Manitowoc Ice K-0250 Owner’s Manual

Ice Machines
Installation and Maintenance Manual
Part Number 000012545 Rev01 9/15
Section 1 General Information
Section 2 Installation Instructions
Table of Contents
Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Location of Ice Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ice Machine Heat of Rejection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Removing Drain Plug and Leveling the Ice Storage Bin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Air Baffle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Maximum Breaker Size & Minimum Circuit Amperage Chart . . . . . . . . . . . . . . . . . . . . . . . . . 8
Water Supply and Drain Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Water Supply and Drain Line Sizing/Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Water-Cooled Condenser Water Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cooling Tower Applications (Water-Cooled Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remote Condenser/Line Set Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Remote Ice Machine Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Guidelines for Routing Line Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Calculating Remote Condenser Installation Distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Route the Line Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connect the Line Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pressure Test and Evacuate Line Set and Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Open Line Set Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Additional Checks for Remote Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Before Starting the Ice Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Part Number 000012545 Rev01 9/15 1
Table of Contents (continued)
Section 3 Operation
Ice Making Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operational Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Section 4 Maintenance
Cleaning and Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Parts Removal for Cleaning/Sanitizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Preventative Maintenance Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Door Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Cleaning the Condenser Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Cleaning the Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Removal from Service/Winterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Safety Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ice Thickness Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cleaning/Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Preventative Maintenance Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Exterior Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Sanitizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Water-Cooled Ice Machines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Section 5 Customer Support
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Safety Limit Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2 Part Number 000012545 Rev01 9/15

Section 1 General Information

!
Warning
!
Warning
Follow these precautions to prevent personal injury:
Remove all panels before lifting and installing.
Two or more people or a lifting device are required to lift or move this appliance to avoid injury or tipping.
Do not damage the refrigeration circuit when installing, maintaining or servicing the unit.
Do not obstruct vents or openings or store gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
It is the responsibility of the equipment owner to perform a Personal Protective Equipment Hazard Assessment to ensure adequate protection during maintenance procedures.
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision concerning use of the appliance by a person responsible for their safety. Do not allow children to play with this appliance.
Ice machines require a deflector when installed on an ice storage bin. Prior to using a storage system with this ice machine, contact the manufacturer to ensure their ice deflector is compatible with this ice machine.
When using electric appliances, basic precautions must always be followed, including the following:
Read all the instructions before using the appliance.
To reduce the risk of injury, close supervision is necessary when an appliance is used near children.
Do not contact moving parts.
Do not use electrical appliances or accessories other than those supplied by the manufacturer.
Do not use outdoors.
All covers and access panels must be in place and properly secured, before operating this equipment.
Connect to a properly grounded outlet only.
For a cord-connected appliance, the following precautions must be observed:
A. Do not unplug by pulling on cord. To unplug,
grasp the plug, not the cord.
B. Unplug from outlet when not in use and
before servicing or cleaning.
C. Do not operate any appliance with a damaged
cord or plug, or after the appliance malfunctions or is dropped or damaged in any manner. Contact the nearest authorized service facility for examination, repair, or electrical or mechanical adjustment.
This equipment contains high voltage electricity and refrigerant charge. Installation and repairs are to be performed by properly trained technicians aware of the dangers of dealing with high voltage electricity and refrigerant under pressure. The technician must also be certified in proper refrigerant handling and servicing procedures. All lock out and tag out procedures must be followed when working on this equipment.
Objects placed or dropped in the bin can affect human health and safety. Locate and remove any objects immediately.
Part Number 000012545 Rev01 9/15 3
General Information Section 1

Model Numbers

This manual covers the following models:
Self-Contained
Air-Cooled
KD0250A KY0250A
KD0350A KY0350A
KD0420A KY0420A
KD0500A KY0500A
KD0600A KY0600A
KD1000A KY1000A
KD1350A KY1350A
KD1800A KY1800A
Self-Contained
Water-Cooled
----
----
KD0350W KY0350W
KD0420W KY0420W
KD0500W KY0500W
KD0600W KY0600W
KD1000W KY1000W
KD1350W KY1350W
----
----
Remote
----
----
----
----
----
----
----
----
----
----
KD1000N KY1000N
KD1350N KY1350N
KD1800N KY1800N

ICE DEFLECTOR

An ice deflector is required when the ice machine is installed on a bin. An ice deflector is not required when the ice machine is installed on a dispenser.

BIN INSTALLATION

All ice machines installed on a bin require an ice deflector.
Koolaire bins have a deflector installed and require no modifications when used with a forward facing evaporator.
Align sides and back of ice machine with sides and back of bin, when placing ice machine on bin.
4 Part Number 000012545 Rev01 9/15

Section 2 Installation Instructions

!
Warning
!
Warning
!
Caution

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.
The location must be free of airborne and other contaminants.
The air temperature must be at least 35°F (1.6°C), but must not exceed 110°F (43.4°C).
NOTE: K1350 Minimum air temperature is 40°F (4.4°C).
Remote air-cooled - The air temperature must be at least
-20°F (-29°C), but must not exceed 120°F (49°C).
The location must not be near heat-generating (ovens, dishwashers, etc) equipment or in direct sunlight and must be protected from weather.
The location must not obstruct airflow through or around the ice machine. Refer to the clearance requirements chart.
These ice machines are intended for use in applications such as:
Staff kitchen areas in shops, offices and other work environments
Clients in hotels, motels, farmhouses, bed and breakfast and other residential type environments
Catering and similar non-retail applications
Two or more people or a lifting device are required to lift this appliance.

Clearance Requirements

Do not obstruct ice machine vents or openings.
K0250
To p/ Si de s 12" (30.5 cm)** N/A
Back 5" (12.7 cm)** N/A
K0350/K0420
K0500/K0600/
K1000/K1350/ K1800
To p/ Si de s 8" (20.3 cm)** 8" (20.3 cm)**
Back 5" (12.7 cm)** 5" (12.7 cm)**
K0420
Tropical Ra ting
50 Hz Only
Top 24" (61.0 cm)** 8" (20.3 cm)**
Sides 12" (30.5 cm)** 8" (20.3 cm)**
Back 5" (12.7 cm)** 5" (12.7 cm)**
K1000
Tropical Ra ting
50 Hz Only
Top 12" (30.5 cm)** 8" (20.3 cm)**
Sides 8" (20.3 cm)** 8" (20.3 cm)**
Back 5" (12.7 cm)** 5" (12.7 cm)**
* There is no minimum clearance required for water-cooled or remote ice
machines. This value is recommended for efficient operation and servicing only.
** Indicates Preliminary Data
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained Wate r-Coo led*
Water-Cooled
and
Remote*
Water-Cooled*
Water-Cooled
and
Remote*
The ice machine must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty.
Part Number 000012545 Rev01 9/15 5
Installation Instructions Section 2
!
Warning
!
Caution

AIR BAFFLE

Ice Machine Heat of Rejection

Series
Ice Machine
K0250 4600 5450 K0350 3800 6000 K0420 5400 6300 K0500 5300 6100 K0600 9000 13900 K1000 16250 18600 K1350 28300 34300 K1800 28800 34700
1 B.T.U./Hour 2 Because the heat of rejection varies during the ice making cycle, the
figure shown is an average.
Air Conditioning
Heat of Rejection
2
Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment where self-contained air-cooled ice machines are installed.
This information is also necessary when evaluating the benefits of using water-cooled or remote condensers to reduce air conditioning loads. The amount of heat added to an air conditioned environment by an ice machine using a water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important when sizing a cooling tower for a water-cooled condenser. Use the peak figure for sizing the cooling tower.
1
Peak

Removing Drain Plug and Leveling the Ice Storage Bin

To avoid instability, the bin/dispenser must be installed in an area capable of supporting the weight of the bin/ dispenser, ice machine and a full bin of ice (48" models 1000 lbs [454 kg], 30" models 750 lbs [340 kg]). The bin/ dispenser must be level side-to-side and front-to-back before installing the ice machine.
1. Remove threaded plug from drain fitting.
2. Screw the leveling legs onto the bottom of the bin.
3. Screw the foot of each leg in as far as possible.
The legs must be screwed in tightly to prevent them from bending.
4. Move the bin into its final position.
5. Level the bin to assure that the bin door closes and seals and the ice machine operates properly. Use a level on top of the bin. Turn the base of each foot as necessary to level the bin.
6. Inspect bin gasket prior to ice machine installation. (Our bins come with a closed cell foam gasket installed along the top surface of the bin.)
7. Remove all panels from ice machine before lifting and installing on bin. Remove front panel, top cover, left and right side panels.
Air Baffle

Self-Contained Air-Cooled Only

The air-cooled baffle prevents condenser air from recirculating. To install:
1. Loosen the back panel screws next to the condenser.
2. Align the keyhole slots in the air baffle with the screw holes and slide the baffle down to lock in place.
6 Part Number 000012545 Rev01 9/15
Section 2 Installation Instructions
!
Warning
!
Caution

Electrical Service

All electrical work, including wire routing and grounding must conform to all applicable national and local electrical codes.

MINIMUM CIRCUIT AMPACITY

The minimum circuit ampacity is used to help select the wire size of the electrical supply. (Minimum circuit ampacity is not the ice machine’s running amp load.)

ELECTRICAL REQUIREMENTS

Refer to Ice Machine Model/Serial Plate for voltage/ amperage specifications.
A separate fuse/circuit breaker must be provided for each ice machine.
The wire size (or gauge) is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.
The ice machine must be grounded. Check all green ground screws in the control box and verify they are tight before starting the ice machine.
The maximum allowable voltage variation is ±10% of the rated voltage at ice machine start-up (when the electrical load is highest).
Observe correct polarity of incoming line voltage. Incorrect polarity can lead to erratic ice machine operation. Operate equipment only on the type of electricity indicated on the specification plate.

GROUND FAULT CIRCUIT INTERRUPTER

Ground Fault Circuit Interrupter (GFCI/GFI) protection is a system that shuts down the electric circuit (opens it) when it senses an unexpected loss of power, presumably to ground. GFCI/GFI circuit protection is not recommended with our equipment. If code requires the use of a GFCI/GFI, then you must follow the local code. The circuit must be dedicated, sized properly and there must be a panel GFCI/GFI breaker. We do not recommend GFCI/GFI outlets as they are known for more intermittent nuisance trips than panel breakers.

MINIMUM POWER CORD SPECIFICATIONS

Maximum
Breaker Size
15 amp 20 amp 30 amp 40 amp
Minimum Wire
Size
14 gauge 6 feet (1.83 m) 12 gauge 6 feet (1.83 m) 10 gauge 6 feet (1.83 m)
8 gauge 6 feet (1.83 m)
Maximum Length of Power
Cord
If a power cord is used, the wire size to the receptacle is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician. Local, state or national requirements will supersede our minimum requirements.

FOR UNITED KINGDOM ONLY

As the colors of the wires in the mains lead of the appliance may not correspond with the colored markings identifying the terminals in your plug, proceed as follows:
The wire which is colored green and yellow must be connected to the terminal in the plug which is marked with the letter E or by the earth ground symbol
The wire colored blue must be connected to the terminal which is marked with the letter N or colored black.
The wire colored brown must be connected to the terminal which is marked with the letter L or colored red.
or colored green or green and yellow.
Part Number 000012545 Rev01 9/15 7
Installation Instructions Section 2
Important

Maximum Breaker Size & Minimum Circuit Amperage Chart

Due to continuous improvements, this information is for reference only. Please refer to the ice machine serial number tag to verify electrical data. Serial tag information overrides information listed on this page.
Air-Cooled Water-Cooled Remote
Ice Machine
K0250
K0350
K0420
K0500
K0600
K1000
K1350
K1800
Voltage/Phase/
Cycle
Maximum Fuse/
Circuit Breaker
Minimum
Circuit Amps
Maximum Fuse/
Circuit Breaker
Minimum
Circuit Amps
115/1/60 15 9.44 N/A N/A N/A N/A 230/1/50 15 4.5 N/A N/A N/A N/A 230/1/60 15 4.7 N/A N/A N/A N/A 115/1/60 15 12.1 15 11.4 N/A N/A 230/1/50 15 6.3 15 5.9 N/A N/A 230/1/60 15 6.2 15 5.8 N/A N/A 115/1/60 15 11.3 15 10.6 N/A N/A 230/1/50 15 6.2 15 5.8 N/A N/A 230/1/60 15 6.2 15 5.8 N/A N/A 115/1/60 20 12.7 20 12.0 N/A N/A 230/1/50 15 6.3 15 5.9 N/A N/A
208-230/1/60 20 9.2 20 8.8 N/A N/A
230/1/50 20 8.6 20 8.2 N/A N/A
208-230/1/60 20 13.9 20 13.2 20 12.8
230/1/50 20 13.8 20 13.1 20 14.1 208-230/1/60 30 18.2 30 16.8 30 17.8 208-230/3/60 20 13.6 20 12.2 20 13.2
230/1/50 30 18.2 30 16.8 30 17.8 208-230/1/60 30 19.6 N/A N/A 30 19.6 208-230/60/3 20 13.3 N/A N/A 20 12.9
230/1/50 30 19.6 N/A N/A 30 19.6
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
8 Part Number 000012545 Rev01 9/15
Section 2 Installation Instructions
!
Warning
!
Caution

Water Supply and Drain Requirements

WATER SUPPLY

Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.
Connect to a potable water supply only. Plumbing must
conform to state, local and national codes.

WATER INLET LINES

Follow these guidelines to install water inlet lines:
If you are installing a water filter system, refer to the installation instructions supplied with the filter system for ice making water inlet connections.
Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)
If water pressure exceeds the maximum recommended pressure of 80 psi (552 kPa), obtain a water pressure regulator from your local distributor.

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:
Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.
The floor drain must be large enough to accommodate drainage from all drains.
Run separate bin and ice machine drain lines. Insulate them to prevent condensation.
Vent the bin and ice machine drain to the atmosphere. Do not vent the condenser drain on water-cooled models.
A separate auxiliary drain is located in the ice machine base to remove moisture in high humidity areas. The drain fitting is a female socket for 1/2" CPVC pipe. The drain is sealed and the seal must be removed before attaching the drain fitting/tubing. Tap the seal out with a wooden dowel or similar tool. Seal the CPVC pipe to the ice machine socket with silicone sealant to allow future removal.
Install a water shut-off valve for both the ice making and condenser water lines.
Insulate water inlet lines to prevent condensation.
Do not apply heat to water valve inlet fitting. This will damage plastic water inlet connection.
Part Number 000012545 Rev01 9/15 9
Installation Instructions Section 2
Important

Water Supply and Drain Line Sizing/Connections

Location Water Temperature Water Pressure Ice Machine Fitting
Ice Making Water
Inlet
Ice Making Water
Drain
Condenser Water
Inlet
Condenser Water
Drain
Bin Drain
Large Capacity
Bin Drain
35°F (2°C) Min.
90°F (32°C) Max.
1/2" (1.27 cm) Female Pipe Thread 1/2" (1.27 cm) min. inside
90°F (32°C) Max. Standard
1/2" (1.27 cm) Female Pipe Thread 1/2" (1.27 cm) min. inside
3/4" (1.91 cm) Female Pipe Thread 3/4" (1.91 cm) min. inside
1" (2.54 cm) Male Pipe Thread 1" (2.54 cm) min. inside diameter
20 psi (140 kPa) Min. 80 psi (552 kPa) Max.
20 psi (140 kPa) Min.
150 psi (1034 kPa) Max.
High Pressure Option
20 psi (140 kPa) Min.
350 psi (2410 kPa) Max.
3/8" (.95 cm) Female Pipe Thread 3/8" (.95 cm) min. inside diameter
3/8" Female Pipe Thread
Tubing Size Up to Ice Machine
Fitting
diameter
diameter
diameter

WATER-COOLED CONDENSER WATER PRESSURE

Water pressure at the condenser cannot exceed 150 psig (1034 kPa) with the standard water-regulating valve. Contact your distributor if your water pressure is greater than 150 psig (1034 kPa). A special order condenser/water­regulating valve is available that allows water pressure up to 350 psig (2413 kPa).
The Commonwealth of Massachusetts requires that all water-cooled models must be connected only to a closed loop, cooling tower system.

COOLING TOWER APPLICATIONS (WATER-COOLED MODELS)

A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.
It is necessary to know the amount of heat rejection and the pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.
Water entering the condenser must not exceed 90°F
(32°C).
Water flow through the condenser must not exceed 5
gallons (19 liters) per minute.
Allow for a pressure drop of 7 psi (50 kPa) between the condenser water inlet and the outlet of the ice machine.
Water exiting the condenser must not exceed 110°F
(43°C).
10 Part Number 000012545 Rev01 9/15
Section 2 Installation Instructions
Important
Important
!
Warning

Remote Condenser/Line Set Installation

Ice Machine
K1000 KC1000
K1350 KC1350
K1800 KC1350
*Line Set Discharge Line Liquid Line
RTK 1/2" (1.27 cm) 5/16" (.79 cm) RLK 1/2" (1.27 cm) 3/8" (.95 cm)
Air Temperature Around the Condenser
Minimum Maximum
-20°F (-29°C) 120°F (49°C)
Remote systems are only approved and warranted as a complete new package. Warranty on the refrigeration system will be void if a new ice machine head section is connected to pre-existing (used) tubing or remote condensers.
Remote Single
Circuit Condenser
Line Set*
RTK-20-R410A RTK-35-R410A RTK-50-R410A
RLK-20-R410A RLK-35-R410A RLK-50-R410A
RLK-20-R410A RLK-35-R410A RLK-50-R410A

REMOTE ICE MACHINE REFRIGERANT CHARGE

Each remote ice machine ships from the factory with a refrigerant charge appropriate for installation with line sets of up to 50' (15 m). The serial tag on the ice machine indicates the refrigerant charge.
Additional refrigerant may be required for installations using line sets between 50' and 100' (15-30 m) long. If additional refrigerant is required, refer to the chart below for the correct amount to be added.
Ice Machine
K1000 2 lbs (907g) K1350 2 lbs (907g) K1800 2 lbs (907g)
Refrigerant to be added for
50'-100' Line Sets
EPA CERTIFIED TECHNICIANS
If remote line set length is between 50' and 100' (15 and 30 m), add additional refrigerant to the nameplate charge. Refer to the table below for the model being worked on.
Tubing length: ______________________________________
Refrigerant added to nameplate: _______________________
New total refrigerant charge: __________________________
Potential Personal Injury Situation
The ice machine contains refrigerant charge. Installation of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Part Number 000012545 Rev01 9/15 11
Installation Instructions Section 2
!
Caution
DOWNWARD HORIZONTAL
SPIRAL

GENERAL

Condensers must be mounted horizontally with the fan motor on top with nothing obstructing it. There must be at least a 16" (41 cm) clearance from the bottom for air intake. The front coupling panel and one other panel (back or side) must also be unobstructed.
Remote condenser installations consist of vertical and horizontal line sets between the ice machine and the condenser. When combined, they must fit within approved specifications. The following guidelines, drawings and calculation methods must be followed to verify a proper remote condenser installation.
The compressor warranty (including the labor replacement warranty) will not apply if the remote ice machine is not installed according to specifications.
The warranty also will not apply if the refrigeration system is modified with a condenser, heat reclaim device, or other parts or assemblies not manufactured by us unless we specifically approved the component in writing.
3
2
1
DOWNWARD HORIZONTAL
SPIRAL
1
2
3

WIRING

Interconnecting line voltage wiring is used to energize and de-energize the condenser fan motor.
The remote condenser voltage matches the ice machine head section voltage.
Interconnecting Wire Connections
Ice Machine Head Section Remote Condenser
F1 L1 F2 L2

GUIDELINES FOR ROUTING LINE SETS

First, cut a 2.5" (6.35 cm) circular hole in the wall or roof for tubing routing. The line set end with the 90° bend will connect to the ice machine. The straight end will connect to the remote condenser.
Follow these guidelines when routing the refrigerant lines. This will help ensure proper performance and service accessibility.
1. Optional - Make the service loop in the line sets (as shown in Routing Line Sets graphic). This permits easy access to the ice machine for cleaning and service. Do not use hard rigid copper at this location.
2. Required - Do not form traps in the refrigeration lines (except the service loop). Refrigerant oil must be free to drain toward the ice machine or the condenser. Route excess tubing in a supported downward horizontal spiral (as shown below). Do not coil tubing vertically.
3. Required - Keep outdoor refrigerant line runs as short as possible.
Routing Line Sets
12 Part Number 000012545 Rev01 9/15
Section 2 Installation Instructions
!
Caution
H
R
Combination of a Rise and a
Horizontal Run
Combination of a Drop and a
Horizontal Run
Combination of a Rise, a Drop and a
Horizontal Run
SV1196 SV1195 SV1194

CALCULATING REMOTE CONDENSER INSTALLATION DISTANCES

Line Set Length
The maximum length is 100' (30 m).
The ice machine compressor must have the proper oil return. The receiver is designed to hold a charge sufficient to operate the ice machine in ambient temperatures between
-20°F (-29°C) and 120°F (49°C), with line set lengths of up to 100' (30 m).
Line Set Rise/Drop
The maximum rise is 35' (10.7 m).
The maximum drop is 15' (4.5 m).
If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.
Calculated Line Set Distance
The maximum calculated distance is 150' (45 m).
Line set rises, drops, horizontal runs (or combinations of these) in excess of the stated maximums will exceed compressor start-up and design limits. This will cause poor oil return to the compressor.
Make the following calculations to make sure the line set layout is within specifications.
1. Insert the measured rise into the formula below. Multiply by 1.7 to get the calculated rise.
(Example: A condenser located 10 feet above the ice machine has a calculated rise of 17 feet.)
2. Insert the measured drop into the formula below. Multiply by 6.6 to get the calculated drop.
(Example. A condenser located 10 feet below the ice machine has a calculated drop of 66 feet.)
3. Insert the measured horizontal distance into the formula below. No calculation is necessary.
4. Add together the calculated rise, calculated drop, and
horizontal distance to get the total calculated distance. If this total exceeds 150' (45 m), move the
condenser to a new location and perform the calculations again.
Maximum Line Set Distance Formula
Step 1. Measured Rise (35' [10.7 m] Maximum) ______ x 1.7 = _______ Calculated Rise Step 2. Measured Drop (15' [4.5 m] Maximum) ______ x 6.6 = _______ Calculated Drop Step 3. Measured Horizontal Distance (100' [30 m] Maximum) _______ Horizontal Distance Step 4. Total Calculated Distance 150' (45 m) _______ Total Calculated Distance
H
D
H
R
D
Part Number 000012545 Rev01 9/15 13
Installation Instructions Section 2

ROUTE THE LINE SET

Route the line set to avoid traps and kinks.
Minimize the amount of line set exposed on the roof.

CONNECT THE LINE SET

Cut the line set to the correct length.
Purge line set with dry nitrogen while brazing.
Line set shutoff valves on the ice machine must remain closed and be protected from heat during brazing.

PRESSURE TEST AND EVACUATE LINE SET AND CONDENSER

Lineset shutoff valves must remain closed until pressure testing and evacuation are complete.
Pressure test @ 150 psi (1000 kPa) for a minimum of 15 minutes.
Minimum evacuation level is 500 microns.
Pressure test the line set and condenser with 150 psig of dry nitrogen. Add nitrogen at the line set shutoff valves located at the back of the ice machine head section. Complete the pressure test, verify no leaks are present and remove the nitrogen from the system before connecting the vacuum pump.

OPEN LINE SET VALVES

You will not hear refrigerant flow when the valves are opened. Refrigerant will not flow until the ice machine is started and the solenoid valve opens.
All valve caps must be reinstalled, tightened and leak­checked to assure no refrigerant leakage exists.
Counterclockwise opens all valves.
14 Part Number 000012545 Rev01 9/15
Section 2 Installation Instructions
!
Warning

Installation Check List

Is the Ice Machine level? Have all of the electrical and water connections
been made?
Has the supply voltage been tested and checked
against the rating on the nameplate?
Is there proper clearance around the ice
machine for air circulation?
Is the ice machine grounded and polarity
correct?
Has the ice machine been installed where
ambient temperatures will remain in the range of 35° - 110°F (1.6° - 43.3°C)?
Has the ice machine been installed where the
incoming water temperature will remain in the range of 35° - 90°F (1.6° - 32.2°C)?
Is there a separate drain for the potable water,
bin and water-cooled condenser?
Are the ice machine and bin drains vented?

Additional Checks for Remote Models

Does the remote condenser fan operate
properly after start-up?
Has the remote condenser been located where
ambient temperatures will remain in the range of -20° - 120°F (-29 - 49°C).
Is the line set routed properly? Are both refrigeration lines to remote condenser
run so they do not lay in water and are properly insulated?

Before Starting the Ice Machine

All ice machines are factory-operated and adjusted before shipment. Normally, new installations do not require any adjustment.
To ensure proper operation, follow the Operational Checks in Section 3 of this manual. Starting the ice machine and completing the Operational Checks are the responsibilities of the owner/operator.
Adjustments and maintenance procedures outlined in this manual are not covered by the warranty.
Are all refrigerant lines free from contact with
other components?
Are all electrical leads free from contact with
refrigeration lines and moving equipment?
Has the owner/operator been instructed
regarding maintenance and the use of our Cleaner and Sanitizer?
Has the owner/operator completed the
warranty registration card?
Has the ice machine and bin been sanitized? Is the ice thickness set correctly? (Refer to
Operational Checks to check/set the correct ice bridge thickness).
Potential Personal Injury Situation
Do not operate equipment that has been misused. abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
Part Number 000012545 Rev01 9/15 15
Installation Instructions Section 2
THIS PAGE INTENTIONALLY LEFT BLANK
16 Part Number 000012545 Rev01 9/15
Loading...
+ 42 hidden pages