Precision Cooling
For Business-Critical Continuity™
Liebert® XDP
User Manual–50-60 Hz; 160kW Nominal Capacity
™
GENERAL SAFETY GUIDELINES
!
!
R
Pump
Redundancy
XDP160–1
Pumping
unit
Revision
level
Liebert
X-treme heat
Density system
160kW
nominal
capacity
Place holder
Example: XDP160A– –1
A
A = 460V-3ph-60Hz
(voltage-phase-frequency)
C = 208V-3ph-60Hz
M = 380/415-3ph-50Hz
–
Place holder
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect local and remote power supplies before working within.
Before proceeding with installation of the XDP, read all instructions, verify that all the parts
are included and check the nameplate to be sure the XDP voltage matches the available
utility power.
Follow all applicable codes.
WARNING
Risk of unit falling over. Can cause death, injury or property damage. The XDP is top-heavy.
Use extreme caution and care when moving and installing this unit.
NOTE
This document is intended to be be used together with site specific documentation and
documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Before any action that could cause a disturbance in the XD system’s cooling function is begun,
the facility manager MUST be informed. In addition, after the action is taken and the work is
finished, the facility manager MUST be informed.
NOTICE
Risk of piping and component rupture. May cause injury or equipment damage.
Do not close service valves without following recommended procedures for repair,
maintenance and replacement of components. Closing service valves may isolate liquid
refrigerant, causing high pressure and rupture of piping. Install pressure relief valves in field
piping that may become isolated by service valves.
Figure iModel number nomenclature
Fluorinated Greenhouse Gas Requirements—European Union
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-gas),
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation also requires operators to use use all measures that are technically feasible
and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly
and to recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system
and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant
to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP consists
of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls,
valves and piping.
The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the refrigerant being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are
automatic.
The Liebert XDP’s minimum recommended operating load is 20% of system nominal capacity. For
example, a Liebert XDP160 60Hz system’s minimum load would be 32 kW. Loading below this value
can unfavorably affect system operation. Consult factory for any loading below this recommendation.
The Liebert XDP is rated for 160kW (546,000 BTU/H) of cooling.
Figure 1Liebert XDP components
Product Description
1.2Equipment Inspection
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be
immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your
sales representative.
1
1.3Equipment Handling
!
!
Remove these 2
tie-down brackets
Remove these 4 lag bolts
to free deck boards
Remove these 4 lag bolts
to free deck boards
WARNING
Risk of unit falling over. Can cause injury or death.
The Liebert XDP is top-heavy. Use extreme caution and care when moving and installing this
unit.
NOTE
Personnel should be properly trained and certified to move and rig equipment.
1.3.1Handling With Skid
• Always keep the unit upright, indoors and protected from damage.
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In
either case, do NOT press on the top edges of the packaging.
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance
to still fit under the skid.
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than
6" (152mm) off the ground. If circumstances require the unit to be lifted higher than 6" (152mm),
great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m)
from the lift point of the unit.
CAUTION
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard
doorway. Any attempt to move the unit, while skidded, through a standard doorway will
cause damage to the unit and to the building.
Product Description
1.3.2Removal from Skid
Liebert recommends using dual hand trucks or a similar method to remove the Liebert XDP from the
skid. This is to ensure that both ends of the unit are firmly secure and to provide a good means of unit
mobility.
1. Always keep the unit upright, indoors and protected from possible damage.
2. Remove the exterior packaging. Leave the plastic bag over the Liebert XDP until the unit has
been moved to its final location. The bag will protect the painted panels against scuffing.
3. Remove two (2) corner tie-down brackets from one side of the unit, on a non-runner notch side of
the pallet. Remove eight (8) lag bolts from two (2) end deck boards on the same end where the
tie-down brackets were removed (refer to Figure 2).
Figure 2Tie-down brackets and lag bolts to be removed
2
4. Remove the two (2) end deck boards from one end of the pallet and the attached, notched section
... and center runner sections
from one end of pallet.
Remove two deck boards ...
Piano jack
Strap secures the
Liebert XDP to the jack
Place cushioning material
between the forks and the Liebert
XDP to protect unit’s finish
(cushion not shown for clarity)
Piano jack’s forks should be
snug against the Liebert XDP
Remaining 6 lag bolts
to remove
of the center runners (refer to Figure 3).
Figure 3Removing pallet boards for piano jack insertion
5. Place a piano jack with its forks snugly against the bottom of the unit and strap the Liebert XDP
securely to the jack (refer to Figure 4).
NOTE
Place a mover’s blanket or other cushioning material between the piano jack and the
unit’s side panels.
Figure 4Liebert XDP strapped to piano jack
Product Description
6. Repeat Steps 2, 4 and 5 for the opposite side of the unit. When these steps have been completed,
the Liebert XDP will be supported by two piano jacks, one on either side.
7. Remove all of the remaining lag bolts from one (1) of the pallet’s outside runners (see Figure 5).
Figure 5Remove remaining lag bolts from one runner
3
8. Remove the runner from which all lag bolts have been removed (refer to Figure 6).
Slide this runner away
from the Liebert XDP
Slide the remaining part of the pallet
from under the Liebert XDP so the unit
may be moved on the piano jacks.
Figure 6Remove runner from pallet
9. Using the pallet jacks, raise the secured unit to the highest point that the piano jacks will allow.
Once the unit has been raised, slide the remainder of the pallet from under the Liebert XDP (see
Figure 7). Lower the Liebert XDP so that its base is approximately 1" (25.4mm) off the ground.
Figure 7Sliding pallet from under Liebert XDP
Product Description
1.3.3Removing Piano Jacks
Once the unit has been moved to the installation location, Emerson Network Power recommends the
following method to remove the piano jacks:
1. Lower the unit as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Remove all cushioning material used to protect the unit from the straps and the piano jacks.
4. Use a pry bar or other lever to lift one side of the Liebert XDP enough to allow removal of the
piano jack.
5. Repeat Step 4 to remove the piano jack on the opposite side.
6. Remove the plastic bag.
4
1.4Mechanical Considerations
1.4.1Positioning the Liebert XDP
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at
least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
For additional technical information, refer to the System Design and Configuration Document for the
Liebert XD
www.liebert.com, as well as from your local Emerson Network Power representative.
Figure 8Dimensions
™
System, SL-16655. The document is available in electronic format at Liebert’s Web site,