Majestic PVISLPB Installation Manual

PVI-SLP
1
Power Vent Inline
- Installation Instructions -
NOTICE
DO NOT DISCARD THIS MANUAL
• Read, understand and follow these instructions for safe installation and operation.
1
• Important operating and maintenance instructions included.
Introduction
Table of Contents
1 Introduction
A. Components and Service Parts List . . . . . . . . . . . . . . . . . . 2
B. Installation of PVI-SLP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Vent Information and Diagrams
A. Installation of Vent Pipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
B. Vent/Pipe Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
C. Venting Length - Model Categories and Length
Requirements by Termination Type . . . . . . . . . . . . . . . . . 10
D. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 12
3 Framing and Clearances
A. Framing and Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Electrical Information
A. Wiring the Appliance for the PVI-SLP . . . . . . . . . . . . . . . . 17
DO NOT
DISCARD
• Leave this manual with party responsible for use and operation.
IMPORTANT: Failure to read and follow these instruc-
tions may create a possible hazard and will void the fi re- place warranty.
These instructions must remain with the equipment.
CAUTION! Risk of Cuts or Abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
INTRODUCTION
The Power Vent Inline (PVI-SLP) is certi ed for use only on replaces manufactured by Hearth & Home Technologies
Note: The battery back-up feature of the IPI system is removed when the PVI-SLP power vent is installed. The fi replace may no longer be operated with battery back-up.
5 Operating Instructions
A. Installation Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
B. Vacuum Switch Orientation . . . . . . . . . . . . . . . . . . . . . . . . 23
C. Setting the PVI-SLP Baffl e Adjustment . . . . . . . . . . . . . . . 23
D. Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
E. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
F. PVI-SLP Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 25
Installation of the PVI-SLP may be done by a qualifi ed service technician only. Installation MUST comply with lo­cal, regional, state and national codes and regulations.
1
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
The PVI-SLP operates on 120VAC, 60Hz electrical service which is supplied at the fi replace junction box.
IMPORTANT OPERATIONAL NOTE: When the control being used to run the fi replace is activated, a 120 second delay will occur before ignition occurs. This is to allow a pre-purge by the PVI-SLP. If fi replace does not light after 135 seconds, refer to the Troubleshooting section of this instruction for further direction. If an RC100, RC200 or RC300 remote is being used, there will also be a 20 minute post-purge in which the PVI-SLP will continue to run after appliance is turned off.
A. Components and Service Parts List
Service Parts List
Replacement parts can be obtained from your dealer. Repair of the Power Vent should only be done by a qualifi ed service technician.
BLOWER ASSEMBLY
2196-025
8K1-PVI
WIRE HARNESS
2196-200
NOTE: Wire Harness connecting PVI to appliance sold separately. The length of wire harness needed varies by installation.
Figure 1.1 Service Parts
VACUUM SWITCH
2196-326
8K1-PVI
2196-150
6VDC POWER RECEPTACLE
2326-131
Required Wire Harness
Lengths Available Part Number
10 ft. PV Wire Harness PVI-WH10
20 ft. PV Wire Harness PVI-WH20
40 ft. PV Wire Harness PVI-WH40
60 ft. PV Wire Harness PVI-WH60
80 ft. PV Wire Harness PVI-WH80
100 ft. PV Wire Harness PVI-WH100
AUX300 MODULE 2166-335
AUX 2
AUX 1
B. Installation of PVI-SLP
1. INSTALLATION PRECAUTIONS
a. This device must be installed by a qualifi ed installer
in accordance with these instructions.
b. Safety inspection of the venting system should
be performed before and after installation of this power vent. Consult local code offi cials and follow applicable installation codes.
c. DO NOT INSTALL DAMAGED EQUIPMENT OR
VENT COMPONENTS.
d. Disconnect electrical power supply before making
wiring connections.
e. Venting of more than one appliance in a common
vent system is prohibited.
f. Clearances between the vent pipe and combustible
materials must be maintained at 1-1/2-inch top, 1-inch sides and bottom.
g. All outer pipe joints must be sealed with high tem-
perature silicone. See Section 2.A.
h. The access panel opening must be located such
that access for service and adjustment is available. The NEC requires a minimum of 30 inches of space around the opening and 36 inches in front of the opening to the access panel. Consult offi cials hav- ing jurisdiction regarding regional requirements.
CAUTION! Failure to install, operate, and maintain the power venting system in accordance with manufacturer's instructions will result in conditions which may produce bodily injury and/or property damage.
NOTICE: The blower motors present in this powervent will generate sound during operation. The effects of the increased sound level can be minimized with careful planning during installation of the system. Locating the powervent service access grill in an area remote of im­mediate living space will reduce the effects of the added sound generated during operation.
2
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
2. INSTALLATION GUIDELINES
WARNING: RISK OF FIRE AND BURNS. DO NOT install PVI-SLP with the access panel facing upward. Overheating may occur.
NOTICE: Installation of the PVI-SLP in an attic is not recommended in regions where temperatures reach 0°F (-18°C) and relative humidity exceeds 60% simultaneously. Low temperatures and high moisture content may cause the PVI-SLP to freeze.
a. If the PVI-SLP is being installed in a confi ned space
(such as a utility closet, mechanical room or attic space) with a total volume less than 250 cubic feet, an access hole with minimum dimensions of 8 inches by 16 inches will be required directly in front of the access panel. The recommended access hole size is 12 inches by 17 inches. This size will allow full access to the 11 inch x 16 inch access panel on the PVI-SLP. See Figure 3.1. The confi ned space where the PVI is installed, and the space to which the access hole opens, must add up to at least 250 cubic feet. This hole may be covered with a decorative cover as long as the cover has a minimum of 50% open air. If the PVI-SLP is being installed in a space greater than 250 cubic feet the access hole is still required, but a solid cover may be used. This also applies to a fi replace chase.
The decorative cover CANNOT be located on an outside
wall that is open to the environment.
b. For installations near loose-fi ll insulation (such as attics)
a minimum clearance of six inches must be maintained between the access panel and the insulation.
c. The PVI-SLP CANNOT be installed with the access
panel facing upward.
d. The exit termination of mechanical draft systems shall
not be less than seven feet above grade when located adjacent to public walkways.
e. A mechanical drafting venting system shall terminate at least
three feet above any forced air inlet located within 10 feet.
2
2
Vent Information and Diagrams
A. Installation of Vent Pipe
For information on standard procedures for venting the
appliance, refer to the "Vent Information and Diagrams"
section of the appliance installation manual.
For the allowable pipe lengths and elbow combinations for an appliance utilizing the PVI-SLP, consult the Power Vent diagrams in the Vent Information and Diagrams sec­tion of the appliance installation manual. The PVI-SLP uses SLP pipe (6-5/8 inch) connections for both the inlet and outlet.
The following termination caps are available for use with the power vent inline (PVI-SLP): SLP-TVHW, SLP-LPC, SLP-TRAP, SLP-HHW2, SLP-HRC-SS, SLP-HRC-ZC­SS, SLP-TB1. Check installation manual for termination caps specifi cations.
In certain cases, a pipe adapter may be used in the vent run. The DVP-2SL adapts from 5 in. / 8 in. DVP series starting collars to 4 in. / 6-5/8 in. SLP series vent pipe.
Either SLP or DVP venting may be used throughout the vent run except on certain models that require DVP pipe. See Table 2.1. Refer to Section 2.B for more information regarding venting regulations.
B. Vent/Pipe Regulations
WARNING! Risk of Fire!
Maintain minimum pipe length between appliance and PVI-SLP on all models. Combustible materials surrounding pipe may overheat.
1. A minimum length of venting is required between the appliance and the PVI-SLP. This minimum length re­quirement varies for the specifi c appliance. Refer to Table 2.1. for requirements for specifi c models. Once the minimum length requirement is met, the PVI-SLP may be installed at any location within the vent run confi guration.
2. A minimum of 18 inches is required between the PVI­SLP and the termination cap to allow room for the pipe to go through a wall or roof.
3. If PVI-SLP is installed in the vertical position, a minimum of two 90 degree elbows and two feet of pipe is required between the appliance and the PVI-SLP.
4. Total allowable length decreases by 2 ft. for every 1 ft. of vertical drop.
Note: See Table 2.1 for model specifi c vent requirements.
SLP pipe may be used on the termination side of the PVI.
All outer pipe joints must be sealed with high temperature silicone (with a minimum of 300ºF continuous exposure rating), including the slip section that connects directly to the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections. See Figure 2.1.
• Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer fl ues shall be sealed in this manner, unless otherwise stated.
Figure 2.1 High Temperature Silicone Sealant
3
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
B. Vent/Pipe Regulations (continued)
WARNING! Risk of Fire!
• PVI-SLP cannot be installed directly on appliance. The PVI-SLP and combustible materials surrounding vent pipe may overheat.
• A minimum length run of initial vent pipe is required between the appliance and the inlet of the PVI-SLP. The initial minimum vent run requirement varies depending on the specifi c appliance and its venting confi guration.
Some models require DVP Series pipe for the initial minimum vent section directly off the appliance.
MODEL MINIMUM VENTING BETWEEN APPLIANCE AND PVI-SLP
6000C, 6000CL, 6000CLX, 8000C, 8000CL, 8000CLX 6000BEC
6000CMOD, 8000CMOD
CD4236, CD4842
CNXT4236, CNXT4842
CRAVE4836, CRAVE4836ST, CRAVE6048, CRAVE6048ST CRAVE7260, CRAVE7260ST, CRAVE8472, CRAVE8472ST
DV3732SBI
GDST3831, GDST4336, GDFL4136, GDCR4136, GDCL4136
MEZZO36, MEZZO36ST, MEZZO48, MEZZO48ST MEZZO60, MEZZO60ST, MEZZO72, MEZZO72ST
NDV3630, NDV3933, NDV4236, NDV4842
NEVO3630, NEVO4236
ST-36TR. ST-36TR, ST-36TRB, PIERI-36TR, PIER-36TRB, LCOR-36TRB, RCOR-36TRB
RED40, RED40ST
REVO-S21, REVO-H31
SLR32, RAVE3012I
SLR-B, SLR-C, RAVE 4013I, RAVE4013I-C
SL-350TRS, SL-550TRS, SL-750STRS
SL-550TR, SL-750TR, SL-950TR
SL-550METRO, SL-550-BE-M
ST-550T, ST-550TM
MODEL MINIMUM VENTING BETWEEN APPLIANCE AND PVI-SLP
ESC-42ST
ESCAPE-36DV, ESCAPE42DV
HEIR36, HEIR42, HEIR50
LUX36, LUX42
PVI installed horizontal orientation: One 90 degree elbow and a total of two feet of straight horizontal or straight vertical SLP pipe. See Figure 2.2 and Figure 2.5.
PVI installed vertical orientation: Two 90 degree elbows and a total of two feet straight horizontal or straight vertical SLP pipe. See Figure 2.3, 2.4, 2.6.
PVI installed horizontal orientation: Minimum two feet straight vertical DVP pipe directly off appliance followed by 90 degree elbow and two feet DVP pipe. PVI-SLP adapter must be located directly between initial DVP pipe and PVI-SLP. See Figure 2.2 and Figure 2.5.
TRUE-36, TRUE-42, TRUE-50 CERONA-36, CERONA-42
PRIMO48, PRIMO48ST, PRIMO60, PRIMO60ST, PRIMO72, PRIMO72ST
Table 2.1
4
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
PVI installed vertical orientation: Minimum two feet straight vertical DVP pipe directly off appliance, followed by two 90 degree elbows and a total of two feet straight horizontal or straight vertical DVP pipe. PVI-SLP adapter must be located directly between initial DVP pipe and PVI-SLP. See Figure 2.3, Figure 2.4, Figure 2.6.
PVI installed vertical or horizontal orientation: Minimum three feet of DVP or SLP pipe is required before connecting the PVI­SLP system. The 3 foot minimum does not include the factory­installed six inch DVP pipe.
Top Vent - Horizontal Termination
H
2
Note: 1 ft. of vertical drop decreases total allowable length by 2 ft.
H
1
V
2
V
1
A DVP-2SL ADAPTER is required in this position in the vent run on certain models. See Table 2.1.
WARNING! Risk of Fire! Use DVP pipe between appliance and PVI-SLP on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50, LUX36, LUX42, TRUE-36, TRUE-42, TRUE-50, CERONA-36, CERONA-42, MEZZO36, MEZZO36ST, CRAVE4836, CRAVE4836ST, MEZZO48, MEZZO48ST, CRAVE6048, CRAVE6048ST, MEZZO60, MEZZO60ST, CRAVE7260, CRAVE7260ST, MEZZO72, MEZZO72ST, CRAVE8472, CRAVE8472ST
Combustibles surrounding pipe may overheat.
Note: For PRIMO models, see the PRIMO Installation Manual for vent con gurations.
Minimum Maximum
H
+ V
1
H
2
V
2
A minimum of 2 ft. of vertical piping is required between the appliance and the PVI-SLP in addition to the minimum venting described above when installing PVI-SLP with certain appliance models. See Table 2.1.
Figure 2.2 Horizontal PVI Orientation
24 in. 610 mm
1
18 in. 457 mm
0 in. 0 mm
See Chart in Section 2.C: "Venting Length - Model Categories and Length Requirements by Termination Type."
5
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
Note: 1 ft. of vertical drop decreases total allowable length by 2 ft.
WARNING! Risk of Overheating!
- Minimum inital length of vent pipe required between appliance and vertically positioned PVI-SLP.
- Must include two 90 degree elbows.
NOTICE: If pipe configuration includes a vertical component that goes downward, a vertical component going back upward is not allowed.
A DVP-2SL ADAPTER is required in this position in the vent run on certain models. See Table 2.1.
H
1
V
1
V
2
V
3
H
2
WARNING! Risk of Fire! Use DVP pipe between appliance and PVI-SLP on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50, LUX36, LUX42, TRUE-36, TRUE-42, TRUE­50, CERONA-36, CERONA-42, MEZZO36, MEZZO36ST, CRAVE4836, CRAVE4836ST, MEZZO48, MEZZO48ST, CRAVE6048, CRAVE6048ST, MEZZO60, MEZZO60ST, CRAVE7260, CRAVE7260ST, MEZZO72, MEZZO72ST, CRAVE8472, CRAVE8472ST
Combustibles surrounding pipe may overheat.
Note: For PRIMO models, see the PRIMO Installation Manual for vent con gurations.
Minimum Maximum
H
+ V1 + V2 24 in. 610 mm
Figure 2.3 Vertical PVI Orientation
6
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
1
H
2
V
3
18 in. 457 mm
0 in. 0 mm
A minimum of 2 ft. of vertical piping is required between the appliance and the PVI-SLP in addition
to the minimum venting described above when installing PVI-SLP with certain appliance models. See Table 2.1. V minimum = 2 ft. and V2 + H1 + V1 minimum = 4 ft. for certain appliance models.
See Chart in Section 2.C: "Venting Length - Model Cat­egories and Length Requirements by Termination Type."
See Table 2.1.
Top Vent - Horizontal Termination - (continued)
H
2
Note: 1 ft. of vertical drop decreases total allowable length by 2 ft.
Minimum Maximum
V
3
H1 + V1 + V
V
3
H
2
24 in. 610 mm See Chart in Section 2.C: "Vent-
2
0 in. 0 mm
18 457 mm
ing Length - Model Categories and Length Requirements by Termination Type."
A minimum of 2ft. of vertical piping is required between the appliance and the PVI-SLP in addition to the minimum venting described above when installing PVI-SLP with certain appliance models. See Table 2.1.
V minimum = 2 ft. and V2 + H1 + V1 minimum = 4 ft. for certain appliance models. See Table 2.1.
A DVP-2SL ADAPTER is required in this position
V
2
in the vent run on certain models. See Table 2.1.
WARNING! Risk of Fire! Use DVP pipe between appliance and PVI-SLP on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50, LUX36, LUX42, TRUE-36, TRUE­42, TRUE-50, CERONA-36, CERONA-42, MEZZO36, MEZZO36ST, CRAVE4836, CRAVE4836ST, MEZZO48, MEZZO48ST, CRAVE6048, CRAVE6048ST, MEZZO60, MEZZO60ST, CRAVE7260, CRAVE7260ST, MEZZO72, MEZZO72ST, CRAVE8472, CRAVE8472ST
Combustibles surrounding pipe may overheat.
WARNING! Risk of Overheating!
- Minimum inital length of vent pipe required between appliance and vertically positioned PVI-SLP.
H
1
- Must include two 90 degree elbows.
V
1
Note: For PRIMO models, see the PRIMO Installation Manual for vent confi gurations.
Figure 2.4 Vertical PVI Orientation
7
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
Top Vent - Vertical Termination
Minimum Maximum
+ V124 in. 610 mm See Chart in Section 2.C: "Venting Length - Model Categories and Length
H
1
V
H
TOTAL
A minimum of 2ft. of vertical piping is required between the appliance and the PVI-SLP in addition to the minimum venting described above when installing PVI-SLP with certain appliance models. See Table 2.1.
18 in. 457 mm See Chart in Section 2.C: "Venting Length - Model Categories and Length
2
00
Requirements by Termination Type."
Requirements by Termination Type."
30% of total vent length allowed in chart: "Venting Length - Model Categories and Length Requirements by Termination Type" in Section 2.C.
V minimum = 2 ft. and H
Note: 1 ft. of vertical drop decreases total allowable length by 2 ft.
V
2
+ V1 minimum = 4 ft. with certain appliance models. See Table 2.1.
1
H
2
H
1
A DVP-2SL ADAPTER is required in this position in the vent run on certain models. See Table 2.1.
V
1
WARNING! Risk of Fire! Use DVP pipe between appliance and PVI-SLP on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50, LUX36, LUX42, TRUE-36, TRUE-42, TRUE-50, CERONA-36, CERONA-42, MEZZO36, MEZZO36ST, CRAVE4836, CRAVE4836ST, MEZZO48, MEZZO48ST, CRAVE6048, CRAVE6048ST, MEZZO60, MEZZO60ST, CRAVE7260, CRAVE7260ST, MEZZO72, MEZZO72ST, CRAVE8472, CRAVE8472ST
Combustibles surrounding pipe may overheat.
Note: For PRIMO models, see the PRIMO Installation Manual for vent con gurations.
Figure 2.5 Horizontal PVI-SLP Orientation
8
Hearth & Home Technologies • Power Vent Inline (PVI-SLP) Instructions • 2196-900 Rev. AC • 12/15
Loading...
+ 16 hidden pages