Liebert Intellislot® Web/485 Card
With Adapter
Quick Start Guide
INSTALL
• Locate the adapter mounting location within your Liebert equipment.
• Secure the card with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal
block or P1 on the card (See equipment user manual for details).
• Connect an Ethernet cable to RJ45.
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal
block; Pin 1 is at the far left, and Pin 2 is the middle pin.
TB3
(P1: +)
(P2: -)
(P3: NC)
P1 is on
left end of
terminal
block.
TB2
(P1: +)
(P2: -);
P1 is at the
right side of
terminal block.
DHCP: The card ships with DHCP service enabled. The MAC address is
printed on a sticker affixed to the top of the card.
OR
Static IP: To assign a static IP address, use the Service Terminal to con-
figure the card. Proceed to Steps 2 & 3.
TB1 (P1: +; P2: -); P1 is at the
right side of terminal block.
P1
Network Port
for NMS and
Web Access
DB-9
Port
MAC Address
CONNECT THE CABLE
• Locate the blue serial configuration cable (null modem) that shipped
with the card.
• Connect the configuration cable to the DB-9 port on the card and to a
COM port on your PC.
CONFIGURE THE CARD
• Use terminal emulation software, such as
HyperTerminal
tion to the card.
•Press Enter for the Main Menu.
• Select option 2 and follow the instructions
to enter an IP ADDRESS,
NETMASK and GATEWAY.
•Press Esc to return to the Main Menu.
• Enter X and press Enter to exit HyperTerminal and save your
changes.
™
, to open a direct connec-
Emulation Software
Configuration
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
User Manual
This Quick Start Guide is designed to give you the information you need to
install and configure the Liebert Intellislot Web/485 Card with adapter. A full
user manual, SL-23150, is available online at www.liebert.com. Liebert
highly recommends that new users consult the user manual.
Web Support
The Intellislot Web/485 Card
delivers Web management and
control to Liebert equipment. All
users on your network will be able to
view status information. Control and
configuration capabilities are
protected by a username and
password combination. The default
username is “Liebert” and the
default password also is “Liebert.”
You can change the password from
the Web or from the service
terminal.
WARNING: Change the username
and password today to prevent
unauthorized access.
SNMP Support
The Liebert Intellislot Web/485 Card
enables SNMP management of
Liebert equipment. To integrate the
card into your SNMP
implementation, you will need to
compile the Liebert Global Products
MIB on your network management
station (NMS).
The Liebert Global Products MIB is
included in this package on CD-ROM
and supports both Windows and
Unix file formats.
Modbus Support
Modbus™ Support
Building Management Systems play
a vital role in the overall operations
of facilities and buildings. Most
building management systems
provide device communications via
the Modbus protocol. The IntelliSlot
Web/485 card with adapter provides
a Modbus interface to Liebert
equipment, enabling integration
with your building management
system.
Product details are available
online at www.liebert.com
Liebert OpenComms Nform
Support
Utilizing the SNMP and Web
technologies built into each
Intellislot Web/485 Card, Liebert
OpenComms Nform will centrally
manage alarm notifications to
provide you with an easy interface to
access critical system information.
A downloadable edition is
available online at
nform.liebert.com
Liebert MultiLink™ Support
A Liebert Intellislot Web/485 Card
installed in a UPS may be used with
Liebert MultiLink software,
providing unattended, graceful
operating system shutdown. The
card can be monitored by MultiLink
over the network, eliminating the
need for serial cables.
Downloadable versions of
MultiLink and information about
MultiLink are available online at
www.liebert.com
Technical Support/ Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
SL-29107_REV0_05-07
Locations
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 25722201
Fax: 852 28029250