Liebert Web485 User Manual

Liebert Intellislot® Web/485 Card
With Adapter
Quick Start Guide
INSTALL
• Locate the adapter mounting location within your Liebert equipment.
• Secure the card with the supplied screws.
• Connect an Ethernet cable to RJ45.
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal block; Pin 1 is at the far left, and Pin 2 is the middle pin.
TB3 (P1: +) (P2: -) (P3: NC) P1 is on left end of terminal block.
TB2 (P1: +) (P2: -); P1 is at the right side of terminal block.
DHCP: The card ships with DHCP service enabled. The MAC address is printed on a sticker affixed to the top of the card.
OR
Static IP: To assign a static IP address, use the Service Terminal to con-
figure the card. Proceed to Steps 2 & 3.
TB1 (P1: +; P2: -); P1 is at the right side of terminal block.
P1
Network Port for NMS and Web Access
DB-9 Port
MAC Address
CONNECT THE CABLE
• Locate the blue serial configuration cable (null modem) that shipped with the card.
• Connect the configuration cable to the DB-9 port on the card and to a COM port on your PC.
CONFIGURE THE CARD
• Use terminal emulation software, such as HyperTerminal tion to the card.
•Press Enter for the Main Menu.
• Select option 2 and follow the instructions to enter an IP ADDRESS, NETMASK and GATEWAY.
•Press Esc to return to the Main Menu.
• Enter X and press Enter to exit HyperTerminal and save your changes.
, to open a direct connec-
Emulation Software Configuration
Baud Rate: 9600 Data Bits: 8 Parity: None Stop Bits: 1 Flow Control: None
User Manual
This Quick Start Guide is designed to give you the information you need to install and configure the Liebert Intellislot Web/485 Card with adapter. A full user manual, SL-23150, is available online at www.liebert.com. Liebert highly recommends that new users consult the user manual.
Web Support
The Intellislot Web/485 Card delivers Web management and control to Liebert equipment. All users on your network will be able to view status information. Control and configuration capabilities are protected by a username and password combination. The default username is “Liebert” and the default password also is “Liebert.”
You can change the password from the Web or from the service terminal.
WARNING: Change the username and password today to prevent unauthorized access.
SNMP Support
The Liebert Intellislot Web/485 Card enables SNMP management of Liebert equipment. To integrate the card into your SNMP implementation, you will need to compile the Liebert Global Products MIB on your network management station (NMS). The Liebert Global Products MIB is included in this package on CD-ROM and supports both Windows and Unix file formats.
Modbus Support
Modbus™ Support
Building Management Systems play a vital role in the overall operations of facilities and buildings. Most
building management systems provide device communications via the Modbus protocol. The IntelliSlot Web/485 card with adapter provides a Modbus interface to Liebert equipment, enabling integration with your building management system.
Product details are available online at www.liebert.com
Liebert OpenComms Nform Support
Utilizing the SNMP and Web technologies built into each Intellislot Web/485 Card, Liebert OpenComms Nform will centrally manage alarm notifications to provide you with an easy interface to access critical system information.
A downloadable edition is available online at
nform.liebert.com
Liebert MultiLink™ Support
A Liebert Intellislot Web/485 Card installed in a UPS may be used with Liebert MultiLink software, providing unattended, graceful operating system shutdown. The card can be monitored by MultiLink over the network, eliminating the need for serial cables.
Downloadable versions of MultiLink and information about MultiLink are available online at
www.liebert.com
Technical Support/ Service
Web Site
www.liebert.com
Monitoring
800-222-5877 monitoring@emersonnetworkpower.com Outside the US: 614-841-6755
Locations
United States
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
SL-29107_REV0_05-07
Locations
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 25722201
Fax: 852 28029250
Loading...