged top access doors provide easy access
into the end compartments to facilitate convenient servicing of the motor, electrical, and refrigeration components.
Center front panel provides easy access to the lter
and the fan shaft bearing on unit sizes 044 and 054.
Filter
Three lter types are offered:
Units come standard with a single-use lter which is
designed to be used once and discarded.
Optional, permanent metal lters are available and
can be removed for cleaning and reused numerous times.
Renewable media lters, which consist of a heavy-
duty, painted-metal structural frame and renewable media.
Figure 13: Easy Access to Filter
Figure 12: Easy Access with Tamper-Resistant Fasteners
Tamper Resistant Fasteners
Tamper Resistant Fasteners
Removable Filter
Discharge Grille
Tamper Resistant Fasteners
Tamper Resistant Fasteners
AAF-HermanNelson Model AEQ Unit Ventilator 11
Features and Benets
Built To Last
Durable, Energy Efcient Fan Motors
AAF-HermanNelson unit ventilators are equipped with 115/60/1 NEMA motors that feature low operating current and wattage (Figure 14).
Figure 14: Energy-Efcient Fan Motor
Energy Efcient NEMA Motor
Decoupled Isolation System
Additional features of these motors include:
Split-capacitor (PSC) design with automatic reset
and thermal-overload protection.
No brushes, contacts or centrifugal starting switch-
es – the most common causes of motor failure.
A built-in, decoupled isolation system to reduce
transmission of vibrations for quieter operation.
A multi-tap, auto-transformer (Figure 15) provides
multiple fan motor speed control through the speed switch. The motor is independent of supply voltage, which allows stocking of one motor (school district­wide) for various voltage applications.
Figure 15: Multi-Tap Auto-Transformer
Additional features include:
Outdoor air dampers are made of galvanized steel to inhibit corrosion, with double-wall welded construction for rigidity and encapsulated insulation (Figure 16). Additional insulation is provided on the exterior of the outdoor air damper blade and on the outdoor air entry portion of the unit.
Figure 16: Outdoor Damper Seals Out Cold Weather
Turned Metal Damper Stop
Wool Mohair End Seal
Additional Insulation
Wool Mohair End Seal
Turned Metal Damper Blade
Full-Length Wool Mohair Damper
Room air dampers are free-oating and designed
to prevent intermittent gusts of cold air from blow­ing directly into the classroom on windy days (Figure 17). They are constructed of aluminum with built-in rigidity. The metal forming technique that is employed resists twisting and incorporates a full­length counter weight for easy rotation. The simple principle of an area exposed to a force is used to automatically close the damper, rather than open it, when gusts of cold air occur.
Figure 17: Room Air Damper Auto-Closed By Wind Gusts
Wind Gust
Durable Damper Design
All dampers in AAF-HermanNelson Unit Ventilators use the turned-metal principle on their long closing edges (Figure 16). Positive sealing is provided by embedding the edge into wool mohair (no metal to metal contact). There are no plastic gaskets to become brittle with time,
sag with heat or age, or require a difcult slot t to seal.
Nylon damper bearings foster quiet, maintenance-free operation.
12 AAF-HermanNelson Model AEQ Unit Ventilator
MicroTech II Controls
MicroTech II Controls For Superior Performance, Easy Integration
AAF-HermanNelson unit ventila­tors equipped with MicroTech II unit controllers can provide supe­rior performance and easy inte­gration into your building automa­tion system of choice. MicroTech II
benets include:
Factory integrated and tested controller, sensor,
actuator and unit options promote quick, reliable
start-up and minimize costly eld commissioning.
High-performance features and advanced control
options can quickly pay for themselves in saved energy costs and more comfortable classrooms.
Select from three control levels: stand-alone, master-servant or network control.
For network control applications, our Protocol Selectability feature provides easy, low-cost integra­tion of AAF-HermanNelson unit ventilators into most building automation systems.
Flexible BAS network communication options guard against controls obsolescence, keeping MicroTech II controls viable for the life of your AAF-HermanNel­son equipment.
Three Control Levels
MicroTech II unit controllers provide the exibility to
operate AAF-HermanNelson unit ventilators on any of three levels:
As stand-alone units, with control either at the unit or from a wall sensor.
In a master-servant relationship, where servant units follow the master unit for some or all functions.
Controlled as part of a network using a centralized building automation system.
Stand-Alone Control
When operating in stand-alone mode, the Micro­Tech II controller performs complete room tempera­ture and ventilation control. Units can be operated in occupied, unoccupied, stand-by, or bypass (tenant override) modes. Occupied/unoccupied changeover can be accomplished:
Manually by a unit-mounted occupied/unoccupied switch.
Automatically by a unit-mounted occupied/unoccu­pied time clock.
Automatically by a remote-mounted time clock that operates unit-mounted day/night relays.
If a school has more than one zone, separate, re­mote time clocks are used to regulate each zone. In this case, the remote-mounted time clock energizes or de-energizes an external, 24-volt or 120-volt control circuit which operates the unit-mounted day/ night relays in that zone.
Master-Servant Control
Designate the master and servant units and we will
factory congure and install the controllers so they are
set up for a local peer-to-peer network between units (leaving only the network wiring between these units to
be eld installed).
Servant units can be eld-congured to be dependent or
independent as follows:
Dependent servant units follow the master unit completely. They are ideal for large spaces that have even loads across the space (such as some libraries).
Independent servant units (default) use master set­points and servant sensors. The servant follows the master unit modes, such as heat or cool, but has
the exibility to provide the conditioning required for
its area within the space. Independent servant units perform better in spaces where loads vary from one area of the space to the other (such as stairwells or cafeterias).
Network Control
MicroTech II unit controllers provide easy integration into your building automation system of choice. All factory-installed options are handled by the unit control-
ler. This simplies the transmission of monitoring and
setpoint data to the building automation system. You select BACnet, LonTalk or Metasys N2 Open
communications to communicate control and monitoring information to your BAS, without the need for costly gateways (see “Optional Communication Modules” on
page 18). Unit controllers are LONMARK certied with
the optional LonWorks communication module. Flexible network communication options via our Proto-
col Selectability feature help you avoid control obsoles­cence over the life of your AAF-HermanNelson equip­ment.
AAF-HermanNelson Model AEQ Unit Ventilator 13
MicroTech II Controls
Control Modes and Functions
AAF-HermanNelson unit ventilators equipped with MicroTech II unit controllers can be programmed to operate in a variety of modes based on the current situation in the room and the status of the unit ventilator. Changes in mode can be triggered manually, via network signals, by sensor readings, or by date and time. External inputs and outputs can be used to change modes, communicate data to network controls or change the functional operation of the unit.
Occupancy Modes
MicroTech II unit controllers can be set up to change modes based on room occupancy. Four different occupancy modes are provided, as described below.
Occupied Mode
This is the normal daytime operation mode. The controller maintains a room set point using the outside air capability and other functions.
Note: For non-school applications, the unit can also
be congured to cycle the fan in response to the room load. In this case, the fan would normally be in the Off Mode until heating or cooling is
required. The outside air damper is always closed
when the fan is off. When the fan starts, the
outside air damper opens to the required position, usually minimum position.
Unoccupied Mode
This is the night setback operating mode, in which the unit responds to a new room set point and cycles to maintain the condition. The fan comes on when heating
or cooling is needed and runs until the load is satised.
The outdoor air damper is closed during this mode.
When a cooling load is satised by a refrigerant system,
the compressor is de-energized and the unit ventilator
indoor fan continues to run for a xed period of time to
remove coldness from the evaporator coil.
Stand By Mode
In this mode, the unit maintains the occupied mode set point temperature with the outdoor air damper closed.
The fan runs continuously unless it is congured to
cycle in response to the load.
Bypass Mode
This is a tenant override operating mode in which the unit is placed back into the Occupied Mode for a predetermined time. The default is 120 minutes. Settings can be made in 1-minute increments from 1 minute to 240 minutes through the Unit Ventilator Service Tool or a network.
Economizer Modes
Economizer operation is facilitated by the outdoor air damper, which automatically adjusts the above­minimum outside air position to provide free cooling when the outdoor air temperature is appropriate. Three levels of economizer control are available:
Basic Economizer Operation:
The MicroTech II controller compares the inside and outside temperatures. If the temperature comparison is satisfactory, then free-air economizer operation is used
to cool the space. Reheat units also come congured
with an indoor humidity sensor.
Expanded Economizer Operation:
In addition to comparing inside and outside temperatures, outdoor relative humidity is measured to calculate outside air enthalpy. Free economizer operation is used to cool the space. This helps to minimize the entrance of humid outside air.
Leading-Edge Economizer Operation:
The MicroTech II controller compares both indoor and outdoor temperatures and indoor and outdoor relative humidities to determine if free economizer operation can cool the space with non-humid outside air. This is a true enthalpy economizer.
Night Purge Mode
Under this mode, the unit is congured to purge the
room space for one hour for various reasons (odor or fume removal, drying, etc.).During Night Purge the outside air damper is open full and the fan is run on high speed. No “normal” heating or cooling takes place (the emergency heat set point is maintained) and the exhaust fan, if the room is so equipped, is signaled to turn on.
Freeze Prevention Mode
This mode helps protect the unit ventilator from freezing air conditions. Control functions vary depending on the type of temperature control used by the unit, as follows:
Emergency Heat Mode
If the unit is left in a mode that does not normally allow heating (such as Off, Fan Only, Cool, or Night Purge) and the room temperature falls below 55°F, the unit will heat the space to above 55°F and then return to the previously set mode of operation. This mode of
operation can be eld congured and/or be disabled.
14 AAF-HermanNelson Model AEQ Unit Ventilator
MicroTech II Controls
External Input Functions
The unit ventilator controller is provided with three (3) binary inputs that allow a single set of dry contacts to be used as a signal to it. Input signal choices are described below. Multiple units can be connected to a single set of dry contacts.
Note: Not all of the functions listed can be used at the
same time. The unit ventilator controller is pro-
vided with conguration parameters that can be adjusted to select which function will be used for
these inputs where multiple functions are indi-
cated below. For wiring examples see installa-
tion manual IM 747: MicroTech II Unit Ventilator
Controller.
Unoccupied Input Signal
This input signals the unit ventilator controller to go into unoccupied or occupied mode. When the contacts close, the unit ventilator controller goes into unoccupied mode; when the contacts open, it goes into occupied mode. Additional variables can affect occupancy mode and override this binary input. See “Occupancy Modes” on page 14.
Dewpoint/Humidity Input Signal (Optional)
This input signals the unit ventilator controller to go
into active dehumidication mode. When the contacts
close (high humidity) the controller will go into active
dehumidication; when the contacts open (low humidity) it will stop active dehumidication.
Remote Shutdown Input Signal
This input signals the unit ventilator controller to go into shutdown mode. When the contacts close, the controller goes into shutdown mode; when the contacts open, it returns to normal operation.
Ventilation Lockout Input Signal
This input signals the unit ventilator controller to close the outdoor air damper. When the contacts close (ventilation lockout signal) the controller closes the outdoor damper; when the contacts open, it returns to normal outdoor damper operation.
Exhaust Interlock Input Signal
This input signals the unit ventilator controller that an exhaust fan within the space has been energized. The controller then repositions the outdoor air damper to a user-adjustable minimum position. When the contacts close (exhaust fan on signal) the controller uses the
value dened by the Exhaust Interlock OA Damper
Min Position Setpoint as the new minimum outdoor air damper position regardless of the indoor air fan speed.
When the contacts open, it returns to normal outdoor damper operation.
External Output Functions
The unit ventilator controller is provided with three (3) binary outputs to perform the functions described below. These are relay type outputs that are intended to be used with signal level voltages only (24 VAC max).
Note: Not all of the functions listed can be used at the
same time. The unit ventilator controller is pro-
vided with conguration parameters that can be adjusted to select which function will be used for
these outputs when multiple functions are indi-
cated below. For wiring examples, see installa-
tion manual IM 747: MicroTech II Unit Ventilator
Controller.
Lights On/Off Signal
This relay output provides one set of NO dry contacts that can be used to signal the operation of the room lights. When the unit ventilator controller is in occupied, standby or bypass occupancy modes, the relay output will signal the lights on (contacts closed); when the controller is in unoccupied occupancy mode the relay output will signal the lights off (contacts open).
Fault Signal
This relay output provides NO, NC, and Common connections that can be used to signal a fault condition. When a fault exists, the unit ventilator controller energizes this relay output. When the fault or faults are cleared, it de-energizes this relay output.
Exhaust Fan On/Off Signal
This relay output provides one set of NO dry contacts that can be used to signal the operation of an exhaust fan. When the outdoor air damper opens more than the Energize Exhaust Fan OA Damper Setpoint, the relay output will signal the exhaust fan on (contacts closed). When the outdoor damper closes below this setpoint, the relay output will signal the exhaust fan off (contacts open).
Auxiliary Heat Signal
This relay output provides one set of NO dry contacts that can be used to operate an auxiliary heat device.
The unit ventilator controller by default is congured to
operate a NO auxiliary heat device (de-energize when heat is required) such as a wet heat valve actuator with a spring setup to open upon power failure. However,
the Auxiliary Heat Conguration variable can be used
to set the controller to use an NC auxiliary heat device (energize when heat is required) such as electric heat.
AAF-HermanNelson Model AEQ Unit Ventilator 15
MicroTech II Controls
Advanced Control Options
MicroTech II controls make possible a number of advanced control options that can quickly pay for themselves in saved energy costs and more comfortable classrooms, as described below.
Part Load Variable Air Control
Part Load Variable Air control can be used to automatically adjust the unit ventilator fan speed based upon the room load and the room-temperature PI control loop. This MicroTech II control option provides higher latent cooling capabilities and quieter operation during non-peak load periods by basing indoor fan speed upon room load.
During low-load or normal operation (about 60% of the time) the fan will operate on low speed. When the load increases to an intermediate demand, the fan will automatically shift to the medium-speed setting. Under near-design or design-load conditions, the fan will operate on high speed. A built-in, 10-minute delay helps minimize awareness of fan speed changes. Low­speed fan operation under normal operating conditions, in conjunction with our GentleFlo fan technology contributes to a very quiet classroom environment.
Demand-Controlled Ventilation (Optional)
AAF-HermanNelson unit ventilators can be equipped to use input from a CO2 controller to ventilate the space
based on actual occupancy instead of a xed design
occupancy. This Demand Controlled Ventilation (DCV) system monitors the amount of CO2 produced by students and teachers so that enough fresh outdoor air is introduced to maintain good air quality. The system is designed to achieve a target ventilation rate (e.g., 15 cfm/person) based on actual occupancy.
By using DCV to monitor the actual occupancy pattern
in a room, the system can allow code-specic levels of
outdoor air to be delivered when needed. Unnecessary over-ventilation is avoided during periods of low or intermittent occupancy.
With DCV you can be condent that your school is
meeting ventilation standards for Indoor Air Quality and that your students are receiving adequate air to be attentive to instruction. At the same time, you are saving money in early morning hours, in between classes, or after hours when classrooms are heated and cooled but not always fully occupied.
Acceptance by Codes and Standards
ASHRAE Standard 62-2004 Ventilation for Indoor Air Quality recognizes CO2 based DCV as a means of con­trolling ventilation based on occupancy. The ASHRAE
standard has been referenced or adopted by most regional and local building codes. This standard refer­ences ventilation on a per-person basis.
Using CO2 control will sometimes lower the absolute amount of outside air delivered into a room but will maintain the per-person rate. For example, if a class­room is designed for 30 students, the ventilation rate is 450 cfm (30 students × 15 cfm/student). However, when there are only ten students in the classroom, the CO2 control will adjust ventilation to 150 cfm (10 students × 15 cfm/student). A minimum base ventilation rate (typically 20% of design levels) is provided when in the occupied mode. This provides outdoor air to offset any interior source contamination while allowing for proper space pressurization.
DX System Control
The unit ventilator controller is congured to operate the
compressor as secondary (mechanical) cooling when economizer cooling is available, and as primary cooling when economizer cooling is not available. Additional DX control features include:
Compressor Envelope:
This helps protect the compressor from adverse operating conditions that can cause damage and or shortened compressor life. It ends compressor
operation if coil temperatures exceed the dened
operating envelope.
Compressor Cooling Lockout:
The unit ventilator controller is congured to lock out
compressor cooling when the outdoor air temperature falls below the compressor cooling lock out setpoint. Below this temperature setpoint only economizer cooling will be available.
Minimum On and Off Time:
The unit ventilator controller is provided with minimum­on and minimum-off timers to prevent adverse compressor cycling (3-minutes default).
Compressor Start Delay Variable:
This variable is intended to be adjusted as part of the start-up procedure for each unit. It is used to prevent multiple unit compressors from starting at the same time after a power failure or after an unoccupied-to-occupied
changeover. Each unit should be congured at start-
up with a slightly different (random) delay, or groups of units should be provided with different delays.
16 AAF-HermanNelson Model AEQ Unit Ventilator
MicroTech II Controls
System Components
The main components of the MicroTech II system are:
The Unit Ventilator Controller (UVC)
The Local User Interface (LUI)
Optional plug-in network communication modules
In addition, unit ventilators equipped with MicroTech II controllers feature factory-mounted sensors and actuators for system control and feedback.
Unit Ventilator Controller
The MicroTech II UVC is a DDC, microprocessor-based controller designed to provide sophisticated comfort control of an economizer-equipped AAF-HermanNelson unit ventilator. In addition to normal operating control,
it provides alarm monitoring and alarm-specic
component shutdown if critical system conditions occur. Each UVC is factory wired, factory programmed and
factory run-tested for the specic unit ventilator model and conguration ordered by the customer.
Figure 18: MicroTech II Control Board
Terminal Connections Plug-In Control Module
Figure 19: User Interface Touch Pad
The User Interface has individual touch-sensitive printed circuit board mounted buttons, and comes with a built-in menu structure (Hidden Key and Password Protected) to change many of the common operating variables.
Four Operating Mode States
Four different user operating mode states can be chosen on the LUI:
Heat: Heating and economizer operation only. Cool: Cooling and economizer operation only. Fan Only: Fan only operation. Auto: The unit automatically switches between heating,
cooling and economizer operation to satisfy the room load conditions. The current unit state is also displayed.
Local User Interface
A built-in LUI touch pad with digital LED Display is located in the right hand compartment below the top right access door. In addition to the Operating Mode States and Fan Functions, the Touch Pad will digitally display:
The room set point temperature.
The current room temperature.
Any fault code for quick diagnostics at the unit.
Four Fan States
Four fan states are provided on all units: high, medium low and Auto speed modulation. The Auto speed function (part load, variable air) varies the fan speed automatically to meet the room load whether the unit is in heating, cooling or economizer mode.
All this is accomplished with a standard, single-speed NEMA frame motor. A built-in 10-minute delay helps minimize awareness of speed changes. During low-load or normal operation (about 60% of the time) the fan will operate at low speed. The low speed operation, along with GentleFlo fan technology, contributes to a very quiet classroom environment.
When the load increases to an intermediate demand, the fan automatically shifts to the medium speed setting. At near-design or design-load conditions the fan will operate on high speed.
With four fan states and GentleFlo fan technology, there is no need to oversize units or worry about uncomfortable conditions.
AAF-HermanNelson Model AEQ Unit Ventilator 17
MicroTech II Controls
Optional Communication Modules
Optional communication modules provide control and monitoring information to your building automation system without the need for costly gateways. Available communication protocols include BACnet, LonTalk and Metasys N2 Open. The communication modules for each are described below.
Figure 20: Typical 2" x 4" Communication Module
BACnet MS/TP Communication Module
This module allows the UVC to inter-operate with systems that use the BACnet (MS/TP) protocol with a conformance level of 3. It meets the requirements of the ANSI/ASHRAE 135-1995 standard for BACnet systems.
LonWorks SCC Communication Module
This module supports the LonWorks SCC (Space
Comfort Communication) prole number 8500-10. Unit controllers are LonMark certied with this optional Lon-
Works communication module.
Figure 21: Wall-Mounted Temperature Sensors
Standard Expanded
Standard Sensor:
This sensor has no remote setpoint adjustment capability.
Expanded Sensor:
This sensor has a remote room setpoint adjustment of ±3°F (±1.5°C) from the room setpoint established on the unit ventilator’s local user interface touch pad. Five temperature settings are provided on each side of center.
Humidity Sensors
On units equipped with humidity sensors, the UVC is
congured to use a 0-100% RH, 0 VDC, capacitive
humidity sensor. Humidity sensors are available as unit­mounted only. The humidity sensors are used with units using an outdoor enthalpy economizer or an indoor/ outdoor enthalpy economizer.
Metasys™ N2 Communication Module
This module provides N2 Open network communication capability to the UVC for communication with Johnson Metasys systems.
Sensors
The UVC is congured to use passive Positive Temperature Coefcient (PTC) unit-mounted and
wall-mounted sensors. These sensors vary their input resistance to the UVC as the sensed temperature changes.
CO2 Sensor for Demand Controlled Ventilation
On units equipped for Demand Controlled Ventilation
(DCV) the UVC is congured to use a 0-2000 PPM,
0-10 VDC, single beam absorption infrared gas sensor. CO2 sensors are available as unit mounted only. An air
collection probe (pitot tube and lter) is installed in the
return air of the unit.
Figure 22: CO2 Sensor For Demand Control Ventilation
Remote Wall-Mounted Temperature Sensors
MicroTech II unit ventilators offer three choices for re­mote wall-mounted room sensors (Figure 20). Each has a tenant override capability and comes with an interna­tional, quick-fastening connection capability.
18 AAF-HermanNelson Model AEQ Unit Ventilator
MicroTech II Controls
MicroTech II Sensors and Component Locations
Figure 23: MicroTech II Sensor and Component Locations
1. MicroTech II Unit Ventilator Controller (UVC): (Located Beneath the Local User Interface Panel). Factory mounted and run tested, microprocessor­based DDC control device capable of complete Standalone unit control, Master/Servant control or incorporated into a building-wide network using an optional plug-in communication module. The UVC contains a microprocessor that is preprogrammed with the application code required to operate the unit. The UVC supports up to 6 analog inputs, 12 binary inputs, and 9 binary outputs. The UVC EXP I/O board supports up to 4 additional analog
AAF-HermanNelson Model AEQ Unit Ventilator 19
inputs and 8 additional binary outputs. Master/Ser-
vant units have the controller factory congured and
installed for a local peer-to-peer network between these units (network wiring between these units needs to be eld installed). Optional network com­munication is provided via plug-in communication modules that connect directly to the UVC.
2. Communication Module (optional): Plug-in net­work communication module that is attached to the UVC via a 12-pin header and 4 locking standoffs. Available communication modules:
MicroTech II Controls
Building Automation and Control Network (BAC­net®) Master Servant/Token Passing (MS/TP) ­Allows the UVC to inter-operate with systems that use the BACnet (MS/TP) protocol with a confor­mance level of 3. Meets the requirements of ANSI/ ASHRAE 135-1995 standard for BACnet systems.
LonWorks® compliant Space Comfort Controller (SCC) – Supports the LonWorks SCC prole num-
ber 8500_10.
Metasys N2® Open – Provides N2 Open network communication capability to the UVC.
3. Local User Interface (LUI): The LUI provides a unit mounted interface which indicates the current unit operating state and can be used to adjust the unit ventilator operating parameters (operating mode, temperature set points, fan speed and occupancy mode). The LUI features a 2-digit display, 7 keys (1 key is hidden), and 9 individual LED indicators. See “Local User Interface” for further details.
4. Tenant Override Switch: Provides a momentary contact closure that causes the unit to enter the “tenant override” operating mode for a set time period (default = 120 minutes).
5. Time Clock (TC) (optional on standalone units only): Factory mounted 7 day/24 hour, digital time
clock with up to twenty (20) programs to sequence the unit ventilator through occupied and unoccupied modes in accordance with a user programmed time schedule.
6. External Signal Connection Plugs: Three (3) multi-pin plugs are factory provided and pre-wired with short wire whips that are capped (they must remain capped if not used).
Provided for eld wiring of :
Remote Wall Mounted Temperature Sensor (op-
tional accessory).
External Input Signals (by others): unoccupied, remote shutdown, ventilation lockout, dew point/ humidity (night time operation), or exhaust interlock signals
External Output Options (by others): lights on/off, fault indication signal, exhaust fan on/off or auxiliary heat signal.
7. Motor Speed Transformer: (Located beneath the Local User Interface Panel). Multi-tap auto-trans­former provides multiple fan motor speed control through the LUI.
8. Unit Main Power “On-Off” Switch (SW1): Discon­nects the main power to the unit for servicing or when the unit is to be shut down for an extended period of time.
9. Fuse(s): Fan motor and controls have the hot line(s) protected by factory installed cartridge type fuse(s).
10. Control Transformer: 75 VA 24-volt NEC Class 2 transformer for 24 volt power supply. (Located behind the motor transformer).
11. Outdoor Air/Return Air Damper Actuator (A1):
Direct coupled, oating point (tristate) actuator that
spring returns the outdoor air damper to the closed position upon a loss of power.
12. Indoor, Direct Expansion (DX) Coil Refrigerant Temperature Sensor – The sensor is installed on
the unit ventilator’s indoor refrigerant coil on the right hand side of the coil “u-bend”. It is used to sense low refrigerant temperatures on the indoor coil.
13. Outdoor, Direct Expansion (DX) Coil Refriger­ant Temperature Sensor - The sensor is installed
on the unit ventilator’s outdoor refrigerant coil on the right hand side of the coil “u-bend”. It is used to sense the refrigerant temperature on the outdoor coil.
14. Room Temperature Sensor (S1): The unit mount­ed sensor is located in the sampling chamber (front, center section) where room air is continuously drawn through for prompt response to temperature changes in the room. A Remote Wall Mounted Temperature Sensor is also available for remote room temperature sensing. (optional accessory).
15. Discharge Air Temperature Sensor (S2): The sensor is located on the second fan from the right to sense discharge air temperatures.
16. Outdoor Air Temperature Sensor (S3): The sen­sor is located in the outdoor air section of the unit before the outdoor air damper. With network appli­cations, the unit mounted sensor can be overridden by a remote sensor through the network.
17. Outdoor Air Humidity Sensor (S8) (optional): Unit mounted humidity sensor for units using Expanded outdoor enthalpy economizer or Lead­ing Edge indoor/outdoor, true enthalpy comparison economizer. The sensor is located in the outdoor air section of the unit before the outdoor air damper. With network applications, the unit mounted sensor can be overridden by a remote sensor through the network.
20 AAF-HermanNelson Model AEQ Unit Ventilator
MicroTech II Controls
18. Room Humidity Sensor (S6) (optional): Unit
mounted humidity sensor for units capable of active
dehumidication or with units using Leading Edge
indoor/outdoor, true enthalpy comparison econo­mizer. The sensor is located in the sampling cham­ber (front, center panel) where room air is continu­ously drawn through for fast response to humidity changes in the room. With network applications, the unit mounted sensor can be overridden by a remote sensor through the network.
19. CO2 Sensor (S7) (optional): Unit mounted, single beam absorption infrared gas sensor with a sensing range of 0 – 2000 ppm and voltage output of 0 to 10 VDC (100 ohm output impedance). The Pitot Tube sensing device is located in the unit ventilator’s return air stream. The optional CO2 sensor is used with the UVC’s Demand Control Ventilation feature to vary the amount of outside air based on actual room occupancy. With network applications, the unit mounted sensor can be overridden by a remote sensor through the network.
Actuators
Outdoor Air/Return Air Damper (OAD) Actuator
The UVC is congured to operate a oating-point (tri-
state) direct-coupled actuator for the outdoor air damp­er. This actuator provides spring-return operation upon loss of power for positive close-off of the outdoor air damper. To determine damper position, the UVC uses
a separate, factory-preset, congurable setting for each
actuator's stroke time.
Figure 25: Outdoor Air Damper Actuator
AAF-HermanNelson Model AEQ Unit Ventilator 21
Accessories
Optional Time Clock for Stand-Alone Units
As an option, stand-alone, non-servant unit ventilators can be factory-equipped with a unit-mounted, digital, 24-hour/7-day time clock with 20 programs (Figure 27). The clock is factory-wired to automatically place the unit into occupied or unoccupied mode based upon its schedule. Features of this clock include:
Large keys with circular programming for easy
schedule setup
An LCD display
Manual 3-way override (On/Auto/Off)
Capacitor backup to retain program memory during
power outages.
Figure 27: Optional Time Clock
ServiceTools™
ServiceTools for MicroTech II Unit Ventilators is a CD containing software for operation on a personal computer. This software provides a visual schematic of the unit, a pictorial representation of the sequence of operation and enables the service technician to:
Monitor equipment operation.
Congure network communications.
Diagnose unit operating problems.
Download application code and congure the unit.
This software is a purchased tool for service technicians and will run on PCs with Windows® 98 (Second Edition), 2000 (SP2), and NT4.0 (SP6) and XP (SP1) operating systems. This tool is highly recommended for startup and servicing. (It may be required for startup and/or servicing, depending upon unit integration and other requirements.) It has no BAS functions, such as scheduling or trending, and it cannot serve as a Work Station Monitoring package.
ServiceTools comes with a service cable having two interface connections:
A 12-pin connection to the main control board.
A 3-pin connection to the optional communication
modules.
22 AAF-HermanNelson Model AEQ Unit Ventilator
Accessories
Wall Louvers & Grilles
The 16-gauge QS 5052 mill nish aluminum louver
frame is divided in half horizontally, with make-up and discharge-air stream sections to reduce air recirculation within the vertical louver blade. The upper half of the louver has a blockoff on the exterior side to increase discharge air velocity and improve the throw of leaving air.
The vertical louver can be ordered with anges that are
attached on the outside of all four sides of the louver, resulting in a vertical dimension of 30" (762 mm). Weep
holes exist behind the bottom ange of the louver. A 1/2"
(13 mm) square aluminum wire mesh (bird screen) is provided on the interior surface of the louver.
The vertical louver is fabricated from 20-gauge QS 5052
mill nish aluminum. The single piece blade has
Figure 28: Typical Wall Louver and Grille
Factory Mounted
Bird Screen
Fasteners
Bird Screen
Frame
Optional Flanges
Louver Blockoff
a turned edge along the entering and leaving surface to reduce visibility of the outdoor coil and fan section, and adds rigidity to the blade. The 72° offset bend near the middle of the blade creates an air-path turn that minimizes moisture carryover, with a total blade depth of
2¼" (57 mm) in direction of airow.
The louver is available in the following colors:
Natural Aluminum nish (paintable QS 5052 Alumi­num)
Autumn Brown - thermosetting urethane powder coat paint electrostatically applied and oven-cured to provide correct chemical cross-linking.
Dark Bronze - thermosetting urethane powder coat paint electrostatically applied and oven-cured to provide correct chemical cross-linking.
Clear Anodized Aluminum nish
Figure 29: Vertical Blade Louver Outside View, Without Flange
Outside View
Condenser Discharge Air
Information Labels
Louver Blade
Bottom Flange
Detail of Notches (Drain Holes)
Mechanical Fasteners (Number Required Varies With Size of Louver)
Drain Notch At Bottom
Optional Factory Mounted Exterior Grille
Condenser Inlet Air
Figure 30: Vertical Blade Louver Inside View, Without Flange
Inside View
Condenser Discharge Air
Condenser Inlet Air
Bird Screen On Side Toward Unit
Louver with weep holes
Bottom
AAF-HermanNelson Model AEQ Unit Ventilator 23
Accessories
VentiMatic™ Shutter Room Exhaust Ventilation
Outdoor air introduced by the unit ventilator must leave the room in some way. In some states, exhaust vents are required by law or code to accomplish this. The VentiMatic Shutter is a more economical solution to the problem.
The VentiMatic shutter is a continuously variable, gravity-actuated room exhaust vent (Figure 33). It operates in direct response to positive static air pressure created when ventilation air is brought into the room by the unit ventilator. It is a “one-way”
shutter that opposes any ow of air into the room.
Figure 33: VentiMatic Shutter
Back (Outdoor Side) Front (Indoor Side)
The VentiMatic Shutter’s ability to exhaust only the amount of air required results in considerable energy savings. In the heating mode, the unit ventilator will be able to bring in only the required percent minimum outdoor air. Unlike systems that rely on powered exhaust, no energy will be wasted heating excess outdoor air. In the cooling mode, the unit ventilator will be able to bring in 100% outdoor air for full natural or free cooling when it is energy effective.
Since it is not powered, VentiMatic Shutter operation is inherently silent. Unlike other non-powered vents, it opens at an extremely low positive pressure (0.005").
Its shutter aps are made of temperature-resistant glass fabric impregnated with silicone rubber for exibility and
long life. This fabric retains its original properties down to -50°F.
VentiMatic Installation Considerations
Figure 34: VentiMatic Shutter Components
Louver ships assembled as one piece
The VentiMatic Shutter should be mounted on the same wall as the unit ventilator. This neutralizes the effect of wind pressure forcing excess air into the room through the unit ventilator louver. That’s because the wind press
air ow that could occur with opposite-wall mounting.
The VentiMatic Shutter is generally mounted on an AAF­HermanNelson wall louver (ordered separately) which is then used for exhaust (Figure 34). For large unit ventilators, two Ventimatic Shutters may be mounted side by side on the same wall louver to adequately promote exhaust air capacity. The size and appearance of wall louvers and grilles used for unit ventilators and for VentiMatic Shutters are identical and present an architecturally coordinated and pleasing installation.
An ideal method of integrating the VentiMatic Shutter with the unit ventilator is to locate the shutter behind a matching open-shelf or closed-shelf storage cabi­net mounted next to the unit ventilator. For example, 48-inch-length wall louver can be accommodated be­hind a 4-foot-high storage cabinet. The cabinet should be ordered with a slotted-type kick plate to provide a concealed exhaust air path to the shutter. This combina-
tion will enable a complete, integrated, energy-efcient
HVAC and room exhaust system
Note: Storage cabinets are provided by others. Contact
your McQuay sales representative for options.
24 AAF-HermanNelson Model AEQ Unit Ventilator
Accessories
Figure 35: VentiMatic Shutter Installation
Louver
VentiMatic Shutter
Steel Shutter Mounting Plate
The VentiMatic shutter as­sembly mounts on the same wall as the unit ventilator louver, to neutralize wind effect.
Outside
Roomside
Building Wall
Closed Shelf Storage Cabinet with Slotted Kickplate
Outside
Exhaust Air
VentiMatic & Louver Assembly behind cabinet.
Flexible Glass Fabric, Silicone-Impregnated Shutter Leaf
Steel Bafe
Leaf Support
Cabinet ­Slotted Kickplate
AAF-HermanNelson Model AEQ Unit Ventilator 25
Accessories
Storage Cabinets, Sink & Bubbler
Note: Storage Cabinets, Sink & Bubbler are provided by
others. Contact your McQuay sales representa-
tive for options.
AAF-HermanNelson storage cabinets are designed to complement our classroom unit ventilators. They are made from furniture-quality, cold-rolled steel and rein­forced for additional strength to withstand the abuse of
a classroom environment. Cabinets are nished with a
durable epoxy powder coating to withstand marring and scratches.
Storage Cabinets
Shelving cabinets feature epoxy powder coated steel tops of charcoal bronze color or laminated tops.
Available in 4 lengths: 24", 36", 48" and 60", in open cabinets or with sliding doors with bottom glide track for good alignment
Optional door locks available
4 heavy-duty leveling legs that allow for 3/4" of verti-
cal adjustment
Sink & Bubbler Cabinet
Sink & bubbler cabinets have a one-piece 18-gauge
stainless steel top with a satin-brushed nish, a raised
front lip, and formed back and end splash boards.
Available in 4 depths for model AEQ; 16-5/8", 19­5/8", 21-7/8" and 28"
Underside of top is fully coated to minimize noise and condensation
Epoxy powder coated to match the Unit Ventilator and other cabinets
Bubbler Bowl provided as option
Figure 36: Typical Unit Ventilator Install with Storage Cabinets Application
Self-Contained Unit Ventilator
A Storage Cabinet, with doors B Corner Filler Section
C Storage Cabinet with shelves, without doors D Sink and Bubbler, with doors E Utility Compartment F 1" End Panel
26 AAF-HermanNelson Model AEQ Unit Ventilator
Accessories
Utility Compartments
Note: Utility Compartments are provided by others.
Contact your McQuay sales representative for
options.
Utility Compartments can be used as spacing between cabinets or walls and to provide added service access.
Available in standard lengths of 18" and 24"
Epoxy powder coated steel tops of Charcoal Bronze
paint or laminated top
Figure 37: Utility Compartment
1/4"- 20 × 1/2" Screws
1/4" Nuts
T extured Metal Top
Figure 38: 1" End Panel
16⅝" Unit
Projection
1/4"- 20 Tinnerman Nut, Clip over Lower Hole in Unit Base
Figure 39: 6" End Panel
1/4"- 20 × 1/2" Screw
Tinnerman Nut, Clip on End Panel
Steel Kickplate
1" End Panel
1/4"- 20 × 1/2" Screw
1/4" Nuts
1/4"- 20 × 1/2" Screws
End Panels
One-inch end panels are typically used to nish off stand-alone oor units (Figure 40). Six-inch end
panels with kick plates can be used to provide extra space needed for piping (Figure 41). All end panels are individually wrapped in plastic and boxed to help prevent damage during construction.
16⅝" Unit
Projection
1/4"- 20 Tinnerman Nut, Clip over Lower Hole in Unit Corner Bracket
1/4"- 20 × 1/2" Screw & 1/4" Flat Washer
Tinnerman Nut, Clip on End Panel
Angle Bracket Welded for Rigidity
5"
End of Unit
Oxford Brown Kickplate, Factory Assembled to Base of End Panel
Bracket YC1934
6" End Panel
AAF-HermanNelson Model AEQ Unit Ventilator 27
Application Considerations
Possible Heat Gain From
Why Classrooms Overheat
Overheated classrooms occur every day in schools in every area of the country. The most serious result is their detrimental effect on students’ ability to concentrate and learn. Research has determined that the ability to learn and retain knowledge decreases rapidly as the temperature exceeds recommendations. Overheated rooms also represent wasted fuel, resulting in excessive operating costs.
Correcting an overheating problem in an existing
building is very difcult and expensive. It calls for
redesign and alteration of the heating and ventilating system, necessitating considerable renovation. This potential problem should be recognized, understood and planned for when heating and ventilating systems are designed for new and existing buildings.
Schools Have Special Needs
Schools have unique heating and ventilating needs, in large part because of their variable occupancy and usage patterns. Fewer cubic feet of space is provided per student in a school building than in any other type of commercial or public building. School classrooms
are typically occupied only six hours a day, ve days a
week, for only three-fourths of the year, with time out for vacations. All in all, this represents approximately 15% of the hours in a year that a classroom is occupied.
To understand the overheating problem in schools, one
must rst realize that the excess heat comes from what
is commonly termed “uncontrolled heat sources.” To gain some perspective on how this affects heating and cooling decisions, let’s take a look at a typical classroom in the northern section of the midwestern United States.
Suppose we have a classroom that is 24 by 38 feet with 10-foot ceilings and 100 square feet of window area along the outside wall. At an outside temperature of 0°F and a desired room temperature of 72°F, let’s assume the normal amount of heat loss from the room to the outside is 55,000 BTUs per hour.
As the outside temperature changes, so does the amount of heat that the room loses. This is represented in Figure 40 by Room Heat Loss Line A, which ranges from 55,000 BTU per hour at 0°F outside air temperature to zero BTU at 70°F. Obviously, if the
Figure 40: Heat Gain vs. Heat Loss In Occupied
A
60,000
50,000
40,000
30,000
20,000
Room Heat Loss, BTU/HR
10,000
-10 010203040506070
ROOM HEAT LOSS LINES
B
C
D
Outside Air Temperature, °F
Temperature On Room Heat Loss Line Above Which Cooling Is Always Required
10,000 BTU/HR
}
Sun, Direct & Reflected
8,500 BTU/HR
}
Heat Gain From Lights
7,800 BTU/HR
}
Heat Gain From Students
Note: As this chart illustrates, even in very cold weather
an occupied classroom is more likely to require cooling than heating.
Heat From Students
Body heat generated by students in a classroom is one of the three primary sources of uncontrolled heat. In a typical classroom of 30 students, the amount of heat given off at all times will vary according to factors such as age, activity, gender, etc. A conservative estimate is 260 BTU per hour per pupil. Multiply this by 30 and you get a total of 7,800 BTU per hour added to the room by the students alone. This excess heat is noted in Figure 40 as “Heat Gain from Students.”
Heat Gain From Lights
Heat emitted by the lighting system constitutes a
second uncontrolled heat source. Articial lighting
is needed in most classrooms even during daylight hours to prevent unbalanced lighting and eye strain. A typical classroom requires approximately 2,500 watts of supplemental lighting to provide properly balanced lighting. Fluorescent lights add heat to the room at the rate of 3.4 BTU per watt per hour, or a total of 8,500 BTU per hour. This extra heat is represented in Figure 40 as “Heat Gain from Lights.”
Add the heat gain from lighting to the 7,800 BTU introduced by student body heat and we now have an extra 16,300 BTU/HR being introduced into the classroom by uncontrolled sources. This heat gain remains constant regardless of the outdoor air temperature.
heating system were the only source of heat in the classroom, the solution would be simple: The room thermostat would cause the heating system to supply exactly the amount of heat required to maintain the room at the thermostat temperature setting. In reality, the introduction of excess heat from a variety of uncontrolled sources makes the challenge considerably more complex.
28 AAF-HermanNelson Model AEQ Unit Ventilator
Solar Heat Gain
The sun is a third uncontrolled source of heat. And, because it is neither positive nor constant, calculating
its contribution to the overall heat gain is difcult. Solar
heat gain can be the worst offender of the three in
classrooms with large windows. Indirect or reected
Application Considerations
solar radiation is substantial even on cloudy days, even in rooms with north exposure, as a result of what is termed “skyshine.”
To get an idea of the potential effect of the sun, let’s assume that the solar heat gain in our hypothetical classroom will peak at 240 BTU/HR per square foot of glass area. If we then assume a glass area of 100 square feet and at least 100 BTU/HR per square foot of glass for solar heat gain, we can calculate a very conservative estimate of 10,000 BTU/HR heat gain through windows. If we add this to the heat from the lights and body heat, total heat gain adds up to 26,300 BTU/HR from sources other than the heating and ventilating system. This is indicated in Figure 40 by the top horizontal line, which intersects Room Heat Loss Line A at approximately 37°F. This is a reasonable estimate of the maximum uncontrolled heat gain that can be received in the typical classroom from these common heat sources.
The Analysis
From Figure 40 it is evident that, at an outside temperature of 48°F or higher, the heat given off by
30 students and classroom lighting is sufcient to
cause overheating. This is true even if the classroom is occupied at night when solar heat gain is not a factor. But, since classrooms are occupied during the day, solar addition provides heat in varying amounts even in classrooms with north exposures. Consequently, the heating and ventilating system in our typical classroom must provide cooling at all times when the outdoor temperature is above 48°F and at any time during colder weather when the solar heat gain exceeds room heat loss.
If we assume an average winter temperature of approximately 33°F in the region where our typical classroom is located, we know that, half of the time, both night and day, the outside temperature will be above 33°F. However, since it is generally warmer during the day, when school is in session, the heating and ventilating system will be required to provide cooling for this classroom during much of the time that the room is occupied.
In this example, we’ve assumed that our classroom had a room heat loss of 55,000 BTU/HR at a design outdoor air temperature of 0°F (Room Heat Loss Line “A”). Bear in mind, however, that the recent trend in “energy-
saving” building design often results in rooms with lower room heat loss, as indicated by Room Heat Loss Lines “B”, “C” and “D.” At 0°F design outdoor air temperature:
Room “B” has a room heat loss of 45,000 BTU/HR
Room “C” has a room heat loss of 35,000 BTU/HR
Room “D” has a room heat loss of 25,000 BTU/HR
Note: The lowering of the temperature above which
cooling will always be required as the room heat loss decreases.
We’ve noted that cooling is always required in Classroom “A” when outdoor air temperatures exceed 48°F. In Classroom “B,” “C,” and “D” cooling is always required when outdoor temperatures exceed 44°, 36° and 23°F, respectively (Figure 40).
Now that we understand the reason for classrooms overheating, the solution is simple: The heating and ventilating system must provide cooling to take care of the heat given off in the classroom by uncontrolled heat sources.
Cooling The Classroom
The AAF-HermanNelson Unit Ventilator has become a standard for heating and ventilating systems in schools because it provides the solution for overheating classrooms. The unit ventilator cools as well as heats. During the heating season the outdoor air temperature is nearly always below the desired room temperature. It stands to reason then that the outside air should be used to provide the cooling necessary to keep classrooms down to thermostat temperature.
The classroom unit ventilator does just that. By incorporating an automatically controlled outdoor air damper, a variable quantity of outdoor air is introduced in the classroom, metered exactly to counteract overheating. Since our problem is more one of cooling than of heating, it is evident that more than just the room heat loss must be determined to design a good heating and ventilating system. The cooling requirements should be assessed as well, and the
free-cooling capacity of the equipment specied along
with the heating capacity required. If this is done, the optimum learning temperature can be maintained in each classroom.
AAF-HermanNelson Model AEQ Unit Ventilator 29
Application Considerations
Meeting IAQ Requirements
Good indoor air quality (IAQ), which is important in the home and at work, is no less important to students and faculty in schools. For the past several years, efforts to reduce energy costs in new school buildings have seen the use of tighter construction, sealed windows and heavier insulation. While these construction techniques have helped reduce energy costs, tightly sealed buildings, or envelopes, when combined with increased use of recirculated air, can lead to unhealthy air.
For this reason, the American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) now recommends 15 cfm of outdoor air per pupil, and no longer endorses the practice of little or no usage of outdoor air.
It should be kept in mind that a properly designed exhaust system is essential for avoiding indoor air quality problems. Simply put, if room air is not being exhausted in a prescribed fashion, fresh outside air cannot be introduced into the room. Likewise, an excessive amount of outside air will be admitted, wasting energy.
The AAF-HermanNelson Ventimatic shutter, a gravity-actuated room exhaust vent, can solve both these problems. The Ventimatic shutter allows the correct amount of outdoor air to be brought into the room while maintaining a slight positive pressure in the room. This slight positive pressure, maintained during normal operation, can also help prevent the
inltration of undesirable gases into the classroom. See
“VentiMatic™ Shutter Room Exhaust Ventilation” on page 24.
Following ASHRAE Control Cycle II
ASHRAE Cycle II is a very economical sequence of control because only minimum amounts of outdoor air are heated and free outdoor air—natural cooling—is available to offset the large internal heat gain associated with the dense occupancy of classrooms.
AAF-HermanNelson unit ventilators are normally controlled according to ASHRAE Control Cycle II. ASHRAE control cycles apply only to heating, heating­and-ventilating and free-cooling operation. (For more information on the ASHRAE Control Cycle II sequence, see Figure 42 on page 33.)
Under ASHRAE Cycle II, the outdoor air damper is closed during warmup of the room. As the room temperature approaches the thermostat setting, the outdoor air damper opens to a predetermined minimum percentage of outside air. The heating coil capacity controller then modulates to maintain the thermostat setting.
If the room temperature rises above the thermostat setting, the heating coil is turned off and the outdoor air damper opens beyond the minimum position to maintain the thermostat setting.
EXAMPLE: For a 60°F entering air mixture temperature and 70°F room temperature, with 30°F outdoor air temperature, 25% outdoor air will produce the 60°F mixture air temperature. When the outdoor air temperature drops to 10°F, 12.5% outdoor air will produce the 60°F mixture air temperature.
Night Setback
Substantial fuel savings can be realized by operating the unit ventilator system at a reduced room setting at night and during other unoccupied periods, such as weekends and holidays. If the space temperature falls below the setting of the unoccupied thermostat, the unit fans will be brought on to provide additional heat. Units with electric heat coils do not provide convective heat. The electric coil and the unit fans will be brought on to maintain the thermostat setting.
Typical Temperature Control Components
In general, unit ventilators require the following basic DDC electrical components in order to operate on any of the standard unit ventilator ASHRAE cycles of control. The control components listed in this section are for familiarization purposes only and should not be construed as a bill of material.
Outdoor Air Damper Actuator
This is a modulating device under the control of the room and discharge sensors. It positions the outdoor air damper to admit the amount of outdoor air required at any given point in the control cycle. The room air damper is mechanically linked to the outdoor air damper, which permits the use of a single actuator. Electric actuators should be of the spring-return type so that the outdoor air damper closes whenever the electric power supply to the unit is interrupted.
Discharge Airstream Sensor
This device overrides the room sensor and modulates the outdoor air damper toward the closed position when the unit discharge air falls to a potentially uncomfortable temperature.
30 AAF-HermanNelson Model AEQ Unit Ventilator
Application Considerations
Electric Heat Step Control:
A modulating step controller, under control of the room sensor, steps individual electric heating elements on and off as required. Staging relays are sometimes used in lieu of a step controller.
Additional Components
Additional components may be required depending on
the specic application. They include:
Room Temperature Sensor Chamber:
When the Room Temperature Sensor is to be mounted within the unit ventilator rather than on the wall, it is located behind a series of holes in the unit front panel with the sensing element sealed within the room tem­perature chamber. The room temperature chamber is a standard feature with units furnished with MicroTech II controls. All units come with a factory mounted room temperature sensor.
DX Cooling Low Ambient Lockout:
This lockout must be used on DX systems to lock out the condensing unit when the outdoor air temperature is below 64°F (17.5°C). This device must be integrated into the control system so that the unit has full ventilation cooling capability during the lockout period.
DX Low Temperature Limit:
This limit must be used on DX cooling units to de­energize the compressor when the refrigerant falls below freezing. DX units with MicroTech II controls have a factory-installed sensor on the return bend of the DX coil that provides a sample of the coil’s temperature.
Two Stage Compressors
Our self-contained units with the two-stage compressor will run on lower fan speeds up to 70% of the time, improving comfort through better humidity control and quieter operation, while minimizing issues with over sizing. The unit is designed to operate in low compression mode while in medium and low fan speed. The reduced cooling capacity in the medium and low fan speed will allow the system to run longer at moderate and low load conditions providing better humidity control. When the high capacity is needed the high speed will provide high compression and full capacity cooling.
Coil Selection
All coils have their own unshared n surfaces (some manufacturers use a continuous n surface, sacricing proper heat transfer). The result is maximum efciency
of heat transfer, which promotes comfort and reduces operating costs.
An air break between coils in all AAF-HermanNelson units is used to enhance decoupling of heat transfer surfaces—providing full capacity output, comfort and reduced operating costs.
Direct expansion (DX) coils are constructed of
aluminum ns with a formed, integral spacing collar. The ns are mechanically bonded to the seamless copper
tubes by expansion of the tubes after assembly. Fins are rippled or embossed for strength and increased heat transfer surface.
Long Lasting Electric Heating Coils
With our draw-thru design, electric coils are directly exposed to the air stream. They come with a built-in switch to de-energize the coil when the center front panel is removed. A unit-mounted disconnect switch is included. A continuous electric sensory element for high temperature is not required because the air is drawn smoothly and evenly across the coils, prolonging life. (Blow-thru designs use cal rods inserted into the tube of
a n tube coil that results in reduced heat transfer. The
constant movement of the electric heating cal rod within the tube shortens life.)
Meeting AHRI 840 Requirements
AAF-HermanNelson unit ventilators are rated per AHRI Standard 840. Per this standard, unit ventilators with outside air ventilation and return air dampers must provide ventilation air at a rate of minimum of 80%
rated standard air ow. They must also be capable
of providing any combination of humidity control,
circulation, heating or cooling, and ltering of air.
AAF-HermanNelson Model AEQ Unit Ventilator 31
Application Considerations
Meeting IBC Seismic Requirements
AAF-HermanNelson unit ventilators can be specied,
as follows, to meet International Building Code seismic requirements:
All components included in these unit ventilators are designed, manufactured and independently tested,
rated and certied to meet the seismic compliance
standards of the International Building Code.
Components designated for use in systems that are life safety, toxic, high hazard, combustible or am-
mable meet the on line, anchorage and load path requirements for life safety as dened in IBC sec­tions 1621.1.6, 1621.3.3,1707.7.2. and IBC Com­mentary, Volume II, section 1621.1.6, IBC notes pertaining to the release of hazardous material.
All components used as part of a system other than the above meet as a minimum, all load path and anchorage standards for components as outlined in IBC section 1621.3.3 & 1707.7.2.
All completed component assemblies are clearly labeled for eld inspection. Seismic Compliance La­bels include the manufacturer's identication, des­ignation of certied models, denitive information
describing the product's compliance characteristics, and the Independent Certifying Agency's name and
report identication.
Figure 41: Typical IBC Seismic Installation
Left End Compartment ­Area for Securing Unit to Floor
In addition to all seismic requirements for IBC
Certication listed elsewhere in the project specication,
submittals for these units include:
1. A Certicate of Compliance from the Independent Certifying Agency clearly indicating that components supplied on this project are included in the compo-
nent manufacturer's Certicate of Compliance.
2. Clear installation instructions including all accessory components that are part of the overall component installation.
Typical Seismic Installation
When the unit is in the correct location, remove the optional casters from the right and left end unit compartments, and retain for later use. The bottom plate cutouts, removed earlier to accomodate the caster wheels, should be replaced.Using a 1/4" masonry bit,
drill through the unit bottom plate and into the oor in the areas indicated in the gure at right (circled).
Determine the location of the holes based on clearance, and the existence of the unit bottom plate, and as close to the front edge of the unit as possible. Vacuum the concrete dust that remains, so it is not drawn into the unit components upon start up.
Using a power drill with a 5/16" hex socket bit, secure the right and left ends of the unit with two (2) (contractor supplied) 1/4" dia. x 2" x 5/16" hex washer head masonry screws (or equivalent). Tighten the
screws down until the unit is secure to the oor, without
distorting the unit bottom plate.
Right End Compartment ­Area for Securing Unit to Floor
Right End - Optional Caster
Right End Compressor Compartment
1/4"dia. x 2" x 5/16" Hex Washer Head Concrete Screw – 2
32 AAF-HermanNelson Model AEQ Unit Ventilator
Application Considerations
ASHRAE Cycle II
We strongly recommend that ASHRAE Cycle II be implemented with all unit ventilators using controls by others. ASHRAE Cycle II is a very economical sequence since only the minimum amount of outside air is conditioned and free natural cooling is available. See Figure 42:
During warm-up (any classroom temperature 3°F or more below heating setpoint), the outdoor air damper is closed and the unit conditions only room air. As room temperature approaches the heating setpoint the outdoor air damper opens to a position that permits a predetermined minimum amount of outside air to be drawn in. Unit capacity is then controlled as needed to maintain room setpoints. If room temperature rises above room cooling setpoint, and the outside air is adequate for economizer cooling, then the outdoor air damper may open above the minimum position to provide economizer cooling.
ASHRAE Cycle II requires that a minimum of three temperature measurements be made:
Figure 42: ASHRAE Cycle II Operation
1 Classroom temperature. 2 Unit discharge air temperature. 3 Outdoor air temperature.
The control sequence should incorporate a Discharge Air Low Limit function which requires a discharge air temperature sensor and can override classroom temperature control in order to maintain a discharge air temperature setpoint of 55°F (ventilation cooling 45°F mechanical cooling).
When the discharge air temperature drops below 55°F, the discharge-air low-limit function will disable cooling (if enabled) and modulate the unit’s heating capability as needed to maintain the 55°F discharge-air setpoint regardless of room temperature.
If the unit’s heating capability reaches 100%, then the discharge air low-limit function will modulate the outdoor air damper toward closed to maintain the 55°F discharge air setpoint. Outdoor air temperature is used
to determine when to use economizer as a rst stage
of cooling, and when to use mechanical or hydronic
cooling as the rst stage of cooling.
Typical Outdoor Air Damper Operation
A Outdoor air damper closed. B Outdoor air damper at minimum position. C Economizer function is increasing the outdoor
air damper position.
Note: If outdoor air temperature is not adequate for
free cooling, secondary mechanical cooling can be used in place of economizer cooling. A low discharge air function is used to help
maintain comfort and provide additional equip-
ment protection by preventing the discharge
air from falling too low (typically 55°F), and may force the outdoor air damper toward
closed to maintain the discharge air tempera-
ture regardless of room temperature.)
D Damper is at full open.
Typical Mechanical Heating Operation
E Heating (DX) is closed (or off). F Heating begins to modulate (or on). G Heating capability has reached 100%.
Typical Mechanical Cooling Operation
H Mechanical cooling (DX) is closed (or off). J Mechanical cooling (DX) has reached 100%.
AAF-HermanNelson Model AEQ Unit Ventilator 33
Application Considerations
Outside Air
Condenser Discharge
Condenser Supply Air
Unit Installation
Carefully arrange the location and installation of each model AEQ unit to provide convenient service access for maintenance and, if necessary, removal of the unit. The installation consists of four basic elements in the following order:
1. Louver
2. Galvanized Wall Sleeve
3. Horizontal Air Splitters by others (if required)
4. AEQ Self-contained Unit Ventilator
The louver brings in outdoor air for the condenser fan section and ventilation air to the classroom while providing a path for heated condenser air to exit.
The Wall Sleeve secures the unit, provides a watertight and air tight seal to the building and brings in electrical and control wiring (if required). It contains the unit main power disconnect switch which is located in the wall
sleeve junction box. All eld electrical connections are
made inside this box. Horizontal Air Splitters provide proper air paths and
minimize air recirculation. The AEQ self-contained unit ventilator provides comfort
cooling and heating for the space. The Model AEQ unit
is designed to be installed into or up against an exterior wall. The louver, air splitters (if required) and wall sleeve are installed before the AEQ unit is installed.
On many jobs, the louver and wall sleeve are shipped ahead of the unit itself. Installation instructions for these components are shipped with the individual components included in this publication.
The following are general instructions for suggested applications. In all cases, good engineering practices and local codes must be followed.
Lintels
When brickwork is built up to the top of the intake, lintels must be used above the wall louvers. While the wall
is still wet, nish the brick on the top, bottom and both
sides of the intake opening with 1/2" cement mortar. With the standard location of the wall louver, the bottom of the intake opening must slope from the louver frame up toward the intake opening to a point 1" above the
nished base of the unit.
If a metal sleeve connection is to be used between the unit ventilator and the wall louver, this sleeve must be installed after the unit ventilator is set, making a weather-tight connection to the unit ventilator cabinet. Turn the sleeve over the edge of the louver frame by
proper peening before the louver is nally installed.
Figure 43: Typical Self-Contained Unit Ventilator Installation
Internal Column for Wall Bracing and Anchoring (by others)
Optional Louver Flange
Seal Horizontal Air Splitters to Building at Both Ends
Drain Holes in Splitters (by others)
Louver–Bird Screen
3. Horizontal Air Splitters
(Field Made to Job Conditions by Others) Pitch Down Toward Louver
Louver Blade
Weep Holes
Textured Charcoal Bronze Unit Projection Top (Except Fully Recessed Wall Sleeve)
Conduit (by others)
Wall Sleeve Junction Box
Bottom Flange
1. Louver
Must be sealed watertight at top and both ends
Galvanized Condenser (Outdoor) Section
Textured, Scuff Resistant, Charcoal Bronze, Environmentally Friendly Thermosetting Urethane Powder Paint Top
4. AEQ Self-Contained Unit V entilator
Caster Kit for Indoor Section (Optional)
Caster on Outdoor Section
Wall Sleeve Threaded Studs for Fastening to Unit (Ships on Wall Sleeve)
2. Galvanized Wall Sleeve
Sealed Cement Mortar, Pitched Away from Unit Toward Louver
6" End Panel (Optional)
34 AAF-HermanNelson Model AEQ Unit Ventilator
Application Considerations
Wall Louvers
The outdoor air wall louver is usually set directly back of the unit ventilator. The position of the wall louver is determined in general by the building construction. The top of the lower channel of the louver frame should be at least 1/2" below the level of the inlet to the unit ventilator.
However, if a high intake opening is necessary, the top of this opening should be not more than 28" above the surface upon which the unit ventilator will set.
Louver (Note 2)
28"
(711mm)
Wall
Sleeve
28"
(711mm)
16-5/8"
(422mm)
3"
(76mm)
Figure 44: Wall Penetrations Detail
Louver (Note 2)
28"
(711mm)
Caulk
Perimeter
Louver (Note 2)
28"
(711mm)
Caulk
Perimeter
See Note 1
Wall
Sleeve
Wall
Sleeve
Steel Lintel (by others)
16-5/8"
(422mm)
3"
(76mm)
3" (76mm)
Full Recess
Steel Lintel (by others)
16-5/8"
(422mm)
3"
(76mm)
3" (76mm)
Partial Recess
Notes:
1. Horizontal splitter (by others) must be installed
whenever there is any space between the wall sleeve and the louver. It is necessary to seal the
ends of the wall opening.
2. The top and two sides of the louver must be
caulked water tight. The bottom edge of the lou-
ver must not be caulked, to allow for drainage.
3. Louvers may be recessed a maximum of 2" (51mm) from the exterior face of the wall.
3" (76mm)
Caulk
Perimeter
No Recess
4. Drain must be ush with oor to allow unit instal-
lation and removal. Unit drain tube is 7/8" (22mm)
O.D. copper.
5. A eld-supplied air seal should be applied to the exterior perimteter of the wall sleeve when unit is
installed with no recess.
Lintels
When brickwork is built up to the top of the intake, lintels must be used above the wall louvers. While the wall
is still wet, nish the brick on the top, bottom and both
sides of the intake opening with 1/2" cement mortar. With the standard location of the wall louver, the bottom of the intake opening must slope from the louver frame up toward the intake opening to a point 1" above the
nished base of the unit.
If a metal sleeve connection is to be used between the unit ventilator and the wall louver, this sleeve must be installed after the unit ventilator is set, making a weather-tight connection to the unit ventilator cabinet. Turn the sleeve over the edge of the louver frame by
proper peening before the louver is nally installed.
Figure 45: Typical Wall Opening with Lintels
Outdoor Side
Bottom of Intake Opening Sloped Down T oward Louver
Indoor Side
Top, Sides and Bottom on Inside of Opening Finished Smooth with Mortar
Lintel (by others)
AAF-HermanNelson Model AEQ Unit Ventilator 35
Application Considerations
Horizontal Splitters & Unit Recess Details
Horizontal splitter (by others) must be installed whenever there is space between the wall sleeve and the louver. Seal the ends of the wall opening to prevent water penetration and air leakage. Pitch the splitters toward the louver for water drainage
Figure 46: 16-5/8" Room Projection or Full Recess
16⅝" (422mm)
Room Projection
Inside T op
16⅝" (422mm)
28" (711mm)
Unit
30"
(762mm)
11½"
(292mm)
28"
(711mm)
(206mm)
4½" (102mm)
Louver
(See CAUTION)
8⅛"
1/2" (13mm)
W
Wall Thickness
S
1"
(25mm)
5/8"
(16mm)
11⅜"
(289mm)
Splitters
(by others)
Note: Shading indicates portion of unit wall sleeve
recessed into wall opening
Figure 47: 19-5/8" Room Projection
19⅝" (498mm)
W
Wall Thickness
Room Projection
Wall
Sleeve
Finish T op
Unit
Inside T op
Figure 48: 21-7/8" Room Projection
Room Projection
Wall
Sleeve
Finish T op
5¼"
(133mm)
28" (711mm)
21⅞" (557mm)
Unit
Inside T op
16⅝" (422mm)
11½"
(292mm)
28"
(711mm)
(206mm)
4½" (102mm)
Louver
(See CAUTION)
Wall Thickness
8⅛"
1/2" (13mm)
W
S
1"
(25mm)
5/8"
(16mm)
Splitters
(by others)
Note: Shading indicates portion of unit wall sleeve
recessed into wall opening
Figure 49: 28" Room Projection
W
Wall Sleeve
1"
28"
(711mm)
Wall Thickness
11½"
(292mm)
8⅛"
(206mm)
4½" (102mm)
S
(25mm)
5/8"
(16mm)
Room Projection
Finish T op
3
11
/8"
(289mm)
Splitters (by others)
28" (711mm)
Unit Inside T op
16⅝" (422mm)
30"
(762mm)
30"
(762mm)
1/2" (13mm)
28" 21⅞" 19⅝" 16⅝"
Figure 49 Figure 48 Figure 47 Figure 46
28" (711mm)
8⅛"
1/2" (13mm)
S
1"
(25mm)
5/8"
(16mm)
3"
(76mm)
Splitters
(by others)
16⅝" (422mm)
28" (711mm)
11½"
(292mm)
28"
(711mm)
(206mm)
4½" (102mm)
Louver
(See CAUTION)
Note: Shading indicates portion of unit wall sleeve
recessed into wall opening
CAUTION
Horizontal splitter (by others) must be installed whenever there is space between the wall sleeve and the louver. Seal the ends of the wall opening to prevent water penetration and air leakage. Pitch the splitters toward the louver for water drainage
30"
(762mm)
Louver
(See CAUTION)
Table 1: Wall Thickness, Unit Projection Into Room
Unit Projection into Room and Wall Sleeve Type
Wall
Thickness Louver
“W”
Splitter Length from Wall Sleeve to Louver "S" 2½" 2½" 0 4" 2½" 1½" 6" 2½" 3½" 8" 2½" 5½"
8⅝" 2½" 6⅛" 0"
10" 2½" 7½" 1⅜"
10⅞" 2½" 8⅜" 2¼" 0"
12" 2½" 9½" 3⅜" 1⅛"
13⅞" 2½" 3" 0"
14" 2½" 3⅛" 1/8"
16" 2½" 2⅛"
18" 2½" 4⅛"
24" 2½" 10⅛"
Note: All dimensions are approximate and subject to change without notice. Actual building dimensions may vary.
36 AAF-HermanNelson Model AEQ Unit Ventilator
Application Considerations
Interior Considerations
The interior wall surface behind the unit ventilator must be smooth and level. A wall that is slightly out of plumb can cause major problems with outside air leakage into the room and unit. This could cause drafts and potentially freeze coils.
Be certain that no gap is left between the unit and the outside air louver opening. Otherwise, outside air can leak into the room.
A rubberized, self-adhering membrane around the outside air opening can be used to seal any air or water leaks that might result from construction. Provide a seal
under the unit to prevent air inltration. In addition, seal
the unit top and side perimeters to prevent unnecessary
air inltration due to uneven walls.
Indoor Air Exhaust Considerations
All outdoor air introduced by the unit ventilator must leave the room in some way. In some states, exhaust
Wall Sleeve Arrangements
vents are required by law. In states where vents are not required by law, a decision must be made about how best to handle this problem.
The venting system chosen should have the ability to exhaust varying amounts of air equal to the amount
of outside air introduced by the oor unit ventilator. A
constant volume system, such as a powered exhaust, is unable to respond to changing conditions. It will either exhaust too much air, resulting in a negative pressure, which draws in more outdoor air than desired. Or, it will exhaust too little air, resulting in increased positive pressure, which restricts the amount of outside air being brought into the room.
The AAF-HermanNelson Ventimatic shutter is a more economical solution to the problem. See “Ventimatic™ Shutter Room Exhaust Ventilation” on page 24 for information on this system and its proper installation.
Figure 50: Recessed Wall Sleeve with Horizontal Air Splitters
By Others. Wall Sleeve must be sealed watertight at top and both ends at location shown.
Wall Sleeve Splitter(s) Rail(s)
Seal Horizontal Air Splitter Rail(s) to Louver. (By Others)
Indoor
By Others. Seal Hori­zontal Air Splitters to building at both ends.
By Others. Seal both ends of opening between Wall Sleeve and Louver to prevent air and water from entering building structure and room.
Important Note:
By Others: Attach Horizontal Air Splitters to Wall Sleeve Splitters as shown. Split­ters to have 1" dia. drain hole approx. 6" from each end. Pitch splitters toward louver for water drainage.
"D" Seal
By Others. Wall Sleeve must be sealed watertight at bottom at location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver.
By Others. Louver must be sealed air and watertight at top and both ends.
Outside
3/16" Under Intake must be free for water run-off. Louver intake must stand on embossed feet located on bottom.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
Condenser Discharge
Condenser Inlet
Outdoor Air Inlet
AAF-HermanNelson Model AEQ Unit Ventilator 37
Application Considerations
Figure 51: Sealing Full Projection Wall Sleeve and Horizontal Air Splitters
By Others. Apply sealant (by others) to bottom edge of unit (not shown)
and to top ange and both end anges of wall sleeve (as shown.) This must
provide a watertight seal to the wall of the building.
Seal Horizontal Air Splitter Rail(s) to Louver. (By Others)
Indoor
Vertical and Horizontal Mounting Bracket(s) Holes for Non-Recessed (Full Projection) Applications
Wall Sleeve Splitter(s) Rail(s)
By Others. Louver must be sealed air and watertight at top and both ends.
By Others. Seal Hori­zontal Air Splitters to building at both ends.
By Others. Seal both ends of opening between Wall Sleeve and Louver to prevent air and water from entering building structure and room.
Important Note:
By Others: Attach Horizontal Air Splitters to Wall Sleeve Splitters as shown. Splitters to have 1" dia. drain hole approx. 6" from each end. Pitch splitters toward louver for water drainage.
"D" Seal
By Others. Wall Sleeve must be sealed air and watertight at bottom “D” seal location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver.
Figure 52: Attaching Splitters to Wall Sleeve Splitter Rails and Seals
Seals
Slope Down
Toward Louver
Screws (by others)
Top Splitter
(by others)
Outside
3/16" Under Intake must be free for water run-off. Louver intake must stand on embossed feet located on bottom.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
1"(25mm)
Top Wall Sleeve Splitter Rail
Slope Down
Toward Louver
Bottom Splitter
(by others)
Seal
Seal
Bottom Wall Sleeve Splitter Rail
5/8"(16mm)
1"(25mm)
38 AAF-HermanNelson Model AEQ Unit Ventilator
Application Considerations
Figure 53: Recessed Wall Sleeve - Direct Sealing Wall Sleeve to Louver
By Others. Wall Sleeve must be sealed watertight at top and both ends at location shown.
Wall Sleeve Splitter Rail(s)
Indoor
By Others. Seal both ends of opening between Wall Sleeve and Louver to prevent air and water from entering building structure and room.
By Others. Wall Sleeve must be sealed air and watertight at bottom at “D” seal location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver.
"D" Seal
IMPORTANT NOTE: By Others. Seal Louver to Wall Sleeve at top and bottom Wall Sleeve Splitter Rails(s), and ends.
3/16" Under Intake must be free for water run-off. Louver intake must stand on embossed feet located on bottom.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
By Others. Louver must be sealed air and watertight at top and both ends.
Outside
Figure 54: Sealing Full Projection Wall Sleeve to Louver Intake Without Horizontal Air Splitters
By Others. Apply sealant (by others) to bottom edge of unit (not shown)
and to top ange and both end anges of wall sleeve (as shown.) This
must provide a watertight seal to the wall of the building.
Wall Sleeve
Indoor
Vertical and Horizontal Mounting Bracket(s) Holes for Non-Recessed (Full Projection) Applications
By Others. Seal both ends of opening be­tween Wall Sleeve and Louver to prevent air and water from entering the building structure and room.
By Others. Wall Sleeve must be sealed air and watertight at bottom “D” seal at location shown. Refer to cross section detail of bottom of Wall Sleeve and Louver.
Splitter Rail(s)
"D" Seal
IMPORTANT NOTE: By Others. Seal Louver to Wall Sleeve at top, Wall Sleeve Splitters and ends.
3/16" Under Intake must be free for water run-off. Louver intake must stand on embossed feet located on bottom.
By Others. Building must be sealed between Wall Sleeve and under Louver for water run-off. Pitch toward Louver.
By Others. Louver must be sealed watertight at top and both ends.
Outside
AAF-HermanNelson Model AEQ Unit Ventilator 39
Unit Selection
Quick Selection Procedure
The following procedure will provide you with a rough determination of unit capacity for cooling and/ or heating based on the number of coil rows. Use
capacity tables for nal selection. Consult your local
AAF-HermanNelson representative for details on the computer selection programs McQuay International provides for this purpose
Cooling Performance Data – Size 024
Table 2: Standard Cooling at High Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 95°F db/75°F wb (35°C/24°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow Btuh Watts Btuh Watts EER kW CFM L/S
21100 6180 15700 4530 9.1 2310 1000 472
Table 3: Partial Load Cooling at Medium Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
16900 4950 12100 3540 11.6 1450 750 354
Table 4: Partial Load Cooling at Low Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
16400 4800 11100 3240 11.7 1410 650 307
Heating Performance Data – Size 024
Table 5: Standard Heating at High Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 47°F db/42°F wb (8°C/6°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
20700 6090 3.0 2050 1000 472
Table 6: Partial Load Heating at Medium Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
17700 5160 3.3 1560 750 354
Table 7: Partial Load Heating at Low Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
17100 5010 3.1 1600 650 307
40 AAF-HermanNelson Model AEQ Unit Ventilator
Unit Selection
Cooling Performance Data – Size 036
Table 8: Standard Cooling at High Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 95°F db/75°F wb (35°C/24°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow Btuh Watts Btuh Watts EER kW CFM L/S
39300 11520 25500 7500 9.7 4065 1250 590
Table 9: Partial Load Cooling at Medium Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
30800 9030 2000 5850 11.7 2630 1000 472
Table 10: Partial Load Cooling at Low Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
29400 8610 18000 5280 11.4 2580 800 378
Heating Performance Data – Size 036
Table 11: Standard Heating at High Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 47°F db/42°F wb (8°C/6°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
35000 10230 2.6 3910 1250 590
Table 12: Partial Load Heating at Medium Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
29100 8520 2.8 3055 1000 472
Table 13: Partial Load Heating at Low Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
28000 8220 2.6 3180 800 378
Note: AEQ sizes 036, 044, & 054, manufactured for replacement applications only, not to be installed in new
construction projects in accordance with ASHRAE 90.1.
AAF-HermanNelson Model AEQ Unit Ventilator 41
Unit Selection
Cooling Performance Data – Size 044
Table 14: Standard Cooling at High Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 95°F db/75°F wb (35°C/24°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow Btuh Watts Btuh Watts EER kW CFM L/S
43700 12810 30000 8790 9.1 4790 1500 708
Table 15: Partial Load Cooling at Medium Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
35500 10410 23800 6990 11.8 3010 1150 542
Table 16: Partial Load Cooling at Low Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
34300 10050 22000 6420 11.6 2955 950 448
Heating Performance Data – Size 044
Table 17: Standard Heating at High Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 47°F db/42°F wb (8°C/6°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
41600 12180 2.6 4620 1500 708
Table 18: Partial Load Heating at Medium Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
36100 10560 3.0 3525 1150 542
Table 19: Partial Load Heating at Low Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
35400 10380 2.9 3625 950 448
Note: AEQ sizes 036, 044, & 054, manufactured for replacement applications only, not to be installed in new
construction projects in accordance with ASHRAE 90.1.
42 AAF-HermanNelson Model AEQ Unit Ventilator
Unit Selection
Cooling Performance Data – Size 054
Table 20: Standard Cooling at High Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 95°F db/75°F wb (35°C/24°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow Btuh Watts Btuh Watts EER kW CFM L/S
51200 15000 34400 10080 9.1 5620 1500 708
Table 21: Partial Load Cooling at Medium Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
41600 12180 26600 7770 11.5 3620 1150 542
Table 22: Partial Load Cooling at Low Indoor Fan Speed
Conditions: Indoor 80°F db/67°F wb (27°C/19°C) Outdoor; 82°F db/65°F wb (28°C/18°C)
Total Capacity Sensible Capacity Efciency Power Nominal Air Flow
Btuh Watts Btuh Watts EER kW CFM L/S
40000 11730 24500 7170 11.2 3570 950 448
Heating Performance Data – Size 054
Table 23: Standard Heating at High Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 47°F db/42°F wb (8°C/6°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
49700 14580 2.5 5820 1500 708
Table 24: Partial Load Heating at Medium Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
43000 12600 2.8 4500 1150 542
Table 25: Partial Load Heating at Low Indoor Fan Speed
Conditions: Indoor 70°F db/60°F wb (21°C/16°C) Outdoor; 62°F db/56.5°F wb (17°C/14°C)
Total Capacity Efciency Power Nominal Air Flow Btuh Watts COP Watts CFM L/S
42300 12390 2.6 4720 950 448
Note: AEQ sizes 036, 044, & 054, manufactured for replacement applications only, not to be installed in new
construction projects in accordance with ASHRAE 90.1.
AAF-HermanNelson Model AEQ Unit Ventilator 43
Unit Selection
Selection Procedure
Step 1: Determine Design Conditions
Determine design indoor and outdoor air temperatures in accordance with established engineering practices, as outlined in the ASHRAE Guide or other authoritative source. Indoor temperatures of 80°F dry bulb, 67°F wet bulb for summer and 70°F dry bulb for winter usually are acceptable for design or peak load conditions, even though the expected operating conditions of the system may be somewhat different.
Step 2: Determine Heating and Cooling Loads
Calculate design winter heating losses and summer cooling loads in accordance with the procedures outlined by the ASHRAE Guide or other authoritative source. Perhaps the greatest consideration in calculating design loads is solar heat gain. August solar heat values might be used for summer cooling loads, but should not be used for ventilation air or “natural cooling” capacity calculations; since these cooling loads reach their maximum in the spring and autumn months. The natural cooling capacity is usually calculated for 55° or 60°F outdoor air temperature.
Equation 7: CFM Based On Sensible Cooling Load
1.086 x TD
Q sensible (space)
CFM =
Q sensible is the maximum sensible room load and T.D. is the temperature difference between the room design
dry bulb temperature and the nal or leaving-air dry bulb
temperature. For these calculations, a T.D. of 20°F is usually assumed to be desirable to avoid delivering air
too cold for comfort. This gure may be varied one or
two degrees for reasons of practicality.
Note: The sensible load used in the preceding equation
is the space load and excludes the ventilation load.
Most areas have ventilation codes which govern the amount of ventilation air required for school applications. For other than school applications or areas not having codes, the ASHRAE Guide may be used for authoritative recommendations and discussion of the relation between odor control and outdoor air quantities.
The minimum outdoor air quantity recommended by ASHRAE is 15 CFM per person. Lower percent minimum outdoor air settings are more economical. In the interest of economy, it may be desirable to use lower percent minimums if there are no ventilation codes.
Step 3: Determine Air Quantity Required
Air quantity for heating applications is determined from
circulation of a denite number of room air volumes per
hour. Table 26 gives the recommended number of room air changes per hour.
Table 26: Recommended Room Air Changes Per Hour
Type of Space
Classrooms, Ofces 6 to 9
Laboratories, Shops 6 to 8 Cafeterias & Kitchens 4-1/2 to 7
For rooms facing east, south or west, the higher values shown in the table should be used so adequate ventilation cooling will be available to prevent overheating during mild sunny weather. The following equation is helpful to determine the CFM air delivery for any given rate of circulation:
Equation 6: CFM For Given Rate Of Circulation
Room Volume (cu ft) × Room Changes per Hour
60
In mechanical cooling applications, the total air quantity
may be determined or veried by use of the sensible
cooling load equation:
Recommended number of
room air changes per Hour
= CFM
Step 4: Select Unit Size
The unit should be selected to meet or exceed the CFM delivery requirement previously determined. All model types are available with nominal capacities of 1000, 1250 and 1500 CFM. Unit sizes 024, 036, 044 and 054.
Heating Capacity
Unit heating capacity should be selected to equal or slightly exceed the computed room heat loss. The heating required to warm the outdoor ventilating air up to room temperature must also be calculated.
Cooling Capacity
Unit cooling capacity should be selected to equal or slightly exceed the sum of computed room sensible and latent heat gains (Room Total Capacity). When operating on the mechanical cooling cycle, the control system introduces a constant amount of outdoor air for ventilation. The latent and sensible heat gain from this outdoor ventilation air must be added to the room total cooling load before choosing the proper capacity unit.
44 AAF-HermanNelson Model AEQ Unit Ventilator
Unit Selection
Engineering Data
Table 27: Model AEQ Electrical Data – Size 024
Voltage Range Voltage
208/60/1 197 228 2.7 2.9 11.4 52.0
High (6-elem.) 16.0 76.9 116.0 125
230/60/1
High (6-elem.) 15.3 66.7 103.2 110
208/60/3
High (6-elem.) 16.0 44.4 71.0 80
230/60/3
High (6-elem.) 15.3 38.5 63.6 70
460/60/3
Min. Max.
207 253 2.7 2.9 11.4 52.0
197 228 2.7 2.9 7.9 59.0
207 253 2.7 2.9 7.9 59.0
414 506 2.7 1.2 3.9 29.7
Room Outdoor
Fan Fan Heater Heater Maximum
FLA FLA
High (6-elem.) 15.3 19.2 32.8 35
Notes:
1
Electric Heat Options are with Compressor and Outdoor Fan
FLA = Full Load Amps RLA = Rated Load Amps MCA = Minimum Circuit Ampacity LRA = Locked Rotor Amps
Compressor Heating Options Power Supply
RLA LRA Heat Type
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
Low (3-elem.) 8.0 38.5 67.9 70
Low (3-elem.) 7.7 33.3 61.5 70
Low (3-elem.) 8.0 22.2 43.2 45
Low (3-elem.) 7.7 19.2 39.5 40
Low (3-elem.) 7.7 9.6 20.8 20
kW Amps
MCA
Fuse
Table 28: Model AEQ Electrical Data – Size 036
Voltage Range
High (6-elem.) 20.0 96.2 152.9 150
High (6-elem.) 19.2 83.3 136.9 150
High (6-elem.) 20.0 55.5 97.6 100
High (6-elem.) 19.2 48.1 88.4 90
Voltage
208/60/1
230/60/1
208/60/3
230/60/3
460/60/3
Min.
Max.
197 228 2.7 6.8 18.6 96.0
207 253 2.7 6.8 18.6 96.0
197 228 2.7 6.8 15.0 88.0
207 253 2.7 6.8 15.0 88.0
414 506 2.7 2.2 6.8 44.0
Room Outdoor
Fan
FLA
High (6-elem.) 19.2 24.1 43.5 45
Notes:
1
Electric Heat Options are with Compressor and Outdoor Fan
FLA = Full Load Amps RLA = Rated Load Amps MCA = Minimum Circuit Ampacity LRA = Locked Rotor Amps
Compressor Heating Options Power Supply
Fan
FLA
RLA LRA
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
Heat Type
Heater Heater Maximum
Low (3-elem.) 10.0 48.1 92.8 90
Low (3-elem.) 9.6 41.7 84.8 90
Low (3-elem.) 10.0 27.8 62.9 70
Low (3-elem.) 9.6 24.1 58.3 60
Low (3-elem.) 9.6 12.0 28.4 30
kW Amps
MCA
Fuse
AAF-HermanNelson Model AEQ Unit Ventilator 45
Unit Selection
Engineering Data
Table 29: Model AEQ Electrical Data – Size 044
Voltage Range
High (6-elem.) 24.0 115.4 183.2 200
High (6-elem.) 23.0 100.0 164.0 175
High (6-elem.) 24.0 66.6 111.5 110
High (6-elem.) 23.0 57.7 100.4 100
Voltage
208/60/1
230/60/1
208/60/3
230/60/3
460/60/3
Min. Max.
197 228 2.7 6.8 23.6 96.0
207 253 2.7 6.8 23.6 96.0
197 228 2.7 6.8 15.0 88.0
207 253 2.7 6.8 15.0 88.0
414 506 2.7 2.2 7.1 41.0
Room Outdoor
Fan Fan Heater Heater Maximum FLA
High (6-elem.) 23.0 28.9 49.9 50
Notes:
1
Electric Heat Options are with Compressor and Outdoor Fan
FLA = Full Load Amps RLA = Rated Load Amps MCA = Minimum Circuit Ampacity LRA = Locked Rotor Amps
Compressor Heating Options Power Supply
FLA
RLA LRA
Heat Type
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
Low (3-elem.) 12.0 57.7 111.1 125
Low (3-elem.) 11.5 50.0 101.5 110
Low (3-elem.) 12.0 33.3 69.9 70
Low (3-elem.) 11.5 28.9 64.3 70
Low (3-elem.) 11.5 14.4 31.8 35
kW Amps
MCA
Fuse
Table 30: Model AEQ Electrical Data – Size 054
Voltage Range
High (6-elem.) 24.0 115.4 189.5 200
High (6-elem.) 23.0 100.0 170.3 175
High (6-elem.) 24.0 66.6 117.3 125
High (6-elem.) 23.0 57.7 106.2 110
460/60/3
Voltage
208/60/1
230/60/1
208/60/3
230/60/3
Min. Max.
197 228 2.7 6.8 28.6 118.0
207 253 2.7 6.8 28.6 118.0
197 228 2.7 6.8 19.6 123.0
207 253 2.7 6.8 19.6 123.0
414 506 2.7 2.2 10.0 62.0
Room Outdoor
Fan Fan Heater Heater Maximum FLA FLA
High (6-elem.) 23.0 28.9 53.5 60
Notes:
1
Electric Heat Options are with Compressor and Outdoor Fan
FLA = Full Load Amps RLA = Rated Load Amps MCA = Minimum Circuit Ampacity LRA = Locked Rotor Amps
Table 31: General Unit Data
Model AEQ 024 036 044 054
Nominal Airow – CFM (L/S) 1000 (472) 1250 (590) 1500 (708) 1500 (708)
Width - In. (MM) 8.25 (210) 8.25 (210) 8.25 (210) 8.25 (210)
Room Fan Motor Horse Power 1/4 Outdoor Fan Motor Horse Power 1/3
Nom. Size – In. (MM) 10 × 48½ × 1 (254 × 1232 × 25) 10 x 60½ Filter Data Area – FT Quantity 1 1 2 2
Approx. Ship Weight – Lbs. (KG) 885 (402) 975 (442) 1075 (448) 1075 (448)
No. of Fans 3 4 4 4
Room
Fan Data
Dia. – In. (MM) 8.12
2
(M2) 3.37 (0.31) 4.20 (0.39) 5.08 (0.47) 5.08 (0.47)
Compressor Heating Options Power Supply
RLA LRA
(206) 8.12 (206)
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
1
Electric Heat
Heat Type
kW Amps
MCA
Low (3-elem.) 12.0 57.7 117.4 125
Low (3-elem.) 11.5 50.0 107.8 110
Low (3-elem.) 12.0 33.3 75.6 80
Low (3-elem.) 11.5 28.9 70.1 80
Low (3-elem.) 11.5 14.4 35.4 40
1/4 3/4
× 1 (254 × 1537 × 25) 10 × 36½ × 1 (254 × 927 × 25)
8.12 (206)
1/4 3/4
8.12 (206)
1/4 3/4
Fuse
46 AAF-HermanNelson Model AEQ Unit Ventilator
Details & Dimensions
Figure 55: Unit Size 024 Dimensions
AAF-HermanNelson Model AEQ Unit Ventilator 47
Details & Dimensions
Figure 56: Model AEQ, Unit Size 036 Dimensions
48 AAF-HermanNelson Model AEQ Unit Ventilator
Details & Dimensions
Figure 57: Model AEQ, Unit Size 044 & 054 Dimensions
AAF-HermanNelson Model AEQ Unit Ventilator 49
Details & Dimensions
27 7/8"
(708mm)
27
7
/8"
(708mm)
7"
(178mm)
2
1
/2"
(64mm)
1"
(25mm)
27
7
/8"
(708mm)
18"
(457mm)
4"
(102mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"
(102mm)
1"
(25mm)
16 5/8"
(422mm)
1"
(25mm)
27 7/8"
(708mm)
28"
(711mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"(102mm)
1"
(25mm)
27
7
/8"
(708mm)
27
7
/8"
(708mm)
7"
(178mm)
2
1
/2"(64mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"
(102mm)
1"
(25mm)
27
7
/8"
(708mm)
18"
(457mm)
4"
(102mm)
1"
(25mm)
27
7
/8"
(708mm)
27
7
/8"
(708mm)
7"
(178mm)
2
1
/2"(64mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"(102mm)
1"
(25mm)
27
7
/8"
(708mm)
18"
(457mm)
4"
(102mm)
1"
(25mm)
19
5
/
8
"
(498mm)
1"
(25mm)
21
7
/
8
"
(556mm)
1"
(25mm)
27 7/8"
(708mm)
27
7
/8"
(708mm)
7"
(178mm)
2
1
/2"
(64mm)
1"
(25mm)
27
7
/8"
(708mm)
18"
(457mm)
4"
(102mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"
(102mm)
1"
(25mm)
16 5/8"
(422mm)
1"
(25mm)
27 7/8"
(708mm)
28"
(711mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"(102mm)
1"
(25mm)
27
7
/8"
(708mm)
27
7
/8"
(708mm)
7"
(178mm)
2
1
/2"(64mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"
(102mm)
1"
(25mm)
27
7
/8"
(708mm)
18"
(457mm)
4"
(102mm)
1"
(25mm)
27
7
/8"
(708mm)
27
7
/8"
(708mm)
7"
(178mm)
2
1
/2"(64mm)
1"
(25mm)
27
7
/8"
(708mm)
22"
(559mm)
4"(102mm)
1"
(25mm)
27
7
/8"
(708mm)
18"
(457mm)
4"
(102mm)
1"
(25mm)
19
5
/
8
"
(498mm)
1"
(25mm)
21
7
/
8
"
(556mm)
1"
(25mm)
16 5/8"
(422mm)
6"
(152mm)
28"
(711mm)
19 5/8"
(498mm)
21
7
/8"
(556mm)
6"
(152mm)
6"
(152mm)
6"
(152mm)
27"
(686mm)
3"
(76mm)
27"
(686mm)
3"
(76mm)
27"
(686mm)
3"
(76mm)
27"
(686mm)
3"
(76mm)
End Panels
Figure 58: 1" (25mm) and 6" (152mm) End Panel Dimensions – Self-Contained Floor Unit Ventilators
All Dim.
in Inches
Top View
165/8" (422mm) Deep
End Panels
5
/8" (498mm) Deep
19
End Panels
217/8" (556mm) Deep
End Panels
28" (711mm) Deep
End Panels
End View
With No
Cut-out
End View with 2
1
/2"
x 7"
(64mm x
178mm)
Cut-out
End View
with 4" x 18"
(102mm x
Dashed lines indicate kickplate
457mm)
Cut-out
End View
with 4" x 22"
(102mm x
559mm)
Cut-out
6" (152mm) End Panel Dimensions – Self-Contained Floor Unit Ventilator
Top View
End View
With No
Cut-out
50 AAF-HermanNelson Model AEQ Unit Ventilator
Details & Dimensions
+
++
+
+
+
+
+
+
+
+
+
+
+
W (see Table)
2
1
/2"
(63.5 mm)
14±
1
/8"
(356±3.2mm)
28"
(711 mm)
1 1/4"
(31.8 mm)
Optional Flange
7
/8"
(22.2 mm)
A (see Table)
Wall Intake Louvers & Grilles
Louvers are available with a vertical blade
conguration, constructed of heavy-gauge (unpainted,
painted, or clear anodized) aluminum.
The louver is divided in half horizontally to prevent condenser air recirculation.
A bird screen is provided on the leaving air side of the intake louver.
Louvers can be supplied with or without anges:
Flanged louvers are typically used for a panel wall
nish.
Unanged louvers are typically used for recessing
into a masonry wall.
An optional (factory-mounted) heavy-duty lattice ex­terior grille is available with horizontal and vertical lines that “line up” with the louver blades to present an aesthetic appearance.
Louvers are available in both horizontal and vertical
blade congurations:
Figure 59. Typical Wall Louver and Grille
Factory Mounted
Bird Screen
Fasteners
Bird Screen
Frame
Optional Flanges
Splitter Lines Up With Wall Sleeve Splitter
Figure 60: Grille Detail
Table 32: Wall Louver Dimensions (W)
Unit Size
024 28" × 84" 711 × 2134 9" 229 036 28" × 96" 711 × 2438 9" 229
044, 054 28" × 108" 711 × 2743 7" 178
Louver (H × W) Discharge Air (A)
Size (H × W) MM Opening (A) MM
Figure 61: Vertical Blade Louver, Without Flange
Outside View
Condenser Discharge Air
Condenser Inlet Air
Information Labels
Louver Blade
Optional Factory Mounted Exterior Grille
Figure 62: Vertical Blade Louver, Without Flange
Inside View
Mechanical Fasteners (Number Required Varies With Size of Louver)
Drain Notch At Bottom
Bottom Flange
Detail of Notches (Drain Holes)
Bird Screen On Side Toward Unit
AAF-HermanNelson Model AEQ Unit Ventilator 51
Condenser Discharge Air
Condenser Inlet Air
Louver with weep holes
Details & Dimensions
V entiMatic Shutter Assembly
Notes:
1. Horizontal blade louver shown. Vertical blade louver
also available with Ventimatic shutter.
2. Optional exterior grille matches unit ventilator louver
in material and design. Mounted in wall louver.
Figure 63: VenitMatic Shutter Assembly with Optional Grille
Two Shutter Assemblies Mounted on One Louver
B
(See table)
3. Optional interior grille mounting hardware is not included.
4. Louver leaves seal against plate to prevent air
inltration.
Aluminum Exterior Grille (optional)
A
(See table)
B
(See table)
Aluminum Louver
Bafe Plate
C
(See table)
Louver
Aluminum Exterior Grille (optional)
Center Cover
Steel Interior Grille (optional)
Steel Interior Grille (optional)
Aluminum Louver
Table 33: VentiMatic Shutter Assembly Dimensions & Maximum Air Capacities
Exterior Grille Louver Interior Grille Recommended Wall Opening
Width A Width B Width C for Louver
on Standard Louver Air Capacity
inches mm inches mm inches mm
23-3/4 603 24 610 27 686 24-1/4 616 10-1/2 267 1 0 500 236 36-3/4 933 36 914 39 991 36 -1/4 921 10-1/2 267 0 1 750 354 47-3/4 1213 48 1219 51 1295 48-1/4 1225 10-1/2 267 2 0 1000 472 59-3/4 1518 60 1524 63 1600 60-1/4 1530 10-1/2 267 1 1 1250 590 71-3/4 1822 72 1829 75 1905 72-1/4 1835 10-1/2 267 0 2 1500 708
Length Width
inches mm inches mm
VentiMatic Shutters to Mount Shutter(s) Max.
Maximum Number of VentiMatic
24" (610mm) 36" (914mm)
Shutter Shutter
inches mm
52 AAF-HermanNelson Model AEQ Unit Ventilator
Details & Dimensions
Sink & Bubbler Cabinet
Notes:
1 Sink top is one-piece, stainless steel construction
with sound-deadening coating on the under side. Front edge has raised lip continuously from end to end.
2 Sliding doors available in decorator colors.
Figure 64: Sink and Bubbler
Top View
Faucet
Bubbler
30-1/8" 765mm
3 Sink and bubbler basin drains equipped with 1-1/2"
O.D. tail pieces, all chrome plated brass.
4 Sink faucet and bubbler valve are shipped loose for
eld installation by the installing contractor.
5 Sink and bubbler top is designed to project 1/16"
higher and 3/16" deeper than the adjoining cabi­nets, unit ventilator or end panels.
Note: Sink & Bubbler and Storage Cabinets, are
provided by others. Contact your McQuay sales representative for details.
Piping Space
48" (1219mm)
Front Skirt with Air Inlet for
Radiation Style Cabinet
Front View
Figure 65: Standard Storage Cabinet
Front Skirt with Air Inlet for
Radiation Style Cabinet or
VentiMatic Shutter
Front View
Solid Skirt for Standard
Style Cabinet
Solid Skirt for Standard
Style Cabinet
30"
762mm
Side View
A
Side View
Total Depth Piping Space
“A” “B”
16-5/8" – 19-5/8" 3-9/16" 21-7/8" 5-13/16" 28" 11-15/16"
B
AAF-HermanNelson Model AEQ Unit Ventilator 53
Details & Dimensions
Utility Compartment & Filler Sections
Filler sections are furnished in 18" and 24" lengths. They are provided with enough hardware to assemble
one right hand and one left hand ller having a
combined length of 18"/24" or less. The minimum length
of one ller after cutting is 3". The ller section may be
used between a cabinet and the wall, between a unit and the wall, between a unit and cabinets, or between cabinets.
Figure 66: Accessories
12"
A
305mm
Top Panel
(Steel)
A A A
Note: Utility Compartments and Filler Sections are
provided by others. Contact your McQuay sales representative for details.
18", 24"
Laminate T op
Laminate T op
Utility Compartment
Figure 67: Utility Compartment Details
A
30"
762mm
3"
(76mm)
12"
(305mm)
Front View
Total Depth Piping Space
“A” “B”
16-5/8" – 19-5/8" 3-9/16" 21-7/8" 5-13/16" 28" 11-15/16"
3" (76mm)
Side View
Corner Filler Sections
12"
(305mm)
B
28"
660mm
14" 356mm
1"
(25mm)
12"
(305mm)
54 AAF-HermanNelson Model AEQ Unit Ventilator
Wiring Diagrams
CAUTION
Use copper conductors only. Unit terminals are not
designed to accept other types of conductors. Failure
to do so may damage the equipment.
DANGER
Disconnect alll electrical power before
servicing unit to prevent injury or death due
CAUTION
to electrical shock.
Refer to unit wiring diagram located on inside of right
front panel, for actual wiring. Improper wiring can cause
MicroTech II Wiring Diagram – Typical
Figure 68 - MicroTech II Wiring Diagram – Model AE Direct Expansion Cooling with Electric Heat, Valve Control 460 Volt/3Ph
Note: Please refer to Schematic on Unit Panel
AAF-HermanNelson Model AEQ Unit Ventilator 55
equipment and property damage.
Wiring Diagrams
Typical Wall Sensors Diagram
Figure 68: Wall-Mounted Temperature Sensor Wiring for Wall Sensor
Figure 69: External Input Wiring Examples with or without Daisy Chaining of Units
Unit Ventilator #1
P1
Connector
GND
Comm
BI-6 BI-5 BI-4 BI-3
Unit Ventilator #2
P1
Connector
GND
Comm
BI-6 BI-5 BI-4 BI-3
Unit Ventilator #3
P1
Connector
GND
Comm
BI-6 BI-5 BI-4 BI-3
908A 907A 906A 905A 904A
908A 907A 906A 905A 904A
908A 907A 906A 905A 904A
896
896
896
Wire
Caps
Wire
Caps
Wire
Caps
Shield
Shield
Shield
External Input
Option 4 Device
(by Others)
WSHP
Boilerless System
(low temp switch)
External Input
Option 3 Device
(by Others)
Ventilation Lockout
(default) or
Exhaust Interlock
Factory Wiring
Field Wiring (by Others)
External Device (by Others)
External Input
Option 2 Device
(by Others)
Remote Shutdown
External Input
Option 1 Device
(by Others)
Unoccupied
Additional Units
56 AAF-HermanNelson Model AEQ Unit Ventilator
Wiring Diagrams
Figure 70: External Output Wiring – Single Unit
Unit Ventilator
UVC
xBO-2
Comm
xBO-1
BO-6 BO-6
Comm
24vac Supply
24vac Comm
P6
Connector
Wire
Caps 601A 602A 603A 604A 605A 606A 608A 610A
Shield
Factory Wiring
Field Wiring (by Others)
External Device (by Others)
Figure 71: External Output Wiring – Multiple Units Shown
Unit Ventilator #1
UVC
XBO-2 Comm
XBO-1
BO-6
BO-6
Comm
24vac Supply 24vac Comm
P6
Connector
Wire
Caps 601A 602A 603A 604A 605A 606A 608A 610A
Shield
Unit Ventilator #2
UVC
XBO-2 Comm
XBO-1
BO-6
BO-6
Comm
24vac Supply 24vac Comm
P6
Connector
601A 602A 603A 604A 605A 606A 608A 610A
Wire
Caps
Shield
Unit Ventilator #...X (last unit)
UVC
XBO-2 Comm
XBO-1
BO-6
BO-6
Comm
24vac Supply 24vac Comm
P6
Connector
601A 602A 603A 604A 605A 606A 608A 610A
Wire
Caps
External Output Option 1 Device
(by Others)
Lights On/Off
Signal
Motorized Water
Valve Open/Close
Additional Units
External Output
Option 2 Device
(by Others)
Fault Indication
or
or
Pump Restart
Signal
External Output Option 3 Device
(by Others)
Auxiliary Heat
Signal
or
Exhaust Fan
On/Off Signal
External Output
Option 2 Device
(by Others)
Fault Indication
or
Pump Restart
Signal
Factory Wiring
Field Wiring (by Others)
External Device (by Others)
AAF-HermanNelson Model AEQ Unit Ventilator 57
Guide Specications
AAF-HermanNelson Self-Contained Air Source Heat Pump Unit Ventilator
Model AEQ Guide Specications
General
Furnish and install where shown on plans, a complete self-contained, air cooled, heating and cooling unit
ventilator. This unit shall meet capacities, airow and conguration as shown on unit schedule.
Each standard unit must be listed by Underwriters Laboratories Inc. (U.L.) as complying with all safety standards.
The units shall ship fully assembled with the exception of the end panels which shall be packaged separately to allow easy access for piping and electrical rough-in. (Option: Wall sleeves shall be shipped in advance of unit for rough-in.)
Unit Construction
All internal sheet metal parts subject to corrosion must be made of galvanized steel. The entire frame must be welded construction to provide strength and rigidity. Frames assembled with sheet metal fasteners are not acceptable. Blow-thru design is not acceptable.
Cabinets
Exterior cabinet panels shall be constructed of heavy­gauge steel and every exposed corner must be welded and ground smooth for appearance and durability. All surfaces shall be cleaned and phosphatized, then painted with an oven baked powder paint. Top surface shall be Charcoal Bronze textured powder paint to resist
scratching and hide ngerprints. Front access panels
and top access door shall be supplied with tamper resistant fasteners.
Removable discharge grille shall be constructed of continuous, round edged, steel bars to provide a
10-degree vertical deection.
Adjustable side deection vanes shall be provided
beneath the discharge grille to give optimal lateral air distribution. (Option: A 1/4" (6mm) mesh screen shall be provided beneath the discharge grille to protect against objects being dropped through the discharge grille.)
dynamically balanced. Motor shall be permanent split capacitor (PSC) plug-in type located out of the airstream and have an internal thermal overload device (auto­reset). Fan speeds shall be controlled by High-Med­Low-Off switch. Fan/coil arrangement shall be draw-thru design for uniform coil face velocity and discharge air temperature.
Fan motors and controls shall have each hot line protected by factory installed cartridge type fuse(s) The unit manufacturer shall provide one (1) spare motor for each size and type of motor furnished as part of a unit ventilator, except units having double extended shaft motors shall be provided with one (1) spare fan board assembly for each unit size.
All components of the fan/motor assembly shall be removable from the front of the unit. The motor and fan shaft shall have sleeve type bearings with precision tolerances and shall not require oiling more than once annually.
Condenser Fans and Motors
The fan board and fan housings shall be constructed of galvanized steel. The fan motor and fan shaft shall have permanently lubricated ball bearings. Motor shall be permanent split capacitor (PSC) type. Fan wheels shall be forward curved centrifugal type.
Outdoor/Room Air Dampers
Each unit shall be provided with separate room air and outdoor air dampers. The room air damper shall be constructed of aluminum and counterbalanced against back pressure. Outdoor air damper shall be two-piece, double wall construction with 1/2" (13mm) thick, 1.5
lbs. (.68 kg) density berglass insulation sandwiched
between welded galvanized steel blades. Outdoor air damper shall have additional foam insulation on the exterior of the blades and end partitions. Dampers shall
be tted with blended mohair seals along all sealing
edges. Damper bearings shall be made of nylon or other material which does not require lubrication.
Room Air Fans and Motor
The motor and fan assembly shall be low speed design and shall be double inlet, forward curved centrifugal type with maximum fan speed of 1100 rpm. Fan wheels shall be constructed of dark, high density, injection molded polypropylene having high impact strength, chemical resistance and thermal stability. Assembly shall be direct drive type and shall be statically and
58 AAF-HermanNelson Model AEQ Unit Ventilator
Drain Pan
All units shall have a drain pan constructed of corrosion resistant composite. A drain outlet shall be provided on both ends of the pan. The drain hand of connection
shall be easily eld reversed to the opposite end. The
drain pan shall be able to be sloped in either direction for proper condensate removal. Drain shall be provided
with an optional secondary, overow drain connection
on both ends of the pan.
Guide Specications
Refrigeration System
The refrigeration section shall be constructed of galvanized steel and shall include a factory sealed, factory piped assembly consisting of a hermetically sealed compressor, a condenser coil, condenser fan and motor, and an evaporator coil. No condensate drain piping system shall be required as the cooling condensate is to be disposed of by directing it into the condenser fan scrolls for re-evaporator on the hot condenser coil. The equipment manufacturer is to be fully responsible for the integrity of the refrigerant piping and the entire refrigeration circult, including compressor. Condenser and evaporator coils shall be fully assembled and tested prior to shipment. The motor compressor unit shall be vibration isolated internally and externally and shall be connected in such a manner as to prevent transmission of vibration to other components within the section.
Single-phase only: Single-phase units shall have permanent split capacitor (PSC) compressor motor with compressor start relay.
Units with three-phase power: Shall utilize three­phase compressors for balanced electrical compressor loads.
The condenser coil shall be constructed of copper tubes mechanically expanded to embossed aluminum plate
ns. The unit shall be so designed as to allow access
to the entering side of the condenser coil for cleaning without opening the sealed refrigeration circuit. The evaporator coil shall be constructed of copper tubing
having embossed aluminum plate ns mechanically
bonded thereto and shall be positioned above a plastic drain pan.
Refrigerant shall be metered by a thermostatic expansion valve in lieu of capillary tubing to achieve evaporator performance and to protect the compressor
from oodback of liquid refrigerant. The refrigerant
section shall be adequately insulated to prevent “sweating.”
The unit shall be furnished and wired with compressor thermal/current overload and high pressure cutout. Gauge ports shall be provided to allow reading of refrigerant pressures at the suction and discharge of the compressor. Compressor shall be equipped with internal pressure relief valve to protect against excessive pressure buildup.(Optional) Electric Coils
Heating elements shall be of the open wire type. Electric heat shall be controlled in [three] stages. A capillary type high limit thermostat shall be provided to disconnect the heating elements through backup contactors if an overheat condition is detected. A front panel interlock switch shall be furnished to de-energize the electric resistance heating element when center front panel is opened. The water-to-refrigerant coil shall be stainless steel plate- to plate heat exchanger. Either type shall be constructed to be suitable for 300 lbs. (2069 kPa) water working pressure and 450 lbs. (3104 kPa) refrigerant pressure.
Filter
Filter shall be one-piece type. Throwaway lter shall be
factory furnished initially installed in the unit. [Option: Furnish _____________ extra set(s) of throw-
away lters.]
[Option: Furnish one set of wire mesh permanent lters as nal lter.]
[Option: Furnish one set of renewable (metal frame with
glass ber media) lters as nal lter.]
[Option: Furnish _____________ roll(s) of renewable
lter media.]
AAF-HermanNelson Model AEQ Unit Ventilator 59
Guide Specications
Acoustical Features
The compressor shall be mounted on compressor isolators for external vibration isolation. Compressor enclosure panels shall be 16-gauge minimum. Complete interior of compressor compartment shall be lined with a multi-functional material that serves as a sound barrier, an absorber of sound and also must act as a decoupler to the compressor enclosure. This multi-functional material shall have a mylar coating on
the face to act as a sound reector and to increase
the strength of the material. Damping material shall be textured foam type.
The exterior of the compressor compartment shall be coated with a high density damping material to eliminate impact noise and vibration. The right-hand front panel and the hinged top access door shall be coated with a high density material to minimize noise and vibration.
VentiMatic Shutter (Room Exhaust)
Where indicated, the unit ventilator manufacturer shall provide an “in-room” air relief VentiMatic shutter mounted on a separate wall intake louver to prevent excessive static pressure build-up In the room. The VentiMatic shutter shall be constructed of galvanized steel with shutter dampers of woven glass fabric impregnated with silicone rubber.
Temperature Controls
The unit ventilator manufacturer shall provide factory installed, calibrated, and tested temperature controls. Units that are capable of providing up to 100% outside air shall provide a microprocessor-based Direct Digital Control (DDC) that can monitor conditions and automatically adjust unit operations to maintain these requirements. This DDC control shall have the following tenant adjustments: (1) room temperature setpoint, (2) minimum percent outdoor air setting, and (3) unoccupied setpoint (offset). An LED status/ fault indicator shall be furnished for inspection and a communications port shall be incorporated to allow manipulation by a remote PC. The remote PC shall be able to access and change pertinent operating and room conditions from a remote location. The microprocessor-based control must be capable of communicating to a local IBM-compatible PC using the RS-232 protocol. When using this remote PC, the unit must be capable of reacting to changes made by the remote PC. The remote PC must also be able to access all pertinent operating and room conditions.
Network System
1. The unit control system shall perform all unit control functions, unit diagnostics and safeties. The unit shall operate in the standalone or network capable mode of AAF-HermanNelson Model AEQ Unit Ven-
tilators 103 Guide Specications operation. Field
furnished and installed controls shall not be allowed. When network capable, network communication modules shall be factory installed, tested and able to communicate via plug-in communication modules that connect directly to the UVC using:
SELECT one:
a. LonMark Space Comfort Control that supports the
LonMark SCC prole number 8500-10 allowing
LonWorks network communication capability to the UVC.
b. BACnet Master Slave/Token Passing (MS/TP) al-
lowing the UVC to inter-operate with systems that use the BACnet (MS/TP) protocol with a confor­mance level of 3 meeting the requirements of ANSI/ ASHRAE 135- 1955 standard for BACnet systems.
c. Metasys N2 Open allowing Metasys N2 Open net-
work communication capability to the UVC.
2. Controls shall allow monitoring and adjustment from a portable IBM compatible PC using the applicable software. When using this PC and software, the unit shall be capable of reacting to commands for changes in control sequence and set points.
Room Temperature Sensor and Tenant Override Options
Unit-Mounted
All units shall come equipped with a factory mounted room temperature sensor located in a sampling chamber (front, center panel) where room air is continuously drawn through for fast response to temperature changes in the room. When using a remote wall-mounted temperature sensor the ability shall exist to simply disconnect the unit-mounted temperature sensor using the provided quick disconnect plug. Tenant override switch shall be factory mounted next to the Local User Interface (LUI) Touch Pad to provide a momentary contact closure that causes the unit to enter the “tenant override” operating mode for a set time period (adjustable) of 120 minutes. The room temperature sensor and override switch shall (SELECT one):
A both be unit-mounted. B be an optional wall-mounted temperature sensor,
with integral tenant override capability
60 AAF-HermanNelson Model AEQ Unit Ventilator
Guide Specications
Sensor with Tenant Override and Setpoint Adjustment
Wall-Mounted
A sensor with integral tenant override and status LED shall be furnished with the unit ventilators. This sensor shall also contain a manually adjustable temperature setting allowing the controller setpoint to be increased or decreased by 3°F (2°C).
(Optional) Night Control with Unit-Mounted Time Clock
Each unit shall be furnished with a unit-mounted, eld
programmed time clock for day/night changeover. This clock will provide up to 150 hours of operation during a power outage.
Wall Sleeve
The galvanized steel, one-piece wall sleeve shall be set in a wall opening and butted up directly against the intake louver. Where it is not possible to butt the wall sleeve against the wall intake louver, the contractor shall fabricate and install horizontal air splitters between the louver and wall sleeve to provide an airtight separation between condenser discharge and return air. The wall sleeve is to be permanently fastened in place and shall be suitably sealed, caulked or grouted by the contractor around the entire perimeter to prevent air leakage.
The wall sleeve shall be tted with an electrical junction box containing a main “on-off ” switch. All eld wiring
connections shall be made in this wall sleeve junction box.
(It shall be the installing contractor’s responsibility to
make the nal load side power wiring connections
between the wall sleeve junction box and the unit terminal block (including the wiring going to the electric heating elements.The wall sleeve shall be cartoned separately and shipped to the jobsite preceding the unit
ventilator. Junction box shall ship separately for eld
installation.)
Wall Intake Louver
The louver shall be supplied by the unit manufacturer and shall be of heavy-gauge (unpainted, painted, or clear anodized) aluminum construction. The louver shall be of the vertical blade type and shall be divided in half horizontally across the louver to prevent condenser air recirculation. A 1/2" (13mm) square mesh bird screen shall be provided on the backside of the wall intake louver. All louvers shall be 28" (711mm) high by 2-1/2" (57mm) thick and suitable for both masonry and panel wall construction. The frame of the louver shall have weep holes along the bottom. Lintels shall be provided by the contractor above the louver opening.
Optional: Heavy-duty lattice grille horizontal and vertical lines shall “line up” with the louver blades to present an aesthetic appearance. Grille shall be fabricated from mill
nish aluminum.
Agency Listing
Unit ventilators shall be listed by Underwriters Laboratories Inc. (U.L.) for the United States and Canada. Unit ventilation rated per AHRI standard
840. Motors shall conform to the latest applicable requirements of NEMA, IEEE, ANSI, and NEC
standards. Unit to be certied and labeled compliant
with the seismic design provisions of the International Building Code (IBC) Chapter 16 and independent test agency requirements of Chapter 17.
AAF-HermanNelson Model AEQ Unit Ventilator 61
®
McQuay Training and Development
Now that you have made an investment in modern, efcient McQuay equipment, its care should be a high
priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form
933-43285Y. To nd your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Manufactured in an ISO Certied Facility
©2010 McQuay International • www.mcquay.com • 800-432-1342
CAT 1650 (8-10)
Loading...