Precision Cooling
For Business-Critical Continuity™
Liebert XDK™ Rack Enclosure With Integrated Water-Based Cooling
User Manual–17kW
Page 2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Liebert engineers will provide comprehensive support on how to install the XDK.
Extensive material, function and quality checks ensure that you fully benefit from product functions
and a long service life. Nevertheless, this product can produce hazards if it is used incorrectly by
untrained personnel or is not used for the correct purpose.
Read these operating instructions carefully before commissioning the XDK.
The electrical equipment complies with the applicable VDE and accident prevention regulations. Hazardous voltages (higher than 50 VAC or higher than 100 VDC) are present:
• inside the electric box in the unit's housing
• behind the fan cover on the outside of the rear door
Shut down the unit immediately if there are problems with electrical input or cold water supply.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
Only qualified personnel may perform repair, maintenance, and cleaning operations.
NOTE
Cleaning and servicing must be performed by qualified personnel. To ensure that the unit
remains safe to use and has a long service life, observe the maintenance and cleaning intervals.
Operate the XDK correctly within the stipulated ratings and with approved equipment.
During all work on and with the unit, observe:
• All applicable regulations (e. g., VDE regulations and other applicable national regulations)
• All applicable accident prevention instructions (BGV)
• All applicable laws on environmental protection
Operate the XDK only if it is in proper working condition. If a malfunction or fault occurs, you must
shut down the unit immediately and notify the responsible facility official or employee.
Resume operating the unit only after the malfunction or fault has been rectified and the XDK’s function has been re-established.
CAUTION
!
Risk of contact with hot surfaces. Can cause burn injury.
Fans, power supplies, PC boards, and other components become extremely hot during unit
operation. Allow sufficient time for them to cool before working within the unit.
Use extreme caution and wear protective gloves and arm protection when working on or near
The Liebert XDK provides the dissipation of heat loads up to 17kW.
The server rack is closed to the installation area, that means no heat load will dissipate to the environment. (see also chapter 2.) The cooling is provided by a closed cooling system via an air-to-water
heat exchanger. The cooling capacity adapts to the heat load.
19" (483mm) rails are designed for components as well as rails and shelves.
Cable entry is possible from the bottom and from the top.
Introduction
1
Page 6
2.0OPERATING CONDITIONS
2.1Proper Application
The XDK is a water-cooled enclosure and is intended for removing heat from electronic equipment
inside the cabinet. The cooling system in the cabinet is thermally independent of the room air. Water
is used to cool equipment installed in the XDK. No additional cooling of the server room is required.
NOTE
Under certain conditions, a small amount of heat, (approximately 0.5kW), can escape into the
room.
CAUTION
!
Risk of improper operation. Can cause equipment damage. For reliable function of the XDK,
cold water must be available in the correct amount, and at the correct temperature and
pressure. Observe water quality specified in VGB-R 455 P. (see 8.0 - Water Purity Requirements ).
Table 1General operating data
Ambient temperature
Absolute humidity in the installation location8g H
Water temperature, supply54°F (12°C); other temperatures upon request
Water temperature, return64°F (18°C); other temperatures upon request
Water connectionfrom below
Condensed water connectionfrom below
Nominal voltage200V to 264V (50Hz and 60 Hz)
Maximum operating pressure145 PSI (10 bar)
50°F to 95°F (10°C to 35°C)
(other temperatures upon request)
O/ kg air maximum
2
Operating Conditions
2
Page 7
3.0DESCRIPTION
3.1General function
The modular design facilitates the installation of 19-inch-wide equipment of varying depth.
Heat produced by equipment in the cabinet, such as servers, is removed by the cold water system
integrated into the server cabinet. The cooling system is isolated from the server area, protecting the
sensitive equipment from water damage.
The cooling system comprises a high-performance air/water heat exchanger, fans with fan control
unit, fan-speed according to heat load.
The air circuit is closed such that no heat is emitted to the environment.
CAUTION
!
Risk of improper operation. Can cause equipment damage.
The XDK works only if cold server feed air and heated server outlet air are fully separated.
Height units not in use must be sealed with blanking panels.
Figure 1Cooling airflow, top view
Description
Air Duct
WarmWarm
WarmWarm
Server
Cold
Air
Separation
Cold
Front
3
Page 8
3.2Principle of Cooling Operation
Figure 2Cooling airflow, side view
Fan
Bank
Description
Rear
of
XDK
19" Equipment
Front
of
XDK
Air / Water
Heat Exchanger
Cold Water Supply
Side of XDK
Air that has been heated by the servers to 95°F (35°C), for example, is circulated to a specially
designed air/water heat exchanger by high-performance fans. The heated air is cooled to 68-77°F
(20-25°C) and fed to the front of the server.
The server fans can draw in the air and feed it over internal components.
Cold water is provided by a separate Liebert XD Pumping unit.
A condensate tray with a 5/8" outlet is below the heat exchanger.
NOTE
If the rear door (with fans) is opened, the front door must be opened. If the front door is opened,
it is not necessary to open the rear door.
4
Page 9
Table 2Technical data
Housing materialAluminium sheet, sheet steel, galvanized and coated
Operating Temperature range50°F to 95°F (10°C to 35°C)
Abs. atmospheric humidity8g / kg maximum
Temperature difference across serverapprox. 15K
Cold Water
Cooling capacity17kW
Supply temperature54°F (12°C) (other temperatures upon consultation)
Return temperature64°F to 72°F (18°C to 22°C) (other temperatures upon consultation)
Max. operating pressure145 PSI (10 bar)
Water supply connection1"
3.2.1Data Overview—XDK
Table 3XDK general data
Nominal Cooling Capacity17kW @ 54°F (12°C) EFT
Height, in (mm)86.6 (2200)
Width, in (mm)31.5 (800)
Depth, in (mm)47 (1200)
Usable Height for Electronic
Equipment
Maximum Electronic
Equipment Depth, in (mm)
Electronic Equipment
Air Temperature, In/Out, °F (°C)
Weight, Empty, lb (kg)683 (310)
Maximum Weight, Filled 2,800 (1310)
Maximum Operating
Water Pressure, psi (bar)
Water Flow Rate, GPM (m
Water Pressure Drop, psi (bar)10 (0.7)
Water Connections, in1
Maximum Air Flow, CFM ( m
Sound Pressure Level 55 dB(A) at 3 ft (1m)
Input Voltage200-264 V, 1 ph, 50/60 Hz
Maximum Power Draw1400W
OptionsLeveling Feet or Casters
Noise level55 dB(A) sound pressure at a distance of 3 ft. (1m)
Useful load2204 lb (1000kg)
40 U
29 (740)
68/98 (20/37
145 (10)
3
/h) 10.7 (2.44)
3
/h)1800 (3,100)
Description
5
Page 10
3.3Control
The server cabinet temperature is controlled by the fan control board
A temperature sensor continuously measures the temperature of the server cabinet (server feed air).
The air circulation flow rate is controlled by the fan speed according to the current thermal load.
At temperatures lower than 70°F (21°C) fans rotate at 75% of maximum speed.
Between 68°F and 73°F (20 and 23°C), speed increases proportionally to the temperature up to 96% of
maximum speed.
The failure of the temperature sensor set the fans to maximum speed.
The water flow rate is controlled by a three-way valve depending on thermal load. In case of failure,
the valve opens and the all the chilled water flows through the heat exchanger.
From 61°F to 66°F (16°C to 19°C), the three-way valve controls the water flow rate from 0% to 100% of
the nominal flow rate.
The programming of the control is factory-set and protected with a password.
The failure of the temperature sensor or one of the fans will set off an alarm using a potential free
contact.
The outgoing alarms with potential free contact are:
• sensor error
• fan malfunction
• high-temperature / low-temperature
Description
The fans are automatically shut down if the server cabinet rear door is opened.
3.4Automatic Door Opening
Figure 3XDK door and automatic opening mechanism
Upper magnet
and retaining
plate
Gas pressure spring
6
Page 11
3.4.1Function
Front and rear door are kept closed with two electromagnets. The door will be pushed open smoothly
by a gas pressure spring if power to the electromagnets fails.
If the doors are opened, the thermal load can escape into the room, preventing the servers from overheating.
The inflow of air with water droplets can also be prevented (Door opening due to humidity alarm).
When the rear door is opened, the fans shut down automatically.
Figure 4Door locking mechanisms, opening switch
Description
Upper and lower
transport-lock
screw
3.4.2Initial Commissioning:
___ 1. Loosen the upper and lower transport lock screw
___ 2. Connect inlet power to the power supply (See 3.4.3 - Manual Closing.)
Door opening switch
with LED (green)
NOTE
If the power supply fails during initial commissioning, the front door opens automatically. If
the transport lock screws are reinstalled, both transport lock screws must be reinserted or the
door could be damaged
7
Page 12
3.4.3Manual Closing
1. Press LED switch for electromagnet activation
2. The LED lights up
3. Push door evenly shut. Both magnetic locks must latch.
3.4.4Manual Opening
1. Press LED switch - green LED doesn’t light
2. Rack door opens itself
Description
8
Page 13
Equipment Inspection, Handling And Storage
4.0EQUIPMENT INSPECTION, HANDLING AND STORAGE
Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the bill of
lading. Inspect all items for damage, either visible or concealed. Damage should be immediately
reported to the carrier and a damage claim filed with a copy sent to your local sales representative.
4.1Packaging Material
All material used to package this unit is recyclable. Please save for future use or
dispose of the material appropriately.
SAFETY INFORMATION
WARNING
!
Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or
death! Read all of the following instructions before attempting to move, lift, remove packaging
from or preparing unit for installation.
WARNING
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and
glasses should attempt to move, lift, remove packaging from or prepare unit for installation.
R
CAUTION
!
Risk of overhead interference. Can cause unit and/or structure damage.
Refer to the installation plans prior to moving the unit to verify clearances.
CAUTION
!
Risk of damage from fork lift! Improper handling with the forklift can cause exterior and/or
underside damage! Keep tines of the fork lift level and at a height suitable to fit below the
skid.
4.2Handling
When possible, transport the unit using a forklift or pallet jack. Otherwise use a crane with belts or
cables.
• When using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest
allowable distance that will fit under the skid.
• Ensure that the fork length is suitable for the unit length.
• When using a forklift while moving the packaged XDK, do not lift it higher than 6" (152mm).
• If circumstances require the XDK to be lifted higher than 6" (152mm), great care must be exercised. Personnel not involved in moving the unit must be at least 20' (5m) from the lift point of the
unit.
• Belts or cables must be used when the XDK is moved with a crane.
• The XDK’s net weight is 749 lb. (340 kg).
• Avoid twisting the housing or other damage during handling.
• Ensure that the XDK’s doors are closed prior to lifting.
• Do not stand under an XDK while it is suspended.
• Hooks used to attach to the unit must be of appropriate tensile strength.
• The XDK must not be lifted at an angle.
9
Page 14
4.3Storage
• If the XDK’s packaging has been removed, cover it with tarpaulins to protect against particulates,
such as sand and dust, and from moisture.
• Keep storage temperature between -22°F and 104°F (-30°C and +40°C).
• The heat exchanger must be completely drained to prevent the risk of freezing damage.
• When stored for more than 12 months, turn fans by hand to check the fan bearings prior to installation.
4.4Returning the Unit in Case of Damage
If the XDK is not returned in its original packaging, the packaging used for return must comply with
the following:
• There must be at least 1-3/16" (30mm) space between the unit and the packaging.
• Footprint of the skid shall extend at least 2-1/2" (64mm) from the perimeter of the unit.
• The XDK must be attached to the skid using original metal brackets or steel banding.
If steel banding is used to hold unit to the skid, place reinforced protective material between the
banding and the XDK.
• Ensure proper shipping information is affixed to the exterior of the packaging.
Equipment Inspection, Handling And Storage
10
Page 15
5.0INSTALLATIONAND COMMISSIONING
5.1Preparation for Installation
CAUTION
!
Risk of improper installation. Can cause equipment damage.
Before installing the unit, a number of points must be checked for safety and to ensure the
correct function of the server cabinet. Take care when performing these checks to ensure that
the unit functions correctly.
CAUTION
!
Risk of improper installation. Can cause equipment damage.
The XDK must be installed on a level surface. For this reason, check the horizontal alignment
with a spirit level prior to starting installation. The floor must be able to support a rack load
of 307 lb/ft² (1500 kg/m²) (with installed equipment per XDK).
To achieve good air circulation, ensure that there is no packaging material or other equipment that
could hinder or prevent air circulation in the area of the equipment, in the area of the heat exchanger,
in the air inlet or in the air outlet.
5.2Positioning the XDK
Installation and Commissioning
After positioning, the XDK’s feet must be adjusted to make the cabinet vertical. When positioned the
doors must close easily.
5.2.1Remove Recirculation Air Duct Transport Lock
The Liebert XDK is shipped without the gas pressure springs for the front and rear automatic door
openers installed. The springs should be installed according to separate instructions before the Liebert XDK is connected and turned on.
After positioning, remove the transport lock screws at the sides of the recirculation air duct (see
Figure 5).
The recirculation air duct may be pulled out to remove items that fall into the heat exchanger tray.
Figure 5Remove the transport lock screws
Remove both screws
11
Page 16
5.3Water Connection
The heat exchanger can be pulled out for servicing
Water pipes should be connected so that the heat exchanger can be pulled out when the connection is
undone. If the heat exchanger is connected to the water circuit using threaded fittings, the pipe fitting
must be supported on tightening.
Before commissioning the server cabinet, the pipe connections should be checked for leaks according
to local codes.
5.3.1Preparing Heat Exchanger for Initial Commissioning
Check the mechanical installation and the supply pipe connection.
Figure 6Heat exchanger access
Remove this air duct
for bleeding, draining the
heat exchanger and
checking the valve
Installation and Commissioning
1. Carefully bleed heat exchanger when filling the system.
2. Open the air bleed valve until the water coming out has no bubbles.
3. Close this valve after bleeding.
Figure 7Control valve
Water return
Water supply
4. If necessary, retighten threaded fittings.
5. After an extended period without use, and particularly in case of risk of freezing temperatures,
the heat exchanger and the supply pipe must be drained of all fluid.
6. Drain completely by blowing out with compressed air and remove all bleed and drain plugs.
Air bleed valve
Drain valve
12
Page 17
Figure 8Heat exchanger
(850mm)
33-7/16"
27-3/8"
(695mm)
2"
(50mm)
Top View
Installation and Commissioning
Space
for
Cabling
9- 7/ 8"
(150mm)
2"
(50mm)
Figure 9Heat exchanger connection
Water return
Water supply
Liebert recommends insulating the cold water pipes with waterproof insulation to prevent condensation and losses.
13
Page 18
Figure 10 Bottom plate with cutouts
Installation and Commissioning
Network
Cable
Entry
Condensed
Water Cutouts
Front
Cable and pipe openings must be sealed air-tight on completion of work.
5.4Condensed Water Connection
If the XDK is operated below dew point, condensed water may occur. As standard there is a water connection, 5/8" diameter, in the condensed water tray for drainage.
Sealed Cable Cutout
Rear
Cutout for
Water Pipes
Preparations for Connecting
Step 1):
Remove
the air
duct
Step 2):
Remove
the cap
Condensate
connection
Step 3.)
Connect the
nipple with a drain
hose 5/8"
Step 4.)
Move and snap the
nipple with hose
into the hole
When connecting to the condensate tray, ensure that the condensed water pipe is connected to a selffilling siphon with return protection and that the condensate drain is properly sloped.
The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so
that air is not drawn into or blown out of the waste pipe.
14
Page 19
The condensate drain is not pressurized; a condensate pump can be used.
5.5Electrical Connection
The wiring diagram is enclosed in the unit.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within. Prior to
beginning installation, shut down the server cabinet, disconnect it and secure it against
unauthorized startup.
As soon as all preparations for installation have been made, you can start electrical installation.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
The XDK unit must be connected by a licensed and qualified electrician only. Ensure that the
server cabinet is electrically isolated for the duration of the connection operation and is
secured against unauthorized startup
Check whether voltage and frequency at installation site as well as fuse ratings match the specifications on the rating plate.
Installation and Commissioning
To connect the unit to the power supply:
1. Shut down the server cabinet.
2. See the wiring diagram for information on the connections to be made.
3. Connect the supply cable in the computer room.
4. Check the secure connection of the earth wire.
To return the server cabinet to operation, switch on the fuse-protected power supply.
NOTE
The unit's fans will rotate clockwise.
5.6Sealing the Cabinet
To ensure the optimal cooling function the cabinet must be sealed:
• Pipe entrances should be cut into the foam and properly closed with a extra foam if required.
• Cable entrances should be closed with the pivoting plate and foamed material.
• Air flows on the warm and cold sides of the cabinet must be separated from each other.
15
Page 20
6.0SERVICINGAND MAINTENANCE
WARNING
!
Risk of high speed rotating fan blades. Can cause serious injury.
Disconnect all local and remote electric powers supplies and assure that fan blades have
stopped rotating before working within the unit.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within the unit.
CAUTION
!
Risk of explosive discharge of water under pressure. Can cause injury or equipment damage.
Shut off the water supply and relieve pressure before working with piping.
NOTE
Service and maintenance work must be performed only by properly trained personnel and in
accordance with applicable regulations as well as with manufacturers’ specifications.
NOTE
Use only original spare parts that have been tested and approved by the manufacturer. If
necessary, request a comprehensive spare parts list from the manufacturer. For cleaning, use
commercially available cleaning agents only. Follow the stipulated safety measures and do not
use any tools that may cause scratching or tools for scraping (surfaces will be irreversibly
damaged).
Servicing and Maintenance
6.1General Inspection on Fans—Annual
• Check for unusual bearing noises. (Check for excessive bearing play.)
6.1.1Fan Replacement
The expected service life is approximately 40,000 operating hours at a temperature of 40°C (104°F).
1. Remove the housing cover from the unit (with earth cable).
2. Determine which fan has failed.
3. Check the surface temperature of the fan and switch off the circuit breaker.
4. Disconnect supply cable at the fan terminal block.
5. Loosen the four fastening nuts for the fan to be replaced.
6. Remove the failed fan.
Figure 11 Replacing a fan
Step 3:
Disconnect
supply cable
at the fan
terminal
block
One of four
fastening nuts
Step 4: Undo
the four
fastening
nuts
Slot to
insert
wrench to
remove
nut
16
Page 21
Reinstall the fan by reversing the steps to remove the fan.
1. Tighten the fan fastening bolts.
2. Connect the power supply cable to the fan.
WARNING
!
Risk of electric shock. Can cause injury or death.
Reconnect the earth ground cable to the sheet metal panel to prevent a potentially hazardous
open circuit in case of loose or disconnected electrical wiring or a fan motor short circuit.
3. Switch on the circuit breaker.
4. Dispose of the old fans correctly.
6.2 Inspect the Heat Exchanger—Annual
The efficiency of heat exchangers is sharply reduced by dirt and debris; retaining high efficiency
requires regular cleaning. Use a vacuum cleaner, compressed air or a soft brush to clean the fins.
Do not bend the fins during cleaning—this will interfere with proper air flow through the unit.
• Check heat exchanger on air side for soiling, damage and corrosion.
• Check feed and return for correct function.
• If necessary clean the air side.
• Regularly check odor trap (external) for correct function.
• Heat exchanger can be pulled out for improved cleaning.
• Regularly visually inspect the water circuit for leaks.
Servicing and Maintenance
17
Page 22
6.3Replacing the Heat Exchanger
Figure 12 Heat exchanger replacement
Step 1: Lift the air
duct off the flange
to remove it.
Step 4: Remove screws
Servicing and Maintenance
Step 5: Pull
out the heat
exchanger
Step 3:
Remove condensate
connection
Reinstall the heat exchanger by reversing the reverse order of removal.
NOTE
Regularly check the condensed water drain and clean if necessary
18
Step 2:
Remove
the grounding
cable
Page 23
7.0DISMANTLINGAND DISPOSAL
The XDK may be dismantled by qualified personnel only.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within the unit.
Disconnect the unit from the external water circuit by closing the shutoff valves and drain the unit’s
water circuit.
Transport the unit as described in 4.0 - equipment Inspection, Handling And Storage, using a
lifting device with sufficient load-bearing capacity.
Dispose of the air conditioner in accordance with the locally applicable disposal and safety instructions. Liebert recommends using a specialist recycling organization.
All parts can be stripped down and consist of:
• aluminium, steel, brass, copper
• labelled plastic parts
• electronic parts
Dismantling and Disposal
19
Page 24
8.0WATER PURITY REQUIREMENTS
To ensure the maximum service life of the air/water heat exchangers, water must comply with the
VGB water regulations (VGB-R 455 P). The water used must be soft enough to prevent deposits, but it
must not be so soft that heat exchanger corrosion occurs.
The following table contains the most important impurities and methods for removing them.
Table 4Prevalent impurities and removal methods
Water ImpurityMethod of Removal
Mechanical pre-treatment (dp < 1 mm)Filtering the water
Excessive hardnessSoften the water using ion exchange
Moderate content of mechanical impurities and hardness formersAddition of dispersing or stabilizing agents
Moderate content of chemical impuritiesAddition of passivation agents and inhibitors
Biological impurities (bacteria and algae)Addition of biocides
It is recommended to achieve the following hydrological data as far as possible:
Table 5Suggested hydrologic levels
Hydrological DataSuggested
pH values7 - 8.5
Carbonate hardness>3 <8 °dH
Free carbon dioxide8 - 15mg/dm
Bound carbon dioxide8 - 15mg/dm
Aggressive carbon dioxide0mg/dm
Sulfides< 10mg/dm
Oxygen< 50mg/dm
Chloride ions< 250mg/dm
Sulfate ions< 10mg/dm
Nitrates and nitrides< 7mg/dm
CSB< 5mg/dm
Ammonia< 5mg/dm
Iron< 0.2mg/dm
Manganese< 0.2mg/dm
Conductivity< 2200μS/cm
Solid evaporation residue< 500mg/dm
Potassium permanganate consumption< 25mg/dm
Suspended matter< 3mg/dm
(Partial flow cleaning is recommended)> 3 < 15 mg/dm
(Continuous cleaning)> 15mg/dm
Water Purity Requirements
Units
Amount
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
20
Page 25
8.1Unit Installation Checklist
___ 1. Check unit for damage on delivery
___ 2. Check for level floor
___ 3. Check maximum floor load
___ 4. XDK feet adjusted, if applicable
___ 5. XDK is level
___ 6. No remains of packaging in the XDK
___ 7. All installation tools removed
___ 8. Cable entries into the unit correct and air-tight
___ 9. Cable connections checked
___ 10. Cold water connection does not leak
___ 11. Pressure test performed
___ 12. Water circuit bled
___ 13. Water flow rate adjusted
___ 14. Condensed water pipe clear
___ 15. Water system odor trap in order
___ 16. Heat exchanger tray connected to condensed water pipe
___ 17. Fan function checked
___ 18. All front panels closed (separation of air flows)
Electrical Acceptance Certificate
by Approved Staff
Comments
YesNo
.
Table 12Function check
Function of All Fans
(Air Blowing Direction)
Fans Shut Down When Rear Door
is Opened
Comments
Function Three Way ValveYesNo
Comments
Door Opens When ____ °F (°C) is
Reached
Comments
YesNo
YesNo
YesNo
24
Page 29
Table 12Function check (continued)
Malfunction Indicator FunctionYesNo
Comments
Water Purity Requirements
Condensate Occurrence at Heat
Exchanger
Comments
Pressure Test Water CircuitYes
Water Flow Rate AdjustedYesNo
Flow Rate
(Possible Only Externally)
Water Feed°F (°C)
Water Return°F (°C)
Air Temperature in the Cabinet
At The Heat Exchanger Inlet°F (°C)
Air Temperature in the Cabinet
At the Heat Exchanger Outlet°F (°C)
YesNo
GPM
Commissioning performed by day to day operating.
Correctness of function check protocol certified by:
Approved StaffDateSignature
ClientDateSignature
25
Page 30
Water Purity Requirements
26
Page 31
Page 32
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.