Liebert XDH User Manual

Precision Cooling For Business-Critical Continuity™
Liebert® XDH
User Manual - 50 & 60Hz
WARNING
!
Risk of top-heavy unit falling over. Can cause death or injury. Improper handling can cause equipment damage, injury, or death. Read all of the following
instructions before attempting to move, lift, remove packaging from the unit, or preparing unit for installation.
WARNING
!
Risk of explosive discharge. Can cause death or injury. This unit contains fluids and/or gases under high pressure. Relieve system pressure before
cutting into or disconnecting piping or piping components.
WARNING
!
Risk of high-speed moving parts. Can cause death or injury. Disconnect all local and remote electric power supplies before working in the unit.
WARNING
!
Risk of electric shock. Can cause death or injury. Disconnect both power cords from the electrical supply outlets or from the receptacles on the
back of the unit before working within.
CAUTION
!
Risk of overhead interference. Can damage unit or structure. The unit may be too tall to fit through a doorway while on the skid. Measure the unit and
doorway heights and refer to the installation plans before moving the unit to verify clearances.
CAUTION
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury. Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and
glasses should attempt to move, lift, remove packaging from, or prepare unit for installation.
CAUTION
!
Risk of improper operation and overpressurization. Can result in injury or property damage. Only qualified personnel trained in HVAC installation or service should install or service this
equipment. Read all installation, operating and safety instructions before proceeding.

Fluorinated Greenhouse Gas Requirements—European Union

Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys­tems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo­sphere.
The F-Gas Regulation also requires operators to use use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
TABLE OF CONTENTS
GENERAL SAFETY GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER
1.0 LIEBERT XDH COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATURE . . . . . . . . .1
2.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Pre-Installation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4 Parts Included With the Liebert XDH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.5 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.5.1 Room Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0 GENERAL PRODUCT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.1 Product/System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2 Checking and Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3.1 Recyclable Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3.2 Unit Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3.3 Unpacking the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3.4 Taking the Unit off the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.0 MECHANICAL CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.1 Determining Placement in the Conditioned Space. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Installing the Liebert XDH Within the Enclosure Row . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2.1 Airflow Direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.0 PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.1 European Union Fluorinated Greenhouse Gas Requirements . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 System Connection Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Connection Methods and Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4 Piping Considerations—Hard-Piped Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4.1 Venting the Holding Charge and Connecting to Mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4.2 Brazing Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.5 Connection Methods for Hard Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.6 Recommended Piping Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.6.1 Connecting Methods—One-Shot Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.7 Field Installation of Liebert XD Flex Pipe Kit on the Liebert XDH . . . . . . . . . . . . . . . . . . . 18
5.8 Connecting Liebert XD Flex Pipes to Liebert XDH Modules. . . . . . . . . . . . . . . . . . . . . . . . . 19
5.8.1 Header System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.9 Connecting a Liebert XDH with Liebert XD Flex Pipe to an Operational Liebert
XD System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.10 Disconnecting a Liebert XDH With Liebert XD Flex Pipe From a Liebert XD System. . . . 21
5.11 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.0 ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.1 Connecting High Voltage Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.2 Connecting Low Voltage Wiring—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
i
7.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP . . . . . . . . . . . . . . . . . . . . . . .25
7.1 Checklist for Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.2 Charging with Refrigerant and Starting the Liebert XD System . . . . . . . . . . . . . . . . . . . . . 25
8.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.1 Start the Liebert XDH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
9.1 Internal Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.2 Fluorinated Greenhouse Gas Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.3 Remove Fan Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
FIGURES
Figure 1 Liebert XDH component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Liebert XDH model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 3 Liebert XDH hydraulic schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 4 Recommended unit handling equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 5 Removing shipping package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6 Prepare ramp to remove the Liebert XDH from shipping pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 7 Attaching ramp, removing the Liebert XDH from pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 8 Liebert XDH dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 9 Liebert XDH placement in enclosure row . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 10 Change airflow direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 11 Typical Liebert XDH piping—interlaced connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 12 Typical Liebert XDH piping—non-interlaced connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 13 Direct system configuration—hydraulic system schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 14 Indirect system configuration—hydraulic system schematic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 15 Hard pipe connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 16 Supply and return—hard-piping connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 17 Piping location and connecting sizes for pre-charged units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 18 Liebert XD Flex Pipe dimensions—straight and 90-degree connections. . . . . . . . . . . . . . . . . . . . 18
Figure 19 Liebert XD prefabricated piping assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 20 Detail view of Liebert XD Flex Pipe and prefabricated piping port. . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 21 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe . . . . . . . . . . 21
Figure 22 Profile view of the Liebert XD system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 23 Piping mains without Liebert XDH and Liebert XD Flex Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 24 Liebert XDH electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 25 Condensate wiring entry points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 26 Fan switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 27 Remove fan tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
TABLES
Table 1 Application limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 2 Branch piping sizes for pumped refrigerant loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 3 Liebert XDH specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 4 Liebert XD Flex Pipe assemblies, supply and return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
ii
Liebert XDH Component Locations and Model Number Nomenclature

1.0 LIEBERT XDH COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATURE

Figure 1 Liebert XDH component locations

FRONT
(Top View)
Air
Controls
Cooling
Air Supply
Ven ts
FRONT
Return
Ven ts
REAR
Return Piping Connection ­Top C i r cuit
Supply Piping Connection ­Bottom Circuit
Upper Refrigeration Circuit
Return Piping Connection ­Bottom Circuit
Supply Piping Connection ­Bottom Circuit
FRONT
(Bottom View)
FRONT
Condensate
Detection
Connections
Condensate Pan and Detection Option (also in bottom circuit)
REAR
Electrical
Connections
Lower Refrigeration Circuit

Figure 2 Liebert XDH model number nomenclature

Example: XDH32BK— —0
XD H 32 B K
Liebert
X-Treme heat
density system
Horizontal row cooler
20 = Model size 32 = Model size
B = Base unit
D = Condensate detection
K = 120V-1ph-60Hz
S = 208-240-1ph-60Hz
220-240-1ph-50Hz
P = Pre-charged (one-shot) Coupling
Casters (one at each corner)
Adjustable Foot (one at each corner)
— = Domestic packaging
E = Export packaging
— = Hard piped
R = Removable Coupling
Stabilizers (one at each corner)
0
Revision level
1

2.0 INTRODUCTION

2.1 Product Description

The Liebert XDH cooling module is designed to be placed within a row of server enclosures in a hot­aisle-cold-aisle arrangement. The Liebert XDH, available in a half-rack-width unit, is intended for use with a Liebert XD pumped refrigerant cooling system, supplied by either a Liebert XDP or Liebert XDC.
Warmer air from the enclosures is drawn in through the rear of the Liebert XDH, cooled and blown into the cold aisle in a diffuse pattern. The cooling air is then drawn into the enclosures to cool the equipment.
The Liebert XDH has dual refrigeration circuits, one in the upper half of the unit and the other in the lower half. This permits increasing and decreasing cooling levels in response to server room condi­tions. The dual refrigeration circuits permits interlaced connection of two Liebert XD refrigerant sources to enhance system reliability.
Controls on the front of the Liebert XDH permit independent operation of the two banks of fans. Dual power connections ensure continued fan operation if one of two electrical sources fails.
The Liebert XDH is intended for use in low-humidity environments and does not need a drain connec­tion. A condensate pan under each refrigeration unit collects the small amount of moisture expected in the server room. An optional, factory-installed condensate detection system is available. The Lie­bert XDH is available with uni-directional or bi-directional air diffusers.
Introduction

2.2 References

This document must be used together with site specific documentation and documentation for other parts of the system.

2.3 Pre-Installation Checks

• Verify that the Liebert XDH voltage matches the available utility power. The serial tag with this information is accessible by opening the Liebert XDH’s rear door. The tag is on a shelf near the Liebert XDH’s midline.
• Check the received materials to be sure all required assemblies and parts have been received. If you discover any external damage, report it to the shipping company and your local Liebert repre­sentative.

2.4 Parts Included With the Liebert XDH

• User manual (this document)
• Liebert XDH module
• Power cords
• Shipping/floor mounting brackets
• Tie-down bracket assembly
• Diffusers (top and bottom)
2

2.5 Installation Considerations

The Liebert XDH is designed for placement within a row of computer cabinets in the data center in a hot-aisle-cold-aisle arrangement. The Liebert XDH is 12" (305mm) wide, so it takes up little space. For installation arrangement, see 4.2 - Installing the Liebert XDH Within the Enclosure Row. Be sure to follow all applicable codes.
Determine whether the Liebert XDH includes the condensate detection option (factory-installed). This option will require separate low voltage connections to a monitoring unit. A front panel alarm and indicator alert the user to condensation inside the unit. To minimize the possibility of condensa­tion, insulate all piping between the Liebert XDH and the Liebert XDP or Liebert XDC.
If the Liebert XDH is installed at the end of a row, Liebert recommends using uni-directional air dif­fusers to direct cooling air into the cold aisle, toward the equipment racks. If the Liebert XDH is installed between racks within a row, Liebert recommends using bi-directional air diffusers, directing the cooling air toward the equipment racks on either side of the Liebert XDH.

Table 1 Application limits

Input Voltage Range of Return Air Conditions to Unit
Minimum Maximum Dry Bulb Temperature Relative Humidity
-10% +10% 60° to 100°F (16° to 38°C) 20% to 80%

2.5.1 Room Preparation

The room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either rubber or plastic.
Introduction
NOTE
The vapor barrier is the single most important requirement for maintaining environmental control in the conditioned space.
Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly controlled. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site. Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.
3

3.0 GENERAL PRODUCT INFORMATION

3.1 Product/System Description

The Liebert XDH is designed for placement within a row of computer cabinets in the data center in a hot-aisle-cold-aisle arrangement to maximize the Liebert XDH’s cooling: The unit takes in hot air through the rear from the hot aisle, cools the air by air-to-fluid heat exchangers and discharges the air through the front of the unit into the cold aisle.
Chilled R-134a refrigerant is provided to the Liebert XDH by a Liebert XD Pumping unit (Liebert XDP) or by a Liebert XD Chiller (Liebert XDC). The Liebert XDH may be installed in a Liebert XD piping system that includes other Liebert XD cooling modules, such as the Liebert XDO, Liebert XDV or Liebert XD CoolFrame.
Replaceable front panels on the Liebert XDH may be customized to match the appearance of various computer manufacturer’s equipment, allowing the Liebert XDH to blend in with adjacent server equipment and enclosures. Air diffusers are available to direct cooling air for more efficient cooling, depending on the Liebert XDH’s positioning in a row or at the end of a row.
The Liebert XDH is not expected to produce any condensation because of its location, usually in the data center. A condensate pan is provided as a precaution. It does not have a drain fitting or other means of being emptied.
A Liebert Liqui-tect moisture detection device and a contact-closure output are available as an option. These options detect condensation in the Liebert XDH’s catch pan and connect to a monitoring or alarm system. A front panel alarm and indicator alert the user to condensation inside the unit.
General product information
The complete cooling system consists of Liebert XDH modules, Liebert XDP or Liebert XDC pumped refrigerant distribution units, power and signal cabling and interconnecting piping, see Figure 3 below.

Figure 3 Liebert XDH hydraulic schematic

Liebert XDC
or
Liebert XDP
Liebert XDC
or
Liebert XDP
Pumped
Refrigerant
Pumped
Refrigerant

3.2 Checking and Unpacking

When the Liebert XDH is delivered, inspect all items for either visible or concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative. If you later find any concealed damage, report it to the shipping company and your local Liebert representative.
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
Supply Lines
(2 per unit )
Return Lines
(2 per unit )
* XDCF, XDH, XDO or XDV
Check to be sure all required assemblies and parts have been received.
The Liebert XDH is shipped in protective packaging and secured to a pallet (see Figure 5). Do not remove these protective items from the Liebert XDH before it is at the installation location. When unpacking and handling the Liebert XDH, exercise extra care to prevent damage.
4

3.3 Equipment Inspection

Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the Bill of Lading. Inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert Corporation or to your sales repre­sentative.

3.3.1 Recyclable Packaging

General product information
All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
R
WARNING
!
Risk of top-heavy unit falling over. Can cause death, injury and equipment damage. Read all of the following instructions before attempting to move, lift, remove packaging from
the unit, or preparing unit for installation.
CAUTION
!
Risk of overhead interference. Can damage unit or structure.
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and doorway heights and refer to the installation plans before moving the unit to verify clearances.
CAUTION
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury. Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and
glasses should attempt to move, lift, remove packaging from, or prepare unit for installation.
CAUTION
!
Risk of damage from forklift. Can cause exterior and/or underside damage. Keep tines of the forklift level and at a height suitable to fit below the skid.
CAUTION
!
Risk of hazardous environments. Can cause unit damage. Keep the unit indoors and protected from dampness, freezing temperatures and contact
damage.
Figure 4 Recommended unit handling equipment
Forklift
Pallet Jack
5

3.3.2 Unit Handling

If possible, transport the unit using a forklift or pallet jack.
• If using a forklift or pallet jack, ensure that the fork tine length is suitable to safely move the packaged unit.
• Liebert recommends keeping the unit in the protective packaging until it has been moved to the installation site.
• When handling and unpacking the unit, exercise great care to prevent damage.
• Do not lift the unit any higher than 6" (152mm) while moving it. If it must be lifted higher than 6" (152mm), exercise great care and keep all personnel who are not helping move the unit at least 20' (5m) away from the unit.
• The Liebert XDH ships with four outrigger-style wheels to permit rolling it into position. Liebert recommends using a forklift or pallet jack to move the Liebert XDH as near as practical to its installation site before removing it from the shipping pallet.

3.3.3 Unpacking the Unit

1. Remove the exterior stretch-wrap packaging from around the unit, exposing the protective corner and side packaging planks.
2. Remove the ramp, corner and side packaging planks from the unit, exposing the bag over the unit. Remove the bag when ready to install the Liebert XDH.
Figure 5 Removing shipping package
Exterior stretch wrapping surrounds other protec­tive shipping features
General product information
Planks at the corners and on the sides protect the Liebert XDH during shipping
(secured to the Liebert XDH by a
Ramp
layer of shrink-wrap) NOTE: One ramp will be shipped per order.
Leave the plastic bag on the unit until it is off the pallet and ready to be installed
Ramp
(removed from pallet)
6

3.3.4 Taking the Unit off the Pallet

WARNING
!
Risk of unsecured unit rolling off pallet. Can cause equipment damage, injury or death. The Liebert XDH is on casters. Ensure that the unit/skid is located on a flat surface before
loosening the hardware securing the Liebert XDH to its shipping pallet. The Liebert XDH ships with four outrigger-style wheels to permit rolling it into position for
installation. Liebert recommends using a forklift or pallet jack to move the Liebert XDH as near as practical to its installation site before removing it from the shipping pallet.
1. Locate the ramp that was shipped with the Liebert XDH (see Figure 5).
2. Loosen the hex screw on the ramp and remove the metal bracket (see Figure 6).
3. Rotate the metal bracket 180 degrees and insert the shortest slot of the metal bracket under the hex screw head and tighten the hex screw.
4. Loosen the two hex screws on the skid.
5. Align the ramp and the metal bracket with the skid. Ensure that the ramp is in contact with the skid (see Figure 7).
6. Insert the opposite end of the metal bracket under the hex screws on the skid. (see Figure 7)
7. Tighten the hex screws on the skid.
8. Remove the six hex screws from each of the two tie-down brackets, one located on either end of the Liebert XDH. (see Figure 7).
9. Remove the two tie-down brackets.
10. At least two properly trained personnel may roll the Liebert XDH down the ramp and off the pallet onto a flat surface.
Figure 6 Prepare ramp to remove the Liebert XDH from shipping pallet
General product information
Metal Bracket
Lag screw to secure bracket to ramp
7