WARNING: Opening or removing the cover may expose you to lethal voltages
within this unit even when it is apparently not operating and the input wiring is
disconnected from the electrical source. Observe all cautions and warnings in
this manual. Failure to do so MAY result in serious injury or death. Refer all
UPS and battery service to qualified service personnel. Do not attempt to
service this product yourself. Never work alone.
1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT
SAFETY INSTRUCTIONS. Read all safety, installation, and operating
instructions before installing and operating the Uninterruptible Power System
(UPS). Adhere to all warnings on the unit and in this manual. Follow all
operating and user instructions. Individuals without previous training can
operate this equipment.
2. This product is designed for Commercial/Industrial use only. It is not intended
for use with life support and other designated “critical” devices. Maximum
load must not exceed that shown on the UPS rating label. The UPS is
designed for data processing equipment. If uncertain, consult your dealer.
See Limited Warranty.
3. This UPS is designed for use on a properly grounded (earthed), 208-240
VAC, 50Hz or 60Hz supply, for installation by qualified personnel. A qualified
electrician must review and approve customer supplied wiring, circuit
breakers, intended loads, and verify correct input, output and ground
connections to ensure compliance with technical standards and local
electrical codes of practice. Installation instructions and warning notices only
for use by qualified personnel are located after the UPS operator instructions
in this manual.
4. ELECTROMAGNETIC COMPATIBILITY - The GXT 6 & 10 kVA complies with
the limits for a Class A digital device, pursuant to Part 15 of FCC rules.
These limits provide reasonable protection against harmful interference in a
commercial environment. This device generates, uses, and radiates radio
frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operating this device in a residential area is likely to cause harmful
interference, which the user must correct at his own expense.
5. Operate the UPS in an indoor environment only in an ambient temperature
range of 0°C to +40°C (32°F to +104°F). Install it in a clean environment, free
from moisture, flammable liquids, gasses, or corrosive substances.
6. This UPS contains no user serviceable parts. The UPS ON/OFF pushbuttons
do not electrically isolate internal parts. Under no circumstances attempt to
gain access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the front panel indications are not in
accordance with these operating instructions, or the UPS performance alters
in use. Refer all faults to your dealer.
7. Only trained engineers authorized by Liebert should perform troubleshooting.
To replace batteries, refer all servicing to qualified service personnel.
PROPER DISPOSAL OF BATTERIES IS REQUIRED. REFER TO YOUR
LOCAL LAWS AND REGULATIONS FOR DISPOSAL REQUIREMENTS.
3
8. Never block or insert any object into the ventilation holes or other openings.
9. DO NOT CONNECT equipment that could overload the UPS or demand DC
current from the UPS, for example: electric drills, vacuum cleaners, laser
printers, hairdryers or any appliance using half wave rectification.
10. Storing magnetic media on top of the UPS may result in data loss or
corruption.
11. Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth,
never liquid or aerosol cleaners. Keep the front and rear vents free of dust
accumulation that could restrict airflow.
GLOSSARY OF SYMBOLS
Indicates AC Input
Indicates AC Output
Indicates Caution: Note the accompanying instruction
Indicates the position of a fuse
Requests the user to consult the manual for additional
information
Indicates that the unit contains a valve regulated lead acid battery
4
INTRODUCTION
Congratulations on your choice of the UPStation GXT™ Uninterruptible Power
System (UPS). It provides conditioned power to microcomputers and other
sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission
and distribution it may be subject to voltage sags, spikes, or complete power
failure, which may interrupt computer operations, cause data loss, or even
damage equipment. The UPStation GXT protects equipment from these
disturbances.
The UPStation GXT is an “on-line” UPS that continuously conditions and
regulates its output voltage, whether the utility power is present or not. It
supplies connected equipment with clean sinewave power. Sensitive electronic
equipment operates best from sinewave power. The GXT 6000/10000T-208X,
and 240X models have an additional output isolation transformer.
For ease of use, the UPStation GXT contains a light emitting diode (LED) display
to indicate either “load percentage” or “battery capacity” depending upon the
mode of operation. It also provides self-diagnostics, a combination On/Alarm
Silence/Manual Battery Test button, a combination Off/Bypass button, and two
levels of alarms when the unit is operating on battery.
The UPStation GXT has an interface port for communications between the UPS
and a LAN server or other computer system. This port provides detailed
operating information including voltages, currents, and alarm status to the host
system when used in conjunction with the SiteNet® 2 software. SiteNet® 2
software can also remotely control UPS operation.
5
Static Bypass
EMI/RFI
Output Transformer
INPUT
EMI/RFI
Filter
MAJOR COMPONENTS
Rectifier/PFC
Inverter
Filter
GXT 208X, 230X, &
240X models only
OUTPUT
Battery
Battery
Charger
EMI /RFI FILTERS
These UPS components provide surge protection, and filter both electromagnetic
interference (EMI) and radio frequency interference (RFI). They minimize any
surges or interference present in the utility line and keep the sensitive equipment
protected.
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT
In normal operation, the rectifier/power factor correction (PFC) circuit converts
utility AC power to regulated DC power for use by the inverter, while ensuring
that the wave shape of the input current used by the UPS is near ideal.
Extracting this sinewave input current achieves two objectives: the utility power is
used as efficiently as possible by the UPS, and the amount of distortion reflected
on the utility is reduced. This results in cleaner power being available to other
devices in the building not being protected by the UPStation GXT.
INVERTER
In normal operation, the inverter utilizes the DC output of the power factor
correction circuit and “inverts” it into precise, regulated sinewave AC power.
Upon a utility power failure, the inverter receives its required energy from the
battery through the Rectifier / PFC. In both modes of the operation, the UPS
inverter is on-line and continuously generating clean, precise, regulated AC
output power.
BATTERY CHARGER
The battery charger utilizes energy from the Rectifier / PFC and precisely
regulates it to continuously “float” charge the battery system. The battery system
charges whenever the UPStation GXT is connected to utility power.
BATTERY
The UPStation GXT employs valve regulated, nonspillable, lead acid batteries.
At a typical room temperature (70° F) and with the UPS float charging, the
battery system will last many years. Optional external battery cabinets are
available to provide extended run times.
6
STATIC BYPASS
The UPStation GXT provides an alternate path for utility power to the connected
load, in the unlikely event of a UPS malfunction. Should the UPS have an
overload, over temperature, or UPS failure condition, the UPS automatically
transfers the connected load to BYPASS providing the bypass voltage is within
specification. BYPASS operation is indicated by an alarm and an illuminated
BYPASS LED (other LED’s may be illuminated to indicate any diagnosed
problem). The load may also be transferred to BYPASS using the control panel.
NOTE: The BYPASS power path does NOT protect the connected equipment
from disturbances on the utility supply and its range of operation is limited to +/17% of the nominal input supply voltage.
AUTO RE-START
Upon restoration of the utility AC power after a utility power outage and complete
battery discharge, the UPS will automatically restart and supply power to the
critical load and the battery charger will automatically recharge the battery.
7
INSTALLATION
These instructions are for use by competent personnel only.
INSTALLATION CONSIDERATIONS
Detailed instructions to help you install the UPS are provided in the following
pages; however, you should give some consideration to the proposed
environment in which the UPS is to be installed, and carry out some preparatory
work.
UNPACKING AND INSPECTION
Follow unloading instructions printed on the carton. Do not discard any
packaging until installation is complete, check that you have removed to a safe
place the user manual, stabilizing brackets, and any other items shipped with the
unit to be used in its installation.
CAUTION: GXT6000 UPS weighs up to 173kg (381lbs) and the GXT10000 UPS
weighs up to 287kg (633lbs). Use adequate handling aids when moving or
installing the UPS. The UPS is fitted with castor wheels for easy movement. Take
care when the UPS is removed from its packing and being wheeled across an
uneven floor without the stabilizers fitted, that it does not tip over.
Before you install the UPS, give it a thorough visual examination to ensure it has
not been subjected to shipping damage. If it is not in perfect condition, you
should advise both the shipper and the supplier immediately. DO NOT ATTEMPT
TO INSTALL A DAMAGED UPS.
IMPORTANT - Check the UPS rating plate that the UPS is suitable for operation
on your UTILITY voltage and load voltage requirements before installing.
LOCATION
Locate the UPStation GXT indoors in a controlled environment, where it cannot
be accidentally disconnected. Locate it in an area with unrestricted airflow, away
from water, flammable liquids, gases, corrosives, or conductive contaminants.
Air vents are located at the front and the rear of the UPS. Do not position the
UPS in an enclosed space where airflow is restricted. Allow at least 150mm (6
inches) free space around the UPS, with a minimum of 300mm (12 inches) at the
back to enable easy operator access to the rear panel mounted
input/output/battery circuit breakers.
Electrical maintenance/servicing requires access to all four sides of the UPS,
provide the necessary free space or use a flexible wiring system to allow the
UPS to be pulled forward.
Maintain an ambient temperature range of 0 - +40° centigrade (32-104° F)
NOTE- UPS operation in temperatures above 25°C (77°F) reduces battery life.
* Increase dissipation 25% for 208X, and 240X transformer models.
** Decrease output rating 10% for 208 and 208X model.
ELECTRICAL INSTALLATION CONSIDERATIONS
This UPS must be installed by competent electrical personnel and wired in
accordance with local/national electrical codes.
The following information is provided for your guidance.
On start-up, the UPS will take a half cycle inrush current of up to 3 times the
rated current. This must be taken into account when selecting the overload
protection device at the input Utility supply distribution point. To avoid random
tripping on start-up, we recommend that the input Utility supply be protected with
an MCB capable of withstanding this initial inrush.
The utility input supply cable must be connected to the UPS via a wall mounted
double pole circuit breaker, rated to carry the input current and be capable of
breaking the maximum prospective short circuit current of this branch circuit. The
breaker is to be mounted within six feet of the UPS and be readily accessible to
the operator.
ELECTRICAL CONNECTIONS
The UPS is supplied with an input/output/battery terminal block assembly on the
rear of the UPS within a cable box. (see outline drawing) The cable box (gland
plate) can be removed to enable knockouts to be removed, or new holes drilled,
to secure the cables.
The cable sizes and distribution methods used during installation are subject to
local/national electrical codes of practice, and therefore are not detailed here.
The following tables detail the standard current ratings. The UPS rating plate
gives details of the current ratings for alternative output voltages.
The terminals will accept wire sizes up to the values below:
GXT6000 = 8 AWG Recommended for all GXT6000 wiring.
GXT10000 = 6 AWG Recommended for all GXT10000 wiring.
(75°C copper wire)
Terminal tightening torque is 35 in-lb.
9
Connecting the UPS Power cables
Power cables connect to screw terminals on a terminal block that is located
behind the rear mounted cable box (see figure). Permanent wiring must be
routed to the cable box using appropriate materials as required by local codes.
Connection of optional remote battery cabinets
Full installation instructions are provided with these cabinets. Safety/EMC
certification limits the use of these terminals to Liebert supplied options.
Properly grounded (earthed) equipment provide multiple benefits
High quality ground (earth) connections are required for the equipment ground
conductors (protective earth) and grounding electrode conductor (power system
earth connection) to reduce electrical noise and provide for safe operation of the
UPS and connected loads. Conduit used alone without a grounding conductor
wire is not an acceptable connection. Size ground (protective earth) conductors
equal to circuit conductors.
GXT6000T / 10000T - 208 UPS ONLY
NOTE 5
NOTE 6
208
208
Models whose part number ends with a “208” are NOT fitted with an isolating
output transformer and are NOT separately derived sources under the NEC. The
output L1 terminal is connected to the input L1 terminal and must not be
connected to ground at the UPS (see NEC 250-5d, 250-26, 250.91, 250.92).
GXT6000T-208 CONNECTIONS
CONNECTION
INPUT 28 AMPS 8 AWG (10 mm²) 40 AMPS
OUTPUT 26 AMPS 8 AWG (10 mm²)
BATTERY 23 AMPS 8 AWG (10 mm²)
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
CURRENT
RATING
GXT10000T-208 CONNECTIONS
CONNECTION
INPUT 45 AMPS 6AWG (16 mm²) 60 AMPS
OUTPUT 43 AMPS 6AWG (16 mm²)
BATTERY 37 AMPS 6AWG (16 mm²)
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
CURRENT
RATING
INPUT
UTILITY
L1 L2
NOTE 4
INPUT TO UPS
NOTE 1
Recommended
Wire Size
Recommended
Wire Size
OUTPUT
L1 L2 + -
OUTPUT TO LOAD
NOTE 2
Recommended External
Overcurrent Protection
Recommended External
Overcurrent Protection
OPTIONAL
BATTERY
OPTIONAL
BATTERIES
NOTE 3
10
NOTES FOR GXT6000T / 10000T - 208 UPS ONLY
1. The installer must provide circuit breaker protection according to local codes.
The UTILITY disconnect must be within sight of the UPS. Maintain service
space around the UPS or use flexible conduit.
2. The installer must provide output distribution panels and circuit breaker
protection according to local codes. Output circuits must not share a
common conduit with input circuits or any other wiring.
3. Refer to the manual provided with any optional battery cabinets.
4. This unit does NOT contain an isolating transformer. It is NOT a separately
derived source. System grounding is provided at the UTILITY. Do not
connect any output circuit conductor to ground at the UPS.
5. The UTILITY may be derived from a single-phase or three-phase source.
The line to ground voltages are dependant upon the grounding of the
UTILITY. Do not use a floating AC source.
6. Output L1 is connected directly to the Input L1. The line-ground voltages will
match the input line-ground voltages.
11
GXT6000T / 10000T - 208X UPS ONLY
208
120
120
240
NOTE 5
NOTE 6
208
Models whose part number ends with a “208X” are fitted with a single-phase
isolating output transformer and are separately derived sources. The output
neutral is already bonded to ground on the output terminals with a Bonding
Jumper (see NEC 250-5d, 250-26, 250.91, 250.92). The output L1 and L2
terminals are not connected to the input L1 and L2.