Manitowoc Ice RF2379R Installation Manual

Flake & Nugget Ice Machines
RF / RFS / RNS Models
Installation, Operation and Maintenance Manual
This manual is updated as new information and models are released. Visit our website for the latest manual.
Part Number: 0000007644 8/14
Section 1 General Information
Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
RF2300 Bin Adapter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section 2 Installation Instructions
Location of Ice Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Water and Drain Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Maximum Breaker Size & Minimum Circuit Amperage Chart . . . . . . . . . . . . . . . . 10
Refrigeration System Installation
Remote Condensing Unit Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Refrigeration Line Set Installation
Remote Condensing Unit Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Additional Checks for QuietQube Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table of Contents
UnderCounter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Modular Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Potable Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Water Supply and Drain Line Sizing/Connections . . . . . . . . . . . . . . . . . . . . . . . 8
Drain Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fuse/Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ground Fault Circuit Interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Minimum Power Cord Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
For United Kingdom Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
QuietQube Remote Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
A. Line Set Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
B. Line Set Rise or Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C. Suction Line Oil Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Section 3 Operation
Evaporator Low Temperature Safety Thermostat and Bin Thermostat . . . . . . . . 19
RF0244/RF0266/RF0385/
RF0388/RF0399/RF0644 & RNS0244/RNS0385 Operation . . . . . . . . . . . . . . . . . . . 19
RFS0300 & RNS0300 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
RFS0650/RFS1200/RFS2300/RF1200/RF2300 Operation . . . . . . . . . . . . . . . . . . . . 20
2 Part Number 000007644 8/14
Section 4 Maintenance
Section 5 Customer Support
Table of Contents (continued)
Interior Cleaning and Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heavily Scaled Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Exterior Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Procedure to Clean Heavily Scaled Flake Ice Machines . . . . . . . . . . . . . . . . . . . 22
Removal of Parts for Cleaning/Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Ice Chute Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Air-Cooled Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Arctic Pure Water Filter System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Manitowoc Cleaner and Sanitizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Commercial Ice Machine Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Residential Ice Machine Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Part Number 000007644 8/14 3
Table of Contents (continued)
THIS PAGE INTENTIONALLY LEFT BLANK
4 Part Number 000007644 8/14
Section 1
!
Warning
!
Warning
!
Caution
General Information

Model Numbers

This manual covers the following models:

FLAKE UNDERCOUNTER MODELS NUGGET UNDERCOUNTER MODELS

Self-Contained
Air-Cooled
RF0244A RF0266A RF0385A RF0399A RF0644A

NUGGET MODULAR MODELS

Self-Contained
Air-Cooled
RNS0308A --- --- --- --­RNS0608A RNS0609W --- --- --­RNS1008A RNS1009W --- RNS1078C RCU1098

FLAKE MODULAR MODELS

Self-Contained
Air-Cooled
RFS0300A --- --- --- --­RFS0650A RFS0650W ---- --- --­RFS1200A RFS1200W RFS1279R RFS1278C RCU1075
RF2300A RF2300W RFS2379R RFS2378C RCU2375
Self-Contained
Water-Cooled
Self-Contained
Water-Cooled
Rack Unit
Head Section
Rack Unit
Head Section
Self-Contained
Air-Cooled
RNS0244A RNS0385A
QuietQube
Head Section
QuietQube
Head Section
Condensing Unit
Condensing Unit
RCU Remote
RCU Remote
Remove all ice machine panels before lifting and installing.
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision concerning use of the appliance by a person responsible for their safety.
Part Number 000007644 8/14 5
Flake ice machines must be installed on a bin. Flake ice machines cannot be installed on dispensers.
General Information Section 1
!
Warning

Adapters

RF2300 BIN ADAPTER INSTALLATION

PERSONAL INJURY POTENTIAL
RF2300 ice machines are not approved for use on B970 bins. RF2300 ice machines ship with a bracket that must be used when installing on B1100 and B1400 Series bins.
1. Refer to diagram. Place bracket on bin top and slide back to engage.
2. Place ice machine on bin: ice machine must fit between bracket and front ridge.
6
Part Number 000007644 8/14
Section 2
Installation Instructions

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.
The location must be free of airborne and other contaminants.
The air temperature must be at least 50°F (10°C), but must not exceed 110°F (43°C).
The water temperature must be at least 40°F (4°C), but must not exceed 90°F (32°C).
The location must not be near heat-generating equipment or in direct sunlight.
The location must be capable of supporting the weight of the ice machine and a full bin of ice.
The location must allow enough clearance for water, drain and electrical connections in the rear of the ice machine.
The location must not obstruct airflow through or around the ice machine.

CLEARANCE REQUIREMENTS

Undercounter Units Air-Cooled Water-Cooled
Top 0” (0 cm) 0” (0 cm)
Sides 2” (5 cm) 2” (5 cm)
Back 8" (20 cm) 8" (20 cm)
NOTE: Allowance must be made for removal when the ice machine is built in. Monthly removal of the top panel is required for cleaning & sanitizing.
Modular Units
Top/Sides 8" (20 cm) 8" (20 cm) 0" (0 cm)
Back 5" (13 cm) 5" (13 cm) 0" (0 cm)
RCU Units Remote Condensing Unit
Front/Back 24" (61 cm)
Sides/Top 6" (15.2 cm)
NOTE: Water-cooled/Remote condensing units only - there is no minimum clearance required. This value is recommended for efficient operation and servicing only.
Air-
Cooled
Water-
Cooled
QuietQube Air-Cooled

Installation Requirements

The ice machine and bin must be level.
Vent the ice machine and bin drains separately.
Bin drain termination must have an air gap.
A backflow preventer is required on water inlet lines.
The ice machine and bin must be sanitized after installation.
Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.
Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty.

Ice Machine Heat of Rejection

Series
Ice Machine
RFS1279R 7850 RFS2379R 15700
B.T.U./Hour
Heat of Rejection
Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment.
This information is also necessary when evaluating the benefits of using water-cooled or remote condensers to reduce air conditioning loads. The amount of heat added to an air conditioned environment by an ice machine using a water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important when sizing a cooling tower for a water-cooled condenser. Use the peak figure for sizing the cooling tower.

Rack Unit Connection Size

Model Suction Line Liquid Line
RFS1279R
RFS2379R
5/8 inch
(15.9 mm)
3/4 inch
(19 mm)
3/8 inch
(9.5 mm)
1/2 inch
(12.7 mm)
Part Number 000007644 8/14 7
Installation Instructions Section 2
!
Caution

Water and Drain Requirements

POTABLE WATER REQUIREMENTS

Follow these guidelines to install water inlet lines:
Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)
If water pressure exceeds the maximum of 80 psig (552 kPA) recommended pressure, obtain a water pressure regulator from your Manitowoc distributor.
Install a water shut-off valve and unio n for both the ice making and condenser water lines.
Insulate water inlet lines to prevent condensation.
Plumbing must conform to local codes.
Do not apply heat to water valve inlet fitting or over tighten. This will damage plastic water inlet connection.

COOLING TOWER APPLICATIONS

A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.
It is necessary to know the amount of heat rejectio n, and pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.
Water entering the co ndenser must not be lower than 37°F (3°C) or exceed 90°F (32°C).
Water flow through the con denser must not exceed 5 gal. (19 L) per minute.
allow for a pressure drop of 7 psi (48 kPa) between the condenser water inlet and the outlet of the ice machine.
Water exiting the condenser must not exceed 110°F (43°C).

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:
Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.
The floor drain must be large enough to accommodate drainage from all drains.
Run separate bin and water-cooled condenser drain lines. Insulate them to prevent condensation.
Vent the bin and ice machine drain to the atmosphere. The ice machine drain requires an 18" (46 cm) vent. Do not vent the condenser drain on water-cooled models.
Drains must have a union or other suitable means to allow in place disconnection from the ice machine when servicing is required.
8
Part Number 000007644 8/14
Section 2 Installation Instructions
VENT TUBE 18" (46 CM)
LONG
ROUTE
DRAIN TUBING TO OPEN SITE
DRAIN
ICE MAKING
WATER INLET
TUBING 3/8" MIN.
I.D. (.95 CM)
VENT TUBE 18" (46 CM)
LONG
SEPERATE BIN AND ICE
MACHINE DRAINS ARE
REQUIRED
ROUTE DRAIN TUBING TO
OPEN SITE DRAIN
WATER SHUT-OFF VALVE REQUIRED - ICE MAKING
WATER INLET TUBING 3/8"
MIN. I.D. (.95 CM)
MODULAR UNITS
UNDERCOUNTER UNITS

WATER SUPPLY AND DRAIN LINE SIZING/CONNECTIONS

Location
Potable
Water Inlet
Potable
Water Drain
Condenser Water Inlet
Condenser
Water Drain
Water Temp
Min/Max
40°/90°F
(4°/32°C)
--- --- 1/2" MPT
40°/90°F
(4°/32°C)
--- --- 1/2" MPT
Water Pressure
Min/Max
14/80 psi
(100/552 kPA)
20/150 psi
(138/1034 kPA)
Fitting/Min Tubing Size
3/8" FPT
3/8” FPT
RF2300 only = 1/2" FPT
Bin Drain --- --- 3/4" FPT
Large Capacity Bin Drain --- --- 1" FPT
Typical Water Supply Drain Installation
Part Number 000007644 8/14 9
Installation Instructions Section 2
!
Warning
!
Warning
Important

Electrical Service

GROUND FAULT CIRCUIT INTERRUPTER

All wiring must conform to local, state and national codes.

VOLTAGE

The maximum allowable voltage variation is ±1 0% of the rated voltage at ice machine star t-up (when the electrical load is highest).
The ice machine must be grounded in accordance with national and local electrical codes.
All electrical work, including wire routing and grounding, must conform to local, state and national electrical codes. The following precautions must be observed:
The ice machine must be grounded.
A separate fuse/circuit breaker must be provide d fo r each ice machine.
A qualified electrician must determine proper wire size dependent upon location, materials used and length of run (minimum circuit ampacity can be used to help select the wire size).
The maximum allowable voltage variation is +/-10 of the rated voltage at ice machine start-up (when the electrical load is highest).
Check all ground screws in the control box and verify they are tight before starting the ice machine.
We do not recommend the use of a GFCI/GFI circuit protection with our equipment. If a GFCI/GFI is required by code, use a GFCI/GFI breaker rather than outlet which is more prone to intermittent nuisance trips than panel circuit breakers.

MINIMUM POWER CORD SPECIFICATIONS

The wire size to the receptacle is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician. Local, state or national requirements will supersede our minimum requirements.

FOR UNITED KINGDOM ONLY

As the colors of the wires in the mains lead of the appliance may not correspond with the colored markings identifying the terminals in your plug, proceed as follows:
The wire which is colored green and yellow must be connected to the terminal in the plug which is marked with the letter E or by the earth ground symbol or colored green or green and yellow.
The wire colored blue with the letter N or colored black.
The wire colored brown marked with the letter L or colored red.
must be connected to the terminal which is marked
must be connected to the terminal which is
Observe correct polarity of incoming line voltage. Incorrect polarity can lead to erratic ice machine operation.

FUSE/CIRCUIT BREAKER

A dedicated circuit and a separate fuse/circuit breaker are required for each ice machine.
10
Part Number 000007644 8/14
Section 2 Installation Instructions
Important

Maximum Breaker Size & Minimum Circuit Amperage Chart

Due to continuous improvements, this information is for reference only. Please refer to the ice machine serial number tag to verify electrical data. Serial tag information overrides information listed on this page.
Air-Cooled Water-Cooled QuietQube
Series Ice
Machine
RF0244
RNS0244
RF0266
RF0385
RNS0385
RF0388
RF0399 RF0644 115/1/60 25 Amp N/A 13.5 N/A N/A
RFS0300 115/1/60 20 Amp 12.8 N/A N/A
RNS0300 115/1/60 20 Amp 12.8 N/A N/A RNS0600
RFS0650
RNS1000
RFS1200
RF2300
RFS2300
RFS1200R 208-230/1/60 15 Amp 1.4 RFS2300R 208-230/3/60 15 Amp 3.2
Maximum allowable voltage variation at compressor start-up is ±10% of voltage listed above and on the model/serial plate.
Voltage
Phase
Cycle
115/1/60 15 Amp N/A 7.5 N/A N/A — 230/1/50 10 Amp N/A 2.7 N/A N/A — 115/1/60 15 Amp N/A 7.5 N/A N/A — 230/1/50 10 Amp N/A 2.7 N/A N/A — 115/1/60 15 Amp N/A 7.5 N/A N/A — 230/1/50 10 Amp N/A 2.7 N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 10 Amp N/A 3.3 N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 10 Amp N/A 3.3 N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 10 Amp N/A 3.3 N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 10 Amp N/A 3.3 N/A N/A
115/1/60 15 Amp 8.2 25 Amp 15.4
208-230/1/60 15 Amp 8.7 25 Amp 16.3
115/1/60 25 Amp 16.3 25 Amp 15.4
208-230/1/60 15 Amp 8.7 15 Amp 8.2
115/1/60 15 Amp 2.9 208-230/1/60 20 Amp 14.2 20 Amp 13.7 15 Amp 1.4 208-230/1/60 20 Amp 12.5 20 Amp 12.5 15 Amp 1.4
230/1/50 10 Amp 1.4 208-230/3/60 20 Amp 15.0 20 Amp 15.0 — 400-415/3/50 16 Amp 13.9 16 Amp 13.9 — 208-230/3/60 15 Amp 3.2
230/1/50 15 Amp 3.2
Max
Fuse/
Circuit
Breaker
Min
Circuit
Amps
Total
Circuit
Amps
Max
Fuse/
Circuit
Breaker
Min
Circuit
Amps
Max
Fuse/
Circuit
Breaker
Total
Circuit
Amps
Part Number 000007644 8/14 11
Installation Instructions Section 2

QUIETQUBE REMOTE CONDENSING UNIT

Condensing Unit Voltage Phase Cycle Maximum Fuse/Circuit Breaker Minimum Circuit Amps
208-230/60/1 15 15
RCU1075
RCU1098
RCU2375
208-230/60/3 208-230/50/1 208-230/60/1 15 15 208-230/60/3 208-230/60/1 15 15 208-230/60/3 208-230/50/1
15 15 15 15
15 15
15 15 15 15
12
Part Number 000007644 8/14
Section 2 Installation Instructions
Important
!
Caution
!
Warning
!
Caution
!
Warning
Refrigeration System Installation Remote Condensing Unit Only
QuietQube®
Ice Machine
RNS1000C
RFS1200C RFS2300C
*Line Set Suction Line Liquid Line
RC 21/31/51
Manitowoc remote systems are only approved and warranted as a complete new package. Warranty on the refrigeration system will be void if a new ice machine head section is connected to pre-existing (used) tubing or condensing units or vice versa.
USAGE WITH NON-MANITOWOC CONDENSING UNITS
Manitowoc Remote Condensing Units are specifically designed for usage with a QuietQube® Ice Machine Head Section. Standard condensing units and Non­Manitowoc condensing units are not approved for use with a QuietQube® Ice Machine Head Section.
Remote
Condensing Unit
RCU1098 RCU1075 RCU2375
5/8 inch
(15.9 mm)
Line Set*
RC-21 RC-31 RC-51
3/8 inch
(9.5 mm)

Factory Equipment Refrigeration Amounts

ICE MACHINE HEAD SECTION Each ice machine condensing unit ships from the factory
with a R-404A refrigerant charge appropriate for the entire system operation. The serial tag on the ice machine indicates the refrigerant charge. The re frigerant charge is sufficient to operate the ice machine in ambient temperatures between -20°F (-28.9°C) and 120°F (48.9°C). With line set lengths of up to 100 feet (30.5 m).
Potential Personal Injury Situation
The QuietQube Condensing Unit contains the refrigerant charge. Installation and brazing of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Never add more than nameplate charge to the refrigeration system for any application.
REFRIGERATION LINE SETS/TRAP KIT Refrigeration Rated Tubing and Trap Kits are shipped
capped with atmospheric pressure.
The 60-month compressor warranty (including the 24­month labor replacement warranty) will not apply if the Manitowoc Ice Machine and Manitowoc Remote Condensing Unit are not installed according to specifications. This warranty also will not apply if the refrigeration system is modified with a condenser, heat reclaim device, or other parts or assemblies not manufactured by Manitowoc Ice.
Installation of a QuietQube® Condensing Unit may require the use of special equipment for placement. Trained and qualified personnel are required for proper rigging and lifting.
Part Number 000007644 8/14 13
Installation Instructions Section 2
!
Warning
!
Warning
Important
35 ft. (10.7 m)
MAX.
DISTANCE
SV1751
15 ft. (4.5 m)
MAX.
DISTANCE
SV1750
Refrigeration Line Set Installation Remote Condensing Unit Only

GENERAL

Refrigeration line set installations consist of vertical and horizontal line set distances between the ice machine and the condensing unit. The following guidelines, drawings and calculation methods must be followed to assure proper oil return and remote condensing unit/ice machine operation.
The refrigeration line set installer must be USA Government-Environmental Protection Agency (EPA) certified in proper refrigerant handling and servicing procedures.
The QuietQube Condensing unit contains refrigerant charge. The two refrigeration valves must remain closed until proper installation of the line sets is completed.
Disconnect electrical power to the ice machine head section and remote condensing unit before proceeding.
A. LINE SET LENGTH 100 feet (30.5 m) Length: The maximum measured
length the line set can be. The receiver is designed to hold a charge sufficient to
operate the ice machine in ambient temperatures between -20°F (-28.9°C) and 120°F (48.9°C), with line set lengths of up to 100 feet (30.5 m).The maximum amount of line set which can be exposed on the rooftop is 25% of the total length of the line set.
QuietQube® ice machines will not function with line sets greater than 100 feet (30.5 m). Do not attempt to go beyond this distance and add refrige rant ch ar ge to compensate!

B. LINE SET RISE OR DROP

Step 1 Verify Ice Machine and Remote Condensing
Unit Locations Are Within Guidelines
Prior to installation of the ice machine head section and remote condensing unit be sure that the distance between them is within the line set routing guidelines outlined in this manual.
Roof/Wall Penetration
If required, cut a 3-inch (76.2 mm) circular hole in the wall or roof for routing of refrigeration tubing. A qualified person must perform all roof penetra tio ns .
Step 2 Route Refrigeration Tubing
Properly route refrigeration tubing between the ice machine head section and the remote condensing unit.
35 feet (10.7 m) Rise: The maximum distance the remote condensing unit can be above the ice machine.
15 feet (4.5 m) Drop: The maximum distance the remote condensing unit can be below the ice machine .
14
Part Number 000007644 8/14
Section 2 Installation Instructions
!
Caution
21 ft. (6.4 m)
OR MORE RISE
ADDITIONAL
TRAP KIT
REQUIRED
!
Caution
!
Caution

C. SUCTION LINE OIL TRAPS

Do not form unwanted traps in refrigeration lines. Never coil excess refrigeration tubing.
0 to 20 feet (0 to 6.1 m) Rise: No oil trap is required when the condensing unit is located 20 feet (6.1 m) or less above the ice machine head section.
21 to 35 feet (6.4 to 10.7 m) Rise: The suction line requires an additional Oil Trap (“S” type) to be installed. Install the trap as close as possible to midpoint between the ice machine head section and remote cond en sin g unit. S-Trap Kits are available from Manitowoc.
Service Loop
A service loop in the line set permits easy access to the ice machine for cleaning and service.
A service loop is not considered an oil trap.
The service loop is not included when calculating length, rise or drop of the tubing run.
Do not use hard rigid copper for the service loop.
If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.
Step 3 Lengthening or Reducing Line Set Lengths
Do not form unwanted traps in refrigeration lines. Never coil excess refrigeration tubing.
When the line set requires shortening or lengthenin g, do so before connecting the line set to the ice machine head section or the remote condensing unit.
Part Number 000007644 8/14 15
Installation Instructions Section 2
!
Warning
!
Warning
MINIMIZE THE TIME THE
REFRIGERATION SYSTEM IS
EXPOSED TO THE A TMOSPHERE
(15 MINUTES MAXIMUM)
SUCTION LINE
LIQUID LINE
Suction and liquid line shut-off valves
must remain closed until evacuation and
pressure testing are complete.
Step 4 Connecting the line set
To prevent oxidation of the copper, purge line set and condensing unit with dry nitrogen while brazing.
A. Connect the Line Set to the Remote Condensing Unit
The QuietQube Condensing unit contains refrigerant charge. The two refrigeration valves must remain closed until proper installation of the line sets is completed.
The line set shut-off valves must remain closed and be protected from heat during the braz ing pro ce ss. Wrap the valves in a wet rag or other type of heat sink prior to brazing. Cool braze joint with water immediately after brazing to prevent heat migration to the valve.
Step 5 Pressure Test and Evacuate Line Set and
Ice Machine Head Section
Suction and liquid line set shutoff valves must remain closed until pressure testing and evacuation are complete.
Pressure testing and evacuation can be performed from the ice machine head section or CVD condensing unit shut-off valves.
Schrader valve core removal tools that allow for removal and installation of the valve cores without removing manifold gauge set hoses are recommended to decrease the evacuation time.
Pressure test @ 150 psi (1000 kPa) for a minimum of 15 minutes.
Minimum evacuation level is 500 microns.
B. Connect the Line Set to the Ice Machine Head Section
The ice machine head section ships from the factory pressurized with R404A refrigerant. Recover the refrigerant from both suction and liquid line access ports prior to cutting into refrigeration lines.
Cut the suction and liquid tubing with a tubing cutter, leaving enough tubing to easily braze.
Connect the line set.
Cool braze joint with water immediately after brazing to prevent heat migration.
16
Part Number 000007644 8/14
Section 2 Installation Instructions
Open suction and liquid line
shut-off valves
Important
Important
Step 6 Leak Check The Refrigeration System
Leak check the new line set connections at the ice machine head section, condensing unit and S trap as well as all factory joints throughout the entire system. Disconnect power to the remote condensing unit. Place the rocker switch into the ON position. This allows the low side and high side pressures to equalize for leak checking. Place the rocker switch in the OFF position. Connect power to the remote condensing unit and allow system to pump down after leak checking is complete.
Step 7 Open The Valves Prior To Starting The Ice
Machine
A. Slowly backseat (open-turn counterclockwise)
the suction line shutoff valve.
B. Slowly backseat (open-turn counterclockwise)
the liquid line shutoff valve.
All refrigeration valve caps must be reinstalled to prevent future refrigeration leaks.
Verify O-ring in schrader valve caps are intact and reinstall on shutoff valves to prevent re frigerant leakage . Replace shutoff valve access caps and torque to the following specifications.
Torque Values
Stem 18-20 ft. lbs. (24.4-27.1 Nm) Caps 12-15 ft. lbs. (16.3-20.3 Nm)
Schrader Core 1.5-3 in. lbs. (0.17-0.34 Nm)
Step 8 Insulation Requirements
To prevent condensation the entire suction line must be insulated. All insulation must be airtight and sealed at both ends.
The following insulation requirements prevent condensation at 90°F (32.2°C) ambient 90% Relative Humidity. If higher humidity is expected, increase insulation thickness.
The entire suction line set requires:
Open Valves
Suction Line Liquid Line
5/8 in. (16 mm) 3/8 in. (10 mm)
Min. Insulation
Thickness
1/2 in. (13 mm)
Suction Line
1/4 in. (7 mm)
Liquid Line
To prevent condensation the entire suction line must be insulated. All insulation must be airtight and sealed at both ends.
The minimum requirements are for conditions at or below 90% humidity and 90°F (32°C) ambient. When higher humidity will be experienced, or local code requires, insulation wall thickness will need to be increased.
Part Number 000007644 8/14 17
Installation Instructions Section 2

Installation Check List

All Manitowoc ice machines are factory-operated and adjusted before shipment. Adjustments and maintenance procedures outlined in this manual are the responsibility of the owner/operator and are not covered by the warranty.
Is the Ice Machine level?
Is the ice machine and adapter (when used)
secured to the dispenser?
Have all of the electrical and water
connections been made?
Has the supply voltage been tested and
checked against the rating on the nameplate?
Is there proper clearance around the ice
machine for air circulation?
Is the ice machine grounded and polarity
correct?
Has the ice machine been installed where
ambient temperatures will remain in the range of 50° - 100°F (14.4° - 37.8°C)?
Is there a separate drain for the water-cooled
condenser?
Is there a separate drain for the dispenser?
Is the ice making water turned on?
Are all electrical leads free from contact with
refrigeration lines and moving equipment?
Has the owner/operator been instructed
regarding maintenance and the use of Manitowoc Cleaner and Sanitizer?
Has the owner/operator comp leted the
warranty registration card?
Has the ice machine and bin been sanitized?
Is the rocker switch set to ON?
Has the ice machine been installed where the
incoming water temperature will remain in the range of 50° - 90°F (14.4° - 32.2°C)?
18
Part Number 000007644 8/14
Loading...
+ 42 hidden pages