LiftMaster LM21XPBB User Manual

OO WW NN EE RR SS MM AA NN UU AA LL
MM OO DD EE LL SS
LL MM 22 11 XX PP BB BB
LL MM 22 11 XX PP BB BB VV BB
EEXXTTEENNDDEEDD PPEERRFFOORRMMAANNCCEE RREELLEEAASSEE DDEEVVIICCEE
APPROVED
The Chamberlain Group, Inc. 845 Larch Avenue Elmhurst, Illinois 60126-1196
www.liftmaster.com
When you see these Safety Symbols and Signal Words on the following pages, they will alert you to the possibility of serious injury or death if you do not comply with the warnings that accompany them. The hazard may come from something mechanical or from electric shock. Read the warnings carefully.
When you see this Signal Word on the following pages, it will alert you to the possibility of damage to your door and/or the door operator if you do not comply with the cautionary statements that accompany it. Read them carefully.
Mechanical
Electrical

TABLE OF CONTENTS

WARNINGWARNING
WARNING
WARNINGWARNING
WARNING
CAUTIONCAUTION
WARNING
WARNING
2

INTRODUCTION

General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Agency Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INSTALLATION
Important Installation Warnings . . . . . . . . . . . . . . . . . . . . . . . . . .4
Mount the Release Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
WIRING
Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wire Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Connections of Initiating Devices and Accessories . . . . . . . . . .8-9
Optional Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
TESTING
Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
TROUBLESHOOTING
Operational Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
MAINTENANCE
Maintenance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Enclosure Mounted LEDs Status Indicators . . . . . . . . . . . . . . . .13
ACCESSORIES AND REPAIR PARTS
. . . . . . . . . . . . . . .14
APPENDIX
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
IMPORTANT NOTES:
• BEFORE attempting to install, operate or maintain the release device, you must read and fully understand this manual and follow all safety instructions.
• DO NOT attempt repair or service of your release device unless you are an Authorized Service Technician.

GENERAL DESCRIPTION

The LiftMaster®LM21XPBB and LM21XPBBVB Release Device is UL/ULC listed normally energized fail-safe device designed for use on rolling doors, single-slide and center-parting level and inclined track doors. All models are normally energized fail-safe releasing devices incorporating state-of-the-art electronic control circuitry. The release devices respond to emergency conditions generated from an automatic initiating device and are used in conjunction with a fusible link system.
The release device can be powered from 120Vac, 24 Vac, or 24Vdc. The 24Vdc cannot be sourced from a fire alarm control panel or UL1481 regulated power supply. The devices can be activated via a smoke detector or an alarm relay from the panel’s
Form C dry contact relay. The release device features include a 10, 20, 30 or 60 second delay on alarm, closed door detection capabilities, Form C relay outputs for the transmission of alarm and trouble signals transmitted to the fire alarm control panel, an audible trouble sounder, and diagnostic feedback LEDs.
The release device is provided with a battery management system that can provide 24Vdc power for up to four smoke detectors and two horn strobes, as well as provide battery backup for the release device and accessories. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with a fusible link systems.
INTRODUCTION
INTRODUCTION
3

AGENCY REQUIREMENTS

Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).

SPECIFICATIONS

To prevent possible SERIOUS INJURY or DEATH:
• DO NOT use this device without fusible links installed.
• Test every 90 days to assure proper operation of release
device.
WARNINGWARNING
WARNING
VOLTAGE RATING: 120Vac, 60Hz; 24Vac, 60Hz; 24Vdc STANDBY CURRENT .06A, .3A, .2A ALARM CURRENT .06A, .3A, .25A BATTERY RATING: 12V 4.5AH Sealed Lead Acid
Battery, Maximum charge current .150Amps
BATTERY STANDBY TIME: LM21XPBB, 72 Hours
LM21XPBBVB, 24 Hours
LOAD RATING: Support and Release 40 lbs. Max. PHYSICAL DIMENSIONS: 9.7" x 7.5" x 5" (h x w x d)

PREPARATION

It is imperative that the wall or mounting surface provide adequate support for the release device.
Refer to the door manufacturer’s recommendations for use of this product with specific door being utilized. Use only hardware approved or recognized by the appropriate testing and listing agencies in conjunction with the installation of this product.
Additional items may be required to complete the installation:
• Concrete anchors or fasteners
• Sash chain or 1/16 cable
• Eyebolts-hook
• Fusible links
• Turnbuckles
• Smoke detectors (up to 4 may be installed with this device)
Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices shall be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.
ELECTRICAL SPECIFICATIONS
MECHANICAL SPECIFICATIONS
FUSES: 3A @ 250V, 2AG Slo-Blo Type INITIATING DEVICE: Maximum line impedance 20 ohm;
Maximum current not to exceed .010A.; Maximum voltage 24Vdc
AUXILIARY POWER: 24Vdc @ .5A Maximum COMMON ALARM AND
TROUBLE RELAYS:
.5A 125Vac 60Hz
(MAX. CONTACT RATING) 1A 24Vdc Resistive
WEIGHT: Approximately 18 lbs. (INCLUDING BATTERIES)
Smoke Detector
Releasing Unit
Turnbuckle
Annunciator
Chain
Fire Door
Chain End Link
Fusible Links
Eyebolt
4

INSTALLATION

Classification:
Releasing device as defined by Underwriters Laboratories.
Installation Requirements:
Intended for “Indoor Dry” locations; all wiring must be performed in accordance with the most current version of NFPA 72 - National Fire Alarm Code and the National Electric Code.

MOUNT THE RELEASE DEVICE

Installation procedures vary according to door types. Refer to door manufacturer’s recommendation that applies to your door.
1. Mount the release device on a vertical surface with chain end link exiting side of enclosure.
2. Secure the release device enclosure with fasteners (#10 is the minimum size recommended). If installing in masonry, use concrete anchors (not provided).
3. Install hardware (sash chain or 1/16" cable, eyebolts-hook, fusible links, turnbuckles—not provided) according to door manufacturer’s recommendations. NOTE: The end link direction
of pull must be perpendicular to the side of the release device enclosure. Install an eyebolt a minimum distance of 12" from the release device to adequately redirect sash chain pull.
4. Install end link by pressing mechanical reset to allow insertion of end link. Push end link completely in and release mechanical reset to latch end link.
5. Remove sash chain or cable slack by adjusting turnbuckle.
IMPORTANT INSTALLATION INSTRUCTIONS
To reduce the risk of SEVERE INJURY or DEATH:
WARNING
WARNINGWARNING
1. READ AND FOLLOW ALL INSTALLATION WARNINGS AND INSTRUCTIONS.
2. NEVER connect release device to power source until instructed to do so.
3. DO NOT use this device without fusible links installed.
4. Concrete anchors MUST be used if mounting release device into masonry.
5. DO NOT exceed maximum pull rating of 40 lbs. on releasing device.
Smoke Detector
Releasing Unit
Turnbuckle
Annunciator
Chain
Fire Door
Chain End Link
Fusible Links
Eyebolt
End Link
Mechanical Reset Plunger
1
2
+
5

WIRING

WIRING INSTRUCTIONS

Verify wiring configuration with that recommended by door manufacturer for use of this product with specific door and accessories being utilized. The use of 18 AWG wire is recommended.
1. Close fire door prior to ANY wiring.
2. Turn off power supply sources for the release device as well as the door operator, before beginning.
3. Verify voltage rating of release device to power source being utilized. Voltage is indicated on the side of the unit. Verify that power is disconnected before proceeding.
4. When powering the device from 120Vac line voltage, locate the 3-position terminal block mounted within the device enclosure. Connect 120Vac (single phase) power source inputs to terminals L1 (line) and L2 (neutral) of the terminal block (Figure 1). The third position is used for earth ground.
5. When powering the device from 24Vac or 24Vdc power, connect to terminal board positions 1 and 2 (Figure 2). Observe proper polarity.
6. Do not connect line power or battery until all field wiring is complete per the following pages. The battery provides backup power in the event of a loss of line voltage and prevents the release of the fusible link assembly and the resulting door closure. A pulsing sounder occurs when the battery is disconnected or when replacement is required. The battery also provides power to the various ancillary devices (i.e., smoke detectors, horn/strobes, etc.).
To reduce the risk of SEVERE INJURY or DEATH:
• ALL electrical connections MUST be made by a qualified individual.
• Disconnect power at the fuse box BEFORE proceeding. Release device MUST be properly grounded and connected in accordance with local electrical codes.
• Installation of ALL wiring and connections, including Class 1 and Class 2 circuits, shall be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes. In addition, ALL installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods.
• ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled.
• ALL power and control wiring MUST be run in separate conduit.
• 120Vac should ONLY be attached to the 3-position terminal block mounted within the enclosure.
• DO NOT disconnect battery or remove battery fuse while unit is under power, the door will drop.
WARNING
WARNINGWARNING
FIGURE 2
To prevent DAMAGE to the circuit board, ALL connections from terminals 3 through 16 MUST be dry contact type.
WARNING
CAUTIONCAUTION
WARNING
WARNING
FIGURE 1
Power Strip
Ground
L2
Option DIP Switch
L1
Mechanical Reset Plunger
24Vac or 24Vdc