This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert XDP. Read this manual thoroughly before attempting to install or
operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the
unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING
Risk of arc flash and electric shock. Can cause property damage, injury or death.
Disconnect all local and remote electric power supplies and wear protective equipment per
NFPA 70E before working within electric control enclosure. Failure to comply can cause
serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off
mode. Some internal components require and receive power even during the Unit Off mode of
Liebert iCOM control.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
WARNING
Risk of unit falling over. Can cause property damage, injury or death.
The XDP is top-heavy. Use extreme caution and care when moving and installing this unit.
CAUTION
Risk of piping and component rupture. Can cause injury or equipment damage.
System is pressurized. Relieve pressure through access valve before working on unit.Closing
service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do
not close valves without following recommended procedures for repair, maintenance and
replacement of components. Install pressure relief valves in field piping that may become
isolated by service valves. System is pressurized. Relieve pressure through access valve
before working on unit
NOTE
This document is intended to be used together with site specific documentation and
documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Before any action that could cause a disturbance in the XD system’s cooling function is begun,
the facility manager MUST be informed. In addition, after the action is taken and the work is
finished, the facility manager MUST be informed.
NOTICE
Risk of leaking chilled water lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe
property damage and loss of critical data center equipment. Do not locate unit directly above
any equipment that could sustain water damage. Emerson Network Power recommends
installing monitored leak detection equipment for the unit and supply and return lines.
1
Figure 1Model number nomenclature
R
Pump
Redundancy
XDP160–*
Pumping
unit
Revision
level
Liebert
X-treme heat
Density system
160kW
nominal
capacity
Place holder
Example: XDP160RA– –4
A
A = 460V-3ph-60Hz
(voltage-phase-frequency)
C = 208V-3ph-60Hz
M = 380/415-3ph-50Hz
–
Place holder
2
1.0PRODUCT DESCRIPTION
Liebert XDP Unit
Control Valve
Liebert XD Cooling Modules
Heat Exchanger
Receiver
Pumps
Chilled Water
1.1General Product Information
1.1.1Product/System Description
Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system
and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant
to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP is rated
for 160kW (546,000BTU/H) of cooling.
The Liebert XDP consists of a cabinet that includes a heat exchanger, circulating pump(s), control
valve, receiver, controls, valves and piping.
The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the
refrigerant being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are
automatic.
Figure 2Liebert XDP components
Product Description
1.1.2Minimum Load
1.2Equipment Inspection
The Liebert XDP's minimum recommended operating load is 30% of system nominal capacity. The
Liebert XDP160 is rated for 160kW (546,000BTU/H) of cooling, therefore the system's minimum
recommended load is 48kW (163,800BTU/H). Loading below this value can unfavorably affect system
operation. Consult the factory for any loading below this recommendation.
To achieve the minimum recommended load, the capacity of all connected modules must total at least
48kW (163,800BTU/H). See
Table 1Number of Liebert XD cooling modules required to achieve at least 48kW
(163,800
BTU/H) load
Number of Liebert XD
cooling modules required
to achieve at least 48kW
(163,800BTU/H) load
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be
immediately reported to the carrier and a damage claim filed with a copy sent to Emerson and to your
sales representative.
Table 1.
Liebert XD Module Type
XDCF10XDV8XDV10XDO16XDO20XDH20XDH32XDR20
56533323
3
1.3Equipment Handling
!
!
WARNING
Risk of unit falling over. Can cause injury or death.
The Liebert XDP is top-heavy. Use extreme caution and care when moving and installing this
unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified
rating organization. See Table 15 for unit weights. Unit weights are specified in section 9.0
Personnel should be properly trained and certified to move and rig equipment
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for
installation.
1.3.1Handling the Liebert XDP While it is on Skid and Packaged
• Always keep the unit upright, indoors and protected from damage.
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In
either case, do NOT press on the top edges of the packaging.
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance
to still fit under the skid.
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than
6"
(152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care
must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift
point of the unit.
Product Description
NOTICE
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard
doorway. Any attempt to move the unit, while skidded, through a standard doorway will
cause damage to the unit and to the building.
NOTICE
Risk of damage from forklift. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to
prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert XDP upright, indoors and protected from dampness, freezing temperatures
and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that
the straps are not tightened to a point of damaging panels.
1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and
side packaging planks.
2. Remove and set aside filter dryer kit.
3. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The
bag may remain in place for dust and panel protection or removed for immediate unit installation.
4. Remove the bag from the unit when ready to remove the skid for installation.
Figure 3Unpacking the Liebert XDP
Product Description
1.3.3Removing the Unit from the Skid Using a Forklift
1. Align the forklift with either the front or rear side of the unit.
Make sure the tines of the forklift are locked to the widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be
equally spaced on either side of the center of gravity indicator.
2. Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without
damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
5
Figure 4Use a forklift to remove the Liebert XDP from the skid
Fit the forklift tines under the Liebert XDP.
Move the forklift forward
until the tines are fully
under the unit.
The forklift tines
must be equally
spaced on either
side of the center of
gravity indicator.
1.3.4Removing the Unit from the Skid using Rigging
1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally
spaced on either side of the center of gravity indicator. Refer to
2. Place slings under the unit using spaces provided between the skid deck boards.
Product Description
Figure 5.
NOTE
Unit is shown without outer packaging. These instructions may be applied with the outer
packaging in place.
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings.
NOTE
If rigging is to be used to move the unit closer to the site for installation, place one or two
horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the
unit.
7. Remove the skid from under the unit.
6
Figure 5Removing the unit from the skid using rigging
Equally
Spaced
Equally
Spaced
Center of
Gravity
Symbols
Spreader
Bars
Lag
Bolts
Bracket
If rigging will be used
to transport the
Liebert XDP, place one
or two horizontal
straps around the unit
and the vertical staps
about this height.
Cushioning material
not shown for clarity.
Product Description
1.3.5Moving the Liebert XDP Using Piano Jacks
1. Elevate the Liebert XDP with a lifting mechanism, such as a forklift or rigging.
2. Position one piano jack at each end of the Liebert XDP.
3. Lower the unit to a height suitable for placing it on the piano jacks.
4. Put protective material between the Liebert XDP and the piano jacks and straps.
5. Secure the Liebert XDP to the piano jacks.
6. Release the the Liebert XDP from the straps securing it to the lifting mechanism and move the
mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
7
Figure 6Securing the Liebert XDP to piano jacks
Using a forklift to put a
Liebert XDP on piano jacks
Using rigging to put a
Liebert XDP on piano jacks
Liebert XDP Secured
to piano jacks
Product Description
1.3.6Removing the Unit from the Piano Jacks
1. Lower the Liebert XDP as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert XDP off one piano jack with a pry bar or similar device, taking care not
to damage the unit’s cabinet.
4. Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert XDP.
5. Remove all material used to protect the unit from the piano jacks and strapping.
8
2.0INSTALLATION
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN001598
Pg. 2, Rev. 7
D
Unit Base
E
Unit Base
F
Height
of Unit
11"
(279mm)
5"
(127mm)
1" (25mm)
2-3/8"
(60mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.
2.1Mechanical Considerations
2.1.1Positioning the Liebert XDP
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at
least 3
For additional technical information, refer to the System Design and Configuration Document for the
Liebert XD
www.liebert.com, as well as from your local Emerson representative.
Figure 7Dimensions
feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
™
System, SL-16655. The document is available in electronic format at Liebert’s Web site,
To first cooling module
or bypass flow controller **
Installation
Close this
valve during
normal
operation
A - Return from Liebert XD
Cooling Modules
17-1/4"
(438mm)
10" (254mm)
19"
(483mm)
16-1/8"
(409.6mm)
Install replaceable filter dryer assembly
in liquid supply line B.
* Orientation
determined
by installer.
B - Supply to Liebert XD Cooling Modules
Emerson recommends field-installation
of shutoff valves at these points to permit
isolating the Liebert XDP for maintenance
Dimensions are
approximate
and subject to change
without notice.
* Allow 8" (204mm) clearance for filter replacement.
** To ensure ensure all refrigerant flow is filtered,
install the filter dryer assembly between the discharge
line of the Liebert XDP and the first bypass flow controlle
or the first Liebert XD cooling module.
D - Chilled Water Return
To Chilled Water Source
Table 3Unit piping outlet connection sizes, inches, OD Cu
ModelPipe Connection Point
50/60 HzABCD
XDP1602-1/8 1-1/8 2-5/8 2-5/8
2.2Electrical Considerations
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated
on the Liebert XDP’s rating plate. The unit must be installed in accordance with national wiring
regulations.
Connect cables for high voltage supply to the electrical box in the Liebert XDP according to Figure 11
and make sure that the phases are correctly connected.
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit.
C - Chilled Water Supply
From Chilled Water Source
10
DPN001598
Pg. 3, Rev. 7
!
WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment
damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp
edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.
2.2.1Connecting High-Voltage Cables
1. Turn the Liebert XDP’s disconnect switch to the Off position (see Figure 9). Open the front doors
and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Figure 9Front view of Liebert XDP and electrical enclosure
Enclosure Cover Latch
Hazardous Volatge
Enclosure Cover
Installation
2. Determine which knockouts in the electrical enclosure will be used and remove them (see
Figure 10).
11
Figure 10 Electrical enclosure knockout location for hazardous voltage wiring
XDP Input Power
Knockout
Enclosure Cover
Not Shown for Clarity
Customer
Power
Connection
Ground
Lug
Fused
Disconnect
Fuse
Blocks
Fuse
Block
Power Block
Pump
Contactors
Transformer 2
(Supplied on 460V
Units Only)
Transformer 6
Transformer 1
Installation
Figure 11 High voltage connections—60Hz
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see
Figure 10) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12). Observe proper
phasing.
4. Connect the ground wire to the ground lug (see Figures 11 and 12), which is in the middle left of
the enclosure.
12
Figure 12 High voltage connections—50Hz
Busbar
Customer Power
Connection
Pump Circuit
Breakers
Pump Contactors
Ground Lug
Disconnect Switch
Transformer 1
Power Block
Transformer 2
Transformer 6
Fuse Blocks
Liebert XD Module Condensate
Connections (optional; depends
on features supplied with
Liebert XD Module)
User Interface Wiring
Temperature/Humidity
Sensor Wiring
Alternate Knockout
for Temperature/Humidity
Sensor Wiring
Enclosure Cover Not Shown for Clarity
2.2.2Extra Low Voltage (ELV) Connections
Extra Low Voltage power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this
equipment (refer to
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.
Figure 13).
Installation
Figure 13 Electrical enclosure knockout locations for Extra Low Voltage
13
Figure 14 Connecting the remote temperature/humidity sensors
P66
Cooling Module
P3P1
See Note 8
Liebert XD
P66 P67
See
Note 4
CAN
Cable
See Note 4
P66P64
P67
CAN Ground
Coupler
Termination
Plug
See Note 8
P2P4
CAN Iso
Adapter
P67
CAN Ground
Coupler
See Note 5
P66
P66
Cooling Module
See Note 5
P67
Liebert XD
Installation
P67
Unit Display
(Rear View)
See
Note 9
Red Crossover
Ethernet Cable
T1 Unit Control
Crossover Coupler
See Note 6
See Note 3
E5
P67
Not
Used
P63
P64
P61
Liebert IntelliSlot 1
P1
P2
Liebert IntelliSlot
Power Supply
Liebert IntelliSlot 2
Ribbon
Cables
P65
P3
Cable A
77
See
Note 2
Cable B
78
P65
P18
Liebert iCOM Microprocessor
and I/O Board
P40
P8
P32
1. See unit electrical schematic, installation and user manuals.
2. Cables “A” and “B” provided with each unit. Only one is used as follows:
Liebert IntelliSlot-based communications - Cable “A” is preconnected to P65
on microprocessor and input/output board and P65 on Liebert IntelliSlot
power supply non-Liebert IntelliSlot-based communications - Vable “B” is
pre-connected to Terminals 77 and 78 but must be exchanged with Cable “A”
at P65 on the microprocessor and input/output board.
3. Install applicable Liebert IntelliSlot cards.
4. Both cables (P64 and P66) are required.
5. It is not necessary to connect ground coupling on end of cable connected
to Sensor “A” or Sensor “B.”
302211
Rev. 2
Remote T/H Sensor BRemote T/H Sensor A
See Note 7
T6 Isolation
Transformer
24VAC Nominal
Transformer
P41
P13
P11
P7
P12
1
2
3
P66
P78
OFF ON
SW
2
21436
5
P68
P43
P4
E4
E3
E2
E1
TB1
P54
P51
E1
P24
Control
Fuse
Board
P45
P4
See Table for
Plug Assignments
P34
P33
P35
P36
P22 P38 P39 P53 P52
6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug
the red cable from P64 on the microprocessor and input/output board
and connect to one side of the crossover coupler. The first customer
connection point is to P64 on the microprocessor and input/output board.
The second customer connection point is to the other side of the crossover
coupler. This connects the microprocessor and input/output board and
display to the private U2U network.
7. The remote sensors are interchangeable as to which connects to the
Liebert XD cooling module and which connects to P2 on CAN Iso.
8. Field-install cables with factory-installed ferrite beads (when provided,
typical two places). Each cable must make three passes through the ferrite
bead. Locate the ferrite bead on top of the electric box. See instruction
sheet provided with the cable assembly.
9. Factory-installed ferrite bead (when provided). Cable passes through
ferrite bead three times
14
2.2.3DIP Switch and Jumper Settings for Remote Sensors
P68
135
246
SW2
MICROPROCESSOR AND I/O BOARD
REMOTE T/HSENSOR “A”REMOTE T/H SENSOR “B”
SW1SW1
OFF
ON
OFF
ON
Jumper
on 1-2
1
2
3
P78
DIP
Switches
ON
1
3
4
9
10
OFF
2
5
6
7
8
Jumpers
on 1-2, 5-6
OFF ON
1
2
3
4
5
6
7
8
9
10
DIP
Switches
ON
None
OFF
1
2
3
4
5
6
7
8
1
2
3
P78
UNIT DISPLAY
Jumper on 1-2
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
DIP
Switches
ON
1
5
OFF
2
3
4
6
7
8
DIP
Switches
ON
2
5
OFF
1
3
4
6
7
8
SW3
1
2
3
4
5
6
7
8
OFF ON
P3
321
Jumper
on 2-3
P3
321
Jumper
on 2-3
302211
Rev. 2
302211
Rev. 2
Te rm i n at i on
Plug
Liebert iCOM
Microprocessor
& I/O Board
Customer
Connection
Points
Crossover
Coupler
Red Crossover
Ethernet Cable
Straight Through
Ethernet Cables
U2U Networking Switch
(Field Supplied)
Unit Display (Rear View)
Not
Used
P64
P66
P64
P66P67
To / From Other
Networked Units
CAN Cable
See Note 1
P65
E5
P61
P63
P11 P13
P7
P12
P67
1. Both cables (P64 and P66) are required.
2. A crossover coupler is provided for unit-to-unit (U2U)
networking. Unplug the red cable from P64 on the
microprocessor and I/O board and connect to one side
of the crossover coupler. The first customer connection
point is to P64 on the microprocessor and I/O board.
The second customer connection point is to the other
side of the crossover coupler. This connects the
microprocessor and I/O board and display to the
private U2U network.
The Liebert XDP is shipped with jumpers and DIP switch settings for normal operation. See
Figure 15.
Figure 15 DIP switch and jumper settings
Installation
Figure 16 Unit-to-unit networking connections
15
2.3Field Connections—Optional for All Units
1
1
2
P67
P64 P66 P67
To Remote T/H Sensor A
Termination Plug
To P66 on Liebert iCOM
Control Board
To P64 on Liebert iCOM
Control Board
Red Ethernet Cable
To Liebert XD Cooling
Module(s) and Remote
T/H Sensor B
To Optional
External
Connections
UNIT DISPLAY (Rear View)
Factory-Wired
Temperature Sensor
Control wiring must be Class 2 and installed in
accordance with the National Electrical Code (NEC).
Requires shielded cable.
NOTES:
DPN001598
Pg. 6, Rev. 7
Do Not
Use
• Connect field wiring from the optional Liebert XD cooling module condensation detection circuit
to terminal strip locations COMM. (24) and H2O (51).
• Connect optional field wiring from remote devices to remote alarm device, common alarm outputs,
site monitor and remote shutdown, if applicable. See terminal strip descriptions in
Figure 17 Liebert XDP extra low voltage field connections points
Installation
Figure 17.
16
2.4Remote Sensor Installation—Proper Placement
Placement of the two remote temperature/humidity sensors is critical to effective cooling of the
conditioned space.
The remote sensors must be installed in areas where conditions are representative of the space
conditioned by the Liebert XDP. Emerson recommends installing the sensors in different areas near
the cooling modules served by the Liebert XDP. If the return air side of the primary air mover, such
as a Liebert DS, represents the conditions where the Liebert XD cooling modules are located, one
sensor could be placed there. Emerson suggests placing the other sensor on the wall opposite the heat
load area (see
Do not install the sensors where ambient air might cause false readings, for example, near unsealed
doors or windows, or areas with stagnant air.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable;
each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14).
3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM input/output board inside
the Liebert XDP. Secure the ring terminal on the cable shield to the electric box adjacent to P67
(see
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14).
5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the
ring terminal on the cable shield to the grounding screw adjacent to P67.
Figure 18 for guidance).
Figure 14).
Installation
Figure 18 Suggested remote sensor placement
17
3.0PIPING
3.1European Union Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection
systems in the European Community market and operating with fluorinated greenhouse gases (fgas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (Fgas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the
atmosphere.
The F-Gas Regulation requires operators to use all measures that are technically feasible and do not
entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to
recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.
3.2Connection Sizes
The copper pipe connections on the Liebert XDP are:
Building Chilled Water Supply2-5/8" OD
Building Chilled Water Return2-5/8" OD
Refrigerant Supply1-1/8" OD
Refrigerant Return2-1/8" OD
Piping
3.2.1Recommended Pipe Size
Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to
site specific documentation and the configuration guide for the Liebert XD system.
Elbows and restrictions must be minimized to get good fluid flow.
Table 4Supply, return pipe sizes for refrigerant loop
Pipe FunctionSize / Equivalent Pipe Length
Liebert XDP supply line, from Liebert XDP supply
to farthest Liebert XD cooling module
Liebert XDP return line, from farthest Liebert XD cooling
module to Liebert XDP return
From any model Liebert XDO/Liebert XDH supply
to supply line of Liebert XDP
From any model Liebert XDO/Liebert XDH return
to return line of Liebert XDP
From any model Liebert XDV/Liebert XDCF supply
to supply line of Liebert XDP
From any model Liebert XDV/Liebert XDCF return
to return line of Liebert XDP
1-1/8" OD for lengths up to 60 feet
1-3/8" OD for lengths over 60 but less than 175 feet
2-1/8" OD for lengths up to 60 feet
2-5/8" OD for lengths over 60 but less than 175 feet
1/2" OD for lengths up to 10 feet
7/8" OD for lengths over 10 but less than 25 feet
7/8" OD for lengths up to 10 feet
1-1/8" OD for lengths over 10 but less than 25 feet
1/2" OD for lengths up to 10 feet
5/8" OD for lengths over 10 but less than 35 feet
5/8" OD for lengths up to 10 feet
7/8" OD for lengths over 10 but less than 35 feet
18
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.