NOTE: Model numbers ending in HP indicate High Pressure water regulating
valve. Standard pressure = 150 psi (10.34 bar) High pressure = 350 psi
(24.13 bar)
Self-Contained
Water-Cooled
SD0303W
SY0305W
SD0323W
SY0325W
SR0421W
SD0423W
SY0425W
SD0453W
SY0455W
SR0501W
SD0503W
SY0505W
SD0603W
SY0605W
SR0851W
SD0853W
SY0855W
SD1003W
SY1005W
SD1003WM
SD1203W
SY1205W
SD1403W
SY1405W
SD1403WM
SR1601W
SD1603W
SY1605W
SR1801W
SD1803W
SY1805W
SD3303W
SD3303WHP
SY3305W
SY3305WHP
SD3303WM
Remote
----
----
----
----
----
----
----
----
----
SR0590N
SD0592N
SY0594N
SD0692N
SY0694N
SR0890N
SD0892N
SY0894N
SD1092N
SY1094N
---
---
SD1492N
SY1494N
SR1690N
SD1692N
SY1694N
SR1890N
SD1892N
SY1894N
----
----
----
----
----
Remove all ice machine panels before lifting and
installing.
ICE DEFLECTOR
An ice deflector is required when the ice machine is
installed on a bin. An ice deflector is not required when
the ice machine is installed on a dispenser.
Manitowoc ice machines require a deflector when
installed on an ice storage bin.
Prior to using a non-Manitowoc ice storage system
with Manitowoc ice machines, contact the
manufacturer to assure their ice deflector is
compatible with Manitowoc ice machines.
Do not operate equipment that has been misused,
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and
knowledge, unless they have been given
supervision concerning use of the appliance by a
person responsible for their safety.
S3000C ice machines are only approved for use on
Manitowoc B1100-00/B1400-00 bins.
BIN INSTALLATION
•All ice machines installed on a bin require an ice
deflector.
•Manitowoc bins have a deflector installed and require
no modifications when used with a forward facing
evaporator.
•Ice machines with multiple evaporators require a
deflector kit.
DISPENSER INSTALLATION
•No adapter is needed for machines that match the
size of the dispenser unless required by the
dispenser manufacturer.
•No deflector is required unless specified by the
dispenser manufacturer.
•A bin thermostat to control ice level is recommended.
4Part Number 000006520 11/11
Section 2
!
Caution
Installation Instructions
Location of Ice Machine
The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met,
select another location.
•The location must be free of airborne and other
contaminants.
•The air temperature must be at least 35°F (1.6°C),
but must not exceed 110°F (43.4°C).
•Remote air cooled - The air temperature must be at
least -20°F (-29°C), but must not exceed 120°F
(49°C).
•The location must not be near heat-generating
equipment or in direct sunlight and must be protected
from weather.
•The location must not obstruct air flow through or
around the ice machine. Refer to the chart below for
clearance requirements.
Clearance Requirements
S300
Top/Sides16" (40.6 cm)8" (20.3 cm)
Back5" (12.7 cm)5" (12.7 cm)
S320/S450/S500/
S600/S850/S1000
Top/Sides8" (20.3 cm)8" (20.3 cm)
Back5" (12.7 cm)5" (12.7 cm)
S420
Top/Sides12" (30.5 cm)8" (20.3 cm)
Back5" (12.7 cm)5" (12.7 cm)
S500
230/50/1 Tropical Rating
To p24" (61 cm)
Sides/Back12" (30.5 cm)
S1200
To p8" (20.3 cm)8" (20.3 cm)
Sides12" (30.5 cm)8" (20.3 cm)
S1400/S1600/S1800
Top/Sides24" (61.0 cm)8" (20.3 cm)
Back12" (30.5 cm)5" (12.7 cm)
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Water-Cooled
Water-Cooled
and Remote*
Water-Cooled
and Remote*
Self-Contained Air-Cooled
Water-Cooled
and Remote*
Water-Cooled
and Remote*
S3300**Water-Cooled
Top/Sides8" (20.3 cm)
Back24" (61.0 cm)
*There is no minimum clearance required for water-cooled or
remote ice machines. This value is recommended for efficient
operation and servicing only.
**S3300 - 24” on all sides is recommended to allow access without
moving the bin/ice machine.
The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C). Failure
caused by exposure to freezing temperatures is not
covered by the warranty.
B.T.U./Hour
Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Air Conditioning
Heat of Rejection
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when sizing
air conditioning equipment where self-contained aircooled ice machines are installed.
This information is also necessary when evaluating the
benefits of using water-cooled or remote condensers to
reduce air conditioning loads. The amount of heat added
to an air conditioned environment by an ice machine
using a water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important
when sizing a cooling tower for a water-cooled
condenser. Use the peak figure for sizing the cooling
tower.
Peak
Removing Drain Plug and Leveling the Ice
Storage Bin
1. Remove threaded plug from drain fitting.
2. Screw the leveling legs onto the bottom of the bin.
3. Screw the foot of each leg in as far as possible.
The legs must be screwed in tightly to prevent them
from bending.
4. Move the bin into its final position.
5. Level the bin to assure that the bin door closes and
seals properly. Use a level on top of the bin. Turn the
base of each foot as necessary to level the bin.
6. Inspect bin gasket prior to ice machine installation.
(Manitowoc bins come with a closed cell foam
gasket installed along the top surface of the bin.)
7. Remove all panels from ice machine before lifting.
and installing on bin. Remove both front panels, top
cover, left and right side panels.
Air Baffle
SELF-CONTAINED AIR-COOLED ONLY
The air-cooled baffle prevents condenser air from
recirculating. To install:
1. Remove the back panel screws next to the
condenser.
2. Align the mounting holes in the air baffle with the
screw holes and reinstall the screws.
6
Part Number 000006520 11/11
Section 2Installation Instructions
!
Warning
!
Warning
Important
Electrical Service
All wiring must conform to local, state and national
codes.
VOLTAGE
The maximum allowable voltage variation is ±10% of the
rated voltage at ice machine start-up (when the electrical
load is highest).
The ice machine must be grounded in accordance
with national and local electrical codes.
All electrical work, including wire routing and grounding,
must conform to local, state and national electrical
codes. The following precautions must be observed:
•The ice machine must be grounded.
•A separate fuse/circuit breaker must be provided for
each ice machine.
•A qualified electrician must determine proper wire
size dependent upon location, materials used and
length of run (minimum circuit ampacity can be used
to help select the wire size).
•The maximum allowable voltage variation is +/-10 of
the rated voltage at ice machine start-up (when the
electrical load is highest).
•Check all green ground screws in the control box and
verify they are tight before starting the ice machine.
Observe correct polarity of incoming line voltage.
Incorrect polarity can lead to erratic ice machine
operation.
FUSE/CIRCUIT BREAKER
A separate fuse/circuit breaker must be provided for
each ice machine. Circuit breakers must be H.A.C.R.
rated (does not apply in Canada).
MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select the
wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)
The wire size (or gauge) is also dependent upon
location, materials used, length of run, etc., so it must be
determined by a qualified electrician.
ELECTRICAL REQUIREMENTS
Refer to Ice Machine Model/Serial Plate for voltage/
amperage specifications.
GROUND FAULT CIRCUIT INTERRUPTER
Ground Fault Circuit Interrupter (GFCI/GFI) protection is
a system that shuts down the electric circuit (opens it)
when it senses an unexpected loss of power,
presumably to ground. Manitowoc Ice does not
recommend the use of a GFCI/GFI circuit protection with
our equipment. If code requires the use of a GFCI/GFI
then you must follow the local code. The circuit must be
dedicated, sized properly and there must be a panel
GFCI/GFI breaker. We do not recommend GFCI/GFI
outlets as they are known for more intermittent nuisance
trips than panel breakers.
MINIMUM POWER CORD SPECIFICATIONS
Maximum
Breaker Size
15 amp14 gauge6 feet (1.83 m)
20 amp12 gauge6 feet (1.83 m)
30 amp10 gauge6 feet (1.83 m)
40 amp8 gauge6 feet (1.83 m)
Minimum
Wire Size
Maximum Length of
Power Cord
If a power cord is used, the wire size to the receptacle is
dependent upon location, materials used, length of run,
etc., so it must be determined by a qualified electrician.
Local, state or national requirements will supersede our
minimum requirements.
FOR UNITED KINGDOM ONLY
As the colors of the wires in the mains lead of the appliance may not
correspond with the colored markings identifying the terminals in your plug,
proceed as follows:
•The wire which is colored green and yellow
terminal in the plug which is marked with the letter E or by the earth
ground symbol or colored green or green and yellow.
•The wire colored blue
with the letter N or colored black.
•The wire colored brown
marked with the letter L or colored red.
must be connected to the terminal which is marked
must be connected to the terminal which is
must be connected to the
Part Number 000006520 11/117
Installation InstructionsSection 2
Important
Important
Maximum Breaker Size & Minimum Circuit Amperage Chart
Due to continuous improvements, this information is for reference only.
Please refer to the ice machine serial number tag to verify electrical data.
Serial tag information overrides information listed on this page.
S3300 Only - Verify the direction of rotation correct is correct on the 3ph
scroll compressor. The ice machine will have high suction pressure, low
discharge pressure and will be noticeably loud. Reverse any two incoming
power leads to reverse rotation.
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
8
Part Number 000006520 11/11
Section 2Installation Instructions
!
Caution
Important
Water Supply and Drain Requirements
WATER SUPPLY
Local water conditions may require treatment of the
water to inhibit scale formation, filter sediment, and
remove chlorine odor and taste.
WATER INLET LINES
Follow these guidelines to install water inlet lines:
•If you are installing a Manitowoc Arctic Pure water
filter system, refer to the Installation Instructions
supplied with the filter system for ice making water
inlet connections.
•Do not connect the ice machine to a hot water
supply. Be sure all hot water restrictors installed for
other equipment are working. (Check valves on sink
faucets, dishwashers, etc.)
•If water pressure exceeds the maximum
recommended pressure of 80 psi (552 kPa), obtain a
water pressure regulator from your Manitowoc
distributor.
•Install a water shut-off valve for both the ice making
and condenser water lines.
•Insulate water inlet lines to prevent condensation.
WATER-COOLED CONDENSER WATER PRESSURE
Water pressure at the condenser cannot exceed 150
psig (10.34 bar) with the standard water-regulating
valve. Contact your distributor if your water pressure is
greater than 150 psig (10.34 bar). A special order
condensing unit is available that allows water pressure
up to 350 psig (24.13 bar)
COOLING TOWER APPLICATIONS
(WATER-COOLED MODELS)
A water cooling tower installation does not require
modification of the ice machine. The water regulator
valve for the condenser continues to control the
refrigeration discharge pressure.
It is necessary to know the amount of heat rejection, and
the pressure drop through the condenser and water
valves (inlet and outlet) when using a cooling tower on
an ice machine.
•Water entering the condenser must not exceed
90°F (32.2°C).
•Water flow through the condenser must not exceed
5 gallons (19 liters) per minute.
•Allow for a pressure drop of 7 psi (0.5 bar) between
the condenser water inlet and the outlet of the ice
machine.
Do not apply heat to water valve inlet fitting. This will
damage plastic water inlet connection.
DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to
prevent drain water from flowing back into the ice
machine and storage bin:
•Drain lines must have a 1.5 inch drop per 5 feet of
run (2.5 cm per meter), and must not create traps.
•The floor drain must be large enough to
accommodate drainage from all drains.
•Run separate bin and ice machine drain lines.
Insulate them to prevent condensation.
•Vent the bin and ice machine drain to the
atmosphere. Do not vent the condenser drain on
water-cooled models.
•S3300 requires base drain connection (1" FPT).
•Water exiting the condenser must not exceed
110°F (43.3°C).
.
The Commonwealth of Massachusetts requires that
all water-cooled models must be connected only to a
closed loop, cooling tower system.
Part Number 000006520 11/119
Installation InstructionsSection 2
!
Caution
ELECTRICAL ENTRANCE
18" (46 CM) VENT TUBE
AIR GAP
1/2" (1.3 CM) MIN
DRAIN ID
1/2" DRAIN CONNECTION
PLASTIC FITTING ON OPPOSITE
SIDE DO NOT APPLY HEAT
OPEN, TRAPPED AND
VENTED DRAIN
DO NOT TRAP DRAIN LINE,
LEAVE AIR GAP BETWEEN
DRAIN TUBE AND DRAIN
3/8" FPT ICE MAKING WATER INLET FITTING,
PLASTIC FITTING ON OPPOSITE SIDE DO NOT
APPLY HEAT
1/2" FPT CONDENSER WATER DRAIN
(WATER COOLED UNITS ONLY)
3/8" FPT CONDENSER WATER INLET
(WATER COOLED UNITS ONLY)
1/2" CPVC SOCKET AUXILLARY
BASE DRAIN
Water Supply and Drain Line Sizing/Connections
Plumbing must conform to state and local codes.
Location
Ice Making
Water Inlet
Ice Making
Water Drain
Condenser
Water Inlet
Condenser
Water Drain
Bin Drain
Large Capacity
Bin Drain
Water
Temperature
35°F (1.6°C) Min.
90°F (32.2°C) Max.
------
90°F (32.2°C) Max.
------
------3/4" (1.91 cm) Female Pipe Thread
------1" (2.54 cm) Male Pipe Thread1" (2.54 cm) min. inside diameter
The exact locations of inlets and drains for the model you are working on may vary.
Each remote ice machine ships from the factory with a
refrigerant charge appropriate for installation with line
sets of up to 50' (15.25 m). The serial tag on the ice
machine indicates the refrigerant charge.
Additional refrigerant may be required for installations
using line sets between 50' and 100' (15.25-30.5 m)
long. If additional refrigerant is required, refer to the
chart below for the correct amount to be added.
EPA CERTIFIED TECHNICIANS
If remote line set length is between 50' and 100'
(15.25 and 30.5 m), add additional refrigerant to the
nameplate charge. Refer to the table below for the
model being worked on.
Tubing length: _________________________________
Refrigerant added to nameplate: ___________________
New total refrigerant charge: ______________________
Manitowoc remote systems are only approved and
warranted as a complete new package. Warranty on
the refrigeration system will be void if a new ice
machine head section is connected to pre-existing
(used) tubing or remote condensers.
The ice machine contains refrigerant charge.
Installation of the line sets must be performed by a
properly trained and EPA certified refrigeration
technician aware of the dangers of dealing withrefrigerant charged equipment.
Never add more than nameplate charge to the
refrigeration system for any application.
Refrigerant to be Added for
50'-100' Line Sets
Maximum System Charge
(Never Exceed)
Part Number 000006520 11/1111
Installation InstructionsSection 2
!
Caution
GENERAL
Condensers must be mounted horizontally with the fan
motor on top with nothing obstructing it. There must be
at least a 16" (41 cm) clearance from the bottom for air
intake. The front coupling panel and one other panel
(back or side) must also be unobstructed.
Remote condenser installations consist of vertical and
horizontal line sets between the ice machine and the
condenser. When combined, they must fit within
approved specifications. The following guidelines,
drawings and calculation methods must be followed to
verify a proper remote condenser installation.
The 60 month compressor warranty (including the
36 month labor replacement warranty) will not apply
if the remote ice machine is not installed according
to specifications.
This warranty also will not apply if the refrigeration
system is modified with a condenser, heat reclaim
device, or other parts or assemblies not
manufactured by Manitowoc Ice unless specifically
approved in writing by Manitowoc Ice.
GUIDELINES FOR ROUTING LINE SETS
First, cut a 2.5" (6.35 cm) circular hole in the wall or roof
for tubing routing. The line set end with the 90° bend will
connect to the ice machine. The straight end will connect
to the remote condenser.
Follow these guidelines when routing the refrigerant
lines. This will help ensure proper performance and
service accessibility.
1. Optional - Make the service loop in the line sets (as
shown below). This permits easy access to the ice
machine for cleaning and service. Do not use hard
rigid copper at this location.
2. Required - Do not form traps in the refrigeration lines
(except the service loop). Refrigerant oil must be
free to drain toward the ice machine or the
condenser. Route excess tubing in a supported
downward horizontal spiral (as shown below). Do
not coil tubing vertically.
3. Required - Keep outdoor refrigerant line runs as
short as possible.
The maximum length is 100' (30.5 m).
The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge
sufficient to operate the ice machine in ambient
temperatures between -20°F (-29°C) and 120°F (49°C),
with line set lengths of up to 100' (30.5 m).
Line Set Rise/Drop
The maximum rise is 35' (10.7 m).
The maximum drop is 15' (4.5 m).
If a line set has a rise followed by a drop, another
rise cannot be made. Likewise, if a line set has a
drop followed by a rise, another drop cannot be
made.
Calculated Line Set Distance
The maximum calculated distance is 150' (45.7 m).
Line set rises, drops, horizontal runs (or combinations of
these) in excess of the stated maximums will exceed
compressor start-up and design limits. This will cause
poor oil return to the compressor.
Make the following calculations to make sure the line set
layout is within specifications.
1. Insert the measured rise into the formula below.
Multiply by 1.7 to get the calculated rise.
(Example: A condenser located 10 feet above the
ice machine has a calculated rise of 17 feet.)
2. Insert the measured drop into the formula below.
Multiply by 6.6 to get the calculated drop.
(Example. A condenser located 10 feet below the
ice machine has a calculated drop of 66 feet.)
3. Insert the measured horizontal distance into the
formula below. No calculation is necessary.
4. Add together the calculated rise, calculated drop,
and horizontal distance to get the total calculated distance. If this total exceeds 150' (45.7 m), move
the condenser to a new location and perform the
calculations again.
Maximum Line Set Distance Formula
Step 1.Measured Rise (35' [10.7 m] Maximum)______ x 1.7=_______ Calculated Rise
Step 2.Measured Drop (15' [4.5 m] Maximum)______ x 6.6=_______ Calculated Drop
Step 3.Measured Horizontal Distance (100' [30.5 m] Maximum)_______ Horizontal Distance
Step 4.Total Calculated Distance 150' (45.7 m)_______ Total Calculated Distance
H
D
H
R
D
Part Number 000006520 11/1113
Installation InstructionsSection 2
SV1603
REMOVE FRONT, TOP,
AND LEFT SIDE PANEL
FOR ACCESS TO
RECEIVER VALVE
TURN
COUNTERCLOCKWISE
TO OPEN
RECEIVER SERVICE
VALVE CAP (TURN
COUNTERCLOCKWISE
TO REMOVE)
LENGTHENING OR REDUCING LINE SET LENGTHS
In most cases, by routing the line set properly,
shortening will not be necessary. When shortening or
lengthening is required, do so before connecting the line
set to the ice machine or the remote condenser. This
prevents the loss of refrigerant in the ice machine or
condenser.
The quick connect fittings on the line sets are equipped
with Schraeder valves. Use these valves to recover any
vapor charge from the line set. When lengthening or
shortening lines follow good refrigeration practices,
purge with nitrogen and insulate all tubing. Do not
change the tube sizes. Evacuate the lines and place
about 5 oz (143g) of vapor refrigerant charge in each
line.
CONNECTING A LINE SET
1. Remove the dust caps from the line set, condenser
and ice machine.
2. Apply refrigeration oil to the threads on the quick
disconnect couplers before connecting them to the
condenser.
3. Carefully thread the female fitting to the condenser
or ice machine by hand.
4. Tighten the couplings with a wrench until they
bottom out.
REMOTE RECEIVER SERVICE VALVE
The receiver service valve is closed during shipment.
Open the valve prior to starting the ice machine.
1. Remove the top and left side panels.
2. Remove the receiver service valve cap.
3. Backseat (open) the valve.
4. Reinstall the cap and panels.
5. Turn an additional 1/4 turn to ensure proper brassto-brass seating. Torque to the following
specifications:
Liquid LineDischarge Line
10-12 ft lb.
(13.5-16.2 N•m)
35-45 ft lb.
(47.5-61.0 N•m)
6. Check all fittings and valve caps for leaks.
7. Make sure Schraeder cores are seated and
Schraeder caps are on and tight.
Backseating the Receiver Service Valve
14
Part Number 000006520 11/11
Section 2Installation Instructions
Important
!
Caution
!
Caution
Remote Ice Machine Usage with Non-Manitowoc Multi-Circuit Condensers
WARRANTY
The sixty (60) month compressor warranty, including
thirty six (36) month labor replacement warranty, shall not apply when the remote ice machine is not installed
within the remote specifications. The foregoing warranty
shall not apply to any ice machine installed and/or
maintained inconsistent with the technical instructions
provided by Manitowoc Ice, Inc. Performance may vary
from Sales specifications. S-Model ARI certified
standard ratings only apply when used with a Manitowoc
remote condenser.
If the design of the condenser meets the specifications,
Manitowoc’s only
to be extended to the Manitowoc manufactured part of
the system. Since Manitowoc does not
condenser in conjunction with the ice machine,
Manitowoc will not endorse, recommend, or approve the
condenser, and will not be responsible for its
performance or reliability.
Manitowoc warrants only complete new and unused
remote packages. Guaranteeing the integrity of a
new ice machine under the terms of our warranty
prohibits the use of pre-existing (used) tubing or
condensers.
HEAD PRESSURE CONTROL VALVE
Any remote condenser connected to a Manitowoc
S-Model Ice Machine must have a head pressure control
valve (available from Manitowoc Distributors) installed
on the condenser package. Manitowoc will not accept
substitute “off the shelf” head pressure control valves.
approval is for full warranty coverage
test the
FAN MOTOR
The condenser fan must be on during the complete ice
machine freeze cycle (do not cycle on fan cycle control).
The ice maker has a condenser fan motor circuit for use
with a Manitowoc condenser. It is recommended that this
circuit be used to control the condenser fan(s) on the
multi-circuit condenser to assure it is on at the proper
time. Do not exceed the rated amps for the fan motor
circuit listed on the ice machine’s serial tag.
INTERNAL CONDENSER VOLUME
The multi-circuit condenser internal volume must not be
less than or exceed that used by Manitowoc (see chart
on next page). Do not exceed internal volume and try
to add charge to compensate, as compressor failure
will result.
CONDENSER T
T is the difference in temperature between the
condensing refrigerant and entering air. The T should
be 15 to 20°F (-9.4 to -6.6°C) at the beginning of the
freeze cycle (peak load conditions) and drop down to
12 to 17°F (-11.1 to -8.3°C) during the last 75% of the
freeze cycle (average load conditions).
REFRIGERANT CHARGE
Remote ice machines have the serial plate refrigerant
charge (total system charge) located in the ice maker
section. (Remote condensers and line sets are supplied
with only a vapor charge.)
Never add more than nameplate charge to ice
machine for any application.
QUICK CONNECT FITTINGS
Do not use a fan cycling control to try to maintain
discharge pressure. Compressor failure will result.
Part Number 000006520 11/1115
The ice machine and line sets come with quick connect
fittings. It is recommended that matching quick connects
(available through Manitowoc Distributors) be installed in
the multi-circuit condenser, and that a vapor “holding”
charge, 5 oz. (150 ml), of proper refrigerant be added to
the condenser prior to connection of the ice machine or
line set to the condenser.
Typical Single Circuit Remote Condenser Installation
16
Part Number 000006520 11/11
Section 2Installation Instructions
!
Warning
Installation Check List
Is the Ice Machine level?
Have all of the electrical and water
connections been made?
Has the supply voltage been tested and
checked against the rating on the nameplate?
Is there proper clearance around the ice
machine for air circulation?
Is the ice machine grounded and polarity
correct?
Has the ice machine been installed where
ambient temperatures will remain in the
range of 35° - 110°F (1.6° - 43.3°C)?
Has the ice machine been installed where the
incoming water temperature will remain in the
range of 35° - 90°F (1.6° - 32.2°C)?
Is there a separate drain for the potable
water, bin and water-cooled condenser?
Are the ice machine and bin drains vented?
S3300 Only - Is the compressor direction of
rotation correct? The ice machine will have
high suction pressure, low discharge
pressure and will be noticeably loud. Reverse
any two incoming power leads to reverse
rotation.
Additional Checks for Remote Models
Has the receiver service valve been opened?
Does the remote condenser fan operate
properly after start-up?
Has the remote condenser been located
where ambient temperatures will remain in
the range of -20° - 120°F (-29 - 49°C).
Is the line set routed properly?
Are both refrigeration lines to remote
condenser run so they do not lay in water and
are properly insulated?
Before Starting the Ice Machine
Are all electrical leads free from contact with
refrigeration lines and moving equipment?
Has the owner/operator been instructed
regarding maintenance and the use of
Manitowoc Cleaner and Sanitizer?
Has the owner/operator completed the
warranty registration card?
Has the ice machine and bin been sanitized?
Is the toggle switch set to ice? (The toggle
switch is located directly behind the front
panel).
Is the ice thickness control set correctly?
(Refer to Operational Checks to check/set the
correct ice bridge thickness).
All Manitowoc ice machines are factory-operated and
adjusted before shipment. Normally, new installations do
not require any adjustment.
To ensure proper operation, follow the Operational
Checks in Section 3 of this manual. Starting the ice
machine and completing the Operational Checks are the
responsibilities of the owner/operator.
Adjustments and maintenance procedures outlined in
this manual are not covered by the warranty.
Potential Personal Injury Situation
Do not operate equipment that has been misused.
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications.
Part Number 000006520 11/1117
Ice Making Sequence Of Operation
Section 3
Operation
NOTE: The toggle switch must be in the ice position and
the water curtain/ice dampers must be in place on the
evaporator before the ice machine will start.
Water Purge Cycle
The ice machine purges any remaining water from the
water trough down the drain.
Freeze Cycle
Water flows across the evaporator and the refrigeration
system chills the evaporator. Ice builds on the
evaporator until water contacts the ice thickness probe.
Harvest Cycle
Any remaining water is purged down the drain as
refrigerant gas warms the evaporator. When the
evaporator warms, the sheet of cubes slides off the
evaporator and into the storage bin. If all cubes fall clear
of the water curtain (or ice damper) the ice machine
starts another freeze cycle.
Off Cycle
If the water curtain or ice damper are held open by ice
cubes the ice machine shuts off. When the water curtain
or ice damper closes the ice machine starts a new cycle
at the water purge.
Control Board Timers
The control board has the following non-adjustable
timers:
•The ice machine is locked into the freeze cycle for 6
minutes before a harvest cycle can be initiated.
Freeze lock is bypassed after moving the toggle
switch from OFF to ICE position for the first cycle
only.
•The maximum freeze time is 60 minutes at which
time the control board automatically initiates a
harvest sequence.
•The maximum harvest time is 3.5 minutes for single
evaporators and 7 minutes for multiple evaporator
model. The control board automatically initiates a
freeze sequence when these times are exceeded.
SAFETY LIMITS
Safety limits are stored and indicated by the control
board after three cycles. The number of cycles required
to stop the ice machine varies for each safety limit.
•Safety Limit 1 all models - If the freeze time reaches
60 minutes, the control board automatically initiates a
harvest cycle. If 6 consecutive 60-minute freeze
cycles occur, the ice machine stops.
•Safety Limit 2 single evaporator models - If the
harvest time reaches 3.5 minutes, the control board
automatically returns the ice machine to the freeze
cycle. If 500 consecutive 3.5 minute harvest cycles
occur, the ice machine stops.
•Safety Limit 2 multiple evaporator models - If the
harvest time reaches 7 minutes, the control board
automatically returns the ice machine to the freeze
cycle. If 500 consecutive 7 minute harvest cycles
occur, the ice machine stops.
•Safety Limit 3 multiple evaporator models - If the low
refrigerant pressure control opens, the ice machine
shuts off and starts a 5 minute delay period. If 3
consecutive low pressure events occur, the ice
machine stops and flashes the harvest light.
Use the following procedures to determine if the control
board contains a safety limit indication.
1. Move the toggle switch to OFF.
2. Move the toggle switch back to ICE. Watch the
safety limit lights/harvest light on the control board. If
a safety limit has been recorded, the corresponding
light will blink once, twice or three times to indicate
which safety limit stopped the ice machine.
18 Part Number 000006520 11/11
Section 3Operation
Important
ADJUSTING SCREW
1/8" (3 mm)
ICE BRIDGE THICKNESS
Operational Checks
GENERAL
Manitowoc ice machines are factory-operated and
adjusted before shipment. Normally, new installations do
not require any adjustment.
To ensure proper operation, always follow the
Operational Checks:
•when starting the ice machine for the first time
•after a prolonged out of service period
•after cleaning and sanitizing
NOTE: Routine adjustments and maintenance
procedures are not covered by the warranty.
Scroll refrigeration compressors must be
operated for a minimum break in period of 24
hours before full ice production will be reached.
ICE THICKNESS CHECK
After a harvest cycle, inspect the ice cubes in the ice
storage bin. The ice thickness probe is factory-set to
maintain the ice bridge thickness at 1/8" (3 mm).
NOTE: Make sure the water curtain is in place when
performing this check. It prevents water from splashing
out of the water trough.
1. Inspect the bridge connecting the cubes. It should
be about 1/8" (3 mm) thick.
2. If adjustment is necessary, turn the ice thickness
probe adjustment screw clockwise to increase
bridge thickness, counterclockwise to decrease
bridge thickness. Set at 1/4" (6 mm) gap between
ice machine and evaporator as starting point, then
adjust to achieve a 1/8" (3 mm) bridge thickness.
NOTE: Turning the adjustment 1/3 of a turn will change
the ice thickness about 1/16" (1.5 mm).
Part Number 000006520 11/1119
Ice Thickness Check
3. Make sure the ice thickness probe wire and the
bracket do not restrict movement of the probe.
Section 4
!
Caution
!
Caution
!
Warning
Maintenance
Cleaning and Sanitizing
GENERAL
You are responsible for maintaining the ice machine in
accordance with the instructions in this manual.
Maintenance procedures are not covered by the
warranty.
Clean and sanitize the ice machine every six months for
efficient operation. If the ice machine requires more
frequent cleaning and sanitizing, consult a qualified
service company to test the water quality and
recommend appropriate water treatment. An extremely
dirty ice machine must be taken apart for cleaning and
sanitizing.
Manitowoc Ice Machine Cleaner and Sanitizer are the
only products approved for use in Manitowoc ice
machines.
Use only Manitowoc approved Ice Machine Cleaner
and Sanitizer for this application (Manitowoc
Cleaner part number 94-0546-3 and Manitowoc
Sanitizer part number 94-0565-3). It is a violation of
Federal law to use these solutions in a manner
inconsistent with their labeling. Read and
understand all labels printed on bottles before use.
Do not mix Cleaner and Sanitizer solutions together.
It is a violation of Federal law to use these solutions
in a manner inconsistent with their labeling.
CLEANING/SANITIZING PROCEDURE
This procedure must be performed a minimum of once
every six months.
•The ice machine and bin must be disassembled
cleaned and sanitized.
•All ice produced during the cleaning and sanitizing
procedures must be discarded.
•Removes mineral deposits from areas or surfaces
that are in direct contact with water.
HEAVILY SCALED CLEANING PROCEDURE
Perform this procedure if you have some or all of these
symptoms.
•Ice machine stops on Safety Shutdown.
•Your water has a high concentration of minerals.
•The ice machine has not been on a regular
maintenance schedule.
EXTERIOR CLEANING
Clean the area around the ice machine as often as
necessary to maintain cleanliness and efficient
operation. Use cleaners designed for use with stainless
steel products.
Sponge any dust and dirt off the outside of the ice
machine with mild soap and water. Wipe dry with a
clean, soft cloth.
Heavy stains should be removed with stainless steel
wool. Never use plain steel wool or abrasive pads. They
will scratch the panels.
Wear rubber gloves and safety goggles (and/or face
shield) when handling Ice Machine Cleaner or
Sanitizer.
20 Part Number 000006520 11/11
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.