U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1600ExpDigAdv REV: 1/8/07
SEQUENCE OF OPERATIONS
SERIAL NUMBERS L28563 AND ABOVE
(WITH PUSH BUTTON CONTROL)
MODEL 1633-000-EA 230 VAC 50HZ NATURAL GAS
MODEL 1634-000-EA 230 VAC 50HZ LP GAS
POWER SUPPLY Electrical power to be supplied to the oven by a three conductor service.
Brown conductor is hot
Blue conductor is neutral.
Green conductor is ground.
CONTROL BOX
AUTO COOL DOWN
When the temperature in either one of the control boxes reaches 120°F ±3° (49°C ±
1.7°), the cooling fan thermostats will switch power to the cooling fans. The thermostats
will interrupt power to the cooling fans when the temperature falls to 100°F ± 3° (37°C ±
1.7°)
MAIN FAN CIRCUIT Line voltage is permanently supplied to a normally open contact of the oven power switch.
Line voltage is permanently supplied to the two normally open cooling fan thermostats, a
normally open contact of the oven power relay. Closing the oven power switch supplies line
voltage, through both normally closed control box hi-limit thermostats, to the oven power
relay. Its contacts now close supplying line voltage to the two main fan motors and the two
burner circuits. Closing the oven power switch also supplies line voltage to the control box
cooling fans, the control transformer, and the conveyor motor.
BURNER CIRCUIT NOTE: This oven utilizes two complete burner systems. The sequence of operations is the
same for each system.
Closing the main fan switch supplies line voltage, through the oven power relay, through a
three Amp.fuse, through the gas pressure switch (gas pressure switch removed at
S/N L31479), through the main fan air pressure switch, through the oven cavity hi-limit
thermostat, to the ignition control. The combustion motor is energized. The normally open
combustion air switch closes upon sensing air pressure. After a pre-pu rge period of
between 30 and 60 seconds, the ignition transformer and the main gas valve are
energized. Ignition should now occur.
TEMPERATURE
CONTROL
Closing the oven power switch supplies line voltage, through the 10 amp. fuse, through the
oven power relay, to the primary of the control transformer. 24VAC is supplied to the oven
control. The oven control is set to desired temperature. The thermocouple will provide
varying millivolts to the oven control. The oven control supplies line voltage to the
temperature regulation valve at intermittent intervals to maintain desired temperature. The
display on the oven control will indicate when the temperature regulation valve is
energized.
NOTE: The display also indicates oven temperature.
CONVEYOR DRIVE Closing the oven power switch supplies line voltage, through the 10 Amp fuse, through the
oven power relay to the conveyor motor and to the primary of the control transformer.
Secondary voltage, 24VAC, is supplied to the oven control. Setting the oven control to the
desired time outputs voltage, through a reversing switch, to the conveyor motor
NOTE: The conveyor system uses a magnet and hall effect sensor to prove operation of
the conveyor motor. If the conveyor motor is not running, “BELT JAM” is indicated on the
display.
2
Low Profile –1600 Series Advantage Digital Service Manual – Int’l
SCHEMATIC
MODELS 1633-000-EA AND 1634-000-EA
SERIAL NUMBER L28563 TO L31478
Low Profile –1600 Series Advantage Digital Service Manual -–Int’l
3
SCHEMATIC
MODELS 1633-00-EA AND 1634-000-EA
SERIAL NUMBER L31479 AND ABOVE
4
Low Profile –1600 Series Advantage Digital Service Manual – Int’l
TROUBLESHOOTING GUIDE
MODEL 1633-000 EA NATURAL GAS 230 VAC 50 HZ 1 PHASE
MODEL 1634-000-EA LP GAS 230 VAC 50 HZ 1 PHASE
NOTE: When checking components on left side of unit, be sure to check for pro per connections in power
connector, (marked P. C. on schematic diagram) located inside motor cover.
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not
run
No control box
cooling
No automatic
control box cooling
Oven will not heat
NOTE: These ovens utilize 2 complete Burner/Temperature control systems. Each system will Follow the same
troubleshooting sequence.
Oven power relay Check for line voltage to the relay coil. If no voltage is
L31478 & Below
Incoming power supplyCheck breakers/ reset if required call Power company
if needed
Oven fan switchCheck continuity between switch terminals.
Hi-limit thermostat(s), control
box
Fan fuse Check, replace if necessary.
Fuseholder Check, replace if necessary.
Oven fan relay Check for power to coil of oven fan relay. If no voltage
Capacitor(s) Check for opens, shorts, or grounds.
Motor(s), main fan Check for opens, shorts, or grounds.
Fan switch (SEE OVEN FAN WILL NOT RUN.)
Hi-limit thermostat(s)
Oven fan relay
Cooling fan(s) Supply voltage should now be at these motors. If
Incoming power supply Check circuit breakers, reset if needed. Call power
Cooling fan thermostat(s) Check the cooling fan thermostat.(thermostat closes
Cooling fan(s) Supply voltage should now be at these motors. If
Gas supply Check for adequate gas supply to oven.
Manual gas shut off valve Check to see that the manual gas shut off valve is
Fan switch Check to see that the fan switch is on.
Main oven fan Check if main oven fan is operating. If not, refer to
Fuse, burner 3A.Check, replace if necessary.Serial Number
Fuseholder
Check, replace if nece ssary.
Terminals are normally closed, if open, reset
thermostat and test oven for proper operation. If it will
not reset, replace thermostat.
is present, trace wiring back to hi-limit thermostat.
Check for supply voltage at terminal #6 of the relay. If
no voltage is present, trace wiring back to fuse holder.
If voltage is present, at the relay coil, check to insure
the contacts are closing.
voltage is present, check motor for open, shorts, or
grounds. WITH POWER OFF: check for locked rotor.
company if needed.
at 120°F and opens at 100°F). With the cooling fan
thermostat preheated, check for continuity. If switch is
open, replace.
voltage is present, check motor for opens, shorts or
grounds. WITH POWER OFF: Check for locked rotor.
open. Also check flexible gas line connection for any
damage.
“Oven fan will not run”.
present, trace wiring back to the control box hi-limit
thermostat(s). If voltage is present, check to insure
contacts are closing. Replace relay as needed.
Low Profile –1600 Series Advantage Digital Service Manual -–Int’l
5
Gas pressure switch (internal to
gas valve)
Oven air pressure switch Check for supply voltage on both sides of switch. If
Hi-limit thermostat Terminals are normally closed. If open, reset and test
Ignition control Check for supply voltage to ignition control at terminal
Burner reset switch Switch is normally open. Check to see that the switch
Burner blower motor Check for supply voltage to burner blower motor.
Burner blower motor Air
pressure switch
Spark generator After a pre-purge time of 30 to 60 seconds after
Igniter/sensor assembly Check for visible damage to igniter/ sensor assembly.
Gas valve Check for supply voltage to gas valve. If there is no
Check for supply voltage to neutral on both sides of
switch. If voltage is present on one side of switch only,
check the following. Check for proper gas pressure
supply to gas valve.(Marked on oven spec. plate.)
Check for proper adjustment of gas pressure switch,
should be set at 10 for Nat., 27 for LP, or 4.5 for town
gas. Check gas filter in gas valve for blockage or
damage. (See Adjustment section for location.) If the
above checks OK, but switch is still not closed replace
gas valve.
voltage is present on one side only, check for air tube
blockage. Adjust air pressure switch. If the above fails,
replace air pressure switch.
oven for proper operation. If thermostat will not hold
for maximum oven temperature, and oven is not
exceeding maximum temperature dial setting, check
for proper location of capillary bulb in its spring holder
If above checks OK, replace hi-limit.
#1 and neutral. If voltage is not present, trace wiring
back to hi-limit thermostat. Check for supply voltage at
terminal #6 to neutral. If no voltage is present, wait 30
seconds and check reset button. If above fails,
replace ignition control.
closes when reset button is pushed. Replace as
needed.
WITH POWER OFF: Turn blower wheel to check for
locked rotor. If supply voltage is present and motor
does not run, replace motor.
Check for supply voltage switching to terminal
N.O. as the air pressure switch closes. Check for air
tube blockage or misalignment, adjust air pressure
switch. If the above fails, replace air pressure switch.
blower motor starts, check for supply voltage to spark
generator. If voltage is not present, Check reset
button located on rear of control box. If voltage is still
not present, replace ignition control. If voltage is
present, visually check for spark at igniter head.
If there is no visible damage to the components, and
no spark, replace the spark generator. If there, is
visible damage to the igniter/sensor assembly,
replace. Also check for frayed or damaged wires in
burner tube.
voltage present, check reset button, check all
connections for tightness. If there still is no voltage at
gas valve, replace ignition control. If there is voltage
present, check for gas pressure at gas pressure tap
located in gas piping at burner manifold. If there is no
gas pressure, replace gas valve.
6
Low Profile –1600 Series Advantage Digital Service Manual – Int’l
Flame will not stay
on
Flame sensor To check for flame sensor operation, connect a digital
multimeter (capable of measuring D.C. micro amps) in
series with the flame sensor wire and ignition control.
Sensor current is 3 micro amps D.C. minimum. NOTE:
The D.C. micro amp test must be conducted with the
oven in low flame (bypass) operation. Turn the
temperature control to its lowest setting. If these
readings are not achieved, replace igniter/sensor
assy. Also, check for any type of damage to flame
sensor wire and connections.
Ignition control If there is sufficient flame sensor current, but the
burner will not remain ignited, check the reset button
on ignition control. NOTE: Check for proper polarity of
the power supply. If all of the above are OK, replace
ignition control.
Oven will not heat
Serial Number
L31479 and above
Oven power relay Check for line voltage to the relay coil. If no voltage is
present, trace wiring back to the control box hi-limit
thermostat(s). If voltage is present, check to insure
contacts are closing. Replace relay as needed.
Fuse, burner, 3A Check, replace if necessary.
Fuse holder Check, replace if necessary.
Air pressure switch Check air switch terminals for supply voltage to
terminals C and NO. If voltage is present on one side
only, check for air tube blockage or misalignment. If
these check okay, adjust air pressure switch, or
replace air pressure switch as needed.
Oven cavity hi-limit thermostat Terminals are normally closed, opens at 350˙C (660˙F).
If open, reset and test oven for proper operation. If
thermostat will not hold for maximum oven temperature,
and oven is not exceeding control setting, check for
proper location of capillary bulb in its spring holder. If
above checks are okay, replace hi-limit thermostat.
Ignition control Check for proper supply voltage to ignition control.
Check for proper voltage to the burner blower motor.
This can be checked at motor connecting plug
terminal 5 and Neutral. If voltage is present, proceed
with next test, if not, wait 30 seconds, push reset
button and try to restart. If this fails, check wires from
burner blower motor to the ignition control. If the
above checks okay, replace ignition control.
Burner blower motor Check for supply voltage to motor.
WITH POWER OFF: Turn blower wheel to check for
locked rotor. If supply voltage is present at motor
connecting plug terminal 5 and Neutral, and motor
does not run, replace burner blower motor.
Air pressure switch
(burner motor)
Check for proper supply voltage switching from “NC”
to “NO” on the air pressure switch. Check for air
pressure switch adjustment, air tube blockage or
misalignment. If these adjustments fail, replace air
pressure switch.
Ignition control A pre-purge time of 30 to 60 seconds occurs after
burner blower motor starts. Check for high voltage
spark output from the ignition control. If there is no
high voltage spark output, check reset button for
ignition control. If there is still no high voltage output,
replace the ignition control.
Low Profile –1600 Series Advantage Digital Service Manual -–Int’l
7
Igniter/sensor assembly Check this assembly for visible damage. Replace as
needed. If there is no visible damage, check for
voltage supply to igniter/sensor assembly. If there is
voltage supplied to the igniter/sensor, but there is no
spark, replace the igniter/sensor assembly.
Gas valve Gas valve should open as the ignition control
generates the high voltage spark. Place a manometer
on the pressure tap fitting (located in the gas piping
just prior to the burner manifold) and check for gas
pressure. If valve does not open, check reset button
on ignition control, and all connections for tightness. If
there is still no gas pressure, remove the ignition
control from the gas valve. Check the coils of the gas
valve for opens or shorts. Readings should be as
follows: V1 – 2.9K ohms approx., V2 – 1.3K ohms
approx. If these readings are not achieved, replace
gas valve. If these readings are achieved, replace
ignition control.
Flame will not
stay on
Flame sensor To check for flame sensor operation, connect a digital
multimeter (capable of measuring D.C. microamps)
between the flame sensor wire and the flame sensor
connection on the ignition control. Sensor current is to
be 0.9 microamps, minimum. If these readings are not
achieved, replace the igniter/sensor assembly. Also
check for any type of damage to the flame sensor wire
and connections.
NOTE: The D.C. microamp test must be conducted
with the oven in low flame (bypass) operation
Power supply Set the temperature to the lowest temperature setting.
If there is sufficient microamp current, but the flame
will not stay lit, check for proper polarity of the power
supply.
Ignition control If there is sufficient microamp current, and there is
proper polarity of the power supply, but the burner will
not stay lit, check the reset button for the ignition
control. If the above test is okay, replace ignition
control.
NOTE: Flame should be on at
this time
Low flame is on,
But no main flame
Control transformer Check for supply voltage to the primary of the control
transformer. If no voltage is present, trace wiring back
to the oven power relay. If primary voltage is present,
check for 24VAC at the transformer secondary. If
there is primary voltage, but no secondary voltage,
replace control transformer.
8
Low Profile –1600 Series Advantage Digital Service Manual – Int’l
Oven control Check for 24VAC supply to control. If no voltage is
present, trace wiring back to control transformer. If
24VAC is present, check for a read-out on the control
display. If there is 24VAC supplied, but there is no
read-out on the control display, replace the oven
control.
If there is a read-out on the control, set the control to
maximum temperature (see installation operations
manual for temperature adjustment). With the control
set at maximum temperature, check for line voltage at
the temperature regulation valve. If there is voltage at
the temperature regulation valve, proceed to
“temperature regulation valve” for next check. If there
is no voltage at the temperature regulation valve,
trace wiring back to the oven control. If there is no
voltage output at the oven control, check the read-out
on the control. If the control reads “LP FAIL” or “RP
FAIL”, this indicates that the thermocouple has failed
or has become disconnected from the control. “LP
FAIL” indicates a problem with the left thermocouple
probe, and “RP FAIL” indicates a problem with the
right thermocouple probe.
Thermocouple probe Check to be sure that the thermocouple is securely
connected to the oven control. If the thermocouple is
connected to the oven control, and the control
indicates “LP FAIL” or “RP FAIL”, disconnect the
thermocouple from the oven control and measure the
resistance of the thermocouple. The left thermocouple
should read approx. 21Ω. The right thermocouple
should read approx. 11Ω. If these readings are not
achieved, replace the thermocouple. If these readings
are correct, proceed.
Oven control If the thermocouple checks good, but the oven control
display indicates that there is a thermocouple failure,
replace the oven control. If the oven control indicates
a temperature reading but the oven will not heat,
proceed.
Thermocouple WITH POWER ON AND THERMOCOUPLE
ATTACHED TO THE OVEN CONTROL: Measure the
DC millivolt output of the thermocouple. Refer to the
thermocouple chart (located in the “Removal” section
of the manual) for proper millivolt readings. If these
readings are not achieved, replace thermocouple.
Oven control If the thermocouple checks good, but there is no
voltage output to the temperature regulation valve,
replace the oven control. If there is voltage output to
the temperature regulation valve, proceed.
Temperature regulation valve Check for line voltage supplied to the temperature
regulation valve. If no voltage is present, trace wiring
back to the oven control. If voltage is present, listen
for the valve to open and close. Also check for opens
or shorts in the operating coil. Replace temperature
regulation valve as needed.
Low Profile –1600 Series Advantage Digital Service Manual -–Int’l
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.