Manitowoc Ice K-0170 Service Manual

Page 1
Undercounter Ice Machines
Technician’s Handbook
This manual is updated as new information and models are released. Visit our website for the latest manual. www.kool-aire.com
Part Number STH047 5/16
Page 2
Page 3
Safety Notices
Read these precautions to prevent personal injury:
Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty.
Proper installation, care and maintenance are essential for maximum performance and trouble-free operation of your equipment.
Visit our website www.kool-aire.com for manual updates, translations, or contact information for service agents in your area.
This equipment contains high voltage electricity and refrigerant charge. Installation and repairs are to be performed by properly trained technicians aware of the dangers of dealing with high voltage electricity and refrigerant under pressure. The technician must also be certified in proper refrigerant handling and servicing procedures. All lockout and tag out procedures must be followed when working on this equipment.
This equipment is intended for indoor use only. Do not install or operate this equipment in outdoor areas.
As you work on this equipment, be sure to pay close attention to the safety notices in this handbook. Disregarding the notices may lead to serious injury and/or damage to the equipment.
Page 4
Warning
n
Follow these electrical requirements during installation of this equipment.
All field wiring must conform to all applicable codes of the authority having jurisdiction. It is the responsibility of the end user to provide the disconnect means to satisfy local codes. Refer to rating plate for proper voltage.
This appliance must be grounded.
This equipment must be positioned so that the plug is accessible unless other means for disconnection from the power supply (e.g., circuit breaker or disconnect switch) is provided.
Check all wiring connections, including factory terminals, before operation. Connections can become loose during shipment and installation.
Page 5
Warning
n
Follow these precautions to prevent personal injury during installation of this equipment:
Installation must comply with all applicable equipment fire and health codes with the authority having jurisdiction.
To avoid instability the installation area must be capable of supporting the combined weight of the equipment and product. Additionally the equipment must be level side to side and front to back.
Ice machines require a deflector when installed on an ice storage bin. Prior to using a non-OEM ice storage system with this ice machine, contact the bin manufacturer to assure their ice deflector is compatible.
Remove all removable panels before lifting and installing and use appropriate safety equipment during installation and servicing. Two or more people are required to lift or move this appliance to prevent tipping and/or injury.
Do not damage the refrigeration circuit when installing, maintaining or servicing the unit.
Connect to a potable water supply only.
This equipment contains refrigerant charge.
Installation of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Page 6
Warning
n
Follow these precautions to prevent personal injury while operating or maintaining this equipment.
Legs or casters must be installed and the legs/ casters must be screwed in completely. When casters are installed the mass of this unit will allow it to move uncontrolled on an inclined surface. These units must be tethered/secured to comply with all applicable codes. Swivel casters must be mounted on the front and rigid casters must be mounted on the rear. Lock the front casters after installation is complete.
Some 50 Hz models may contain up to 150 grams of R290 (propane) refrigerant. R290 (propane) is flammable in concentrations of air between approximately 2.1% and 9.5% by volume (LEL lower explosion limit and UEL upper explosion limit). An ignition source at a temperature higher than 470°C is needed for a combustion to occur.
Refer to nameplate to identify the type of refrigerant in your equipment.
Only trained and qualified personnel aware of the dangers are allowed to work on the equipment.
Crush/Pinch Hazard. Keep hands clear of moving components. Components can move without warning unless power is disconnected and all potential energy is removed.
Moisture collecting on the floor will create a slippery surface. Clean up any water on the floor immediately to prevent a slip hazard.
Page 7
Warning
n
Follow these precautions to prevent personal injury while operating or maintaining this equipment.
Objects placed or dropped in the bin can affect human health and safety. Locate and remove any objects immediately.
Never use sharp objects or tools to remove ice or frost.
Do not use mechanical devices or other means to accelerate the defrosting process.
When using cleaning fluids or chemicals, rubber gloves and eye protection (and/or face shield) must be worn.
DANGER
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision concerning use of the appliance by a person responsible for their safety. Do not allow children to play with, clean or maintain this appliance without proper supervision.
Page 8
DANGER
Follow these precautions to prevent personal injury during use and maintenance of this equipment:
It is the responsibility of the equipment owner to perform a Personal Protective Equipment Hazard Assessment to ensure adequate protection during maintenance procedures.
Do Not Store Or Use Gasoline Or Other Flammable Vapors Or Liquids In The Vicinity Of This Or Any Other
Appliance. Never use flammable oil soaked cloths or combustible cleaning solutions for cleaning.
All covers and access panels must be in place and properly secured when operating this equipment.
Risk of fire/shock. All minimum clearances must be maintained. Do not obstruct vents or openings.
Failure to disconnect power at the main power supply disconnect could result in serious injury or death. The power switch DOES NOT disconnect all incoming power.
All utility connections and fixtures must be maintained in accordance with the authority having jurisdiction.
Turn off and lockout all utilities (gas, electric, water) according to approved practices during maintenance or servicing.
Units with two power cords must be plugged into individual branch circuits. During movement, cleaning or repair it is necessary to unplug both power cords.
We reserve the right to make product improvements at any time. Specifications and design are subject to change without notice.
Page 9
Table of Contents
General Information
Model Numbers............................... 13
How to Read a Model Number ................ 14
Accessories ...................................14
Bin Caster .................................14
Cleaner and Sanitizer ......................14
Model/Serial Number Location ............... 15
Ice Machine Warranty Information............ 15
Installation
Location of Ice Machine....................... 17
Ice Machine Clearance Requirements......... 18
Ice Machine Heat of Rejection ................ 18
Leveling the Ice Machine......................19
Electrical Requirements....................... 20
Voltage ...................................20
Fuse/Circuit Breaker .......................20
Total Circuit Ampacity ..................... 20
Electrical Specifications....................... 21
Air-cooled Ice Machine .................... 21
Water-cooled Ice Machines ................22
Water Service/Drains .........................23
Water Supply.............................. 23
Water Inlet Lines ..........................23
Drain Connections ........................ 23
Water Supply and Drain Line Sizing/
Connections .............................. 24
Cooling Tower Applications ................25
Component Identification
Evaporator Compartment ....................27
Part Number STH047 5/16 9
Page 10
Maintenance
Ice Machine Inspection .................... 29
Exterior Cleaning ..........................29
Cleaning the Condenser ...................29
Interior Cleaning and Sanitizing............ 31
Removal from Service/Winterization .........44
Operation
Initial Start-up or Start-up After Automatic
Shut-off ................................... 47
Freeze Sequence ..........................47
Harvest Sequence ......................... 48
Automatic Shut-off ........................48
Energized Parts Chart...................... 49
Operational Checks ...........................51
Troubleshooting
Diagnosing an Ice Machine that Will Not Run..
........................................... 54
Diagnosing Ice Thickness Control Circuitry . 55
Ice Production Check ......................58
Installation and Visual Inspection Checklist. 60
Water System Checklist.................... 61
Ice Formation Pattern......................62
Safety Limit Feature .......................64
Analyzing Discharge Pressure .............71
Analyzing Suction Pressure ................ 73
Harvest Valve.............................. 77
Comparing Evaporator Inlet/Outlet
Temperatures ............................. 81
Discharge Line Temperature Analysis.......82
Refrigeration Component Diagnostic Chart 84
Procedure................................. 85
Final Analysis.............................. 86
Refrigeration Component Diagnostic Chart 87 Ice Quality Is Poor — Cubes are Shallow,
Incomplete or White....................... 90
Freeze Cycle Is Long, Low Ice Production ...91 Ice Machine Runs and No Ice Is Produced...92
10 Part Number STH047 5/16
Page 11
Component Check Procedures
Main Fuse .....................................93
Bin Switch..................................... 94
Diagnosing Start Components................ 97
Capacitor .................................97
Relay...................................... 97
ON/OFF/WASH Toggle Switch .................98
Ice Thickness Probe . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Ice Thickness Check ......................100
Compressor Electrical Diagnostics...........101
Fan Cycle Control ............................103
High Pressure Cutout (HPCO) Control........104
Filter-Driers ..................................105
Refrigerant Recovery/Evacuation............106
Refrigerant Re-use Policy .................107
Recovery and Recharging Procedures ....109
System Contamination Cleanup .............112
Mild System Contamination Cleanup
Procedure................................114
Severe System Contamination Cleanup
Procedure................................115
Replacing Pressure Controls without
Removing Refrigerant Charge.............117
K270 Condenser Fan Motor Access...........119
Part Number STH047 5/16 11
Page 12
Component Specifications
Main Fuse ....................................121
Bin Switch....................................121
ON/OFF/WASH Toggle Switch ................121
Fan Control Cycle ............................121
High Pressure Cutout (HPCO) Control........121
Filter-Driers ..................................121
Total System Refrigerant Charge.............122
Charts
Cycle Times, 24 Hr. Ice Production and
Refrigerant Pressure Charts..................123
K170 Self-contained Air-cooled ...........124
K270 Self-contained Air-cooled ...........125
K270 Self-contained Water-cooled ........126
Diagrams
Wiring Diagrams .............................127
K170 / K270 Wiring Diagram ..............128
Electronic Control Boards....................130
K170/K270 Tubing Schematic .............131
12 Part Number STH047 5/16
Page 13
General Information

Model Numbers

This manual covers the following models:
Self-contained Air-cooled Self-contained Water-cooled
KD0172A N/A KY0174A N/A KR0270A KR0271W KD0272A KD0273W KY0274A KY0275W
Warning
n
An ice machine contains high voltage electricity and refrigerant charge. Repairs are to be performed by properly trained refrigeration technicians aware of the dangers of dealing with high voltage electricity and refrigerant under pressure.
Part Number STH047 5/16 13
Page 14

How to Read a Model Number

Cube Size
Series
Capacity
Condenser
Type
K D 0172 A
A - Air-cooled
D - Dice Y - Half-dice

Accessories

Contact your distributor for these optional accessories:

BIN CASTER

Replaces standard legs.

CLEANER AND SANITIZER

Manitowoc Ice Machine Cleaner and Sanitizer are available in convenient 16 oz. (473 ml) and 1 gal (3.78 l) bottles. These are the only cleaner and sanitizer approved for use with Koolaire products.
Cleaner Part Number Sanitizer Part Number
16 oz 94-0456-3 16 oz 94-0565-3 *16 oz 000000084 1 Gallon 4-0580-3 1 Gallon 94-0581-3
2 - Dice, Air-cooled 4 - Half-dice, Air-cooled
14 Part Number STH047 5/16
Page 15

Model/Serial Number Location

The model and serial numbers are required when requesting information from your local distributor, service representative, or Manitowoc KitchenCare®. The model and serial number are listed on the OWNER WARRANTY REGISTRATION CARD. They are also listed on the MODEL/ SERIAL NUMBER DECAL affixed to the ice machine.
MODEL/SERIAL NUMBER PLATE
MODEL/SERIAL NUMBER PLATE
SV1687G
Model/Serial Number Location

Ice Machine Warranty Information

For warranty information visit:
http://www.koo-aire.com/Service/Warranty
Warranty Verification
Warranty Registration
View and download a copy of the warranty
Part Number STH047 5/16 15
Page 16
THIS PAGE INTENTIONALLY LEFT BLANK
16 Part Number STH047 5/16
Page 17

Installation

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.
The location must be indoors.
The location must be free of airborne and other contaminants.
Air temperature:
Must be at least 40°F (4°C) but must not exceed
110°F (43.4°C).
The location must not be near heat-generating equipment or in direct sunlight.
The location must be capable of supporting the weight of the ice machine and a full bin of ice.
The location must allow enough clearance for water, drain, and electrical connections in the rear of the ice machine.
The location must not obstruct airflow through or around the ice machine (condenser airflow is in and out the front). Refer to the chart below for clearance requirements.
The ice machine must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty.
Part Number STH047 5/16 17
Page 18

Ice Machine Clearance Requirements

Self-contained
Air-cooled
Top/Sides 5" (127 mm)*
Back 5" (127 mm)*
*NOTE: The ice machine may be built into a cabinet.
There is no minimum clearance requirement for the top or left and right sides of the ice machine. The listed values are recommended for efficient operation and servicing only.

Ice Machine Heat of Rejection

Series
Ice Machine
K170 2200 2600 K270 3800 6000
* B.T.U./Hour ** Because the heat of rejection varies during the ice making
cycle, the figure shown is an average.
Air Conditioning** Peak
Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment where self-contained air­cooled ice machines are installed.
Heat of Rejection*
18 Part Number STH047 5/16
Page 19

Leveling the Ice Machine

1. Screw the leveling legs onto the bottom of the ice machine.
2. Screw the foot of each leg in as far as possible.
Caution
,
The legs must be screwed in tightly to prevent them from bending.
3. Move the ice machine into its final position.
4. Level the ice machine to ensure that the siphon system functions correctly. Use a level on top of the ice machine. Turn each foot as necessary to level the ice machine from front to back and side to side.
NOTE: An optional 2-1/2" (6.35 cm) caster assembly is available for use in place of the legs on the K170, K210, and K270. Installation instructions are supplied with the casters.
THREAD LEVELING LEG INTO BASE OF
CABINET
THREAD “FOOT”
IN AS FAR AS
POSSIBLE
SV1606
Leg Installation
Part Number STH047 5/16 19
Page 20

Electrical Requirements

VOLTAGE

The maximum allowable voltage variation is ±10% of the rated voltage on the ice machine model/serial number plate at start-up (when the electrical load is highest).
The 115/1/60 ice machines are factory pre-wired with a 6' (1.8 m) power cord, and NEMA 5-15P-plug configuration.
The 208-230/1/60 and 230/1/50 ice machines are factory pre-wired with a power cord only, no plug is supplied.

FUSE/CIRCUIT BREAKER

A separate fuse/circuit breaker must be provided for each ice machine. Circuit breakers must be H.A.C.R. rated (does not apply in Canada).

TOTAL CIRCUIT AMPACITY

The total circuit ampacity is used to help select the wire size of the electrical supply.
The wire size (or gauge) is also dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.
20 Part Number STH047 5/16
Page 21

Electrical Specifications

AIRCOOLED ICE MACHINE
Ice Machine Voltage Phase
Cycle
K170 115/1/60 15 amp 7.0
208/1/60 15 amp 3.5 230/1/50 15 amp 4.0
K270 115/1/60 15 amp 10.7
208-230/1/60 15 amp 5.2
230/1/50 15 amp 5.2
Warning
n
All wiring must conform to local, state and national codes.
Warning
n
The ice machine must be grounded in accordance with national and local electrical code.
Max. Fuse/
Circuit
Breaker
Total
Amps
Part Number STH047 5/16 21
Page 22
WATERCOOLED ICE MACHINES
Ice Machine Voltage
Phase Cycle
K170 115/1/60 15 amp 6.3
208/1/60 15 amp 3.6 230/1/50 15 amp 4.0
K270 115/1/60 15 amp 9.9
208-230/1/60 15 amp 4.7
230/1/50 15 amp 4.7
Max. Fuse/
Circuit
Breaker
Total
Amps
22 Part Number STH047 5/16
Page 23

Water Service/Drains

WATER SUPPLY

Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.
Important
If you are installing a water filter system, refer to the Installation Instructions supplied with the filter system for ice making water inlet connections.

WATER INLET LINES

Follow these guidelines to install water inlet lines:
Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)
If water pressure exceeds the maximum recommended pressure, 80 psig (5.5 bar) obtain a water pressure regulator from your distributor.
Install a water shut-off valve for ice making potable water.
Insulate water inlet lines to prevent condensation.

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:
Drain lines must have a 1.5-inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.
The floor drain must be large enough to accommodate drainage from all drains.
Run separate bin and ice machine drain lines. Insulate them to prevent condensation.
Vent the bin and ice machine drain to the atmosphere.
Part Number STH047 5/16 23
Page 24

WATER SUPPLY AND DRAIN LINE SIZING/ CONNECTIONS

to Ice Machine
Tubing Size Up
Ice Machine
Water
Water
Fitting
Fitting
Pressure
Temperature
inside diameter
inside diameter
3/8" (9.5 mm) min.
3/8” Female
Pipe Thread
80 psi (5.5 bar) max.
20 psi (1.38 bar) min.
(32.2°C) max.
40°F (4°C) min. 90°F
inside diameter
3/8" (9.5 mm) min.
3/8" (9.5 mm) min.
3/8” Female
3/8” Female
Pipe Thread
Pipe Thread
20 psi (1.38 bar) min.
150 psi (10.3 bar) max.
33°F (0.6°C) min.
90°F (32.2°C) max.
diameter
min. inside
1/2" (12.7 mm)
1/2” Female
Pipe Thread
Location
24 Part Number STH047 5/16
Condenser
Ice Making
Water Inlet
Water Inlet
Bin Drain
Condenser
Water Drain
Page 25

COOLING TOWER APPLICATIONS

Water Cooled Models Only
A water-cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.
It is necessary to know the amount of heat rejected, and the pressure drop through the condenser and water valves (inlet to outlet) when using a cooling tower on an ice machine.
Water entering the condenser must not exceed 90°F (32.2°C).
Water flow through the condenser must not exceed 5 gallons (19 liters) per minute.
Allow for a pressure drop of 7 psig (.48 bar) between the condenser water inlet and the outlet of the ice machine.
Water exiting the condenser must not exceed 110°F (43.3°C).
Caution
,
Plumbing must conform to state and local codes.
Part Number STH047 5/16 25
Page 26
THIS PAGE INTENTIONALLY LEFT BLANK
26 Part Number STH047 5/16
Page 27

Component Identification

Evaporator Compartment

DISTRIBUTION
TUBE
DAMPER
WATER
TROUGH
FLOAT VALVE
ICE THICKNESS
PROBE
ICE
WATER
PUMP
SV1694A
SIPHON CAP
BIN SWITCH
MAGNET
SV1695A
Evaporator Compartment
Part Number STH047 5/16 27
Page 28
ON/OFF/WASH
TOGGLE SWITCH
CONDENSED AIR
FILTER
ON/OFF/WASH
TOGGLE
SWITCH
COMPRESSOR
COMPARTMENT ACCESS
SCREWS
COMPRESSOR
COMPARTMENT
ACCESS SCREWS
SV1686G
K170 Ice Machines
CONDENSED AIR
FILTER
PT1288
K270 Ice Machines
28 Part Number STH047 5/16
Page 29

Maintenance

ICE MACHINE INSPECTION

Check all water fittings and lines for leaks. Also, make sure the refrigeration tubing is not rubbing or vibrating against other tubing, panels, etc.
Do not put anything (boxes, etc.) in front of the ice machine. There must be adequate airflow through and around the ice machine to maximize ice production and ensure long component life.

EXTERIOR CLEANING

Clean the area around the ice machine as often as necessary to maintain cleanliness and efficient operation.
Sponge any dust and dirt off the outside of the ice machine with mild soap and water. Wipe dry with a clean, soft cloth.
A commercial grade stainless steel cleaner/polish can be used as necessary.

CLEANING THE CONDENSER

Warning
n
Disconnect electric power to the ice machine at the electric service switch before cleaning the condenser.
Caution
,
If you are cleaning the condenser fan blades with water, cover the fan motor to prevent water damage.
COMB DOWN
Part Number STH047 5/16 29
CONDENSER
FIN COMB
ONLY
Page 30
Air-cooled Condenser
A dirty condenser restricts airflow, resulting in excessively high operating temperatures. This reduces ice production and shortens component life. Clean the condenser at least every six months. Follow the steps below.
Warning
n
The condenser fins are sharp. Use care when cleaning them.
1. The washable aluminum filter on self-contained air­cooled ice machines is designed to catch dust, dirt, lint and grease. This helps keep the condenser clean. Clean the filter with a mild soap and water solution.
2. Clean the outside of the condenser with a soft brush or a vacuum with a brush attachment. Clean from top to bottom, not side to side. Be careful not to bend the condenser fins.
3. Shine a flashlight through the condenser to check for dirt between the fins. If dirt remains:
A. Blow compressed air through the condenser
fins from the inside. Be careful not to bend the fan blades.
B. Use a commercial condenser coil cleaner. Follow
the directions and cautions supplied with the cleaner.
4. Straighten any bent condenser fins with a fin comb.
5. Carefully wipe off the fan blades and motor with a soft cloth. Do not bend the fan blades. If the fan blades are excessively dirty, wash with warm, soapy water and rinse thoroughly.
30 Part Number STH047 5/16
Page 31

INTERIOR CLEANING AND SANITIZING

General
Clean and sanitize the ice machine every six months for efficient operation. If the ice machine requires more frequent cleaning and sanitizing, consult a qualified service company to test the water quality and recommend appropriate water treatment.
The ice machine must be taken apart for cleaning and sanitizing.
Caution
,
Use only Manitowoc Ice Machine Cleaner (part number 95-0546-3) and Sanitizer (part number 94­0565-3). It is a violation of Federal law to use these solutions in a manner inconsistent with their labeling. Read and understand all labels printed on bottles before use.
Cleaning and Sanitizing Procedure
Caution
,
Do not mix Ice Machine Cleaner and Sanitizer solutions together. It is a violation of Federal law to use these solutions in a manner inconsistent with their labeling.
Warning
n
Wear rubber gloves and safety goggles (and/or face shield) when handling Ice Machine Cleaner or Sanitizer.
Ice machine cleaner is used to remove lime scale and mineral deposits. Ice machine sanitizer disinfects and removes algae and slime.
Part Number STH047 5/16 31
Page 32
Step 1 Set the toggle switch to the OFF position after ice falls from the evaporator at the end of a Harvest cycle. Or, set the switch to the OFF position and allow the ice to melt off the evaporator.
Caution
,
Never use anything to force ice from the evaporator. Damage may result.
Step 2 Remove all ice from the bin.
Step 3 To start a cleaning cycle, move the toggle
switch to the WASH position.
Step 4 Add the proper amount of Ice Machine Cleaner to the water trough.
Model Amount of Cleaner
K170 2 ounces (60 ml) K270 2 ounces (60 ml)
Step 5 Wait until the clean cycle is complete (approximately 22 minutes) then place the toggle switch in the OFF position, disconnect power and water supplies to the ice machine.
Warning
n
Disconnect electric power to the ice machine at the electric switch box before proceeding.
32 Part Number STH047 5/16
Page 33
Step 6 Remove parts for cleaning.
A. Remove Two Thumbscrews and Water Pump
Cover (When Used).
B. Remove the Vinyl Hose Connecting the
Water Pump and Water Distribution Tube
C. Remove Water Pump
• Disconnect the water pump power cord
• Loosen the screws securing the pump­mounting bracket to the bulkhead
• Lift the pump and bracket assembly off the mounting screws.
WHEN USED - REMOVE
THUMBSCREWS AND
WATER PUMP COVER
DO NOT SOAK WATER
PUMP MOTOR IN
CLEANER OR SANITIZER
SOLUTION
Water Pump Removal
Part Number STH047 5/16 33
Page 34
D. Remove the Ice Thickness Probe
• Compress the side of the ice thickness probe near the top hinge pin and remove it from the bracket.
ICE
THICKNESS
PROBE
COMPRESS SIDES OF
ICE THICKNESS PROBE
SV1138A
Ice Thickness Probe Removal
NOTE: At this point, the ice thickness probe can easily be cleaned. If complete removal is desired, follow the ice thickness probe wire to the bulkhead grommet (exit point) in the back wall. Pop the bulkhead grommet out of the back wall by inserting fingernails or a flat object between the back wall and the grommet and prying forward. Pull the bulkhead grommet and wire forward until the connector is accessible, then disconnect the wire lead from the connector.
Ice Thickness Probe Cleaning
Mix a solution of ice machine cleaner and water (2 ounces of cleaner to 16 ounces of water) in a container.
Soak the ice thickness probe a minimum of 10 minutes.
Clean all ice thickness probe surfaces and verify the ice thickness probe cavity is clean. Rinse thoroughly with clean water, then dry completely. Incomplete rinsing and drying of the ice thickness probe can cause premature harvest.
34 Part Number STH047 5/16
Page 35
E. Remove the Water Distribution Tube
1. LIFT UP
2. SLIDE BACK
3. SLIDE TO RIGHT
DISTRIBUTION
TUBE
3
2
1
THUMBSCREW
THUMBSCREW
SV1630
Water Distribution Tube Removal
• Loosen the two thumbscrews, which secure the distribution tube.
• Lift the right side of the distribution tube up off the locating pin, then slide it back and to the right.
Caution
,
Do not force this removal. Be sure the locating pin is clear of the hole before sliding the distribution tube out.
Part Number STH047 5/16 35
Page 36
Disassembly
Twist both of the inner tube ends until the tabs line up with the keyways.
Pull the inner tube ends outward.
INNER
TUBE
INNER
TUBE
TAB
KEYWAY
SV1211
Water Distribution Tube Disassembly
36 Part Number STH047 5/16
Page 37
F. Remove the Float Valve
• Turn the splash shield counterclockwise one or two turns.
FLOAT VALVE
BRACKET
COMPRESSION
FITTING
SHUT-OFF
VALVE
CAP AND FILTER
SPLASH
SHIELD
Float Valve Removal
• Pull the float valve forward and off the mounting bracket.
• Disconnect the water inlet tube from the float valve at the compression fitting.
• Remove the cap and filter screen for cleaning.
SCREEN
FL OAT
SV1695-2
Part Number STH047 5/16 37
Page 38
G. Remove the Water Trough
• Apply downward pressure on the siphon tube and remove from the bottom of the water trough.
• Remove the upper thumbscrew.
• While supporting the water trough remove the two thumbscrews from beneath the water trough.
• Remove the water trough from the bin area.
UPPER
THUMBSCREW
SV1689-1
LOWER
THUMBSCREWS
REMOVE
SIPHON
TUBE
SV1689-2
Remove the Ice Damper
38 Part Number STH047 5/16
Page 39
H. Remove the ice damper
Grasp ice damper and apply pressure toward the left­hand mounting bracket.
Apply pressure to the right-hand mounting bracket with thumb.
Pull ice damper forward when the right-hand ice damper pin disengages.
STEP 3
STEP 2
STEP 1
SV1742A
Installation
Place ice damper pin in left-hand mounting bracket and apply pressure toward the left-hand mounting bracket.
Apply pressure to the right-hand mounting bracket with thumb.
Push ice damper toward evaporator until right-hand damper pin engages.
STEP 2
STEP 1
Part Number STH047 5/16 39
STEP 3
SV1742H
Page 40
Remove the Bin Door
Grasp the rear of the bin door and pull bin door forward approximately 5".
Slide bin door to the rear while applying upward pressure (The rear door pins will ride up into the track slot and slide backward to the stop tab).
While applying pressure against the bin door pull down on the rear of each bin door track until the door pins clear the stop tabs.
Slide the rear door pins off the end and then below the door track. Slide bin door forward allowing the back of the door to lower into the bin. Continue forward with the bin door until the front pins bottom out in the track.
Lift right side of door until the front pins clear the track, then remove door from bin.
Remove rollers (4) from all door pins.
STOP TAB
TRACK SLOT
SLIDE DOOR
FORWARD
SV1748
40 Part Number STH047 5/16
Page 41
Step 7 Mix a solution of cleaner and warm water. Depending on the amount of mineral buildup, a larger quantity of solution may be required. Use the ratio in the table below to mix enough solution to thoroughly clean all parts.
Solution Type Water Mixed with
Cleaner 1 gal. (4 l) 16 oz (500 ml) cleaner
Step 8 Use 1/2 of the cleaner/water solution to clean all components. The cleaner solution will foam when it contacts lime scale and mineral deposits; once the foaming stops use a soft bristle brush, sponge or cloth (not a wire brush) to carefully clean the parts. Soak the parts for 5 minutes (15 – 20 minutes for heavily scaled parts). Rinse all components with clean water.
Step 9 While components are soaking, use 1/2 of the cleaner/water solution to clean all foodzone surfaces of the ice machine and bin. Use a nylon brush or cloth to thoroughly clean the following ice machine areas:
Evaporator plastic parts – including top, bottom andsides
Bin bottom, sides and top
Rinse all areas thoroughly with clean water.
Step 10 Mix a solution of sanitizer and warm water.
Solution Type Water Mixed With
Sanitizer 6 gal. (23 l) 4 oz (120 ml) sanitizer
Part Number STH047 5/16 41
Page 42
Step 11 Use 1/2 of the sanitizer/water solution to sanitize all removed components. Use a cloth or sponge to liberally apply the solution to all surfaces of the removed parts or soak the removed parts in the sanitizer/ water solution. Do not rinse parts after sanitizing.
Step 12 Use 1/2 of the sanitizer/water solution to sanitize all foodzone surfaces of the ice machine and bin. Use a cloth or sponge to liberally apply the solution. When sanitizing, pay particular attention to the following areas:
Evaporator plastic parts - including top, bottom and sides
Bin bottom, sides and top
Do not rinse the sanitized areas.
Step 13 Replace all removed components.
Step 14 Reapply power and water to the ice machine
and place the toggle switch in the WASH position.
Add the proper amount of Ice Machine Sanitizer to the water trough.
Model Amount of Sanitizer
K170 2.2 ounces (66 ml) K270 1.9 ounces (57 ml)
Step 15 Wait until the sanitize cycle is complete (approximately 22 minutes) then place the toggle switch in the OFF position, disconnect power and water supplies to the ice machine.
Warning
n
Disconnect electric power to the ice machine at the electric switch box before proceeding.
Step 16 Repeat step 6 to remove parts for hand sanitizing.
42 Part Number STH047 5/16
Page 43
Step 17 Mix a solution of sanitizer and warm water.
Solution Type Water Mixed With
Sanitizer 6 gal. (23 l) 4 oz (120 ml) sanitizer
Step 18 Use 1/2 of the sanitizer/water solution to sanitize all removed components. Use a cloth or sponge to liberally apply the solution to all surfaces of the removed parts or soak the removed parts in the sanitizer/ water solution. Do not rinse parts after sanitizing.
Step 19 Use 1/2 of the sanitizer/water solution to sanitize all foodzone surfaces of the ice machine and bin. Use a cloth or sponge to liberally apply the solution. When sanitizing, pay particular attention to the following areas:
Evaporator plastic parts - including top, bottom and sides
Bin bottom, sides and top
Do not rinse the sanitized areas.
Step 20 Replace all removed components.
Step 21 Reapply power and water to the ice machine
and place the toggle switch in the ICE position.
Part Number STH047 5/16 43
Page 44

Removal from Service/Winterization

General
Special precautions must be taken if the ice machine is to be removed from service for an extended period of time or exposed to ambient temperatures of 32°F (0°C) or below.
Caution
,
If water is allowed to remain in the ice machine in freezing temperatures, severe damage to some components could result. Damage of this nature is not covered by the warranty.
Follow the applicable procedure below.
Self-contained Air-cooled Models
1. Disconnect the electric power at the circuit breaker or the electric service switch.
2. Turn off the water supply.
3. Remove the water from the water trough.
4. Disconnect and drain the incoming ice-making water line at the rear of the ice machine.
5. Blow compressed air in both the incoming water and the drain openings in the rear of the ice machine until no more water comes out of the inlet water lines or the drain.
6. Make sure water is not trapped in any of the water lines, drain lines, distribution tubes, etc.
44 Part Number STH047 5/16
Page 45
Water-cooled Ice Machines
1. Perform steps 1-6 under “Self-contained Air-cooled Models” on page 44.
2. Disconnect the incoming water and drain lines from the water-cooled condenser.
3. Insert a large screwdriver between the bottom spring coils of the water regulating valve. Pry upward to open the valve.
SV1624
Pry Open the Water Regulating Valve
4. Hold the valve open and blow compressed air through the condenser until no water remains.
Part Number STH047 5/16 45
Page 46
THIS PAGE INTENTIONALLY LEFT BLANK
46 Part Number STH047 5/16
Page 47

Operation

INITIAL STARTUP OR STARTUP AFTER AUTOMATIC SHUTOFF
1. Pressure Equalization
Before the compressor starts the harvest valve is energized for 15 seconds to equalize pressures during the initial refrigeration system start-up.
2. Refrigeration System Start-up
The compressor starts after the 15-second pressure equalization, and remains on throughout the entire Freeze and Harvest Sequences. The harvest valve remains on for 5 seconds during initial compressor start-up and then shuts off.
At the same time the compressor starts, the condenser fan motor (air-cooled models) is supplied with power throughout the entire Freeze and Harvest Sequences. The fan motor is wired through a fan cycle pressure control, therefore it may cycle on and off. (The compressor and condenser fan motor are wired through the relay. As a result, any time the relay coil is energized, the compressor and fan motor are supplied with power.)

FREEZE SEQUENCE

3. Prechill
The compressor is on for 30 seconds prior to water flow to prechill the evaporator.
4. Freeze
The water pump starts after the 30-second prechill. An even flow of water is directed across the evaporator and into each cube cell, where it freezes.
When sufficient ice has formed, the water flow (not the ice) contacts the ice thickness probe. After approximately 7 seconds of continual water contact, the Harvest Sequence is initiated. The ice machine cannot initiate a Harvest Sequence until a 6-minute freeze time has been surpassed.
Part Number STH047 5/16 47
Page 48

HARVEST SEQUENCE

5. Harvest
The water pump de-energizes stopping flow over the evaporator. The rising level of water in the sump trough diverts water out of the overflow tube, purging excess minerals from the sump trough. The harvest valve also opens to divert hot refrigerant gas into the evaporator.
The refrigerant gas warms the evaporator causing the cubes to slide, as a sheet, off the evaporator and into the storage bin. The sliding sheet of cubes contacts the ice damper, opening the bin switch.
The momentary opening and re-closing of the bin switch terminates the Harvest Sequence and returns the ice machine to the Freeze Sequence (steps 3 - 4).
AUTOMATIC SHUTOFF
6. Automatic Shut-off
When the storage bin is full at the end of a harvest sequence, the sheet of cubes fails to clear the ice damper and will hold it down. After the ice damper is held open for 7 seconds, the ice machine shuts off. The ice machine remains off for 3 minutes before it can automatically restart.
The ice machine remains off until enough ice has been removed from the storage bin to allow the ice to fall clear of the damper. As the ice damper swings back to the operating position, the bin switch re-closes and the ice machine restarts (steps 1 - 2), provided the 3 minute delay period is complete.
48 Part Number STH047 5/16
Page 49

ENERGIZED PARTS CHART

Time1
3B
Compressor
3A
Compressor
3
Relay
2
Harvest Valve
Control Board Relays Relay Length of
Water Pump
probe
Until 7 sec.
Water contact
w/ice thickness
Fan Motor*
Coil
OPERATION
ICE MAKING
SEQUENCE OF
Initial Start-up
1. Water purge off on off off off 15 seconds
2. Refrigeration
System Start-up off on on on on 5 seconds
3. Pre chill off off on on on 30 seconds
Freeze Sequence
4. Freeze on off on on on
* Condenser Fan Motor: The fan motor is wired through a fancycle pressure control; therefore, it may cycle on and off.
Part Number STH047 5/16 49
Page 50
Time1
Bin switch
activation
switch
Until bin
re-closes
3B
Fan Motor*
Compressor
3A
Compressor
3
Coil
Relay
2
Harvest Valve
Control Board Relays Relay Length of
Water Pump
Harvest
OPERATION
ICE MAKING
SEQUENCE OF
off on on on on
5. Harvest
Sequence
off off off off off
Shut-off
Automatic
6. Auto Shut-off
50 Part Number STH047 5/16
Page 51

Operational Checks

Siphon System
To reduce mineral build-up and cleaning frequency, the water in the sump trough must be purged during each harvest cycle.
When the water pump de-energizes, the level in the water trough rises above the standpipe, starting a siphon action. The siphon action stops when the water level in the sump trough drops. When the siphon action stops, the float valve refills the water trough to the correct level.
Follow steps 1 through 6 under water level check to verify the siphon system functions correctly.
Water Level
Check the water level while the ice machine is in the ice mode and the water pump is running. The correct water level is 1/4" (6.3 mm) to 3/8" (9.5 mm) below the top of the standpipe. A line in the water trough indicates the correct level.
SET THE WATER LEVEL TO
THE LINE IN THE WATER
TROUGH
SIPHON CAP
SV1689-1
Part Number STH047 5/16 51
Page 52
Water Level Check
The float valve is factory-set for the proper water level. If adjustments are necessary:
1. Verify the ice machine is level.
2. Remove the siphon cap from the standpipe.
3. Place the main ON/OFF/WASH toggle switch to the ON position, and wait until the float valve stops adding water.
4. Adjust the water level to [1/4" to 3/8" (6.3 to 9.5 mm) below the standpipe] the line in the water trough:
A. Loosen the two screws on the float valve
bracket.
B. Raise or lower the float valve assembly as
necessary, then tighten the screws.
5. Move the main ON/OFF/WASH toggle switch to the OFF position. The water level in the trough will rise above the standpipe and run down the drain.
6. Replace the siphon cap on the standpipe, and verify water level and siphon action by repeating steps 3 through 5.
Ice Thickness Check
After a harvest cycle, inspect the ice cubes in the ice storage bin. The ice thickness probe is set to maintain an ice bridge of 1/8" (3.2 mm). If an adjustment is needed, follow the steps below.
1. Turn the ice thickness probe adjustment screw clockwise for a thicker ice bridge, or counterclockwise for a thinner ice bridge.
52 Part Number STH047 5/16
Page 53
ADJUSTING
SCREW
1/8" ICE BRIDGE
THICKNESS
SV3113
SV3114
Ice Thickness Adjustment
2. Make sure the ice thickness probe wire and bracket does not restrict movement of the probe.
Part Number STH047 5/16 53
Page 54

Troubleshooting

DIAGNOSING AN ICE MACHINE THAT WILL NOT RUN

Warning
n
High (line) voltage is applied to the control board (terminals #2 and #4) at all times. Removing control board fuse or moving the toggle switch to OFF will not remove the power supplied to the control board.
1. Verify primary voltage is supplied to ice machine and the fuse/circuit breaker is closed.
2. Verify control board fuse is okay.
3. If the bin switch light functions, the fuse is okay.
4. Verify the bin switch functions properly. A defective bin switch can falsely indicate a full bin of ice.
5. Verify ON/OFF/WASH toggle switch functions properly. A defective toggle switch may keep the ice machine in the OFF mode.
6. Verify low DC voltage is properly grounded. Loose DC wire connections may intermittently stop the ice machine.
7. Replace the control board.
8. Be sure Steps 1 – 5 were followed thoroughly. Intermittent problems are not usually related to the control board.
Page 55

DIAGNOSING ICE THICKNESS CONTROL CIRCUITRY

Ice Machine Does Not Cycle Into Harvest when Water Contacts the Ice Thickness Control Probe
Step 1 Bypass the freeze time lock-in feature by
moving the ON/OFF/WASH switch to OFF and back to ON. Wait until the water starts to flow over the evaporator.
Step 2 Clip the jumper wire to the ice thickness probe and any cabinet ground.
ICE THICKNESS
PROBE
GROUND
JUMPER WIRE
PROBE
CONNECTION
EVAPORATOR
HARVEST LIGHT
(RED)
BIN SWITCH
LIGHT
(GREEN)
SV1592i
Step 2 Jumper wire connected from probe to ground
Monitoring Harvest Light Correction
The harvest light comes on, and 6-10 seconds later, ice machine cycles from freeze to harvest. The harvest light comes on but the ice machine stays in the freeze sequence.
The ice thickness control circuitry is functioning properly. Do not change any parts. The ice control circuitry is functioning properly. The ice machine is in a six minute freeze time lock-in. Verify Step 1 of this procedure was followed correctly.
The harvest light does not
Proceed to Step 3.
come on.
Part Number STH047 5/16 55
Page 56
Step 3 Disconnect the ice thickness probe from the control board terminal. Clip the jumper wire to the terminal on the control board and any cabinet ground. Monitor the harvest light.
PROBE
ICE THICKNESS
PROBE
JUMPER WIRE
GROUND
CONNECTION
EVAPORATOR
BIN SWITCH
LIGHT
(GREEN)
HARVEST LIGHT
(RED)
SV1592J
Step 3 Jumper wire connected from control board
terminalto ground
Monitoring Harvest Light Correction
The harvest light comes on, and 6-10 seconds later, ice
The ice thickness probe is
causing the malfunction. machine cycles from freeze to harvest. The harvest light comes on but the ice machine stays in the freeze sequence.
The control circuitry is
functioning properly. The ice
machine is in a six-minute
freeze time lock-in (verify
step 1 of this procedure was
followed correctly). The harvest light does not come on.
The control board is causing
the malfunction.
56 Part Number STH047 5/16
Page 57
Ice Machine Cycles Into Harvest Before Water Contact with the Ice Thickness Probe
Step 1 Bypass the freeze time lock-in feature by
moving the ON/OFF/WASH switch to OFF and back to ON. Wait until the water starts to flow over the evaporator, then monitor the harvest light.
Step 2 Disconnect the ice thickness probe from the control board terminal.
ICE THICKNESS
PROBE
DISCONNECT
PROBE WIRE
BIN SWITCH
(GREEN)
LIGHT
HARVEST LIGHT
(RED) SV1592J_2
Step 2 Disconnect probe from control board terminal.
Monitoring Harvest Light Correction
The harvest light stays off and the ice machine remains in the freeze sequence.
The ice thickness probe is causing the malfunction. Verify that the ice thickness probe is
adjusted correctly. The harvest light comes on, and 6-10 seconds later, the ice
The control board is causing
the malfunction. machine cycles from freeze to harvest.
Part Number STH047 5/16 57
Page 58

ICE PRODUCTION CHECK

The amount of ice a machine produces directly relates to the operating water and air temperatures. This means an ice machine with a 70°F (21.2°C) ambient temperature and 50°F (10.0°C) water produces more ice than the same ice machine with 90°F (32.2°C) ambient and 70°F (21.2°C) water.
1. Determine the ice machine operating conditions:
Air temp entering condenser: ____°
Air temp around ice machine: ____°
Water temp entering sump trough: ____°
2. Refer to the appropriate 24-Hour Ice Production Chart. Use the operating conditions determined in step 1 to find published 24-Hour Ice Production:_____
• Times are in minutes.
Example: 1 min. 15 sec. converts to 1.25 min. (15 seconds ÷ 60 seconds = .25 minutes)
• Weights are in pounds.
Example: 2 lb. 6 oz. converts to 2.375 lb. (6 oz. ÷ 16 oz. = .375 lb.)
3. Perform an ice production check using the formula below.
1. _________ Freeze Time
2. 1440
_________
Minutes in
24 Hrs.
3. _________
Weight of
One Harvest
+ _________
Harvest
Time
÷ _________
Total Cycle
Time
× _________
Cycles per
Day
= _________
Total Cycle
Time
= _________
Cycles per
Day
= _________
Actual
24-Hour
Production
58 Part Number STH047 5/16
Page 59
Weighing the ice is the only 100% accurate check. However, if the ice pattern is normal and the 1/8" (.44 cm) thickness is maintained, the ice slab weights listed with the 24-Hour Ice Production Charts may be used.
4. Compare the results of step 3 with step 2. Ice production is normal when these numbers match closely. If they match closely, determine if:
• Another larger ice machine is required.
• Relocating the existing equipment to lower the
load conditions is required.
Contact the local distributor for information on available options and accessories.
Part Number STH047 5/16 59
Page 60

INSTALLATION AND VISUAL INSPECTION CHECKLIST

Ice machine is not level
Level the ice machine
Condenser is dirty
Clean the condenser
Water filtration is plugged (if used)
Install a new water filter
Water drains are not run separately and/or are not vented
Run and vent drains according to the Installation Manual
60 Part Number STH047 5/16
Page 61

WATER SYSTEM CHECKLIST

A water-related problem often causes the same symptoms as a refrigeration system component malfunction.
Example: A water dump valve leaking during the freeze cycle, a system low on charge, and a starving TXV have similar symptoms.
Water system problems must be identified and eliminated prior to replacing refrigeration components.
Water area (evaporator) is dirty
Clean as needed
Water inlet pressure not between 20 and 80 psig (1–5bar, 138–552 kPa)
Install a water regulator valve or increase the water pressure
Incoming water temperature is not between 35°F (1.7°C) and 90°F (32.2°C)
If too hot, check the hot water line check valves in other store equipment
Water filtration is plugged (if used)
Install a new water filter
Vent tube is not installed on water outlet drain
See Installation Instructions
Hoses, fittings, etc., are leaking water
Repair/replace as needed
Water float valve is stuck open or closed
Clean/replace as needed
Water is spraying out of the sump trough area
Stop the water spray
Uneven water flow across the evaporator
Clean the ice machine
Water is freezing behind the evaporator
Correct the water flow
Plastic extrusions and gaskets are not secured to the evaporator
Remount/replace as needed
Part Number STH047 5/16 61
Page 62

ICE FORMATION PATTERN

Evaporator ice formation pattern analysis is helpful in ice machine diagnostics.
Analyzing the ice formation pattern alone cannot diagnose an ice machine malfunction. However, when this analysis is used along with the Refrigeration System Operational Analysis Table, it can help diagnose an ice machine malfunction.
Any number of problems can cause improper ice formation.
Example: An ice formation that is “extremely thin at the outlet” could be caused by a hot water supply, water leaking out the overflow pipe, a faulty water float valve, a low refrigerant charge, etc.
OUTLET
OUTLET
INLET
K170 K270
INLET
Examples of Evaporator Tubing Routing
Normal Ice Formation
Ice forms across the entire evaporator surface.
At the beginning of the Freeze cycle, it may appear that more ice is forming on the inlet of the evaporator than at the outlet. At the end of the Freeze cycle, ice formation at the outlet will be close to, or just a bit thinner than, ice formation at the inlet. The dimples in the cubes at the outlet of the evaporator may be more pronounced than those at the inlet. This is normal.
If ice forms uniformly across the evaporator surface, but does not do so in the proper amount of time, this is still considered a normal ice fill pattern.
62 Part Number STH047 5/16
Page 63
Extremely Thin at Evaporator Outlet
There is no ice, or a considerable lack of ice formation on the outlet of the evaporator.
Examples: No ice at all at the outlet of the evaporator, but ice forms at the inlet half of the evaporator. Or, the ice at the outlet of the evaporator reaches the correct thickness, but the outlet of the evaporator already has 1/2" to 1" of ice formation.
Possible cause: Water loss, low on refrigerant, starving TXV, hot water supply, faulty float valve, etc.
Extremely Thin at Evaporator Inlet
There is no ice, or a considerable lack of ice formation at the inlet of the evaporator. Examples: The ice at the outlet of the evaporator reaches the correct thickness, but there is no ice formation at all at the inlet of the evaporator.
Possible cause: Insufficient water flow, flooding TXV, etc.
Spotty Ice Formation
There are small sections on the evaporator where there is no ice formation. This could be a single corner, or a single spot in the middle of the evaporator. This is generally caused by loss of heat transfer from the tubing on the backside of the evaporator.
No Ice Formation
The ice machine operates for an extended period, but there is no ice formation at all on the evaporator.
Possible cause: Water float valve, water pump, starving expansion valve, low refrigerant charge, compressor, etc.
Part Number STH047 5/16 63
Page 64

SAFETY LIMIT FEATURE

In addition to the standard safety controls, your Koolaire ice machine features built-in safety limits that will stop the ice machine if conditions arise which could cause a major component failure.
Before calling for service, re-start the ice machine using the following procedure:
1. Move the ON/OFF/WASH switch to OFF and then back to ON.
2. If the safety limit feature has stopped the ice machine, it will restart after a short delay. Proceed to step 4.
3. If the ice machine does not restart, see “Ice machine does not operate”.
4. Allow the ice machine to run to determine if the condition is reoccurring.
A. If the ice machine stops again, the condition has
reoccurred. Call for service.
B. If the ice machine continues to run, the
condition has corrected itself. Allow the ice machine to continue running.
64 Part Number STH047 5/16
Page 65
Safety Limits
In addition to standard safety controls, the control board has two built in safety limit controls which protect the ice machine from major component failures.
Safety Limit #1: If the freeze time reaches 60 minutes, the control board automatically initiates a harvest cycle. 3 cycles outside the time limit = 1 hour Stand-by Mode.
Safety Limit #2: If the harvest time reaches 3.5 minutes, the control board automatically returns the ice machine to the freeze cycle. 3 cycles outside the time limit = Safety Limit (must be MANUALLY reset).
Safety Limit Stand-by Mode: The first time a safety limit shut down occurs, the ice machine turns off for 60 minutes (Stand-by Mode). The ice machine will then automatically restart to see if the problem reoccurs. During the Stand-by Mode the harvest light will be flashing continuously and a safety limit indication can be viewed. If the same safety limit is reached a second time (the problem has reoccurred), the ice machine will initiate a safety limit shut down and remain off until it is manually restarted. During a safety limit shut down the harvest light will be flashing continuously.
Determining Which Safety Limit Stopped the Ice Machine: When a safety limit condition causes the
ice machine to stop, the harvest light on the control board continually flashes on and off. Use the following procedures to determine which safety limit has stopped the ice machine.
1. Move the toggle switch to OFF.
2. Move the toggle switch back to ON.
3. Watch the harvest light. It will flash one or two times, corresponding to safety limits 1 and 2, to indicate which safety limit stopped the ice machine.
After safety limit indication, the ice machine will restart and run until a safety limit is exceeded again.
Part Number STH047 5/16 65
Page 66
Safety Limit Notes
A safety limit indication is completed before the water pump starts. Water contacting the ice thickness probe in the freeze cycle will cause the harvest light to flash. Do not mistake a harvest light flashing in the freeze cycle with a safety limit indication.
A continuous run of 100 harvests automatically erases the safety limit code.
The control board will store and indicate only one safety limit – the last one exceeded.
If the toggle switch is moved to the OFF position and then back to the ON position prior to reaching the 100-harvest point, the last safety limit exceeded will be indicated.
If the harvest light did not flash prior to the ice machine restarting, then the ice machine did not stop because it exceeded a safety limit.
66 Part Number STH047 5/16
Page 67
ANALYZING WHY SAFETY LIMITS MAY STOP THE ICE MACHINE
According to the refrigeration industry, a high percentage of compressor failure is a result of external causes. These can include flooding or starving expansion valves, dirty condensers, water loss to the ice machine, etc. The safety limits protect the ice machine (primarily the compressor) from external failures by stopping ice machine operation before major component damage occurs.
The safety limit system is similar to a high-pressure cutout control. It stops the ice machine, but does not tell what is wrong. The service technician must analyze the system to determine what caused the high-pressure cutout, or a particular safety limit, to stop the ice machine.
The safety limits are designed to stop the ice machine prior to major component failures, most often a minor problem or something external to the ice machine. This may be difficult to diagnose, as many external problems occur intermittently.
Example: An ice machine stops intermittently on safety limit #1 (long freeze times). The problem could be a low ambient temperature at night, a water pressure drop; the water is turned off one night a week, etc.
When a high-pressure cutout or a safety limit stops the ice machine, they are doing what they are supposed to do. That is, stopping the ice machine before a major component failure occurs.
Refrigeration and electrical component failures may also trip a safety limit. Eliminate all electrical components and external causes first. If it appears that the refrigeration system is causing the problem, use the Refrigeration System Operational Analysis Table, along with detailed charts, checklists, and other references to determine the cause.
Part Number STH047 5/16 67
Page 68
Safety Limit Checklist
The following checklists are designed to assist the service technician in analysis. However, because there are many possible external problems, do not limit your diagnosis to only the items listed.
Safety Limit #1
Freeze time exceeds 60 minutes for 6 consecutive freeze cycles.
Possible Cause Checklist
Improper Installation
Refer to “Installation and Visual Inspection Checklist” on page 60
Water System
Water Level set too high (water escaping through over flow tube)
Low water pressure (20 psig min.)
High water pressure (80 psig max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective float valve
Defective water pump
Electrical System
Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Compressor relay not energizing
Compressor electrically non-operational
High inlet air temperature (110°F/43.3°C max.)
Defective fan cycling control
Defective fan motor
Dirty condenser
68 Part Number STH047 5/16
Page 69
Refrigeration System
Restricted condenser air flow
Condenser discharge air re-circulation
Dirty condenser fins
Non-OEM components
Improper refrigerant charge
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensable in refrigeration system
Plugged or restricted high side refrigerant lines or component
Defective harvest valve
Part Number STH047 5/16 69
Page 70
Safety Limit #2
Harvest time exceeds 3.5 minutes for 6 Consecutive harvest cycles.
Possible Cause Checklist
Improper Installation
Refer to “Installation and Visual Inspection Checklist” on page 60.
Water System
Water area (evaporator) dirty
Dirty/defective water dump valve
Vent tube not installed on water outlet drain
Water freezing behind evaporator
Plastic extrusions and gaskets not securely mounted to the evaporator
Low water pressure (20 psig min.)
Loss of water from sump area
Clogged water distribution tube
Dirty/defective float valve
Defective water pump
Electrical System
Ice thickness probe out of adjustment
Ice thickness probe dirty
Bin switch defective
Premature harvest
Refrigeration System
Non-OEM components
Improper refrigerant charge
Defective harvest valve
TXV flooding (check bulb mounting)
Defective fan cycling control
70 Part Number STH047 5/16
Page 71

ANALYZING DISCHARGE PRESSURE

1. Determine the ice machine operating conditions:
Air temp. entering condenser ______
Air temp. around ice machine ______
Water temp. entering sump trough ______
2. Refer to “Cycle Times, 24 Hr. Ice Production and Refrigerant Pressure Charts” on page 123 for ice machine being checked.
Use the operating conditions determined in step 1 to find the published normal discharge pressures.
Freeze Cycle ______
Harvest Cycle ______
3. Perform an actual discharge pressure check.
Freeze Cycle
PSIG
Beginning of
Cycle __________ __________
Middle of
Cycle __________ __________
End of
Cycle __________ __________
Harvest Cycle
PSIG
4. Compare the actual discharge pressure (step 3) with the published discharge pressure (step 2).
The discharge pressure is normal when the actual pressure falls within the published pressure range for the ice machine’s operating conditions. It is normal for the discharge pressure to be higher at the beginning of the freeze cycle (when load is greatest), then drop through out the freeze cycle.
Part Number STH047 5/16 71
Page 72
Discharge Pressure High Checklist
Improper Installation
Refer to “Installation and Visual Inspection Checklist” on page 60.
Restricted Condenser Air Flow
High inlet air temperature
Condenser discharge air re-circulation
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Improper Refrigerant Charge
Overcharged
Non-condensable in system
Wrong type of refrigerant
Other
Non-OEM components in system
High side refrigerant lines/component
Restricted (before mid-condenser)
Freeze Cycle Discharge Pressure Low Checklist
Improper Installation
Refer to “Installation and Visual Inspection Checklist” on page 60.
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-OEM components in system
High side refrigerant lines/component restricted (before mid-condenser)
Defective fan cycle control
NOTE: Do not limit your diagnosis to only the items listed in the checklists.
72 Part Number STH047 5/16
Page 73

ANALYZING SUCTION PRESSURE

The suction pressure gradually drops throughout the freeze cycle. The actual suction pressure (and drop rate) changes as the air and water temperature entering the ice machine changes. These variables also determine the freeze cycle times.
To analyze and identify the proper suction pressure drop throughout the freeze cycle, compare the published suction pressure to the published freeze cycle time.
NOTE: Analyze discharge pressure before analyzing suction pressure. High or low discharge pressure may be causing high or low suction pressure.
Part Number STH047 5/16 73
Page 74
Procedure
Step
1. Determine the ice machine operating conditions.
Example: Air temp. entering condenser: 90°F/32.2°C Air temp. around ice machine: 80°F/26.7°C Water temp. entering water fill valve: 70°F/21.1°C
2A. Refer to “Cycle Time” and “Operating Pressure” charts for ice machine model being checked. Using operating conditions from Step 1, determine published freeze cycle time and published freeze cycle suction pressure.
Example: Published freeze cycle time: 14.8 - 15.9 minutes Published freeze cycle suction pressure: 65 - 26 psig
2B. Compare the published freeze cycle time and published freeze cycle suction pressure. Develop a chart.
Example: Published Freeze Cycle Time (minutes)
1 2 4 7 10 12 14 | | | | | | | 65 55 47 39 34 30 26
Published Freeze Cycle Suction Pressure (psig) In the example, the proper suction pressure should be approximately 39 psig at 7 minutes; 30 psig at 12 minutes; etc.
3. Perform an actual suction pressure check at the beginning, middle and end of the freeze cycle. Note the times at which the readings are taken.
Example: Manifold gauges were connected to the example ice machine and suction pressure readings taken as follows: ________ PSIG Beginning of freeze cycle: 79 (at 1 min.) Middle of freeze cycle: 48 (at 7 min.) End of freeze cycle: 40 (at 14 min.)
4. Compare the actual freeze cycle suction pressure (Step 3) to the published freeze cycle time and pressure comparison (Step2B). Determine if the suction pressure is high, low or acceptable.
Example: In this example, the suction pressure is considered high throughout the freeze cycle. It should have been: Approximately 65 psig (at 1 minute) – not 79 Approximately 39 psig (at 7 minutes) – not 48 Approximately 26 psig (at 14 minutes) – not 40
74 Part Number STH047 5/16
Page 75
Suction Pressure High Checklist
Improper Installation
Refer to “Installation and Visual Inspection Checklist” on page 60.
Discharge Pressure
Discharge pressure is too high, and is affecting suction pressure, refer to “Discharge Pressure High Checklist” on page 72.
Improper Refrigerant Charge
Overcharged
Wrong type of refrigerant
Non-condensables in system
Other
Non-OEM components in system
Harvest valve leaking
TXV flooding (check bulb mounting)
Defective compressor
Part Number STH047 5/16 75
Page 76
Suction Pressure Low Checklist
Improper Installation
Refer to “Installation and Visual Inspection Checklist” on page 60.
Discharge Pressure
Discharge pressure is too low, and is affecting suction pressure, refer to “Freeze Cycle Discharge Pressure Low Checklist”
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-OEM components in system
Improper water supply over evaporator refer to “Water System Checklist” on page 61.
Loss of heat transfer from tubing on back side of evaporator
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of refrigeration system
TXV starving
NOTE: Do not limit your diagnosis to only the items listed in the checklists.
76 Part Number STH047 5/16
Page 77

HARVEST VALVE

General
The harvest valve is an electrically operated valve that opens when energized, and closes when de-energized.
Normal Operation
The valve is de-energized (closed) during the freeze cycle and energized (open) during the harvest cycle. The valve is positioned between the receiver and the evaporator and performs two functions:
1. Prevents refrigerant from entering the evaporator during the freeze cycle.
The harvest valve is not used during the freeze cycle. The harvest valve is de-energized (closed) preventing refrigerant flow from the receiver into the evaporator.
2. Allows refrigerant vapor to enter the evaporator in the harvest cycle.
During the harvest cycle, the harvest valve is energized (open) allowing refrigerant gas from the discharge line of the compressor to flow into the evaporator. The heat is absorbed by the evaporator and allows release of the ice slab.
Exact pressures vary according to ambient temperature and ice machine model. Harvest pressures can be found in the Cycle Time/24 Hour Ice Production/Refrigerant Pressure Charts in this book.
Part Number STH047 5/16 77
Page 78
Harvest Valve Analysis
The valve can fail in two positions:
Valve will not open in the harvest cycle.
Valve remains open during the freeze cycle.
VALVE WILL NOT OPEN IN THE HARVEST CYCLE
Although the circuit board has initiated a harvest cycle, the evaporator temperature remains unchanged from the freeze cycle.
Caution
,
Coil must be seated 100% on solenoid to function correctly. Install coil with a twisting motion to properly seat.
VALVE REMAINS OPEN IN THE FREEZE CYCLE:
Symptoms of a harvest valve remaining partially open during the freeze cycle can be similar to symptoms of an expansion valve, float valve or compressor problem. Symptoms are dependent on the amount of leakage in the freeze cycle.
A small amount of leakage will cause increased freeze times and an ice fill pattern that is “Thin at the Outlet”, but fills in at the end of the cycle.
As the amount of leakage increases the length of the freeze cycle increases and the amount of ice at the outlet of the evaporator decreases.
Refer to the Parts Manual for proper valve application. If replacement is necessary, use only “original” replacement parts.
78 Part Number STH047 5/16
Page 79
Use the following procedure and table to help determine if a harvest valve is remaining partially open during the freeze cycle.
1. Wait five minutes into the freeze cycle.
2. Feel the inlet of the harvest valve.
Important
Feeling the harvest valve outlet or across the harvest valve itself will not work for this comparison.
The harvest valve outlet is on the suction side (cool refrigerant). It may be cool enough to touch even if the valve is leaking.
3. Feel the compressor discharge line.
Warning
n
The inlet of the harvest valve and the compressor discharge line could be hot enough to burn your hand. Just touch them momentarily.
4. Compare the temperature of the inlet of the harvest valve to the temperature of the compressor discharge line.
Part Number STH047 5/16 79
Page 80
Findings Comments
The inlet of the harvest valve is
cool enough to touch and the
compressor discharge line is hot.
Cool & Hot
The inlet of the harvest
valve is hot and approaches
the temperature of a hot
compressor discharge line.
Hot & Hot
Both the inlet of the harvest
valve and the compressor
discharge line are cool enough
to touch.
Cool & Cool
This is normal as the
discharge line should always be too hot to touch and the harvest valve inlet,
although too hot to touch
during harvest, should be
cool enough to touch after 5
minutes into the freeze cycle.
This is an indication
something is wrong, as the
harvest valve inlet did not
cool down during the freeze
cycle. If the compressor
dome is also entirely hot,
the problem is not a harvest
valve leaking, but rather
something causing the
compressor (and the entire
ice machine) to get hot.
This is an indication
something is wrong, causing
the compressor discharge
line to be cool to the touch.
This is not caused by a
harvest valve leaking.
5. Record your findings on the table.
80 Part Number STH047 5/16
Page 81

COMPARING EVAPORATOR INLET/OUTLET TEMPERATURES

The temperatures of the suction lines entering and leaving the evaporator alone cannot diagnose an ice machine. However, comparing these temperatures during the freeze cycle, along with using the Refrigeration System Operational Analysis Table, can help diagnose an ice machine malfunction.
The actual temperatures entering and leaving the evaporator vary by model, and change throughout the freeze cycle. This makes documenting the “normal” inlet and outlet temperature readings difficult. The key to the diagnosis lies in the difference between the two temperatures five minutes into the freeze cycle. These temperatures must be within 7°F (4°C) of each other.
Use this procedure to document freeze cycle inlet and outlet temperatures.
1. Use a quality temperature meter, capable of taking temperature readings on curved copper lines.
2. Attach the temperature meter sensing device to the copper lines entering and leaving the evaporator.
Important
Do not simply insert the sensing device under the insulation. It must be attached to and reading the actual temperature of the copper line.
3. Wait five minutes into the freeze cycle.
4. Record the temperatures below and determine the difference between them.
___________ ___________ ___________
Inlet
Temperature
Difference must be within 7°F (4°C) at 5minutes into
the freeze cycle
Outlet
Temperature
5. Use this with other information gathered on the Refrigeration System Operational Analysis Table to determine the ice machine malfunction.
Part Number STH047 5/16 81
Page 82

DISCHARGE LINE TEMPERATURE ANALYSIS

GENERAL
Knowing if the discharge line temperature is increasing, decreasing or remaining constant can be an important diagnostic tool. Maximum compressor discharge line temperature on a normally operating ice machine steadily increases throughout the freeze cycle. Comparing the temperatures over several cycles will result in a consistent maximum discharge line temperature.
Ambient air temperatures affect the maximum discharge line temperature.
Higher ambient air temperatures at the condenser = higher discharge line temperatures at the compressor.
Lower ambient air temperatures at the condenser = lower discharge line temperatures at the compressor.
Regardless of ambient temperature, the freeze cycle discharge line temperature will be higher than 150°F (66°C) on a normally operating ice machine.
PROCEDURE
Connect a temperature probe on the compressor discharge line within 6" (15.2 cm) of the compressor.
Observe the discharge line temperature for the last three minutes of the freeze cycle and record the maximum discharge line temperature.
82 Part Number STH047 5/16
Page 83
Discharge Line Temperature Above 150°F (66°C) at End of Freeze Cycle:
Ice machines that are operating normally will have consistent maximum discharge line temperatures above 150°F (66°C).
Verify the expansion valve sensing bulb is positioned and secured correctly.
Discharge Line Temperature Below 150°F (66°C) at End of Freeze Cycle
Ice machines that have a flooding expansion valve will have a maximum discharge line temperature that decreases each cycle.
Verify the expansion valve sensing bulb is 100% insulated and sealed airtight. Condenser air contacting an incorrectly insulated sensing bulb will cause overfeeding of the expansion valve.
Part Number STH047 5/16 83
Page 84

REFRIGERATION COMPONENT DIAGNOSTIC CHART

All electrical and water related problems must be corrected before these charts will work properly. These tables must be used with charts, checklists and other references to eliminate refrigeration components not listed and external items and problems that will cause good refrigeration components to appear defective.
The tables list four different defects that may affect the ice machine’s operation.
NOTE: A low-on-charge ice machine and a starving expansion valve have very similar characteristics and are listed under the same column.
84 Part Number STH047 5/16
Page 85

PROCEDURE

Step 1 Complete each item individually in the
“Operational Analysis” column.
Enter check marks () in the boxes.
Each time the actual findings of an item in the “Operational Analysis” column matches the published findings on the table, enter a check mark.
Example: Freeze cycle suction pressure is determined to be low. Enter a check mark in the “low” box.
Perform the procedures and check all information listed. Each item in this column has supporting reference material.
While analyzing each item separately, you may find an “external problem” causing a good refrigerant component to appear bad. Correct problems as they are found. If
the operational problem is found, it is not necessary to complete the remaining procedures.
Step 2 Add the check marks listed under each of the
four columns. Note the column number with the highest total and proceed to “Final Analysis.”
NOTE: If two columns have matching high numbers, a procedure was not performed properly and/or supporting material was not analyzed correctly.
Part Number STH047 5/16 85
Page 86

FINAL ANALYSIS

The column with the highest number of check marks identifies the refrigeration problem.
Column 1 – Harvest Valve Leaking
A leaking harvest valve must be replaced.
Column 2 – Low Charge/TXV Starving
Normally, a starving expansion valve only affects the freeze cycle pressures, not the harvest cycle pressures. A low refrigerant charge normally affects both pressures. Verify the ice machine is not low on charge before replacing an expansion valve.
Add refrigerant charge in 2 oz. increments as a diagnostic procedure to verify a low charge. (Do not add more than the total charge of refrigerant). If the problem is corrected, the ice machine is low on charge. Find the refrigerant leak.
The ice machine must operate with the nameplate charge. If the leak cannot be found, proper refrigerant procedures must still be followed. Change the liquid line drier, evacuate the system and weigh in the proper charge.
If the problem is not corrected by adding charge, the expansion valve is faulty.
Column 3 – TXV Flooding
A loose or improperly mounted expansion valve bulb causes the expansion valve to flood. Check bulb mounting, insulation, etc., before changing the valve.
Column 4 – Compressor
Replace the compressor and start components. To receive warranty credit, the compressor ports must be properly sealed by crimping and soldering them closed. Old start components must be returned with the faulty compressor.
86 Part Number STH047 5/16
Page 87
Ice formation is normal
-or-
entire evaporator
No ice formation on
-or-
Ice formation is
evaporator
evaporator
no ice formation on
extremely thin on the
bottom of evaporator
-or-
entire evaporator
No ice formation on
-or-
entire evaporator
No ice formation on the
Calculated (actual) 24 hour ice production_______________
Ice Production Published 24 hour ice production________________
Operational Analysis 1 2 3 4
10% of charted capacity.
NOTE: The ice machine is operating properly if the ice fill pattern is normal and ice production is within
All installation and water related problems must be corrected
Installation and Water
-or-
Ice formation is normal
before proceeding with chart.
thin on top of the
Ice formation extremely
extremely thin on top of
System
Ice Formation Pattern Ice formation is

REFRIGERATION COMPONENT DIAGNOSTIC CHART

Part Number STH047 5/16 87
evaporator
Page 88
1
High
Stops on safety limit:
Stops on safety limit:
Stops on safety limit:
Stops on safety limit:
1 or 2
1
1 or 2
checklist to eliminate problems and/or components not listed on this table before proceeding.
If discharge pressure is High or Low, refer to freeze cycle high or low discharge pressure problem
Suction pressure is
High
Suction pressure is
Low
Suction pressure is
eliminate problems and/or components not listed on this table before proceeding.
If suction pressure is High or Low refer to freeze cycle high or low suction pressure problem checklist to
High
Suction pressure is
Safety Limits
Operational Analysis 1 2 3 4
88 Part Number STH047 5/16
Refer to “Analyzing Safety
Limits” to eliminate all non-
Freeze Cycle
refrigeration problems.
DischargePressure
________ ______ ______
1 minute Middle End
into cycle
Freeze Cycle
SuctionPressure
________ ______ ______
1 minute Middle End
Page 89
and
COOL
inlet is
The harvest valve
and
COOL
inlet is
The harvest valve
The compressor
discharge line is
The compressor
discharge line is
HOT
COOL
Discharge line temp
Discharge line temp
150°F (66°C) or higher
at the end of freeze cycle
TXV Flooding Compressor
less than 150°F (66°C)
at the end of freeze cycle
Low On Charge
Final Analysis
Harvest Valve
-or-
Leaking
Enter total number of boxes
TXV Starving
checked in each column.
and
COOL
inlet is
The harvest valve
and
HOT
inlet is
The harvest valve
Harvest Valve
Operational Analysis 1 2 3 4
Part Number STH047 5/16 89
The compressor
discharge line is
The compressor
discharge line is
HOT
HOT
Discharge line temp
Discharge line temp
Discharge Line Temp.
150°F (66°C) or higher
150°F (66°C) or higher
Record freeze cycle
at the end of freeze cycle
at the end of freeze cycle
end of freeze cycle.
discharge line temp at the
Page 90

ICE QUALITY IS POOR — CUBES ARE SHALLOW, INCOMPLETE OR WHITE

Ice machine is dirty
Clean and sanitize the ice machine
Water filtration is poor
Replace the filter
Water softener is working improperly (if applicable)
Repair the water softener
Poor incoming water quality
Contact a qualified company to test the quality of the incoming water and make appropriate filter recommendations
Water escaping from sump during freeze cycle
Check standpipe and drain
Check for water tracking out of water circuit
90 Part Number STH047 5/16
Page 91

FREEZE CYCLE IS LONG, LOW ICE PRODUCTION

Water temperature is too high
Connect to a cold water supply, verify check valves in faucets and other equipment are functioning correctly
Dirty Condenser
Clean condenser
High air temperature entering condenser
Air temperature must not exceed 120°F (39°C)
Water inlet valve filter screen is dirty
Remove the water inlet valve and clean the filter screen
Water inlet valve stuck open or leaking
Turn off ice machine, if water continues to enter ice machine, verify water pressure is ok then replace water inlet valve
Water inlet valve is not working
Water inlet valve must be replaced
Refrigeration problem
Refer to refrigeration diagnostics
Water escaping from sump during freeze cycle
Check standpipe and drain
Check for water tracking out of water circuit
Part Number STH047 5/16 91
Page 92

ICE MACHINE RUNS AND NO ICE IS PRODUCED

No water to ice machine
Correct water supply
Incorrect incoming water pressure
Water pressure must be 20-80 psi (1.4-5.5 bar)
Excessive mineral buildup
Clean and sanitize the ice machine
Ambient temperature is too high or low
Ambient temperature must be between 50°F and 110°F (10°C and 43°C)
Compressor relay inoperable
No voltage to coil or coil defective
Defective contacts
Compressor off on overload
Condenser fan motor defective
Incorrect flow to water cooled condenser
Ambient temperature too high
Condenser blocked
Faulty start components
92 Part Number STH047 5/16
Page 93

Component Check Procedures

Main Fuse

Function
The control board fuse stops ice machine operation if electrical components fail causing high amp draw.
Specifications
The main fuse is 250 Volt, 10 amp.
Warning
n
High (line) voltage is applied to the control board at all times. Removing the control board fuse or moving the toggle switch to OFF will not remove the power supplied to the control board.
Check Procedure
1. If the bin switch light is on with the ice damper closed, the fuse is good.
Warning
n
Disconnect electrical power to the entire ice machine before proceeding.
2. Remove the fuse. Check the resistance across the fuse with an ohmmeter.
Reading Result
Open (OL) Replace fuse Closed (O) Fuse is good
Part Number STH047 5/16 93
Page 94

Bin Switch

Function
Bin switch operation is controlled by the movement of the ice damper. The bin switch has two main functions:
1. Terminating the harvest cycle and returning the ice machine to the freeze cycle.
This occurs when the bin switch is opened and closed again within 7 seconds of opening during the harvest cycle.
2. Automatic ice machine shut-off.
If the storage bin is full at the end of a harvest cycle, the sheet of cubes fails to clear the ice damper and holds it down. After the ice damper is held down for 7 seconds, the ice machine shuts off.
The ice machine remains off until enough ice is removed from the storage bin to allow the sheet of cubes to drop clear of the ice damper. As the ice damper swings back to the operating position, the bin switch closes and the ice machine restarts.
Important
The ice damper must be up (bin switch closed) to start ice making.
Check Procedure
1. Set the toggle switch to OFF.
2. Watch the bin switch light on the control board.
3. Move the ice damper upward, toward the evaporator. The bin switch must close. The bin switch light “on” indicates the bin switch has closed properly.
4. Move the ice damper away from the evaporator. The bin switch must open. The bin switch light “off” indicates the bin switch has opened properly.
94 Part Number STH047 5/16
Page 95
Ohm Test
1. Disconnect the bin switch wires to isolate the bin switch from the control board.
2. Connect an ohmmeter to the disconnected bin switch wires.
3. Cycle the bin switch open and closed numerous times by opening and closing the water curtain.
NOTE: To prevent misdiagnosis:
Always use the water curtain magnet to cycle the switch (a larger or smaller magnet will affect switch operation).
Watch for consistent readings when the bin switch is cycled open and closed (bin switch failure could be erratic).
Part Number STH047 5/16 95
Page 96
Bin Switch Removal
1. Disconnect power to the ice machine at service disconnect.
2. Disconnect bin switch wires in control box.
3. Insert a small screwdriver through the hole located in the top of the bin switch, and depress mounting tab slightly.
4. While depressing mounting tab roll bin switch to right to release.
5. Pull wiring into evaporator compartment.
INSERT
SCREWDRIVER AND
DEPRESS TAB
BIN SWITCH
SV1695B
Bin Switch Removal
96 Part Number STH047 5/16
Page 97

Diagnosing Start Components

If the compressor attempts to start, or hums and trips the overload protector, check the start components before replacing the compressor.

CAPACITOR

Visual evidence of capacitor failure can include a bulged terminal end or a ruptured membrane. Do not assume a capacitor is good if no visual evidence is present. A good test is to install a known good substitute capacitor. Use a capacitor tester when checking a suspect capacitor. Clip the bleed resistor off the capacitor terminals before testing.

RELAY

The relay has a set of contacts that connect and disconnect the start capacitor from the compressor start winding. The contacts on the relay are normally open. The relay senses the voltage generated by the start winding and closes and then opens the contacts as the compressor motor starts. The contacts remain open until the compressor is de-energized.
Part Number STH047 5/16 97
Page 98

ON/OFF/WASH Toggle Switch

Function
The switch is used to place the ice machine in ON, OFF or WASH mode of operation.
Specifications
Single-pole, double-throw switch. The switch is connected into a varying low D.C. voltage circuit.
Check Procedure
NOTE: Because of a wide variation in D.C. voltage, it is not recommended that a voltmeter be used to check toggle switch operation.
1. Inspect the toggle switch for correct wiring.
2. Isolate the toggle switch by disconnecting all wires from the switch, or by disconnecting the Molex connector from the control board.
3. Check across the toggle switch terminals using a calibrated ohmmeter. Note where the wire numbers are connected to the switch terminals, or refer to the wiring diagram to take proper readings.
Switch Setting Terminals Ohm Reading
ON 24-21 Open
24-20 Closed 20-21 Open
WASH 24-20 Open
24-21 Closed 20-21 Open
OFF 24-20 Open
24-21 Open 20-21 Open
Replace the toggle switch if ohm readings do not match all three-switch settings.
98 Part Number STH047 5/16
Page 99

Ice Thickness Probe

How the Probe Works
Koolaire’s electronic sensing circuit does not rely on refrigerant pressure, evaporator temperature, water levels or timers to produce consistent ice formation.
As ice forms on the evaporator, water (not ice) contacts the ice thickness probe. After the water completes this circuit across the probe continuously for 6-10 seconds, a harvest cycle is initiated.
Freeze Time Lock-In Feature
The ice machine control system incorporates a freeze time lock-in feature. This prevents the ice machine from short cycling in and out of harvest.
The control board locks the ice machine in the freeze cycle for six minutes. If water contacts the ice thickness probe during these six minutes, the harvest light will come on (to indicate that water is in contact with the probe), but the ice machine will stay in the freeze cycle. After the six minutes are up, a harvest cycle is initiated. This is important to remember when performing diagnostic procedures on the ice thickness control circuitry.
To allow the service technician to initiate a harvest cycle without delay, this feature is not used on the first cycle after moving the toggle switch OFF and back to ON.
Maximum Freeze Time
The control system includes a built-in safety, which will automatically cycle the ice machine into harvest after 60minutes in the freeze cycle.
Part Number STH047 5/16 99
Page 100

ICE THICKNESS CHECK

The ice thickness probe is factory-set to maintain the ice bridge thickness at 1/8" (3.2 mm).
1. Inspect the bridge connecting the cubes. It should be about 1/8" (3.2 mm) thick.
2. If adjustment is necessary, turn the ice thickness probe adjustment screw clockwise to increase bridge thickness, or counterclockwise to decrease bridge thickness.
NOTE: Turning the adjustment 1/3 of a turn will change the ice thickness about 1/16" (1.5 mm).
ADJUSTING
SCREW
1/8" ICE BRIDGE
THICKNESS
NOTE:
SV3113
SV3114
Ice Thickness Check
Make sure the ice thickness probe wire and the bracket do not restrict movement of the probe.
100 Part Number STH047 5/16
Loading...