Manitowoc Ice RF-0244 Installation Manual

Installation, Use & Care Manual
This manual is updated as new information and models are released.
Visit our website for the latest manual. www.manitowocice.com
America’s #1 Selling Ice Machine
Part Number 000007644 10/10
RF Model
Flake Ice Machines
This manual contains English and French text
Section 1 General Information
Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section 2 Installation Instructions
Location of Ice Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RF2300 Bin Adapter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Water and Drain Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Maximum Breaker Size & Minimum Circuit Amperage Chart . . . . . . . . . . . . . . . . 10
Refrigeration System Installation
Remote Condensing Unit Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Refrigeration Line Set Installation
Remote Condensing Unit Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Additional Checks for QuietQube Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table of Contents
UnderCounter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Modular Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Potable Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Water Supply and Drain Line Sizing/Connections . . . . . . . . . . . . . . . . . . . . . . . 7
Drain Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fuse/Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Ground Fault Circuit Interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Minimum Power Cord Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
For United Kingdom Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
QuietQube Remote Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
A. Line Set Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
B. Line Set Rise or Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C. Suction Line Oil Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Section 3 Operation
Evaporator Low Temperature Safety Thermostat and Bin Thermostat . . . . . . . . 19
RF0244/RF0266/RF0385/
RF0388/RF0399 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RF0300 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
RF0650/RF1200/RF2300 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2 Part Number 000007644 10/10
Section 4 Maintenance
Section 5 Customer Support
Table of Contents (continued)
Interior Cleaning and Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heavily Scaled Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Exterior Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Procedure to Clean Heavily Scaled Flake Ice Machines . . . . . . . . . . . . . . . . . . . 22
Removal of Parts for Cleaning/Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Ice Chute Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Ice Chute Switch Actuator Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Air-Cooled Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Arctic Pure Water Filter System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Manitowoc Cleaner and Sanitizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Commercial Ice Machine Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Residential Ice Machine Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Part Number 000007644 10/10 3
Table of Contents (continued)
4 Part Number 000007644 10/10

Model Numbers

!
Warning
!
Warning
!
Caution
This manual covers the following models:

UNDERCOUNTER MODELS

Self-Contained
Air-Cooled
RF0244A RF0266A RF0385A RF0388A RF0399A

MODULAR MODELS

Section 1
General Information
Self-Contained
Air-Cooled
RF0300A --- --- --­RF0650A RF0650W --- --­RF1200A RF1200W RF1278C RCU1275 RF2300A RF2300W RF2378C RCU2375
Remove all ice machine panels before lifting and installing.
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision concerning use of the appliance by a person responsible for their safety.
Self-Contained
Water-Cooled
QuietQube
Head Section
Flake ice machines must be installed on a bin. Flake ice machines cannot be installed on dispensers.
RCU Remote
Condensing Unit
5 Part Number 000007644 10/10
Section 2
!
Warning
Installation Instructions

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.
The location must be free of airborne and other contaminants.
The air temperature must be at least 50°F (10°C), but must not exceed 110°F (43°C).
The water temperature must be at least 40°F (4°C), but must not exceed 90°F (32°C).
The location must not be near heat-generating equipment or in direct sunlight.
The location must be capable of supporting the weight of the ice machine and a full bin of ice.
The location must allow enough clearance for water, drain and electrical connections in the rear of the ice machine.
The location must not obstruct airflow through or around the ice machine.

CLEARANCE REQUIREMENTS

RF0244 RF0266 RF0385 RF0388 RF0399
Top 0” (0 cm) 0” (0 cm)
Sides 2” (5 cm) 2” (5 cm)
Back 8" (20 cm) 8" (20 cm)
NOTE: Allowance must be made for removal when the ice machine is built in. Monthly removal of the top panel is required for cleaning & sanitizing.
Air-Cooled Water-Cooled

Installation Requirements

The ice machine and bin must be level.
Vent the ice machine and bin drains separately.
Bin drain termination must have an air gap.
A backflow preventer is required on water inlet lines.
The ice machine and bin must be sanitized after installation.
Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.
Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty.

RF2300 Bin Adapter Installation

PERSONAL INJURY POTENTIAL
RF2300 ice machines are not approved for use on B970 bins. RF2300 ice machines ship with a bracket that must be used when installing on B1100 and B1400 Series bins.
1. Refer to diagram. Place bracket on bin top and slide back to engage.
2. Place ice machine on bin: ice machine must fit between bracket and front ridge.
RF0300 RF0650 RF1200 RF2300
Top/Sides 8" (20 cm) 8" (20 cm) 0" (0 cm)
Back 5" (13 cm) 5" (13 cm) 0" (0 cm)
RCU Units Remote Condensing Unit
Front/Back 24" (61 cm)
Sides/Top 6" (15.2 cm)
NOTE: Water-cooled/Remote condensing units only - there is no minimum clearance required. This value is recommended for efficient operation and servicing only.
Part Number 000007644 10/10 6
Air-
Cooled
Water-
Cooled
QuietQube Air-Cooled
Installation Instructions Section 2
VENT TUBE 18" (46 CM)
LONG
ROUTE
DRAIN TUBING TO OPEN SITE
DRAIN
ICE MAKING
WATER INLET
TUBING 3/8" MIN.
I.D. (.95 CM)
VENT TUBE 18" (46 CM)
LONG
SEPERATE BIN AND ICE
MACHINE DRAINS ARE
REQUIRED
ROUTE DRAIN TUBING TO
OPEN SITE DRAIN
WATER SHUT-OFF VALVE REQUIRED - ICE MAKING
WATER INLET TUBING 3/8"
MIN. I.D. (.95 CM)

Water and Drain Requirements

POTABLE WATER REQUIREMENTS

Follow these guidelines to install water inlet lines:
Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)
If water pressure exceeds the maximum of 80 psig (552 kPA) recommended pressure , obtain a water pressure regulator from your Manitowoc distributor.
Install a water shut-off valve and unio n for both the ice making and condenser water lines.
Insulate water inlet lines to prevent condensation.
Plumbing must conform to local codes.

WATER SUPPLY AND DRAIN LINE SIZING/ CONNECTIONS

Water
Pressure
Min/Max
14/80 psi
(100/552 kPA)
20/150 psi
(138/1034 kPA)
Location
Potable
Water Inlet
Potable
Water Drain
Condenser Water Inlet
Condenser
Water Drain
Water Temp
Min/Max
40°/90°F
(4°/32°C)
--- --- 1/2" MPT
40°/90°F
(4°/32°C)
--- --- 1/2" MPT
Bin Drain --- --- 3/4" FPT
Large Capacity Bin Drain --- 1" FPT
Fitting/Min
Tubing
3/8" FPT
3/8” FPT
RF2300 only
= 1/2" FPT
Size
Typical Water Supply Drain Installation

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:
Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.
The floor drain must be large enough to accommodate drainage from all drains.
7
Run separate bin and water-cooled condenser drain lines. Insulate them to prevent condensation.
Vent the bin and ice machine drain to the atmosphere. The ice machine drain requires an 18" (46 cm) vent. Do not vent the condenser drain on water-cooled models.
Part Number 000007644 10/10
Section 2 Installation Instructions
!
Warning
!
Warning
Important
Drains must have a union or other suitable means to allow in place disconnection from the ice machine when servicing is required.

Electrical Service

All wiring must conform to local, state and national codes.

VOLTAGE

The maximum allowable voltage variation is ±10 % of the rated voltage at ice machine start-up (when the electrical load is highest).
The ice machine must be grounded in accordance with national and local electrical codes.
All electrical work, including wire routing and grounding, must conform to local, state and national electrical codes. The following precautions must be observed:
The ice machine must be grounded.
A separate fuse/circuit breaker must be provided for each ice machine.
A qualified electrician must determine proper wire size dependent upon location, materials used and length of run (minimum circuit ampacity can be used to help select the wire size).
The maximum allowable voltage variation is +/-10 of the rated voltage at ice machine start-up (when the electrical load is highest).
Check all ground screws in the control box and verify they are tight before starting the ice machine.
Observe correct polarity of incoming line voltage. Incorrect polarity can lead to erratic ice machine operation.

FUSE/CIRCUIT BREAKER

A dedicated circuit and a separate fuse/circu it breaker are required for each ice machine.
Part Number 000007644 10/10 8
Installation Instructions Section 2

GROUND FAULT CIRCUIT INTERRUPTER

We do not recommend the use of a GFCI/GFI circuit protection with our equipment. If a GFCI/GFI is required by code, use a GFCI/GFI breaker rather tha n ou tle t which is more prone to intermittent nuisance trips than panel circuit breakers.

MINIMUM POWER CORD SPECIFICATIONS

The wire size to the receptacle is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician. Local, state or national requirements will supersede our minimum requirements.

FOR UNITED KINGDOM ONLY

As the colors of the wires in the mains lead of the appliance may not correspond with the colored markings identifying the terminals in your plug, proceed as follows:
The wire which is colored green and yellow must be connected to the terminal in the plug which is marked with the letter E or by the earth ground symbol or colored green or green and yellow.
The wire colored blue with the letter N or colored black.
The wire colored brown marked with the letter L or colored red.
must be connected to the terminal which is marked
must be connected to the terminal which is
9
Part Number 000007644 10/10
Section 2 Installation Instructions
Important

Maximum Breaker Size & Minimum Circuit Amperage Chart

Due to continuous improvements, this information is for reference only. Please refer to the ice machine serial number tag to verify electrical data. Serial tag information overrides information listed on this p age.
Air-Cooled Water-Cooled QuietQube
Series Ice
Machine
RF0244
RF0266
RF0385
RF0388
RF0399
RF0300
Voltage
Phase
Cycle
115/1/60 15 Amp N/A 7.5 N/A N/A — 230/1/50 10 Amp N/A 0.87 N/A N/A — 115/1/60 15 Amp N/A 7.5 N/A N/A — 230/1/50 10 Amp N/A 0.87 N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 N/A N/A N/A N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 10 Amp N/A 2.9 N/A N/A — 115/1/60 15 Amp N/A 10.0 N/A N/A — 230/1/50 10 Amp N/A 2.9 N/A N/A — 115/1/60 15 Amp 10.0 N/A N/A N/A — 230/1/50 10 Amp 2.9 N/A N/A N/A — 115/60/1 20 Amp 13.7 N/A 20 Amp 13.7
RF0650
208-230/1/60 15 Amp 7.3 N/A N/A N/A
230/1/50 16 Amp 4.6 N/A N/A N/A
RF1200
RF2300
Maximum allowable voltage variation at compressor start-up is ±10% of voltage listed above and on the model/serial plate.
208-230/1/60 15 Amp 15.0 N/A 15 Amp 15.0 15 Amp 1.4
230/1/50 16 Amp 7.3 N/A 16 Amp 7.3 10 Amp 1.4 208-230/3/60 20 Amp 15.0 N/A 20 Amp 15.0 15 Amp 3.2 400-415/3/50 16 Amp 13.9 N/A 16 Amp 13.9 10 Amp 3.2
Max
Fuse/
Circuit
Breaker
Min
Circuit
Amps
Total
Circuit
Amps
Max
Fuse/
Circuit
Breaker
Min
Circuit
Amps
Max
Fuse/
Circuit
Breaker
Total
Circuit
Amps

QUIETQUBE REMOTE CONDENSING UNIT

Condensing Unit Voltage PhaseCycle Maximum Fuse/Circuit Breaker Minimum Circuit Amps
208-230/60/1 15 15
RCU1075
RCU2375
208-230/60/3 208-230/50/1 208-230/60/1 15 15 208-230/60/3 208-230/50/1
Part Number 000007644 10/10 10
15 15 15 15
15 15 15 15
Installation Instructions Section 2
Important
!
Caution
!
Warning
!
Caution
!
Warning

Refrigeration System Installation Remote Condensing Unit Only

QuietQube®
Ice Machine
RF1200C RF2300C
*Line Set Suction Line Liquid Line
RC 21/31/51
Manitowoc remote systems are only approved and warranted as a complete new package. Warranty on the refrigeration system will be void if a new ice machine head section is connected to pre-existing (used) tubing or condensing units or vice versa.

USAGE WITH NON-MANITOWOC CONDENSING UNITS

Manitowoc Remote Condensing Units are specifically designed for usage with a QuietQube® Ice Machine Head Section. Standard condensing units and Non­Manitowoc condensing units are not approved for use with a QuietQube® Ice Machine Head Section.
Remote
Condensing Unit
RCU1075C
RCU2375C
5/8 inch
(15.9 mm)
Line Set*
RC-21 RC-31 RC-51
3/8 inch
(9.5 mm)

Factory Equipment Refrigeration Amounts

ICE MACHINE HEAD SECTION Each ice machine condensing unit ships from the factory
with a R-404A refrigerant charge appropriate for the entire system operation. The serial tag on the ice machine indicates the refrigerant charge. The re frigerant charge is sufficient to operate the ice machine in ambient temperatures between -20°F (-28.9°C) and 120°F (48.9°C). With line set lengths of up to 100 feet (30.5 m).
Potential Personal Injury Situation
The QuietQube Condensing Unit contains the refrigerant charge. Installation and brazing of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Never add more than nameplate charge to the refrigeration system for any application.
REFRIGERATION LINE SETS/TRAP KIT Refrigeration Rated Tubing and Trap Kits are shippe d
capped with atmospheric pressure.
The 60-month compressor warranty (including the 24­month labor replacement warranty) will not apply if the Manitowoc Ice Machine and Manitowoc Remote Condensing Unit are not installed according to specifications. This warranty also will not apply if the refrigeration system is modified with a condenser, heat reclaim device, or other parts or assemblies not manufactured by Manitowoc Ice.
Installation of a QuietQube® Condensing Unit may require the use of special equipment for placement. Trained and qualified personnel are required for proper rigging and lifting.
11
Part Number 000007644 10/10
Section 2 Installation Instructions
!
Warning
!
Warning
Important
35 ft. (10.7 m)
MAX.
DISTANCE
SV1751
15 ft. (4.5 m)
MAX.
DISTANCE
SV1750

Refrigeration Line Set Installation Remote Condensing Unit Only

GENERAL

Refrigeration line set installations consist of vertical and horizontal line set distances between the ice machine and the condensing unit. The following guidelines, drawings and calculation methods must be followed to assure proper oil return and remote condensing unit/ice machine operation.
The refrigeration line set installer must be USA Government-Environmental Protection Agency (EPA) certified in proper refrigerant handling and servicing procedures.
The QuietQube Condensing unit contains refrigerant charge. The two refrigeration valves must remain closed until proper installation of the line sets is completed.
Disconnect electrical power to the ice machine head section and remote condensing unit before proceeding.
A. LINE SET LENGTH 100 feet (30.5 m) Length: The maximum measured
length the line set can be. The receiver is designed to hold a charge sufficient to
operate the ice machine in ambient temperatures between -20°F (-28.9°C) and 120°F (48.9°C), with line set lengths of up to 100 feet (30.5 m).The maximum amount of lineset which can be exposed on the rooftop is 25% of the total length of the lineset.
QuietQube® ice machines will not function with line sets greater than 100 feet (30.5 m). Do not attempt to go beyond this distance and add refr ige rant ch ar ge to compensate!

B. LINE SET RISE OR DROP

Step 1 Verify Ice Machine and Remote Condensing
Unit Locations Are Within Guidelines
Prior to installation of the ice machine head section and remote condensing unit be sure that the distance between them is within the line set routing guidelines outlined in this manual.
Roof/Wall Penetration
If required, cut a 3-inch (76.2 mm) circular hole in the wall or roof for routing of refrigeration tubing. A qualified person must perform all roof penetrations.
Step 2 Route Refrigeration Tubing
Properly route refrigeration tubing between the ice machine head section and the remote condensing unit.
35 feet (10.7 m) Rise: The maximum distance the remote condensing unit can be above the ice machine.
15 feet (4.5 m) Drop: The maximum distance the remote condensing unit can be below the ice machine.
Part Number 000007644 10/10 12
Installation Instructions Section 2
!
Caution
21 ft. (6.4 m)
OR MORE RISE
ADDITIONAL
TRAP KIT
REQUIRED
SV1751
SV1760
!
Caution
!
Caution

C. SUCTION LINE OIL TRAPS

Do not form unwanted traps in refrigeration lines. Never coil excess refrigeration tubing.
0 to 20 feet (0 to 6.1 m) Rise: No oil trap is required when the condensing unit is located 20 feet (6.1 m) or less above the ice machine head section.
21 to 35 feet (6.4 to 10.7 m) Rise: The suction line requires an additional Oil Trap (“S” type) to be installed. Install the trap as close as possible to midpoint between the ice machine head section and remote condensing unit. S-Trap Kits are available from Manitowoc.
Service Loop
A service loop in the line set permits easy access to the ice machine for cleaning and service.
A service loop is not considered an oil trap.
The service loop is not included when calculating length, rise or drop of the tubing run.
Do not use hard rigid copper for the service loop.
If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.
Step 3 Lengthening or Reducing Line Set Lengths
Do not form unwanted traps in refrigeration lines. Never coil excess refrigeration tubing.
When the line set requires shortening or lengthening, do so before connecting the line set to the ice machine head section or the remote condensing unit.
13
Part Number 000007644 10/10
Section 2 Installation Instructions
!
Warning
!
Warning
MINIMIZE THE TIME THE
REFRIGERATION SYSTEM IS
EXPOSED TO THE A TMOSPHERE
(15 MINUTES MAXIMUM)
SUCTION LINE
LIQUID LINE
Suction and liquid line shut-off valves
must remain closed until evacuation and
pressure testing are complete.
Step 4 Connecting the line set
To prevent oxidation of the copper, purge line set and condensing unit with dry nitrogen while brazing.
A. Connect the Line Set to the Remote Condensing Unit
The QuietQube Condensing unit contains refrigerant charge. The two refrigeration valves must remain closed until proper installation of the line sets is completed.
The line set shut-off valves must remain closed and be protected from heat during the brazing process. Wrap the valves in a wet rag or other type of heat sink prior to brazing. Cool braze joint with water immediately after brazing to prevent heat migration to the valve.
Step 5 Pressure Test and Evacuate Line Set and
Ice Machine Head Section
Suction and liquid line set shutoff valves must remain closed until pressure testing and evacuation are complete.
Pressure testing and evacuation can be performed from the ice machine head section or CVD condensing unit shut-off valves.
Schrader valve core removal tools that allow for removal and installation of the valve cores without removing manifold gauge set hoses are recommended to decrease the evacuation time.
Pressure test @ 150 psi (1000 kPa) for a minimum of 15 minutes.
Minimum evacuation level is 500 microns.
B. Connect the Line Set to the Ice Machine Head Section
The ice machine head section ships from the factory pressurized with R404A refrigerant. Recover the refrigerant from both suction and liquid line access ports prior to cutting into refrigeration lines.
Cut the suction and liquid tubing with a tubing cutter, leaving enough tubing to easily braze.
Connect the line set.
Cool braze joint with water immediately after brazing to prevent heat migration.
Part Number 000007644 10/10 14
Installation Instructions Section 2
Open suction and liquid line
shut-off valves
Important
Important
Step 6 Leak Check The Refrigeration System
Leak check the new line set connections at the ice machine head section, condensing unit and S trap as well as all factory joints throughout the entire system. Disconnect power to the remote condensing unit. Place the rocker switch into the ON position. This allows the low side and high side pressures to equalize for leak checking. Place the rocker switch in the OFF position . Connect power to the remote condensing unit and allow system to pump down after leak checking is complete.
Step 7 Open The Valves Prior To Starting The Ice
Machine
A. Slowly backseat (open-turn counterclockwise)
the suction line shutoff valve.
B. Slowly backseat (open-turn counterclockwise)
the liquid line shutoff valve.
All refrigeration valve caps must be reinstalled to prevent future refrigeration leaks.
Verify O-ring in schrader valve caps are intact and reinstall on shutoff valves to preven t refrigerant leakage. Replace shutoff valve access caps and torque to the following specifications.
Torque Values
Stem 18-20 ft. lbs. (24.4-27.1 Nm) Caps 12-15 ft. lbs. (16.3-20.3 Nm)
Schrader Core 1.5-3 in. lbs. (0.17-0.34 Nm)
Step 8 Insulation Requirements
To prevent condensation the entire suction line must be insulated. All insulation must be airtight and sealed at both ends.
The following insulation requirements prevent condensation at 90°F (32.2°C) ambient 90% Relative Humidity. If higher humidity is expected, increase insulation thickness.
The entire suction line set requires:
Open Valves
Suction Line Liquid Line
5/8 in. (16 mm) 3/8 in. (10 mm)
Min. Insulation
Thickness
1/2 in. (13 mm)
Suction Line
1/4 in. (7 mm)
Liquid Line
To prevent condensation the entire suction line must be insulated. All insulation must be airtight and sealed at both ends. The minimum requirements are for conditions at or below 90% humidity and 90°F (32°C) ambient. When higher humidity will be experienced, or local code requires, insulation wall thickness will need to be increased.
15
Part Number 000007644 10/10
Section 2 Installation Instructions

Installation Check List

All Manitowoc ice machines are factory-operated and adjusted before shipment. Adjustments and maintenance procedures outlined in this manual are the responsibility of the owner/operator and are not covered by the warranty.
Is the Ice Machine level?
Is the ice mach in e an d ad a pt er (whe n used )
secured to the dispenser?
Have all of the electrical and water
connections been made?
Has the supply voltage been tested and
checked against the rating on the nameplate?
Is there proper clearance around the ice
machine for air circulation?
Is the ice machine grounded and polarity
correct?
Has the ice machine been installed where
ambient temperatures will remain in the range of 50° - 100°F (14.4° - 37.8°C)?
Is there a separate drain for the water-cooled
condenser?
Is there a separate drain for the dispenser?
Is the ice making water turned on?
Are all electrical leads free from contact with
refrigeration lines and moving equipment?
Has the owner/operator been instructed
regarding maintenance and the use of Manitowoc Cleaner and Sanitizer?
Has the owner/operator completed the
warranty registration card?
Has the ice machine and bin been sanitized?
Is the rocker switch set to ON?
Has the ice machine been installed where the
incoming water temperature will remain in the range of 50° - 90°F (14.4° - 32.2°C)?
Part Number 000007644 10/10 16
Section 2 Installation Instructions

Additional Checks for QuietQube Models

Is the lineset length, rise and drop within the
guidelines?
Are the suction and liquid line shut-off valves
open?
Is the line set routed properly?
Are both refrigeration lines to remote
condensing unit run so they do not lay in water and are properly insulated?
Does the condenser fan motor(s) operate
properly after start-up?
Have all the refrigeration fittings and joints
been leak checked?
Has the condenser/condensing unit been
installed to prevent any roofing damage?
Have the refrigeration lines been insulated and
secured properly to prevent vibration?
Has the RCU remote condensing unit been
located where ambient temperatures will remain in the range of -20° to 120°F (-29° to
48.9°C)?
Is a refrigeration oil trap (S-trap) installed if the
condenser is installed 21 to 35 fe et (6 to 11 m) above the ice machine head?
Part Number 000007644 10/10 17