Liftmaster SW2000-B3 User Manual

INSTALLATION MANUAL
MODEL SW2000-B3
HEAVY DUTY, HIGH CYCLE SLIDE GATE OPERATOR
Serial #
(located on electrical box)
Installation Date
3 YEAR WARRANTY
NOT INTENDED FOR PEDESTRIAN PASSAGE GATE USE
ESTATE SERIES
B3
2

TABLE OF CONTENTS

SAFETY SUMMARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
BASIC INSTALLATION HINTS AND RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SITE PREPARATION
LOCATION AND LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
PAD AND MOUNT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
POWER WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
LOOP DETECTORS AND PHOTO-SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
OTHER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
MASTER/SECOND INTERCONNECTION (MASTER/SECOND SYSTEM ONLY) . . . . . . . . . . . . . . .9
GROUNDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SYSTEM INSTALLATION
GATE AND PHOTO-SENSOR LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
MOUNTING GATE OPERATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
CONNECTING POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
RUNNING INPUT WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
SETTING GATE OPEN DIRECTION SWITCHES S2 AND S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
POWER UP PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
USING MANUAL CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
GATE ARM INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SETTING LIMIT CAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-16
GATE SENSITIVITY ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-18
SETTING GATE CONTROL SWITCH S1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-20
CONNECTING INPUT WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21-22
POST INSTALLATION PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22-24
FINAL ASSEMBLY OF GATE OPERATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
PROGRAMMING THE RADIO RECEIVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
LIFTMASTER LOOP DETECTOR BOARDS (OPTIONAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
TROUBLESHOOTING AND MAINTENANCE
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-31
FAULT LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
FAULTS AND THEIR CAUSES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33-35
APPENDIX A: SYSTEM OPERATION REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36-40
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
INDICATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
FUNCTIONAL INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38-39
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
CONNECTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
APPENDIX B: SW 2000-B3 PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-42
GLOSSARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
FCC REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
NOTICE TO CANADIAN USERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
3
TABLE OF CONTENTS
Figure 1. Gate Operator Layout Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 2. Pad and Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Figure 3. Photo-Sensor Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Figure 4. AC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Figure 5. Gate Direction and UPS Low Battery Switch Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Figure 6. Manual Controls, Location and Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figure 7. Gate Arm Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 8. Setting Right Gate Limit Cam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 9. Setting Left Gate Limit Cam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 10. Gate Sensitivity Adjustments Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 11. Gate Control Switch S1 Location And Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 12. Reclose Timer Enable and Adjustment Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 13. Control Board Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Figure 14. Photo-Sensor Coverage Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 15. Gate Operator Final Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Figure 16. High Security and Normal Security Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 17. Constant and Momentary Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 18. Programming the Remote to the Receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 19. Typical Swing Gate Loop Detector Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 20. Gate Operator Disassembly and Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Figure 21. Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
4

THE LIFTMASTER MODEL SW2000-B3 GATE OPERATOR

The LiftMaster model SW2000-B3 is a full featured, commercial swing gate operator with master/second wiring capability. The gate operator contains the following features:
Satisfies U.L. 325 requirements for primary (motor current) and secondary (photo) obstruction senses.
Five different open inputs are available for a variety of devices.
Alternate action OPEN/CLOSE inputs.
Manual Open/Close/Stop inputs are provided for three-button station.
Inside and outside Interrupt Loops and Photo-Sensors Inputs enhance gate control and distinguish between entering and exiting traffic.
Gate lock relay can be used for electromagnetic locks and CCTV cameras or lights.
Interrupt Bar input is included for use with edge sensors.
Quick gate setup is facilitated by eight-position dip switch.
Adjustable Reclose timer.
Selectable anti-tailgate function prevents two cars from entering on one open command.
Dynamic motor braking limits gate overtravel.
Senses obstructions through adjustable peak and fixed average motor current sense.
Two separate peak motor current sense adjustments for reversing direction or stopping; one for clockwise motion and the other for counterclockwise motion.
Start-up current sense adjustment offsets initial inrush current to the motor.
Obstruction Alarm sounds off the second time the gate is obstructed.
Open Motor detection in case of motor thermal overload.
Maximum Run Time feature stops run-away motor in case of belt breakage.
Diagnostic LEDs on controller board indicate gate operator actions and assist in troubleshooting.
Master/Second operation for two operators on bi-part gates and vehicle trap gates.
Separated arm segment joints reduce the risk of injury to users.
Two 115 VAC accessory plugs provided.
24 VAC accessory power provided.
True 1/2 HP high starting torque motor reduces stalling.
80:1 worm gear reduction.
Handles any gate weight up to 1000 pounds and length up to 18 feet.
Quick disconnect arm cap for fast and easy release of gate arm.
Cover access door provides easy access to the control box.
Optional loop detector add-on boards plug into the controller board for easy installation.
DIMENSIONS WEIGHT ELECTRICAL
Height 24" 159 lbs. 115 VAC, 60 Hz. Single Phase Width 20" 15 amp (A separate 20 AMP circuit Depth 23" is required by most codes.)
5

SAFETY SUMMARY

It is important for everyone involved in the installation and operation of the Gate Operator to read the following warnings.
1. READ AND FOLLOW ALL INSTRUCTIONS. Improper installation of a gate operator can result in a
dangerous system. SAVE THESE INSTRUCTIONS.
2. A vehicle gate is a large, heavy object that is moved by an electric motor. A moving gate can
cause serious injury or death! The safety and well-being of others depends on the installation of a safe system.
3. The entrance is for VEHICLES ONLY. Pedestrians must use a separate entrance. Always keep
people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Choose one or more controls that together will allow complete control of the gate. Most
importantly, the gate must be able to be stopped at all times in case of emergency, and the emergency control should be conveniently located, clearly marked and visible.
5. All controls must be kept out of the reach of small children. Serious injury or death can result
from children playing with the controls.
6. All controls should be located so the person operating them can see the full area of gate
movement.
7. Use the emergency release only when the gate is not moving.
8. KEEP GATES PROPERLY MAINTAINED. Have a qualified person make repairs to the gate
hardware.
• Test the gate operator safety features monthly. The gate MUST reverse on contact with a rigid object or stop when an object activates the non-contact sensors.
• After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of damage, injury or death.
9. Gate operators and associated control equipment should be installed by qualified professional installers who should observe the following safe installation procedures:
• Power should always be disconnected whenever installing, wiring or servicing a gate operator. Moving chains in gate operators can catch clothing or fingers and cause severe injury.
• Installation of wiring should comply with local building and electrical codes.
• All manual gate locks should be disabled to avoid damage to the gate or gate operator should the lock become engaged after the operator is installed.
• All operator controls and safety equipment should be tested at the conclusion of installation to be sure they are functioning properly.
• The operation of the gate controls and safety equipment should be reviewed with the owner and/or end user of the automated gate system. They should also be informed of the need to maintain control and safety equipment on a regular basis. Safety equipment should be checked monthly to ensure it is working properly. All installation manuals and safety information should be left with the owner.
• Moving gates have pinch points and entrapment zones which can be extremely dangerous to pedestrians, especially small children.
WARNING
WARNING
6

BASIC INSTALLATION HINTS AND RULES

READ THIS SECTION CAREFULLY BEFORE BEGINNING YOUR INSTALLATION.
1. UNDERSTAND THE SYSTEM AND INSTALLATION SITE THOROUGHLY. The SW2000 is a flexible
and reliable gate operator system, but the quality of service depends directly on the quality of installation. Please read these instructions carefully and study the applicable diagrams before planning your installation. In particular, understand any site characteristics that may affect the system installation.
WARNING
2. INSTALL PERMANENT WIRING. UL specifications require the SW 2000 system to be permanently
wired. Refer to your local wiring code for specific information.
WARNING: Damage caused by faulty wiring is not covered by warranty.
3. U.L. OBSTRUCTION-SENSING REQUIREMENTS. To maximize safety, UL325 standards require
primary obstruction sensing (gate sensitivity to impact) and secondary obstructions sensing (photo-sensors) be in operation at all times.
4. GROUND THE SYSTEM. The system contains parts which may be damaged by static discharge. A proper earth ground connected to the gate operator housing at the lower left grounding screw (see Figure 14) will significantly reduce the chances of damage or improper operation. The shielding in the cables specified for all remote sensors and controls should also be connected to earth ground at the controller end of the cable only.
To be effective, the ground connection must be made by running 12 AWG copper wire to a good ground point (e.g., an electrical panel, a metallic cold water pipe that runs into the earth, or a grounding rod at least 10 feet in length that is driven into the earth) within 12 feet of the system Even if you have a good earth ground, you should try to discharge any static before handling the circuit boards.
WARNING: Damage caused by static discharge and lightning is not covered by warranty.
5. PROVIDE POWER FROM A DEDICATED SOURCE. The outlet into which you connect the Gate
Operator should be wired to its own circuit breaker. This will reduce the line noise introduced into system power and minimize the risk of having other equipment interrupt system operation. In a master/second system, master and second must each have separate circuits.
6. DO NOT OVERLOAD THE TERMINAL BLOCKS. The terminal blocks are removable and the pins are soldered into the boards. To connect your wires, remove the “head” from the correct terminals and open the screws. Insert the wire into the correct opening on the front and tighten the screw until the wire is held firmly. When you have made all connections for a given “head,” plug it back onto the pins designated for that terminal block.
Stranded wire must be between 16 and 24 AWG. Solid wire must be between 18 and 24 AWG. This is the total thickness measurement so, if you are putting two wires in, the combined thickness must fall within this range. NEVER try to insert more than two wires per terminal.
7. ENSURE GOOD CONNECTIONS. A light tug on the wire will tell you if the connection is secure. When reconnecting system components, make sure all pins are straight on chips, connectors, and terminal block heads.
8. READ THE MARKINGS CAREFULLY. The connection points are marked on the boards clearly. Before making any connection, be sure to read the marking and check it against the corresponding figure in these instructions so that you understand the connection you are making.
9. TRAIN YOUR CUSTOMERS THOROUGHLY. Although customer responsibility is limited to proper installation, the quality of service is determined by the care of system setup. Ensure that the customer has a copy of this manual to guide them. It will save you and them a lot of inconvenience and aggravation later.
7

LOCATION AND LAYOUT

Figure 1. Gate Operator Layout Options

SITE PREPARATION

NOTES
• Left Gate and Right Gate are determined by looking from inside the complex toward the street.
• Figure 1 shows a typical Bi-Parting gate in standard and compact installations.
8

PAD AND MOUNT

Figure 2. Pad and Mount
1. The concrete pad must be sufficient to support the gate operator and the dynamic forces created by the moving gate. LiftMaster recommends a pad 24" wide by 27" long by 30" deep.
2. The operator must be level and parallel to the gate, so the pad should be level and about 4" above grade to prevent water entrance.
3. Four anchor bolts are required to secure the gate operator to the pad. The mounting holes in the gate operator are 5/8" in diameter. Concrete anchoring bolts 1/2" x 3-1/2" are recommended.
4. Be sure to provide access for wiring conduits. In systems, remember to include conduit stubs for separate inputs (if any) and for the Master/Second connection cable between gate operators. For more information about Master/Second systems, see Master/Second Systems for B3 Series Gate Operators.
NOTE: Shading indicates conduit stub access areas .
1. Always install gate operators inside of the fence line, NEVER on the public side of the fence.
2. Mount all manual controls and activating devices at least 6 ft. away from the gate for safety.
3. Allow enough clearance around the gate and the gate operator for installation and service.
9

POWER WIRING

OTHER CONNECTIONS

LOOP DETECTORS AND PHOTO-SENSORS

MASTER/SECOND INTERCONNECTION (MASTER/SECOND SYSTEM ONLY)

1. Provide a separate conduit stub for the AC power.
2. Each gate operator requires a 115 VAC 20 AMP single phase circuit
NOTE: Master and Second units each require separate circuits to prevent false overcurrent faults (see B3 Series Master/Second Systems).
3. Wiring must comply with the local Electrical Code for operating a 1/2 HP motor. 12 AWG for up to 300' and 10 AWG for up to 500' long wire runs is suggested.
4. Be sure to pull a ground wire in the conduit for the connection to the gate operator.
NOTE: Do not rely on metallic conduit for earth ground.
1. A shelf is provided (13” x 10” x 9” high) to support non-LiftMaster loop detector electronics.
Power for the loop detector can come from the auxiliary 115 VAC plugs in the gate operator or from the 24 VAC provided by the gate operator control board.
NOTE: The auxiliary plugs have power regardless of the unit power switch setting.
2. Conduit provisions should be made for the “loop” wire entrance to the loop detector.
3. Wiring should be 16-24 AWG stranded or 18-24 AWG solid.
NOTE: Optional LiftMaster-supplied loop detector add-on boards are available, both pre-installed and for installation in the field. See Part 3, Gate Operator Model SW 2000-B3 Options.
1. Provisions should be made for conduit entrance into the gate operator for external activating devices such as key switches, telephone entry systems, loops, etc.
2. Wire size requirement: 16-24 AWG stranded or 18-24AWG solid wire should be used.
1. A conduit between the Master and Second units should be provided for the Master/Second interconnection cable.
2. Two shielded twisted pair wire 16-24 AWG will be connected between the two units at TB1 on the controller board.
NOTES:
1. Do not run the Master/Second cable and AC power wires in the same conduit.
2. Master/Second interconnection cable should not exceed 3000 feet in length.

GROUNDING

1. The system contains parts which may be damaged by static discharge. A proper earth ground connected to the gate operator housing will significantly reduce the chances of damage or improper operation. The shielding in the cables specified for all remote sensors and controls should also be connected to earth ground at the controller end of the cable only.
2. To be effective, the ground connection must be made by running 12 AWG copper wire to a good ground point (e.g., an electrical panel, a metallic cold water pipe that runs into the earth, or a grounding rod at least 10' in length that is driven into the earth) within 12' of the system. Even if you have a good earth ground, you should try to discharge any static before handling the boards.
10

GATE AND PHOTO-SENSOR LAYOUT

Figure 3. Photo-Sensor Layout

SYSTEM INSTALLATION

11

MOUNTING GATE OPERATOR

IMPORTANT NOTE
The installation shown in Figure 3 is a suggested layout using emitters and receivers. Any UL-approved photo-sensors are acceptable, but they must cover the entire area of gate travel to be effective.

CONNECTING POWER

1. Install photo-sensors in three Coverage Areas as shown in Figure 3.
Coverage Area A - Inside-Open Coverage:
Inside the gate, from the gate post(s) to the gate fully open position(s).
Coverage Area B - Inside-Closed Coverage:
Inside the gate, from the gate open position across full arc of gate travel.
Coverage Area C - Outside-Closed Coverage:
Single Gates: Outside the gate, from the gate post to the fence. Dual Gates: Outside the gate, from gate post to gate post.
2. For wiring instructions, see Connecting Power, below.
NOTE: If you are installing a Master/Second system, refer to Series B3 Master/Second Systems for additional layout information.
WARNING
To avoid injury, always turn off the unit power switch before working on gate.
1. Pull red release lever to disengage and remove quick disconnect arm cap from the output shaft (see Figure 7).
2. Remove 4 protective bolts holding the cover on, lift off the cover and set aside.
3. Remove the assembly kit and parts.
4. Remove the 4 bolts that attach the gate operator to the shipping pallet.
5. Mount gate operator on cement pad using the previously installed anchors. Be sure the operator is mounted level and square, with the control box facing away from the gate.
6. Connect the power conduit into the switch box.
7. Reinstall gate arm assembly onto output shaft/hub. Close red release lever until engagement pin fully seats into hub and ball plunger engages on handle. This may require slight side-to-side motion — HANDLE WILL CLOSE WHEN PIN IS PROPERLY ALIGNED — DO NOT FORCE SHUT.
CAUTION
Ensure that the AC power circuit breaker is turned off before wiring power to the switchbox.
Run power cables through the conduit to Gate Operator, then connect wires to the switch box as shown in Figure 4:
1. Wire nut the hot (black) wire to the black pig tail.
2. Wire nut the neutral (white) wire to the white pig tail.
3. Wire nut the ground (green) wire to the green pig tail.
4. Dress all wiring inside the switch box and install cover.
Figure 4. AC Wiring
12

RUNNING INPUT WIRING

WARNING
Route but do not connect input wires at this time. If inputs are connected now, the gate operator may activate at random during installation, potentially injuring installation personnel.
1. Remove the plastic control box cover.
2. Run wires from input component conduits and Master/Second conduits into control box.
3. For Master/Second wiring, refer to Master/Second Systems for B3 Series Gate Operators, Part 2.
NOTE: For swing gate operation, controls are Left/Clockwise and Right/Counterclockwise.
• Switch S2 sets gate opening direction (open to left or open to right).
• Switch S2 is sensed only on power up, it should be set when the power is off, or power should be cycled after setting the switch.
1. Set switch S2 to the Left for Clockwise Gate Opening, or to the Right for Counterclockwise Gate Opening as required.
2. Set switch S3 to the direction you wish the gate to move (left or right) and remain when the LOW BATTERY input is activated by an Uninterruptible Power Supply (UPS).

SETTING GATE OPEN DIRECTION SWITCHES S2 AND S3

Figure 5. Gate Direction and UPS Low Battery Switch Locations
13

POWER UP PROCEDURE

CAUTION
If gate is positioned at the ‘open’ limit, gate will automatically close if Reclose Timer is enabled and power is switched on. Position gate either at the closed limit or at no limit when preparing to switch power on. Always use extreme caution and follow all warnings in the Safety Summary.
If necessary, use the manual controls on Manual Input Terminal TB2 (OPEN, CLOSE, and STOP, as shown in Figure 6), to move the gate arm during system installation.
To open the gate: connect the OPEN and STOP terminals to the COMMON terminal.
To close the gate: connect the CLOSE and STOP terminals to the COMMON terminal.
To stop the gate: disconnect the STOP terminal from the COMMON terminal.
IMPORTANT NOTE
If the STOP terminal is disconnected from the COMMON terminal, the gate is prevented from moving and no command will affect the gate.

USING MANUAL CONTROLS

Figure 6. Manual Controls, Location and Use
1. Turn on circuit breaker that provides power to gate operator.
2. On Manual Input Terminal TB2, connect the STOP terminal to the COMMON terminal (see Figure 14).
3. Turn on gate operator power switch and verify that the row of LEDs on the right side of the controller board all turn on, then turn off sequentially, starting from the top. The only LEDs that should remain on are Power ON, MAGLOCK, and CLOSE LIMIT or OPEN LIMIT, if one of the limit switches are engaged.
NOTE: If the LEDs do not follow this pattern, the controller board may not be working correctly. Stop installation and call LiftMaster Technical Support for assistance.
4. On Manual Input Terminal TB2, disconnect the STOP terminal from the COMMON terminal.
14

GATE ARM INSTALLATION

NOTES:
1. All dimensions are measured from one pivot point to the next pivot point.
2. The dimensions shown above are only recommended settings. Your installation may require different dimensions.
3. The SW2000-B3 can be installed without welding. The anchor, swing arm and drag link may be attached using the supplied hardware only, may be welded, or bolted and welded.
4. Paint or other anti-rust coating must be applied to the cut areas of the swing arm and/or drag link pipe to prevent rust.
1. Attach gate anchor to gate by welding or using hardware (not supplied).
2. Using manual controls, move the swing arm cap assembly until it points roughly to the anchor. See Figure 7.
3. Measure and cut the swing arm to length. Attach swing arm to swing arm cap assembly with gate stop on driveway side, using supplied hardware or by welding.
WARNING: Installing gate stop on the wrong side will cause damage to the gate operator.
4. Measure and cut Drag Link pipe to length, then insert spherical rod end assembly into pipe and tighten locking nut.
5. Attach welded end of Drag Link Assembly to Anchor and unwelded end to Swing Arm.
Figure 7. Gate Arm Installation
Quick Disconnect
Release Lever
Swing Arm Cap Assembly
Disengaged
Engaged
15

SETTING LIMIT CAMS

• Adjust the limit cams by loosening the clamp and rotating the cams. The cams rotate with the swing arm shaft, so small adjustments are magnified by the length of the gate.
• To avoid damage to the gate and gate operator due to the gate overrunning its limits, perform the following steps carefully:
Figure 8. Setting Right Gate Limit Cam
1. SETTING RIGHT GATE LIMIT CAMS
1. Make sure that switch S2 is set to the “Right” position.
2. Turn on gate operator power switch.
3. Using manual CLOSE and STOP, move the gate to its proper closed limit position.
4. Loosen the clamp on the bottom limit cam and turn the cam clockwise until it just barely closes the limit switch.
5. Retighten the clamp. Do not overtighten.
6. Using manual OPEN and STOP, move the gate to its proper open limit position.
7. Loosen the clamp on the top limit cam and turn the cam counterclockwise until it just barely closes the limit switch.
8. Retighten the clamp. Do not overtighten.
9. Open and close the gate to check the limit cam settings. If required, readjust the limit cams until they are set properly.
Top Limit Cam
Top Limit Switch
Open Gate Closed Gate
Bottom Limit Cam
Bottom Limit Switch
Loading...
+ 33 hidden pages