LINK Systems LinkNet I User Manual

LinkNet
g
Pressroom
Monitorin
Software
Installation and Operatin
Manual
LinkNet
LinkNet
Table of Contents
1. Introduction.......................................................................1.1
1.1 Features ....................................................................1.1
1.2 System Requirements ..........................................................1.1
2. Installation........................................................................2.1
2.1 RS232-RS485 Converter Connections .............................................2.2
2.2 OmniLink 5000 Connections ....................................................2.2
2.3 System 1100 Connections ......................................................2.3
2.4 Drop Box Terminals...........................................................2.3
2.5 Software Installation ..........................................................2.4
3. Configuration .....................................................................3.1
3.1 Configuring the Comm Port .....................................................3.1
3.2 Configuring Shifts ............................................................3.1
3.3 Configuring Down Time Codes ..................................................3.2
3.3.1 Adding a Down Time Code ..................................................3.2
3.3.2 Editing a Down Time Code ..................................................3.3
3.3.3 Deleting a Down Time Code .................................................3.3
3.4 Configuring Machines .........................................................3.3
3.4.1 Adding a Machine to LinkNet.................................................3.3
3.4.2 Editing Machine Information .................................................3.4
3.4.3 Deleting a Machine from LinkNet ..............................................3.4
3.5 Configuring Dies .............................................................3.5
3.5.1 Adding Dies ..............................................................3.5
3.5.2 Editing Die Information .....................................................3.6
3.5.3 Deleting Dies .............................................................3.6
3.6 Configuring Tonnage Wave Capture............................................3.6
3.7 Configuring Preventive Maintenance ...........................................3.7
3.7.1 Adding a Preventive Maintenance Item..........................................3.7
3.7.2 Editing a Preventive Maintenance Item..........................................3.8
3.7.3 Resetting a Preventive Maintenance Item ........................................3.9
3.7.4 Deleting a Preventive Maintenance Item .........................................3.9
4. Using LinkNet .....................................................................4.1
4.1 The Overview Window ........................................................4.1
4.2 Detail Dialogs ...............................................................4.2
4.2.1 Counter Detail ............................................................4.2
4.2.2 Average Tonnage Detail.....................................................4.2
4.2.3 Production Rate Detail ......................................................4.3
4.2.4 Tonnage Detail............................................................4.4
4.3 The “Window” Menu ..........................................................4.4
4.4 The “View” Menu ............................................................4.4
4.5 The “Help” Menu.............................................................4.4
i.1
manual rev 2.1 March 25, 1999
LinkNet
5. Reports ..........................................................................5.1
5.1 The Event Log Report .........................................................5.1
5.2 The Summary Report ..........................................................5.2
5.3 Press Performance Overview Report ..............................................5.3
5.4 Press Average Tonnage Graph ...................................................5.3
5.5 Press Production Rate Graph ....................................................5.4
5.6 Die Performance Overview Report ................................................ 5.4
5.7 Die Tonnage Alarms Report .....................................................5.5
5.8 Die High/Low/Average Tonnage Report ...........................................5.5
5.9 Quick Reports..............................................................5.5
6. Using the OmniLink 5000 with LinkNet ..................................................6.1
6.1 Configuring the OmniLink 5000 for LinkNet ........................................6.1
6.2 Using Down Time Codes on the OmniLink 5000 .....................................6.2
6.3 Network Job Storage on the OmniLink 5000 ........................................6.3
6.4 Network Job Recall on the OmniLink 5000 .........................................6.3
6.5 Sending Tonnage Graphs from the OmniLink 5000 ...................................6.4
6.6 Viewing Machine and Die Notes on the OmniLink 5000 ................................6.4
7. Using the System 1100 Tonnage Monitor with LinkNet ......................................7.1
7.1 Configuring the System 1100 Tonnage Monitor for LinkNet ............................7.1
7.2 Using Down Time Codes on the System 1100 Tonnage Monitor .........................7.1
7.3 Network Job Storage on the System 1100 ..........................................7.2
7.4 Network Job Recall on the System 1100 ............................................7.3
7.5 Sending a Tonnage Graph from the System 1100 .....................................7.3
7.6 The Network Clock on the System 1100 ...........................................7.3
Appendix A - Upgrading Link Equipment .............................................. A.1
A.1 General Chip Changing Rules ................................................... A.1
A.2 System 1100 Tonnage Monitor Upgrade Procedure .................................. A.1
A.2.1 System 1100 OIT Software Upgrade Procedure .................................. A.1
A.2.2 System 1100 Motherboard Software Upgrade Procedure ........................... A.2
A.3 OmniLink 5000 Upgrade Procedure .............................................. A.3
A.3.1 OmniLink OIT Communications Board Upgrade Procedure ......................... A.3
A.3.2 OmniLink OIT Software Upgrade Procedure .................................... A.4
A.3.3 OmniLink OIT Communications Card Software Upgrade Procedure................... A.5
A.3.4 OmniLink Logic Module Upgrade Procedure .................................... A.5
A.3.5 OmniLink Die Protection Module Software Upgrade Procedure...................... A.6
A.3.6 OmniLink Tonnage Monitor Module Software Upgrade Procedure ................... A.6
A.3.7 OmniLink Auto-Setup Module Software Upgrade Procedure ........................ A.7
i.2
manual rev 2.1 March 25, 1999
LinkNet
1. Introduction
The Link Systems Network Application (LinkNet) provides detailed monitoring of stamping operations utilizing Link equipment. Supported equipment includes the OmniLink 5000 press control and associated option modules, and the System 1100 tonnage monitor. By using a simple to wire “daisy chained cable arrangement to attach these units to an Intel based personal computer running Microsoft Windows, a wealth of information can be gathered automatically.
1.1 Features
d
Average tonnage, highest good tonnage, and lowest good tonnage is collected (from equipment with tonnage monitors) in 10 minute intervals. This gives a good view of the consistency of the production process.
d
Production Rate is collected in 10 minute intervals. The production rate is also factored into summary information for press utilization calculations versus standard rate.
d
Down time codes may be defined. A description for each down time code can be typed in once at the computer and the descriptions are downloaded to all Link equipment on the network. The user may choose from the descriptions, not just the numeric code, at the press. Down time code information is collected and stored by shift, day, week, month, year, since last rework, and over all time.
d
Events are recorded. Events are automatically logged in the same databases as down time codes. Examples of events include tonnage alarms, bypass changes to tonnage monitor and die protection, die protection faults, part counter limit s, etc.
d
All data is stored in industry standard Microsoft Access database files. These files can be read from many common spreadsheets, reporting tools, visual basic,
etc.
d
Jobs may be stored and recalled to and from the host computer giving Link equipment attached to the network essentially unlimited job storage
d
Standard reports are provided by LinkNet to make the information gathered by the system more accessible and easier to interpret.
d
Reports are generated using Seagate Software Crystal Reports. This allows the end user to customize (with separate purchase of Crystal Reports) LinkNet reports for any special requirements, add a company logo, etc.
d
Preventive Maintenance setpoints can be set by elapsed time, press running time, and strokes. OmniLink 5000 controls additionally support setpoints by “Motor On time, Total feed length, and Clutch/Brake engagements.
d
Tonnage signatures can be sent from OmniLink 5000 and System 1100 tonnage monitors to the network for analysis, storage, or printing. Previous signatures can be overlaid for direct comparison.
d
Notes for each machine and die can be entered at the computer and viewed on OmniLink 5000 operator terminals.
1.2 System Requirements
LinkNet has been designed to run on the
Windows 95 or Windows NT operating systems.
Minimum Hardware Requirements:
d
Pentium 166MHz CPU
d
16MB memory
d
1.2GB hard drive
d
VGA (640 by 480) display
d
Mouse
1.1
manual rev 2.1 March 25, 1999
d
At least one free RS232 serial port
Recommended Hardware:
d
Pentium II 333MHz CPU or better
d
32MB memory
d
4GB or larger hard drive
d
SVGA (800 by 600) display or better
d
Mouse
d
At least one free RS232 serial port
LinkNet
1.2
manual rev 2.1 March 25, 1999
2. Installation
LinkNet is connected to each piece of equipment in a bussed arrangement commonly called “daisy chaining. The means that the communications cable goes from the computer to the first machine, from the first machine to the second, from the second to the third, and so on as shown in Figure
2.1.
The “Drop Boxes” shown in the figure are small boxes that contain plugable terminal strips. The boxes are mounted on the press and serve as junctions for the network wire to come in to the machine, go out to the next machine, and drop to Link equipment on the press. In addition, the boxes can contain circuitry (called a repeater) to enable the network to work with extremely long cable lengths or with more than 32 machines.
LinkNet
Figure 2.1:
Daisy Chained Network Example
2.1
manual rev 2.1 March 25, 1999
At the computer, an RS232 to RS485 converter is necessary. This converts the standard serial port on the host computer to a differential serial port suitable for electrically noisy industrial environments. Link makes an RS232 to RS485 converter specifically for this purpose with termination resistors built in that provide for reliable communications.
The computer that runs the network should be capable of running Windows 95, Windows 98, or Windows NT 4.0 (service pack 4 or higher). Suggested computer is at least a Pentium II 333MHz with 32 MB of memory, 4GB of hard disk space, Super VGA with resolution of 800 by 600 or better, mouse, and at least one spare RS-232 port.
The network wiring should be Belden 8103 or equivalent (three twisted pairs and a shield) and should not exceed 4000 ft (unless using a repeater).
LinkNet
2.2
manual rev 2.1 March 25, 1999
Belden 8103 cable and many similar cables organized as twisted pairs use a special color code scheme. Instead of each wire using a different color, each pair uses a color. One wire in the pair is predominately white with a thin color stripe, and the other wire in the pair is predominately the color with a thin white stripe. When referring to these wires a common convention is to name the predominate color first. For example, a blue wire with a thin whit e stripe is called blue with white (shortened to blue/white). A white wire with a thin blue stripe is called white with blue (shortened to white/blue). This convention will be used in this document.
Other wire types can be used, but assuming Belden 8103 cable and the Link RS232 to RS485 converter, the network should be wired as shown in the following sections.
2.1 RS232-RS485 Converter Connections
The Link converter is labeled the same way as network drop boxes on the RS485 side. The RS232 side is equipped with a 6' cable that plugs into any standard 9 pin serial port connector on the host computer. A power cord is also provided. The six terminal RS485 connector should be wired as follows:
GND - Green/White and White/Green RXD+ - Orange/White RXD- - White/Orange TXD+ - Blue/White TXD- - White/Blue SHLD - Shield (bare) Wire of Cable
LinkNet
5) RX- should connect to TXD- on the drop box (White/Blue wire).
Note that “RX” and “TX can be called different things depending on the manufacturer of the converter, but will almost always reflect some variation of “transmit” and “receive” (such as TXD and RXD).
2.2 OmniLink 5000 Connections
There should be 5 connectors on the back of the OmniLink 5000 operator interface terminal as shown in Figure 2.2. If only 4 connectors are present, then an older communications board is installed. If this is the case, contact Link for pricing to upgrade the unit to the new communications board with network support. Appendix “A has complete instruct ions for updating OmniLink 5000 software and retrofitting the new communications board. Port 5 is the network port and should be wired as follows:
REF - Green/White and White/Green RXD+ - Orange/White RXD- - White/Orange TXD+ - Blue/White TXD- - White/Blue
If another kind of RS-232 to RS-485 converter
is used, it should be set up in the following manner:
1) If configurable, transmit should always be on.
2) TX+ should connect to RXD+ on the drop box (Orange/White wire).
3) TX- should connect to RXD- on the drop box (White/Orange wire).
4) RX+ should connect to TXD+ on the drop box (Blue/White wire).
Figure 2.2:
2.3
OmniLink 5000 OIT Backpanel
manual rev 2.1 March 25, 1999
2.3 System 1100 Connections
System 1100 tonnage monitors with software versions older than version 3.2 in the operator interface board (the circuit board that is mounted on the door of the 1100) will need to have a software upgrade in order to function with LinkNet. Contact Link for the appropriate software. Appendix “A has complete instructions for upgrading the software. The System 1100 has 3 terminal strips on the circuit board mounted to the door of the unit, two of which should already be wired. The NETWORK port (see Figure 2.3) should be wired as follows:
Terminal A - Green/White and White/Green Terminal B - White/Blue Terminal C - Blue/White Terminal D - White/Orange Terminal E - Orange/White
LinkNet
box has. This circuitry allows the network to extend over 4000ft and can allow more than 32 units to be attached to the line.
Drop boxes have three sets of plugable terminal strips labeled “DATA IN”, “DATA OUT, and UNIT. The terminal strip labeled DATA IN should be connected to the wire coming from the host computer side, DATA OUT should go to the next drop box, and “UNIT” should go to the Link equipment on the press. All three connectors should be wired as follows:
GND - Green/White and White/Green RXD+ - Orange/White RXD- - White/Orange TXD+ - Blue/White TXD- - White/Blue SHLD - Shield (bare) Wire of Cable
For Repeaters Only:
Figure 2.3:
System 1100 Door Circuit Board
2.4 Drop Box Terminals
There are two kinds of drop boxes, regular and
repeater.
Regular drop boxes (Figure 2.4) simply have connectors for field wiring to pass the communication signals through.
Repeater drop boxes (Figure 2.5) have active circuitry in addition to the terminals the regular drop
L1 - Hot side of 110V AC L2 - Neutral side of 110V AC M. GND - Machine Ground
Some older versions of the drop box do not have the “SHLD” terminal. In this case, tie the shields of all the cables together with a wire nut.
2.4
manual rev 2.1 March 25, 1999
Figure 2.4:
Regular Drop Box Connectors
LinkNet
2.5 Software Installation
Once the wiring is completed, the software on the host computer must be installed. Insert the LinkNet compact disk (CD) in the computers CD­ROM drive. If Auto Insert Notification is enabled for the drive (it is by default), then the LinkNet installation program will automatically start when the CD is inserted. If for some reason Auto Insert Notification is not enabled, hit the “Start” button on the desktop, select “Run..., and when prompted for the name of the program to run type D:\SETUP (without the quotes) and hit the “OK button. Note that the “D” in “D:\SETUP” should be the drive letter of your CD-ROM drive.
The installation program will ask where to put the LinkNet files. It is strongly recommended that the default directory be accepted. Program and data files will then be installed.
Figure 2.5:
Repeater Drop Box Connections
Whenever possible, the drop boxes should be mounted on the press in easy reach for troubleshooting purposes. In addition, the length of the line from the drop box to the Link equipment should be kept as short as is reasonably possible. The drop boxes have knockouts sized for ½” conduit or cord grips.
2.5
manual rev 2.1 March 25, 1999
The installation program will create a new program group called “LinkNet and will put a LinkNet icon on the windows desktop. To start LinkNet, double click on the icon on the desktop, or select it from the programs menu by hitting the Windows “Start button, then “Programs, then the LinkNet group, and then the “LinkNet selection in that group.
LinkNet
2.6
manual rev 2.1 March 25, 1999
3. Configuration
After the software is installed, it must be configured. This consists of the following steps:
d
Select a communications port for LinkNet to use
to talk to the presses.
d
Set the number, days, and starting times of
shifts.
d
Enter down time codes and their descriptions.
d
Tell LinkNet what machines are present.
d
Tell LinkNet what dies are present.
d
Configure Preventive maintenance.
LinkNet
Figure 3.1: Configuration Menu
3.1 Configuring the Comm Port
LinkNet uses a standard RS-232 serial port (commonly called a comm port) to communicate with the machines on the factory floor via an external RS-232 to RS-485 converter. No boards have t o be installed or configured on the host computer. There are typically two comm ports installed in most computers, COM1" and “COM2". A spare comm port must be available for LinkNet to use.
Select “Configure and then Comm Port from the menu in LinkNet as shown in Figure 3.1 and a dialog box similar to Figure 3.2 should appear. Note that only comm ports that are not currently in use (by anything other than LinkNet itself) show up in the list. Pick the comm port that will be used by LinkNet from the list and click on the “OK” button.
Figure 3.2: Comm Port Selection Dialog
3.2 Configuring Shifts
LinkNet collects information only while in a shift. This keeps the system from needlessly filling up the hard drive with information not related to production and lets many types of information be tracked by shift. The relative performance of different shifts can then be compared and analyzed.
To configure shifts, select “Configure and then Shifts from the LinkNet menu as shown in Figure
3.1. A dialog similar to Figure 3.3 should appear.
3.1
manual rev 2.1 March 25, 1999
Figure 3.3:
Shift Configuration Dialog
Each day may have up to three shifts configured. The Use This Shift checkbox by each shift determines whether or not the shift will be used for that day. Note that a shift can be used some days and not others - each day is individually configurable. Also note that each starting time can be on the day before the current day, and that each ending time can be on the day following the current day. This allows the flexibilit y to assign a shift to a day on which it does not necessarily start or end. For example, it may be desired to have a shift that starts at 10PM on Monday and runs until 6AM on Tuesday to be considered a Tuesday shift. Likewise, a shift that starts a 6PM on Monday and runs until 2AM on Tuesday can be considered a Monday shift.
LinkNet
same day or across days. If any shifts overlap in time, a message will be displayed indicating which days have a problem.
3.3 Configuring Down Time Codes
Down time codes (DTCs) are numeric values that have a user assigned meaning attached to them. These codes allow the user to track the uptime, downtime, and usage of each press. Each DTC has a user entered description that is downloaded to the Link equipment on the presses. When a machine has to be stopped (or is stopped by monitoring equipment such as tonnage monitors, die protection, and so on) the operator can enter the reason for the stop by selecting one of the DTC descriptions that were downloaded to the press.
The time spent in a DTC is logged by LinkNet into a database that can be viewed and analyzed. Problem spots (such as repeated problems with a feed, material, lubrication, etc.) can be easily identified by the percentage of down time that they cause. This enables supervisors to target limited time, money, and other resources at the areas that will do the most good in terms of production.
To configure down time codes, select Configure and then Down Time Codes as shown in Figure 3.1. A dialog box similar to Figure 3.4 should appear.
NOTE: Each day except Monday has a “Set Same as Monday button. Since the typical case is for Monday through Friday to have the same shift times, set the shift times for Monday first, and then go to each day that should be the same as Monday and hit the Set Same as Monday button to copy the shift times over to that day. Any other days can be set according to need.
The starting and ending time of each shift can be configured in 10 minute intervals. Use the up and down arrows next to the hour, minute, and AM/PM boxes to change each setting. When the shifts are configured as desired, click on the OK” button.
No two shifts may overlap in time either on the
Figure 3.4:
DTC Configuration List
This dialog allows DTCs to be added, edited, or
deleted.
After all additions and changes have been made,
click the “OK” button. The DTC descriptions will
3.2
manual rev 2.1 March 25, 1999
LinkNet
then be sent to each press on the network automatically.
3.3.1 Adding a Down Time Code
To Add a DTC, click on the Add DTC button. A dialog box similar to Figure 3.5 should appear.
Figure 3.5:
Add/Edit DTC Dialog Box
By default the DTC number is the next available number, but may be changed to any unused number between 1 and 250 if desired. Up to 25 characters can be entered for the DTC description, but note that the System 1100 can only display the first 19 characters. In addition, a down time category can be assigned. Available categories are Miscellaneous, Die Change Related, Press Related, Die Related, Feed Related, Straightener Related, Material Related, and Scheduled Maintenance. When viewing a down time report, the down time percentages will be shown by individual down time code and by category.
information in the database has been stored. If the DTC needs to be changed, delete the old DTC and add a new one with the desired number.
3.3.3 Deleting a Down Time Code
To delete a DTC, select a DTC from the list (see Figure 3.4) and click on the “Delete DTC button. A message will appear indicating that the select ed DTC is about to be deleted and will ask for confirmation. Click the “Yes” button to delete the DTC or the “No button to keep the DTC.
3.4 Configuring Machines
Since the same network cable is shared by each machine on the network, LinkNet uses a machine number to identify the particular press that it wants to talk to. Each machine on the network must therefore be assigned a unique non-zero number.
Before a piece of Link equipment can “talk” to LinkNet, it must be assigned a machine number. Refer to section 6.1 for details on how to set the machine number for OmniLink 5000 press automation controls, and section 7.1 for System 1100 tonnage monitors.
3.4.1 Adding a Machine to LinkNet
When the machine numbers of each unit connected to the network have been entered, LinkNet must be told what they are. Select Configure from the main LinkNet menu as shown in Figure 3.1, then select “Machine and a dialog box similar to Figure 3.6 should appear.
3.3.2 Editing a Down Time Code
To Edit a DTC, select a DTC from the list (see Figure 3.4) and click on the Edit DTC” button. The dialog box of Figure 3.5 will appear but will not allow the DTC number to be changed - only the description and category. This is to prevent accidental changes that would affect the way
3.3
manual rev 2.1 March 25, 1999
Loading...
+ 32 hidden pages