Liebert Hipulse E Installation And User Manual

Page 1
Power Quality Solutions
Liebert Hipulse E
Hi-Availability UPS
Uninterruptible Power Supply
Installation and User Manual
EN
SINGLE UNIT AND '1+N' (EXPANDABLE)
Page 2
(07/04)
Dear Customer,
Please allow us to congratulate you on choosing a Liebert manufactured Uninterruptible Power Supply (UPS)
system.
If this is your first Liebert UPS, we cordially welcome you to a lifetime relationship of post-sales support
designed to keep your Liebert UPS and your systems permanently at their peak performance.
If you already own and use a Liebert UPS, then we are doubly honoured by your decision to continue this
valued relationship.
It is our constant endeavour to partner you to ensure the growth & success of your business;
our philosophy is reflected in our mission statement “Keeping Business in Business”.
Please give us your valued feedback to help us realise our mission.
EMERSON NETWORK POWER
Page 3
Installation Manual Liebert Hipulse E Single or '1+N' UPS System
(07/04) Page iii
This manual contains information concerning the installation, and operation of the Liebert Hipulse E Single Module
(Expandable) Uninterruptible Power System (UPS).
All relevant parts of the manual should be read prior
to commencing installation.
The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or his agent).
Failure to do could result in personnel safety risk, equipment malfunction and invalidation of warranty.
The Liebert Hipulse E UPS has been designed for Commercial/Industrial use only, and is not recommended
for use in any life support applications.
Warning: This is a product for restricted sales distribution
to informed partners.
Installation restrictions or additional measures may be needed to prevent disturbance.
(See EN 50091-2)
When Class A option is fitted, this is a Class A UPS (for Unrestricted sales distribution).
Anyway in a domestic environment this product may be cause radio interference in which case, the user may be
required to take additional measures.
(See EN 50091-2)
If you encounter any problems with the procedures contained in this manual
you should seek immediate assistance from the Liebert Sales Office
from whom the equipment was purchased.
Alternatively, contact the Liebert's Customer Service & Support department
at the address shown below:
Liebert HIROSS Services (HQ)
Customer Service and Support Department
Via Leonardo da Vinci 8
35028 - Piove di Sacco (PD)
Italy
Help Desk Telephone +39 049 9719311
Fax +39 049 9719053
service@liebert-hiross.com
Emerson Network Power Ltd - United Kingdom
Customer Service and Support Department
Globe Park
Marlow
Buckinghamshire SL71YG
United Kingdom
Telephone +44 1628 40 32 00
Fax +44 1628 40 32 03
Please visit our web site: http://ups.liebert-hiross.com/
While every precaution has been taken to ensure accuracy and comleteness in this manual, Liebert Corporation
assumes no responsibility and disclaims all liability for damages resulting from use of this information or for
any errors or omissions.
Liebert Corporation pursues a policy of continual product development and reserves the right to change the
equipment design without notice.
Copyright 2004 by Liebert Corporation.
Unauthorized reproduction prohibited
All rights reserved.
Page 4
Single or '1+N' UPS System Liebert Hipulse E Installation Manual
Page iv (07/04)
This manual describes the following equipment:
EQUIPMENT PART NUMBER
300 kVA
300 kVA UPS Module (6 Pulse) 5410318E-E
300 kVA UPS Module (12 Pulse) 5410338Y-E
Battery Circuit Breaker Box (BCB) 800 A 4646016Y-E
Common battery box 800 A 4641090M-E
Battery Circuit Breaker Control Board 4520079F
Battery Temperature Board 4532029V
Top cable entry cabinet 5312105T-E
Class A option filter (UPS 6 or 12 pulse rectifier) 4641134E
400 kVA
400 kVA UPS Module (6 Pulse) 5410319F-E
400 kVA UPS Module (12 Pulse) 5410339Z-E
Battery Circuit Breaker Box (BCB) 1000 A 4646017Z-E
Battery Circuit Breaker Control Board 4520079F
Battery Temperature Board 4532029V
Top cable entry cabinet 5312108O-E
OPTIONS (300 and 400 kVA)
Maintenance bypass cabinet - 1+ 1 Configuration (two UPS's with parallel redundant connection)
5312155R-E
Mechanical Castell Interlock BP1 4644059R
Mechanical Castell Interlock BP2 4644060S
Optional kit to uprate the neutral cut-off current rating SFA code
Page 5
Installation Manual Liebert Hipulse E Single or '1+N' UPS System
(07/04) Page v
Safety Precautions
CONFORMITY AND STANDARDS
This equipment complies with the following requirements: Normative references: Uninterruptible Power System (UPS).
* IEC 62040-1-1 (2002) — ‘General and safety requirements for use in operator access area’; * EN 50091-2 (1995) — ‘EMC requirements’; * IEC 62040-3 (2001) — ‘Performance requirements and test methods’; * EN 60950 (2001) — ‘Information technology equipment; * EN 60529 (1989) — ‘Degrees of Protection provided by enclosures (IP Code)’
and published technical standards. For more details, see Chapter 5 ‘Conformity and standards’. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
WARNING
HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
This equipment must be earthed in accordance with local electrical authority codes of practise.
Caution
This equipment can be fitted with RFI suppression filters (optional).
Earth leakage current exceeds 3.5 mA and is less than 1000 mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices. Residual Current Circuit Breakers ( RCCBs ) must be selected sensitive to DC unidirectional pulses ( class A ) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
WARNING
This system has a signal available for use with an automatic device, externally located, to protect against backfeeding voltage through the mains Static Bypass circuit. If this protection is not used with the switchgear that is used to isolate the bypass circuit, a label must be added at the switchgear to advise service personnel that the circuit is connected to a UPS system. The text is the following or equivalent:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM
BEFORE WORKING ON THIS CIRCUIT.
The warning triangle indicates all the personal safety instructions.
Follow these instructions carefully to avoid injury.
Page 6
Single or '1+N' UPS System Liebert Hipulse E Installation Manual
Page vi (07/04)
General
As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these voltages is minimized as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
Batteries
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
WARNING
Follow these instructions scrupulously:
The Liebert Hipulse E is designed exclusively for indoor use. Protect the unit from excessive condensation and install it in a place free of flammable liquids, gases and corrosive substances. Electrical installation must be performed by a qualified electrician. Personnel working with the equipment described in this manual must be thoroughly familiar with the product. Before making connections inside the unit, make sure that all incoming power sources are de-energised and insulated. When the incoming power source is active, the unit contains a dangerous level of voltage, even when it has “maintenance bypass” status. To insulate the unit, turn it off and insulate all incoming power sources and auxiliary power sources.
Support Information:
If you require assistance for any reason, please have the following information available:
Model and size Part number Serial number Date installed Location Voltage & Frequency Battery reserve time
Page 7
Installation Manual Liebert Hipulse E Single or '1+N' UPS System
(07/04) Page vii
Table of Contents
Part I – Installation Manual ............................................. 1-1
1 Chapter 1 - Installation Procedure ................................................................................................................... 1-1
1.1 Introduction ...................................................................................................................................................... 1-1
1.2 Environmental considerations.......................................................................................................................... 1-2
1.2.1 UPS location..................................................................................................................................................... 1-2
1.2.2 Battery location ................................................................................................................................................ 1-2
1.2.3 Storing .............................................................................................................................................................. 1-2
1.3 Mechanical Considerations.............................................................................................................................. 1-3
1.3.1 System composition ......................................................................................................................................... 1-3
1.3.2 Frame and enclosure ........................................................................................................................................ 1-3
1.3.3 300 kVA UPS with rectifier 6 pulses .............................................................................................................. 1-3
1.3.4 300 kVA UPS with rectifier 12 pulses ............................................................................................................ 1-3
1.3.5 400 kVA UPS with rectifier 6 pulses .............................................................................................................. 1-3
1.3.6 400 kVA UPS with rectifier 12 pulses ............................................................................................................ 1-3
1.3.7 Moving the cabinets ......................................................................................................................................... 1-3
1.3.8 Clearances ........................................................................................................................................................ 1-4
1.3.9 Floor installation............................................................................................................................................... 1-4
1.3.10 Fixing of the magnetic components................................................................................................................. 1-4
1.3.11 Cable entry ....................................................................................................................................................... 1-4
1.3.12 Top Cable entry................................................................................................................................................ 1-4
1.4 Preliminary Checks .......................................................................................................................................... 1-4
1.4.1 Identification .................................................................................................................................................... 1-4
2 Chapter 2 - Installation (Electrical).................................................................................................................. 2-1
2.1 Power Cabling.................................................................................................................................................. 2-1
2.1.1 System Configuration....................................................................................................................................... 2-1
2.1.2 Table for determining power cable size........................................................................................................... 2-2
2.1.3 General Notes................................................................................................................................................... 2-2
2.1.4 Cable connections ............................................................................................................................................ 2-2
2.1.5 Safety earth....................................................................................................................................................... 2-2
2.1.6 Protective devices............................................................................................................................................. 2-3
2.1.7 Cabling procedure for 300 kVA UPS with 6 pulse rectifier (or 12 pulse rectifier)........................................ 2-4
2.1.8 12-phase wiring procedure (for 300 kVA UPS) ............................................................................................. 2-6
2.1.9 Cabling procedure for 400 kVA UPS with 6 pulse rectifier (or 12 pulse rectifier)........................................ 2-7
2.2 Distance from floor to connection point on the equipment:............................................................................ 2-9
2.3 Control cables................................................................................................................................................. 2-10
2.3.1 Battery Control............................................................................................................................................... 2-10
2.3.2 Auxiliary terminal block X4...................................................................................................................... 2-11
2.3.3 Emergency Stop ............................................................................................................................................. 2-12
2.3.4 Back Feed Protection ..................................................................................................................................... 2-13
2.3.5 Fan Failure Alarm Indicator (Optional)......................................................................................................... 2-13
2.3.6 Battery ground fault detection (Optional)...................................................................................................... 2-13
3 Chapter 3 - Battery Installation........................................................................................................................ 3-1
3.1 Introduction ...................................................................................................................................................... 3-1
3.2 Safety................................................................................................................................................................ 3-2
3.3 UPS Batteries ................................................................................................................................................... 3-2
3.4 Installation design considerations.................................................................................................................... 3-3
3.5 Battery Installation and Maintenance .............................................................................................................. 3-3
3.5.1 Temperature considerations ............................................................................................................................. 3-3
3.5.2 Battery population............................................................................................................................................ 3-3
3.6 Battery protection............................................................................................................................................. 3-3
3.7 Battery installation ........................................................................................................................................... 3-4
3.7.1 Fitting & connecting the batteries.................................................................................................................... 3-4
3.7.2 Fitting the batteries........................................................................................................................................... 3-4
3.7.3 Connecting the battery ..................................................................................................................................... 3-4
Page 8
Single or '1+N' UPS System Liebert Hipulse E Installation Manual
Page viii (07/04)
3.7.4 Battery room design ......................................................................................................................................... 3-4
3.8 Battery circuit breaker box............................................................................................................................... 3-5
3.8.1 Battery Temperature Board (Optional P/N 4532029V) .................................................................................. 3-8
4 Chapter 4 - 1+N System................................................................................................................................... 4-1
4.1 General ............................................................................................................................................................. 4-1
4.2 Installation procedure....................................................................................................................................... 4-3
4.2.1 Preliminary Checks .......................................................................................................................................... 4-3
4.2.2 Protective Devices............................................................................................................................................ 4-3
4.2.3 Power cables..................................................................................................................................................... 4-3
4.2.4 Control cables................................................................................................................................................... 4-3
4.2.5 Battery Control................................................................................................................................................. 4-4
4.2.6 Emergency Stop (EPO).................................................................................................................................... 4-5
4.3 Common battery box (Option)......................................................................................................................... 4-6
4.3.1 Common Battery box for two UPS in parallel ................................................................................................ 4-6
4.4 Maintenance Bypass cabinet (Option)............................................................................................................. 4-9
4.4.1 Auxiliary connections between the maintenance bypass cabinet and two UPS's........................................... 4-9
4.4.2 Castell Interlock ............................................................................................................................................. 4-10
5 Chapter 5 - Specification.................................................................................................................................. 5-1
5.1 Conformity and Standard................................................................................................................................. 5-1
5.2 UPS Environmental.......................................................................................................................................... 5-1
5.3 UPS Mechanical Characteristics...................................................................................................................... 5-2
5.4 UPS Electrical Characteristics (Input Rectifier).............................................................................................. 5-3
5.5 UPS Electrical Characteristics (DC Intermediate Circuit) .............................................................................. 5-4
5.6 UPS Electrical Characteristics (Inverter Output) ............................................................................................ 5-5
5.7 UPS Electrical Characteristics (Bypass Input Mains) ..................................................................................... 5-6
5.8 UPS Electrical Characteristics (System Performance).................................................................................... 5-7
5.8.1 Losses ............................................................................................................................................................... 5-7
6 Chapter 6 - Installation Drawings.................................................................................................................... 6-1
6.1 Introduction ...................................................................................................................................................... 6-1
6.1.1 300kVA UPS Module with 6 pulse rectifier ................................................................................................... 6-2
6.1.2 300kVA UPS Module with 6 pulse rectifier – Top and base view................................................................. 6-3
6.1.3 300kVA UPS Module with 6 pulse rectifier with Top Cable entry option .................................................... 6-4
6.1.4 300kVA UPS Module with 6 pulse rectifier with Top Cable entry option – Top and base view.................. 6-5
6.1.5 300kVA UPS Module with 12 pulse rectifier ................................................................................................. 6-6
6.1.6 300kVA UPS Module with 12 pulse rectifier – Top and base view............................................................... 6-7
6.1.7 300kVA UPS Module with 12 pulse rectifier with Top Cable entry option .................................................. 6-8
6.1.8 300kVA UPS Module with 12 pulse rectifier with Top Cable entry option - Top and base view ................ 6-9
6.1.9 300kVA UPS Module with 6 pulse rectifier - open door view..................................................................... 6-10
6.1.10 Cable connections for 300 kVA UPS............................................................................................................ 6-11
6.1.11 Internal connections between the 300 kVA UPS and the 12 pulse cabinet.................................................. 6-12
6.1.12 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier).............................................................. 6-13
6.1.13 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier) – base and top view ............................ 6-14
6.1.14 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier) with Top Cable entry option............... 6-15
6.1.15 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier) with Top Cable entry option – base and
top view .......................................................................................................................................................... 6-16
6.1.16 400 kVA UPS – Front view open doors........................................................................................................ 6-17
6.1.17 Cable connections for 400 kVA UPS (Rectifier/Static Switch cabinet)....................................................... 6-18
6.1.18 400 kVA UPS – View of auxiliary, control signals and power connections between the 400 kVA UPS
cabinets........................................................................................................................................................... 6-19
6.1.19 Top Cable entry option .................................................................................................................................. 6-20
6.1.20 Cable connections for 300 / 400 kVA UPS with Battery Circuit Breaker ................................................... 6-21
6.1.21 Maintenance Bypass cabinet (Option) – general view.................................................................................. 6-22
6.1.22 Maintenance Bypass cabinet (Option) – Front view with open doors......................................................... 6-23
6.1.23 RS232 Communications for 300-400 kVA UPS (Option) – Modem and NIC card locations.................... 6-24
Page 9
Installation Manual Liebert Hipulse E Single or '1+N' UPS System
(07/04) Page ix
Part II – User Manual .......................................................... 7-1
7 Chapter 7 - General Description ...................................................................................................................... 7-1
7.1 Introduction ...................................................................................................................................................... 7-1
7.2 Design Concept ................................................................................................................................................ 7-1
7.2.1 Introduction ...................................................................................................................................................... 7-1
7.2.2 Bypass supplies ................................................................................................................................................ 7-2
7.2.3 System Control Philosophy.............................................................................................................................. 7-3
7.2.4 ECOMODE (for single UPS only) .................................................................................................................. 7-4
7.2.5 UPS Power Switch Configuration ................................................................................................................... 7-4
7.2.6 Battery circuit breaker...................................................................................................................................... 7-4
7.2.7 Battery temperature compensation .................................................................................................................. 7-4
7.2.8 Socket outlet..................................................................................................................................................... 7-4
7.2.9 System Expansion ............................................................................................................................................ 7-5
7.2.10 Frequency Converter........................................................................................................................................ 7-5
8 Chapter 8 - Operator Control and Display Panel............................................................................................. 8-1
8.1 Introduction ...................................................................................................................................................... 8-1
8.1.1 Operator control panel ..................................................................................................................................... 8-2
8.1.2 The Menu Options ........................................................................................................................................... 8-6
9 Chapter 9 - Operating Instructions................................................................................................................... 9-1
9.1 Introduction ...................................................................................................................................................... 9-1
9.1.1 General notes.................................................................................................................................................... 9-1
9.1.2 Power Switches ................................................................................................................................................ 9-1
9.2 Procedure for UPS Start-Up: without interrupting power to the load ........................................................... 9-3
9.3 Procedure for UPS Start-Up: without power initially supplied to the load .................................................... 9-5
9.4 Procedure for Switching the UPS into a Maintenance Bypass condition from normal operation................. 9-7
9.5 Procedure for Switching the UPS ON from a Maintenance Power condition................................................ 9-8
9.6 Procedure for completely powering down a UPS ........................................................................................... 9-9
9.7 RESET procedure following shutdown of automatic switching or emergency stop (EPO action). .......... 9-10
9.8 Adding a single Module to an existing system.............................................................................................. 9-11
9.9 Procedure to completely switch ON\OFF the UPS at the ups display control panel. .................................. 9-11
9.10 Procedure to switch ON\OFF the inverter at ups display control panel. ...................................................... 9-13
9.11 Setting the Battery Test.................................................................................................................................. 9-14
9.12 Language Selection ........................................................................................................................................ 9-15
9.13 Changing the current Date and Time............................................................................................................. 9-15
9.14 Alarm History................................................................................................................................................. 9-16
9.15 Hours run meter.............................................................................................................................................. 9-16
10 Chapter 10 - Display Panel Interpretation ..................................................................................................... 10-1
10.1 LED interpretation ......................................................................................................................................... 10-1
10.2 Display panel messages.................................................................................................................................. 10-3
11 Chapter 11 - 1+N System............................................................................................................................... 11-1
11.1 Installation procedure..................................................................................................................................... 11-1
11.1.1 Preliminary Checks ........................................................................................................................................ 11-1
11.1.2 Protective Devices, power and control cables ............................................................................................... 11-1
11.1.3 Emergency Stop (EPO).................................................................................................................................. 11-1
11.2 Operating Instruction ..................................................................................................................................... 11-2
11.2.1 System Start-Up and shutdown procedures................................................................................................... 11-2
11.2.2 Procedure for Switching the UPS system into a Maintenance Bypass condition from normal operation -
1+ 1 Configuration (two UPS's with parallel redundant connection) ......................................................... 11-5
11.2.3 Procedure for Switching the UPS system into normal operation from a Maintenance Bypass condition -
1+ 1 Configuration (two UPS's with parallel redundant connection) ......................................................... 11-7
11.2.4 Procedure for Switching the UPS system into a Maintenance Bypass condition from normal operation
- 1 + N Configuration (> two UPS's) or two UPS's with parallel power connection.................................. 11-8
11.2.5 Procedure for Switching the UPS system into normal operation from a Maintenance Bypass condition
- 1 + N Configuration (> two UPS's) or two UPS's with parallel power connection................................ 11-10
11.2.6 SWITCHING THE SYSTEM ON FROM A MAINTENANCE POWER DOWN CONDITION. ........ 11-11
11.3 Display panel message interpretation '1+N' System.................................................................................... 11-13
12 Chapter 12 - Additional Equipment............................................................................................................... 12-1
Page 10
Single or '1+N' UPS System Liebert Hipulse E Installation Manual
Page x (07/04)
12.1 LBS Control System ...................................................................................................................................... 12-2
12.1.1 OPERATOR CONTROLS............................................................................................................................ 12-2
12.1.2 OPERATOR PROCEDURES....................................................................................................................... 12-2
12.2 Interface Alarm Boards.................................................................................................................................. 12-3
12.2.1 Introduction .................................................................................................................................................... 12-3
12.2.2 Board Installation – 4590055P ...................................................................................................................... 12-3
12.2.3 Board Installation – 4590056Q...................................................................................................................... 12-3
12.3 UPS I\O AS400 Alarm Interface Board (P\N 4590055P) ............................................................................ 12-4
12.3.1 Remote Control Inputs (X5) .......................................................................................................................... 12-4
12.3.2 AS 400 Interface (X3).................................................................................................................................... 12-4
12.3.3 Alarm Outputs (X4) ....................................................................................................................................... 12-5
12.3.4 X2 Extension.................................................................................................................................................. 12-5
12.4 UPS Extension Alarm Interface Board (P\N 4590056Q) ............................................................................. 12-7
12.4.1 Standard Alarm Outputs................................................................................................................................. 12-7
X3 12-7
12.4.2 Field defined alarms (X3 auxiliary terminal board)...................................................................................... 12-8
12.5 EMC Class A filter......................................................................................................................................... 12-9
12.6 Input Harmonic Filter (5th and 11th)............................................................................................................. 12-9
12.7 Additional autotransformer............................................................................................................................ 12-9
12.8 Input isolation transformer (IT) ................................................................................................................... 12-10
12.9 Degree of protection for the UPS enclosure................................................................................................ 12-10
12.10 RS232 communications ............................................................................................................................... 12-11
12.10.1 RS232 communication kit............................................................................................................................ 12-11
12.10.2 Modem.......................................................................................................................................................... 12-11
12.10.3 Communication kit – installation with several modules ............................................................................. 12-11
12.10.4 NIC (Network Interface Card)..................................................................................................................... 12-12
12.10.5 Modbus/Jbus ................................................................................................................................................ 12-12
12.10.6 Remote control panel ................................................................................................................................... 12-13
Page 11
Installation Manual Liebert Hipulse E Chapter 1 - Installation Procedure Single or '1+N' UPS System Installation (Mechanical)
(07/04) Page 1-1
Part I – Installation Manual
1 Chapter 1 - Installation Procedure
1.1 Introduction
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
WARNING
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with details of its own mechanical and electrical installation.
WARNING
Battery hazards
Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400 VDC and is potentially lethal.
Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and all metal objects. Only use tools with insulated handles. Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin the affected area should be washed immediately with water. For more details, see Chapter 3 ‘Battery Installation’
Note
The UPS System can also be connected to an IT (isolated neutral) power system.
This section describes the UPS system's environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site has its peculiarities, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide as to the general procedures and practices that should be observed by the installing engineer.
Page 12
Chapter 1 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Mechanical) Single or '1+N' UPS System
Page 1-2 (07/04)
1.2 Environmental considerations
1.2.1 UPS location
The UPS module should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Chapter 5 UPS Environmental). All models in the 'Hipulse' UPS range are cooled with the aid of internal fans. Cooling air enters the devices through the ventilation grids located at various points on the cabinet and is released through the grids on the roof. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS via the floor void. If necessary, a system of extractor fans should be installed to aid cooling-air flow, and a suitable air filtration system used where the UPS is to operate in a dirty environment.
Note 1: When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS.
Note 2: Power losses from the System which may be used in an air conditioning system are intended for operation using the Inverter, as in the ECOMODE configuration they would be undersized.
Air filters:
The optional dust filters can be installed behind the air intake in the front door(s). By opening the front door, the filters can be changed easily without exposing personnel to high voltage. A schedule for inspection of the air filters is required. The period between inspections will depend upon environmental conditions.
1.2.2 Battery location
Temperature is a major factor in determining the battery life and capacity. Battery manufacturers quote figures for an operating temperature of 20°C. Operating above this temperature will reduce the battery life, operation below this temperature will reduce the battery capacity. On a normal installation the battery temperature is maintained between 15°C and 25°C. Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Keep batteries away from main heat sources or main air inlets etc. If the batteries are rack-mounted, or otherwise located remote to the main UPS cabinet, a battery circuit breaker must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible. The battery circuit breaker controller board (P\N° 4520079F) must be used in conjunction with the battery circuit breaker. This control board, which should be located near to the battery circuit breaker, interfaces with the UPS control system.
1.2.3 Storing
If unit is to be stored before installation, it is recommended to store the unit in a dry environment with temperatures in the range of -25°C to 70°C. Use original packing materials or other suitable means to keep the unit clean.
Page 13
Installation Manual Liebert Hipulse E Chapter 1 - Installation Procedure Single or '1+N' UPS System Installation (Mechanical)
(07/04) Page 1-3
1.3 Mechanical Considerations
1.3.1 System composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements
- e.g. UPS cabinet, External Bypass cabinet. In general, all the cabinets used in a particular installation are of the same height and designed to be positioned side-by-side to form an aesthetically appealing equipment suite. Refer to the drawings provided in Chapter 6 for the positioning of the cabinets described below.
1.3.2 Frame and enclosure
The UPS is housed in an IP20 enclosure, designed for floor mounting. The top and side removable panels are secured to the chassis by screws. The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. Front door can be opened at 180° for better Service and more flexibility in installations. The UPS comes with an operator control panel, which provides basic operational status and alarm information. The cabinet houses the power components, control boards and fuses. The cabinet is structurally designed to handle lifting from the base. Cooling is by internal removable fans.
1.3.3 300 kVA UPS with rectifier 6 pulses
The 300 kVA UPS consists of a single cabinet.
1.3.4 300 kVA UPS with rectifier 12 pulses
While the 6 pulse 300 kVA UPS consists of a single cabinet, the 12 pulse 300 kVA UPS is divided into two cabinets for easier transport and positioning at the installation site; one cabinet contains the standard UPS sections, while the other contains the section including the second rectifier bridge, the magnetic components and the control circuits. Once the equipment is in position, and before it is anchored in place permanently
, make the electrical power and
auxiliary connections and mechanically join the two cabinets of the UPS.
1.3.5 400 kVA UPS with rectifier 6 pulses
The 400 kVA UPS is split into two cabinets to allow easier transportation and positioning, one houses the Inverter and the other houses the Rectifier/Static Bypass. Once the equipment is positioned and prior to fixing the equipment in place, the two cabinet have to be bolted together and the interlinking power and control cable connections made.
1.3.6 400 kVA UPS with rectifier 12 pulses
The 12 pulse 400 kVA UPS also consists of two cabinets, but while it has the same overall length as the 6 pulse version, it incorporates the 12 pulse section in the Rectifier/ Static Bypass cabinet.
1.3.7 Moving the cabinets
The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).
WARNING
Ensure any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity.
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL.
Ensure that the UPS weight is within the designated surface weight loading (Kg/cm2) of any handling equipment. See the UPS specification for weight details - see Table 5-3. UPS and optional cabinets (battery cabinets, top cable entry cabinets, etc.) can be handled by means of a fork lift or similar equipment. For operations with a fork lift, it is necessary to remove either the lower protection panel located at the base of the cabinet and rear panels (or both side panels). Be aware of the location of the load supporting feet so as not to damage them, refer to installation drawings in Chapter 6. In the eventuality that the equipment cannot be moved by fork lift, then rollers should be used. Because the weight distribution in the cabinet is uneven, use extreme care during handling and transporting. When moving the unit by forklift, lift the unit from the rear so as to protect the front panel. Do not exceed a 15 degrees tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.
The handling with straps is not authorised. Note: Do not move the battery cabinet with the batteries fitted.
Page 14
Chapter 1 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Mechanical) Single or '1+N' UPS System
Page 1-4 (07/04)
1.3.8 Clearances
Liebert Hipulse E has no ventilation grills at either side or at the rear of the UPS. To enable routine tightening of power terminations within the UPS, it is recommended that service access of 800 mm (minimum) be allowed for at the rear. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 800 mm between the top of the UPS and the ceiling of the room in which it is installed to permit adequate circulation of air coming out of the unit.
1.3.9 Floor installation
The installation diagrams in Chapter 6 of this manual identify the location of the holes in the base plate through which the equipment can be bolted to the floor. If the equipment is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal.
1.3.10 Fixing of the magnetic components
Before the equipment is in place, remove the transportation restraints that hold the input inductance and output transformer in place.
1.3.11 Cable entry
Cables can enter the UPS cabinet from bottom.
Note
When selecting the power cables for side entry to a module located on a solid floor, consideration must be given to the minimum permissible radius of the proposed cables to ensure that they can be fashioned to reach the UPS connection busbars.
1.3.12 Top Cable entry
Optionally a top cable entry extension may be used, see the figures in Chapter 6. The cabinet extends t he overall width of the UPS and permits connection of all incoming AC/DC power cables from above through horizontally supported copper bars. The top cable entry option is fitted on the side of the UPS cabinet and is supplied without side panels; the side cover from the UPS being used.
The cabinet with cables coming in from the top for the 300 kVA UPS must be positioned on the right side, whereas the cabinet for the 400 kVA UPS must be positioned on the left side.
This facilitates cable entry through the top aluminium panel after the appropriate cable entry holes have been cut. Roof­mounted eyebolts are fitted on shipment to optional cabinet, to enable the cabinet to be crane-handled. These can be removed once the equipment has been finally positioned.
Note 1: The top cable entry also includes the power connection cables between the cabinet and the UPS.
Note 2: For special installation requirements regarding the position of the optional unit for incoming cables entering
from the top, special alternatives to the standard position are available.
1.4 Preliminary Checks
Before you install the UPS hardware you should carry out the following preliminary checks:
1. Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.
2. Remove any packaging debris, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper immediately.
1.4.1 Identification
The equipment supplied has an identification tag on the back of the main door reporting: the type, size, and main calibration parameters of the UPS. A metal disk fastened to the inside top of the cabinet is engraved with its serial number.
Record the model and serial numbers in the table at the beginning of this installation manual. A record of this information is necessary should servicing be required.
Page 15
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-1
2 Chapter 2 - Installation (Electrical)
The UPS requires both «power» and «control» cabling once it has been mechanically installed. All «control» cables, whether screened or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected.
2.1 Power Cabling
WARNING
BEFORE CABLING-UP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL ISOLATORS THAT CONNECT THE UPS INPUT/BYPASS SUPPLY TO THE MAINS DISTRIBUTION PANEL. CHECK THAT THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY WARNING SIGNS TO PREVENT THEIR INADVERTENT OPERATION.
For cable entry, refer to section 1.3.11.
2.1.1 System Configuration
The main factors affecting the choice and size of cable are voltage, current (also taking into account overcurrent), room temperature and conditions of installation of the cable.
Note: Correct cable size must also take into account the system’s overload capacity (see Chapter 5 – Technical Specifications: - Electrical Characteristics).
The power cables of the system must be size with respect to the following description:
Module input cables
The module input cables must be sized for the maximum input current, including the maximum battery recharge current, given in table 2-1, with respect to the module rating and the input a.c. voltage.
WARNING (300 kVA UPS)
Note 1: For split Bypass operation ensure that the busbars (*) between Bypass and Rectifier input are removed.
Note2: With a Class ‘A’ EMC filter (optional) and a ‘common’ input configuration, the capacitors on the
Rectifier input bars must be removed.
WARNING (400 kVA UPS)
Note: for a common input power configuration (single supply) interconnecting cables are required, connecting the
rectifier input with the bypass input (links about 1.5m long), with cables sized for the maximum input current in table 2-1.
Module Bypass and output cables
The bypass and output cables must be sized for the nominal output current, given in table 2-1, with respect to the module rating and the output a.c. voltage.
Battery cables
Each UPS module has its own battery, which is connected using two cables, one positive and one negative. The battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in table 2-1 with respect to the module rating.
Page 16
Chapter 2 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Electrical) Single or '1+N' UPS System
Page 2-2 (07/04)
2.1.2 Table for determining power cable size
The table below gives nominal currents for determining the size of UPS power cables. Other factors, which must be taken into consideration include cable route length, coordination with protective devices, etc.
The power cables can be sized to suit the UPS module rating according to the table below:
NOMINAL CURRENT: Amps BUSBAR STUD SIZE
Input Mains
with full battery recharge
(subtract 5% for 12-
pulse)
Bypass\Output
at full load
Input/
Cables
Bypass/
Output Cables
Battery
Cables
Torque
Load (Nm)
UPS
RATING
(kVA)
380V 400V 415V 380V 400V 415V
Battery at minimum
battery
voltage
(400Vac)
*
300
632 600 578 470 446 430 775
M12 (Bolt) Ø13 (holes)
45
400
842 800 771 627 595 574 1030 M12 Ø13 M10 Ø11 M12 Ø13
45 (M12) 26 (M10)
Table 2-1 UPS Module cabinet power cable rating
*Maximum battery discharge current at 380VAC supply increase by 3%, and for a 415VAC supply decrease by 3%
2.1.3 General Notes
The following are guidelines only and superseded by local regulations and codes of practice where applicable:
1. Take special care when determining the size of the neutral cable, as current circulating on the neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the values given in the ‘UPS Electrical characteristics’ table in Chapter 5.
2. The earth conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The earth cable connecting the UPS to the main ground system must follow the most direct route possible.
3. Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.
4. When sizing battery cables, a maximum volt drop of 3Vd.c. is permissible at the current ratings given in Table 2-1.
5. In most installations, especially those concerning parallel multi-module systems, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output rather than being connected directly to the UPS itself. Where this is the case the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.
6. When laying the power cables, do not form coils, so as to avoid increasing formation of electromagnetic interference.
7. In parallel multi-module systems, the output cable of each unit should be kept as equi-distant as possible between the unit output terminals and the parallel distribution busbar to prevent from affecting the shared current.
2.1.4 Cable connections
The rectifier input, bypass, output and battery power cables ( all require lug type terminations ) are connected to busbars situated below the power isolator switches - as shown in Chapter 6. These are accessible when the power compartment cover plate is removed. A terminal block X3 is used for connecting the control cables to the battery circuit breaker and a second terminal block X4 is used for the external emergency stop facility, external OFF inverter, ext. Bypass, etc. these are female spade type connections ( Fast-on 6,3 x 0,8 ) and are described later in Section 2.3.
2.1.5 Safety earth
The safety earth bus-bar is located near the input and output power supply connections as shown in Chapter 6. The safety earth cable must be connected to the earth bus-bar and bonded to each cabinet in the system. All cabinets and cable trunking should be earthed in accordance with local regulations.
Note: Proper grounding considerably reduces problems in systems caused by electromagnetic interference.
WARNING
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC SHOCK HAZARD TO PERSONNEL, OR THE RISK OF FIRE, SHOULD AN EARTH FAULT OCCUR.
Page 17
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-3
2.1.6 Protective devices
For safety reasons, it is necessary to install, external to the UPS system, circuit breaking protective devices in the input a.c. supply and towards the battery. Given that every installation has its own characteristics, this chapter provides general useful information for qualified installation engineers, with knowledge of operating practices, of regulatory standards, and of the equipment to be installed.
Rectifier and Bypass input supply of the UPS:
Protection against excessive overcurrents and short circuits in the mains supply input:
These inputs must be protected, installing suitable protective devices at the distribution panel of the incoming main supply, considering that the protection should discriminate with overload capacity of the system (see Chapter 5 Specification: - Electrical Characteristics).
Split bypass: in the case of a split bypass being used, separate protective devices should be installed in the incoming mains distribution panel. The protective devices must be selected for the nominal input current, with respect to the UPS rating and the input a.c. supply voltage as given in table 2-1.
Protection against earth faults (RCD devices):
In the event of a differential (RCD) device being installed upstream of the input supply, one must take into account the transient and steady state earth leakage currents that are produced during start-up of the UPS. The presence of an RFI suppression filter inside the UPS, determines a residual earth current greater than 3.5 mA and less than 1000 mA. Residual current circuit breakers (RCCB) must be sensitive to d.c. unidirectional pulses (class A) in the network and insensitive to transient current pulses. They are identified by the symbols respectively:
These isolators must have an average sensitivity, possibly adjustable between 0.3 and 1A. It is recommended that the selectivity with every differential switch be verified both upstream of the input distribution board and downstream (towards the load).
Parallel 1+N:
Use of differential circuit breakers on UPS unit inputs in a configuration with separate inputs and one battery for each unit requires installation of a common device only on the system bypass mains. Use of differential circuit breakers on UPS unit inputs sharing a common battery requires installation of a device common to all the input lines. If inputs are configured for separate mains, a common device will also be required for all System bypass mains.
UPS Battery:
The UPS Battery is protected by means of a control circuit that operates the tripping mechanism of an automatic circuit breaking device (having a variable trip setting). The tripping mechanism using an undervoltage release coil that operates on a preset minimum voltage level.
The circuit breaker is essential for maintenance of the battery and is normally located near to the battery installation. The characteristics and operation of the automatic circuit breaker are given in Chapter 3.
Output of the System:
In the eventuality that an external distribution panel is used for load distribution, the selection of protective device must provide discrimination with those that are used at the input to the UPS module.
Page 18
Chapter 2 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Electrical) Single or '1+N' UPS System
Page 2-4 (07/04)
2.1.7 Cabling procedure for 300 kVA UPS with 6 pulse rectifier (or 12 pulse rectifier)
Note on 12-pulse UPS: before proceeding with wiring procedures, make the connections between the two cabinets,
referring to the detailed description provided in section 2.1.8 – 12-phase wiring procedure (for300 kVA UPS).
Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure.
Study the connection diagram as illustrated in Chapter 6.
1. Verify that the UPS equipment is totally isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.
2. Open the door(s) to the UPS cabinet and remove the lower protective cover to gain access to the connections bars. The protective cover on the UPS cabinet must be removed subsequent to removal of the handles on the power isolators.
3. Connect the safety earth and any necessary bonding earth cables to the copper earth busbar located on the floor of the equipment below the power connections.
The safety earth cable must be connected to the earth busbar and bonded to each rack\cabinet in the system.
Note: The earthing and neutral bonding arrangement must be in accordance with local and national codes of practice.
Common Input Connections
4. For common bypass and rectifier inputs, connect the a.c. input supply cables between the mains distribution panel and the UPS bypass input supply busbars (U3-V3-W3-N3 terminals) and tighten the connections to 45 Nm (M12 Bolts).
Note: With a Class ‘A’ EMC filter (optional) and a ‘common’ input configuration, the capacitors on the Rectifier input bars must be removed.
ENSURE CORRECT PHASE ROTATION.
Split Bypass Connections
5. If a 'split-bypass' configuration is used, connect the a.c. input supply cables to the rectifier input busbars (U1­V1-W1 terminals) and the a.c. bypass supply cables to the bypass input basbars (U3-V3-W3-N3 terminals) and tighten the connections to 45 Nm (M12 Bolts).
WARNING
Ensure that any links ( ) fitted between rectifier input and bypass busbars are
removed (see figures 6.1.10)
ENSURE CORRECT PHASE ROTATION.
Page 19
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-5
Output System Connections
6. Connect the system output cables between the UPS output busbars (U2-V2-W2 N2 terminals) and the critical load and tighten the connections to 45 Nm (M12 Bolt).
ENSURE CORRECT PHASE ROTATION.
WARNING
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then ensure that
the system output cables are safely isolated at their ends.
UPS Battery Connections
7. Connect the battery cables between the UPS terminals (+\-) and its associated battery circuit breaker (as shown in Chapter 6).
Note: When connecting the cables between the battery extremities to the circuit breaker always connect the circuit breaker end of the cable first.
The auxiliary cables of the battery must be screened and double insulated. Connect screened auxiliary cables from each battery circuit breaker controller board (P/N 4520079F) to the UPS auxiliary terminal block (X3) (as shown in Chapter 6) of their metal frame of the Battery circuit breaker box (if used), not of UPS.
OBSERVE THE BATTERY CABLE POLARITY.
WARNING
Do not close the Battery circuit breaker before the equipment has been commissioned
Auxiliary Connections
8. Connect the auxiliary cables of any external interface/signals to the respective connections of the output auxiliary terminal block (X4) (see Chapter 6).
9. Refit the lower metal protective cover and the handles on the UPS power isolators.
Page 20
Chapter 2 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Electrical) Single or '1+N' UPS System
Page 2-6 (07/04)
2.1.8 12-phase wiring procedure (for 300 kVA UPS)
Important
The operations described in this section must be performed by authorised electricians or qualified technical personnel. If you have any difficulties do not hesitate to contact our Customer Service & Support department at the address given at the beginning of this manual.
12 Pulse UPS
Once the equipment is in position, and before it is anchored in place permanently
, make the electrical power and auxiliary connections and mechanically join the two cabinets of the (12 pulse) UPS. Refer to the drawings provided in Chapter 6 for guidance during connection.
Power connections
1. Connect the wires provided (+\-) from the UPS rectifier bridge to the connection bar of the second rectifier bridge (optional 12 pulse cabinet). The wire numbered 215 (+) must be connected to the positive bar, while the wire numbered 214 (-) must be connected to the negative bar. Perform the connection in the order specified.
2. Connect the wires provided (205\206\207) from transformer T2 (in the optional 12 pulse cabinet) to the L1 ­A’\B’\C’ inductor connection bar on the UPS. The wire numbered 205 must be connected to the terminal marked A’, wire 206 to B’, and wire 207 to C’. Perform the connection in the order specified.
Auxiliary connections
3. Insert the flat cable (W13) provided in the optional 12 pulse cabinet to the fixed connector (X4) on the Rectifier Logic card (code 4520074A) in the UPS cabinet. Follow connection directions precisely.
4. Insert the loose connectors provided in the UPS cabinet to the fixed connectors in the optional 12 pulse cabinet. The loose connector (X25) must be inserted in the fixed 6-way connector; repeat the same operation for the loose connector (X24) on the fixed 4-way connector.
5. The two units must be positioned side by side and bolted together using the holes on the uprights at the sides of the cabinet.
6. Proceed to make input connections as described in the previous section.
Page 21
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-7
2.1.9 Cabling procedure for 400 kVA UPS with 6 pulse rectifier (or 12 pulse rectifier)
Important
The operations described in this section must be performed by authorised electricians or qualified technical personnel. If you have any difficulties do not hesitate to contact our Customer Service & Support department at the address given at the beginning of this manual.
Once the equipment is positioned and prior to fixing the equipment in place, it is necessary to make the electrical and auxiliary connections between the two cabinets that make up the UPS.
Electrical power connections and auxiliary connections between the two cabinets must be made from the front of the UPS.
Refer to the drawings provided in Chapter 6 for guidance during connection.
Power connections between the rectifier cabinet and the inverter cabinet
1. Open the inside doors to access the cabinet connection bars.
2. Connect the copper plaits supplied coming out of transformer T1 in the inverter cabinet to the connection bars located alongside the right-hand rear upright of the static switch cabinet. First connect plait 18 from ‘T1-c’ to terminal I3 of the static switch unit; next connect plait 17 from ‘T1-b’ to terminal I2, then connect plait 16 from ‘T1-a’ to terminal I1 of the static switch unit, and finally connect plait 25 from ‘T1-N’ to the Neutral bar. Perform the connection in the order specified.
3. Connect the prepared plaits (+/-) already supplied coming out of the UPS rectifier bridge to the inverter cabinet connection bar. Be careful to comply with connection polarity.
Note: Make all connections with a torque of 45 Nm for M12 bolts.
Auxiliary connections between the rectifier cabinet and the inverter cabinet
Open the inner door on the left side of the inverter cabinet and make the following auxiliary connections:
4. Connect the ribbon cables already fitted in the inverter cabinet to the respective connectors in the rectifier cabinet. The ribbon cable W20 must be connected to X47, while the ribbon cable W21 must be connected to X48. Respect the indications of these connections rigorously.
5. Connect the loose lead cables in the inverter cabinet to their respective connectors in the rectifier cabinet. The loose lead cables X39 is connected to 12 way connector socket; repeat the same operation for the loose lead cable X40, connecting to the 4 way connector socket.
Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure.
Study the connection diagram as illustrated in Chapter 6.
6. Verify that the UPS equipment is totally isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.
7. Open the door(s) to the UPS cabinet and remove the lower protective cover to gain access to the connections bars.
8. Connect the safety earth and any necessary bonding earth cables to the copper earth busbar located on the floor of the equipment below the power connections.
The safety earth cable must be connected to the earth busbar and bonded to each rack\cabinet in the system.
Note: The earthing and neutral bonding arrangement must be in accordance with local and national codes practice.
Page 22
Chapter 2 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Electrical) Single or '1+N' UPS System
Page 2-8 (07/04)
Common Input Connections
9. For common bypass and rectifier inputs, connect the a.c. input supply cables between the mains distribution panel and the UPS rectifier input busbars (U1-V1-W1 terminals) and tighten the connections to 45 Nm (M12 Bolt). Additional connecting cables must be used (see note in paragraph 2.1.1) from the rectifier input bars (U1-V1-W1) to the bypass input bars (U3-V3-W3). The input neutral cable must be connected to the bypass input bar (N3).
Note: It is important that the connections between the input cables from the external distribution box and the additional cables (links) are connected to the rectifier input bars (U1-V1-W1).
ENSURE CORRECT PHASE ROTATION.
Split Bypass Connections
10. If a 'split-bypass' configuration is used, connect the a.c. input supply cables to the rectifier input busbars (U1­V1-W1 terminals) and the a.c. bypass supply cables to the bypass input basbars (U3-V3-W3-N3 terminals) and tighten the connections to 45 Nm (M12 Bolts).
ENSURE CORRECT PHASE ROTATION.
Output System Connections
11. Connect the system output cables between the UPS output busbars (U2-V2-W2 N2 terminals) and the critical load and tighten the connections to 45 Nm (M12 Bolt).
ENSURE CORRECT PHASE ROTATION.
WARNING
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then ensure that
the system output cables are safely isolated at their ends.
UPS Battery Connections
12. Connect the battery cables between the UPS terminals (+\-) and its associated battery circuit breaker (as shown in Chapter 6).
Note: When connecting the cables between the battery extremities to the circuit breaker always connect the circuit breaker end of the cable first.
The auxiliary cables of the battery must be screened and double insulated. Connect screened auxiliary cables from each battery circuit breaker controller board (P/N 4520079F) to the UPS auxiliary terminal block (X3) (as shown in Chapter 6) of their metal frame of the battery circuit breaker box (if used), not of UPS.
OBSERVE THE BATTERY CABLE POLARITY.
WARNING
Do not close the Battery circuit breaker before the equipment has been commissioned
Auxiliary Connections
13. Connect the auxiliary cables of any external interface/signals to the respective connections of the output auxiliary terminal block (X4) (see Chapter 6).
14. Refit the lower metal protective cover.
Page 23
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-9
2.2 Distance from floor to connection point on the equipment:
UPS
UPS
300 kVA
minimum distance (mm)
UPS
400 kVA
minimum distance (mm)
Rectifier a.c. Input supply
345 360
Bypass a.c. Input supply
345 480
UPS Output a.c.
345 800
Battery Power
345 460
Auxiliary cables: Battery Control / Temp. Compensation (X3)
570 330
Communications to AS400/External Alarm monitor
750 350
Remote Emergency Power Off (EPO) (X4)
450 400
Earth 350 360
Table 2-2
Page 24
Chapter 2 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Electrical) Single or '1+N' UPS System
Page 2-10 (07/04)
2.3 Control cables
2.3.1 Battery Control
The battery circuit breaker is controlled by the battery circuit breaker controller board, which is located within the battery cabinet — or adjacent to the battery circuit breaker when the batteries are rack-mounted. This board controls the circuit breaker's undervolt release coil and also provides a path for the circuit breaker auxiliary contacts to signal the circuit breaker status back to the UPS control logic. All connections between the controller board and the UPS module are made via the auxiliary terminal block (X3), which is located in the base of the UPS cabinet.
Figure 2-1 Auxiliary terminal block detail
Connect the battery circuit breaker control and temperature compensation cables between the UPS auxiliary terminal block and battery circuit breaker controller board as shown in figure 2-1. These cable must be shielded and double insulated, shield should be connected at protective earth of battery cabinet or battery breaker, not at UPS.
Caution
If battery temperature compensation is not used the system must be de-activated by the commissioning engineer.
T
Page 25
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-11
Auxiliary terminal block X3 at UPS.
X3
terminal
reference
Reference label Description
2 Common Temperature sensor common (0V)
3 T Batt. Temperature sensor signal
4 Common Common (0V)
5 Batt. Sw Battery Circuit Breaker open
6 Bat Trp Battery Circuit Breaker trip control
Table 2-3
Note: The auxiliary cables of the battery must be screened and double insulated. The screen is connected to the earth of the battery circuit breaker cabinet or supporting rack. Use multiple-core shielded cables with a section of 0.5 to 1 mm
2
.
Connect the cables with the Fast-on 6.3x 0.8 mm terminals (female).
2.3.2
Auxiliary terminal block X4
Next to terminal board X3 there is a second terminal board which may be used for auxiliary connection of equipment or devices external to the UPS. Use the following table to identify the terminals corresponding to the equipment or device to be connected.
Auxiliary terminal block X4 at UPS.
X4
terminal
reference
Reference
label
Description
1-2 Ext. OFF Inv
Remotely provides control for switching off the inverter. The external contact employed must be normally open with the input switch open.
3-4 Ext. Sw Out
Indication to be provided at the UPS to note the opening of an external module output isolator. The external contact employed must be normally open with the output switch open. If unused, leave the standard connectors in place.
5-6 Ext. EPO
Remotely provides control for switching off the UPS using a remote emergency button. Normally closed contact. If unused, leave the standard connectors in place.
7-8 Ext. BYP
Indication to be provided at the UPS to note the opening of an external maintenance bypass switch. The external contact employed must be normally closed with the external maintenance bypass switch open. If unused, leave the standard connectors in place.
9-10 Back Feed
Signal from the UPS to indicate a return flow of energy in the bypass mains. The contact employed is normally open; if it is closed, this means a failure has been detected. Refer to point 2.3.4 on the next page.
11-12 Int EPO
One contact is available for opening an external EPO switch assembled upstream of the UPS. The normally closed contact is opened when the internal emergency button is pressed. See Note 2 on the next page.
Table 2-4
Note: All auxiliary cables of terminal block X4 must be double insulated. The cross-sectional area of the auxiliary cables is from 0.5 to 1 mm
2
. Connect the cables with the Fast-on 6.3x 0.8 mm terminals (female). Maximum contact rating on auxiliary terminals: 50 Vdc @ 1 Amp.
Page 26
Chapter 2 - Installation Procedure Liebert Hipulse E Installation Manual Installation (Electrical) Single or '1+N' UPS System
Page 2-12 (07/04)
Figure 2-2 Battery Connection
2.3.3 Emergency Stop
If an external Emergency Stop facility is required it is connected to terminals 5 & 6 of the Auxiliary Terminal Block (X4) and connected to the `normally closed' remote stop switch between these two terminals using shielded cable. If this facility is not used then terminals 5 & 6 must be linked-out as shown in Figure 2-1.
Note 1
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass and trips the battery circuit breaker. It does not however internally disconnect the input mains supply. If required, this additional action can be facilitated by feeding the UPS input via an isolator which can be tripped by a second contact of the Emergency Stop switch.
Note 2
Terminals 11 & 12 of the Auxiliary Terminal Block(X4) are connected to a «normally closed» contact of the UPS Display Panel emergency Stop button and go open circuit when the button is pressed. This output can be used as part of a wider Emergency Stop system to initiate an external action (such as tripping an external supply breaker).
Page 27
Installation Manual Liebert Hipulse E Chapter 2 - Installation Procedure Single or '1+N' UPS System Installation (Electrical)
(07/04) Page 2-13
2.3.4 Back Feed Protection
Using an auxiliary terminal (pins 9-10 of connector X4) the UPS provides a normally open contact to be used for opening of an external circuit protection device, to protect the operator against backfeed of energy resulting from a short-circuit fault of the Bypass line SCRs. This auxiliary contact can be used, for example, in series with an external low voltage source, in order to supply the trip coil of an automatic circuit breaking device, located upstream of the UPS Bypass mains input. In the event of energy being backfed the auxiliary circuit will activate closing the normally open contact and as a result opening of the external circuit breaking device; the UPS is disconnected from the Bypass mains supply. The electrical characteristics of the auxiliary contact are 50V (a.c. or d.c.) @ 1 Amp.
2.3.5 Fan Failure Alarm Indicator (Optional)
Liebert Hipulse E is designed to allow the installation of a device to control the correct operation of fans. The kit includes the Fan Failure Alarm Indicator, interconnection components (loose and anchored connector) and related wiring. This function employs an electromagnetic device installed on each individual fan, which gives an alarm signal on the operator display panel and turns on a Led on the Fan Failure Alarm Indicator in the event that a fan slows down or shuts down entirely. If an alarm displays on the operator control panel, determine the physical location of the faulty fan using the identification lable placed next to the "Fan Failure Alarm Indicator card". A remote signal may be provided by installing appropriate alarm interface cards.
2.3.6 Battery ground fault detection (Optional)
To guarantee a continuously uninterruptible power supply to the critical load, single module UPS or parallel UPS systems are provided with external batteries, so the battery insulation to PE (Protection Earth) shall be monitored to be in a safe range. For this purpose the battery system is fitted with a DC monitoring device to detect and eliminate earth faults to ensure operational continuity, this is included in a Battery Fault Detection Set. The Battery Ground Fault Detection is the same for all UPS sizes. When a battery ground fault is detected, an alarm will appear on the display panel (if the interface card is installed within UPS and X6 jumper has fitted on 2-3). A remote warning may be provided by installing an other alarm interface card.
The Battery ground fault detection (P/N 4645313X) contains fault detection device only. The wiring cables are already installed within UPS. This option is fitted on DIN guide as shown in the installation drawings in Chapter 6.
Page 28
Installation Manual Liebert Hipulse E Chapter 3 – Battery Installation Single or '1+N' UPS System
(07/04) Page 3-1
3 Chapter 3 - Battery Installation
3.1 Introduction
The UPS battery consists of battery blocks connected in series to provide a nominal d.c. input voltage for the UPS inverter. The required ‘AUTONOMY TIME’ (the time that the battery can maintain supply to the load in the event of a mains failure) is limited by the ampere hour size of the individual battery blocks and in some cases this could mean several strings are connected in parallel. Usually, with UPS installations in the high power range covered by the 'Hipulse' equipment, the batteries are contained in a dedicated battery room. It must be possible to install batteries of various types and capacity in the battery room to obtain the required autonomy characteristics.
If multiple sets of batteries connected in parallel are used to provide the required battery autonomy, each set should be fitted with an isolating devices to permit work to be performed on one set of batteries while the others remain in service.
It must be possible to disconnect the battery from the UPS module when undertaking maintenance or service procedures. This is facilitated by means of a suitably rated circuit breaker which must be located as close as possible to the battery terminals, and the power and control cables connected to the UPS using the most direct route possible. The circuit breaker can be switched manually ON or OFF but should also contains an under-voltage release mechanism (having a variable trip setting) which is used in conjunction with battery circuit breaker controller board.
For battery room assembly, Liebert offers a battery circuit breaker option (the rating of which depends on the size of the UPS) including a battery circuit breaker controller board (the same for all sizes). This box is designed to be either wall­mounted or assembled on a frame, and is connected between the UPS and the battery. Refer to section 3.8 for more information. A Common Battery Circuit Breaker is available for systems incorporating two parallel UPSs with a common battery. It comprises two switches, which may be used to section one UPS while the other remains active. Refer to section 4.3 for more information.
Page 29
Chapter 3 - Battery Installation Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 3-2 (07/04)
3.2 Safety
Special care should be taken when working with the batteries associated with the 'Hipulse' UPS System equipment. When all the cells are connected together, the battery terminal voltage will exceed 400V and is potentially lethal. A primary safety consideration is to physically isolate the battery installation from all but appropriately qualified maintenance personnel; which is best achieved by locating the cells in a dedicated battery room. Specific battery cabinet and battery room design details are given later in this section.
WARNING
The following general battery safety precautions and WARNINGS should be observed at all times:
a) A battery can present risk of electric shock or burn from high short circuit currents.
b) When connected in a string the voltage could be 460V d.c. this voltage is potentially lethal always observe high
voltage precautions.
c) Only qualified personnel should install or service batteries.
d) Eye protection should be worn to prevent injury from accidental electrical arcs.
e) Remove rings, watches, necklaces, bracelets and all metal objects.
f) Only use tools with insulated handles.
g) Wear rubbers gloves and a rubber apron when handling batteries.
h) If a battery leaks electrolyte, or is otherwise physically damaged, it should be placed in a container resistant to
sulphuric acid and disposed of in accordance with local regulations.
i) If electrolyte comes into contact with the skin the affected area should be washed with plenty of clean water
immediately.
j) Batteries must always be disposed of according to local environmental laws.
k) When replacing batteries use the same number and type that were originally fitted.
l) Disconnect charging source prior to connecting or disconnecting battery terminals.
m) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact
with any part of a grounded battery can result in electrical shock.
3.3 UPS Batteries
Battery can be VRLA, Ni-Cd or wet cell type. It is common practice in UPS installations to use valve regulated cells. The term ‘valve regulated’ is used currently in place of either ‘sealed’ or ‘maintenance free’ both of which have been used in the past. Valve-regulated cells are not ‘sealed,’ and will vent. The amount of gas given off is less than for a flooded cell but when considering the design of the battery installation allowances must be made for adequate ventilation and heating of the cells. Boost charging must not
be applied to valve regulated cells as this will cause them to overcharge and subsequently vent. Similarly, valve-regulated cells cannot be regarded as ‘maintenance-free’ as they must be kept clean and their connections checked periodically for tightness and lack of corrosion. It is not possible to check the cells’ specific gravity directly but the battery can be checked by the ‘CS PG battery service programme’ which can give an indication of faulty cells or cell degradation within the battery. Batteries are fully charged before delivery; however, storage and transportation times mean that, inevitably, some charge is lost by the time the battery is commissioned. All the cells forming the battery should be brought to the same state of charge and be recharged within 6 months of the factory charge. It is especially important that the battery is fully charged before attempting a witness test of the autonomy time. This may require several days to complete; therefore any witness test concerning the batteries should take place only after the battery has been on uninterrupted float charge for at least one week. Cell performance typically improves after a few weeks in service or after two or three discharge/recharge cycles.
Page 30
Installation Manual Liebert Hipulse E Chapter 3 – Battery Installation Single or '1+N' UPS System
(07/04) Page 3-3
3.4 Installation design considerations
Note:
Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturers manuals. The battery safety information contained in this section relates to key considerations which must be taken into account during the installation design process and might affect the design outcome depending on localised conditions.
3.5 Battery Installation and Maintenance
3.5.1 Temperature considerations
Battery performance depends on the ambient battery temperature. Capacity and autonomy times are quoted for a new battery operating at 20°C. Battery capacity is increased by 1% for every 1°C increase in temperature up to 25°C. If a battery is used at temperatures above 25°C, its life is reduced; consequently its capacity and UPS autonomy time will reduce more rapidly over a period of time. Operating below 20°C will reduce the battery capacity by approximately 1%-1.5% per 1°C. For example: if a battery discharge test is attempted during the middle of winter when the ambient temperature is 5°C the battery capacity will be only 77.5% of its design value and will not satisfy its specified autonomy time. Ambient temperature, ventilation, spacing, float voltage and ripple current all affect the battery temperature. Uneven temperature distribution through the battery string will cause the voltage distribution to be uneven which can also lead to problems — it is therefore important to maintain a even temperature across the whole battery chain. ‘Valve-regulated’ cells are very sensitive to temperature and should be operated at a temperature between 15°C and 25°C. To help sustain this operating temperature range the battery is normally float charged at 2.25V/cell. When batteries are mounted in the same room to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS. — i.e. in the case of ‘valve-regulated’ cells the ambient room temperature should be kept between 15°C and 25°C, and not between 0°C and 40°C (which is the specified main equipment operating temperature range). Temperature excursions are permissible for short periods of time provided the average temperature does not exceed 25°C.
3.5.2 Battery population
The nominal DC bus voltage, and therefore battery float voltage, is set according the module’s rated input/output voltage, and usually set to 432Vdc (380Vac), 446Vdc (400Vac) or 459V (415Vac). Given that the desired cell float voltage is 2.25V, this means that a different number of cells are required in each case (see Chapter 5 - DC Intermediate Circuit).
3.6 Battery protection
The battery is connected to the UPS through a circuit breaker which is manually closed and electronically tripped via the UPS control circuitry. If the cells are rack -mounted (or located remote from the main UPS cabinet), this circuit breaker, fitted within the cabinet, must be positioned as near as possible to the batteries themselves, and the power and control cables connected to the UPS using the most direct route possible. The UPS electronic circuitry will trip the circuit breaker if any of the following conditions occur:-
a) If the d.c. busbar drops below 330V d.c. (This would normally occur during a mains failure when the battery
autonomy time has been exceeded.
b) If there is a rectifier problem and the d.c. bus rises above (2.45 V/cell exceeded on the battery).
c) If the Emergency Stop is operated.
Note: All equipment servicing procedures should be carried out only by trained personnel.
Page 31
Chapter 3 - Battery Installation Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 3-4 (07/04)
3.7 Battery installation
3.7.1 Fitting & connecting the batteries
The following notes, in conjunction with the diagrams, illustrate the broad principles to be followed when fitting and connecting the majority of battery installations.
3.7.2 Fitting the batteries
1. In general a minimum space of 10 mm must be left on all vertical sides of the battery block to permit free air
movement around the cells.
2. Clearance should be allowed between the top of the cells and the underside of the shelf above (this is necessary
for monitoring and servicing the cells).
3. When installing the batteries on racks always work from the bottom shelf upwards to prevent raising the centre
of gravity.
3.7.3 Connecting the battery
1. When the battery circuit breaker cabinet is installed on a raised floor the battery power cables and circuit
breaker control cables can be routed to the UPS cabinet via the floor of the cabinet. If the UPS and battery circuit breaker cabinet are located adjacent to each other and located on a solid floor these cables can be passed between the cabinets via the lifting apertures located in the lower sides of the cabinets.
2. In general it is recommended that the inter-connecting cables are fitted to the batteries within their particular
level before fitting the inter-level connecting cables, followed finally by the cables to the circuit breaker.
3. An insulating shroud should be fitted to each terminal after its connection has been made.
4. When connecting the cables between the battery extremities to the circuit breaker always connect the circuit
breaker end of the cable first.
3.7.4 Battery room design
Whatever the type of mounting system selected, the following conditions should be noted:
Layout of cells:
Whatever battery mounting system is used, the batteries should be laid out in such a manner as to make simultaneous contact with two exposed live parts having a potential greater than 150V impossible. Where this is not possible, insulated terminal shields must be installed and insulated cables must be used for connections.
Service platform:
The service platform (or duckboard) must be slip-proof, insulated from the floor and be at least one metre wide.
Connections:
All connections must be as short as possible.
Battery protection circuit breaker:
The battery circuit breaker is generally installed at the front of the battery room. The connection of Circuit Breaker Box available for the 'Hipulse' is described in the following paragraph.
Figure 3-1 Battery Room Design
Page 32
Installation Manual Liebert Hipulse E Chapter 3 – Battery Installation Single or '1+N' UPS System
(07/04) Page 3-5
3.8 Battery circuit breaker box
The box contains a battery isolating circuit breaker and the circuit breaker controller board (P/N 4520079F) as also mounted in the Battery cabinet. A range of battery circuit breaker boxes is available for use in installations where the battery is not installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible to the battery and connected to the UPS equipment as illustrated in Figure 3-4.
The battery circuit breaker box, used with the circuit breaker controller board, is required to protect the battery from deep discharging and overcurrents. It also provides electrical isolation between the UPS and the battery, permitting technical service personnel to reduce the risks involved in maintenance work to a minimum. Inside the box are connection bars for power cables arriving from the UPS and from the battery.
Note: The control cables from the UPS module to the controller board must be made using a 5-core shielded cable located in a separate conduit to that containing the battery power cables. The control signal cable is connected to the circuit breaker controller board (P/N 4520079F) through the terminal board (X1). The cable shield must be earthed to prevent induced noise affecting the control operation, and a separate safety earth must be connected between the UPS module and Circuit Breaker Box.
The battery circuit breaker boxes are of the same size (save for height) for both the 300 kVA and the 400 kVA UPS, but switch capacity and the section of the connection bar are different.
UPS (kVA)
Dimensions (H-W-D) (mm)
Weight
(Kg)
Circuit
Breaker
Cable entry
300 800x600x300 41
800A 4p
Bottom
400 1000x600x300 47
1000A 4p
Top & bottom
For mechanical details refer to the information shown in the following figures.
Page 33
Chapter 3 - Battery Installation Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 3-6 (07/04)
Figure 3-2 Battery circuit breaker box - 800A
BCB 800A
LEGEND
Battery connections (+/-)
Connections
from UPS (+/-)
Battery circuit breaker controller board
Cable entry: bottom. User to size and cut holes for the cables to be used.
Wall mounting holes
Page 34
Installation Manual Liebert Hipulse E Chapter 3 – Battery Installation Single or '1+N' UPS System
(07/04) Page 3-7
Figure 3-3 Battery circuit breaker box - 1000A
BCB 1000A
LEGEND
Battery connections (+/-)
Connections
from UPS (+/-)
Battery circuit breaker controller board
Cable entry: top and bottom. User to size and cut holes for the cables to be used.
Wall mounting holes
Page 35
Chapter 3 - Battery Installation Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 3-8 (07/04)
Figure 3-4 Battery circuit breaker box connection
3.8.1 Battery Temperature Board (Optional P/N 4532029V)
A battery temperature sensor card, supplied separately from the battery circuit breaker, is connected with the UPS logic through the battery circuit breaker control card. With this feature fitted, the nominal float voltage supplied to the battery is adjusted so as to be inversely proportional to the ambient battery cabinet/room temperature. This prevents the battery being over charged at high ambient temperatures.
Page 36
Installation Manual Liebert Hipulse E Chapter 4 - ‘1+N’ System Single or '1+N' UPS System
(07/04) Page 4-1
4 Chapter 4 - 1+N System
4.1 General
The 1+N system has two or more (up to a maximum of six) modules of the same size (kVA). The load is equally divided between the units that form the system. The system can be of two types:
Parallel power
All the UPS's are able to provide the full power requested for the load.
Parallel redundant
The system comprises a higher number of UPS's able to provide the full power required for the load. For more detailed information on the operating principle of 1 + N parallel systems, see Chapter 7.
The 1+N system is used to:
Increase the reliability of the system in order to ensure a good supply to the critical load connected.
Increase the power availability (system expansion) in the event an unforeseen power demand occurs. This
guarantees a greater flexibility in relation to the critical load connected.
Increase serviceability and allow the execution of maintenance operations and reparations without affecting the
ordinary operating conditions of the system (depending on the redundancy level).
The system can comprise of up to 6 UPS modules of the same power rating connected in parallel without the need for a centralized mains static bypass. The following components are installed inside each UPS unit in the 1+N parallel system: The parallel logic board, the parallel connector board and the corresponding flat connection cables. From a ‘power’ viewpoint each module is internally identical to the ‘single module’ configuration. A 1+N parallel system requires inverter and bypass supplies, inter-module control signals to manage current sharing, synchronizing and bypass switching between the modules. In figure 4-1 this is shown as the ‘inter-module control bus’, which is facilitated through the use of multi-way ribbon cables connected between the units of the system. The number and length of these flat cables is determined by the positioning of the equipment in the system, so this supply is determined when the order is placed.
If the load is transferred onto a static bypass line, in a configuration in which three or more units are connected in parallel, there may be a problem dividing up currents on the power circuit. Each case is different, and depends on the length of the cables used, for example the resistance upstream and downstream of the static bypass line. The differences between the impedances could result in undesirable division of currents over one or more UPS units. This problem may be solved by including an optional inductance on the static bypass line of each UPS unit.
Note: For each additional UPS unit, the operator control panel must be programmed with the correct size and the configuration of the static switch must be identified as ‘internal’.
1 + N Configuration (>2 UPS's) or two UPS's with parallel power connection
IMPORTANT
(*) With configurations consisting of two UPS's with parallel power or 1+N systems integrated with more than two
UPS's, where the load level is above the rated power of the single UPS, it is necessary to install an adequate external maintenance bypass. It is also necessary to adopt all the measures required to prevent the internal manual bypass switch of the UPS (Q3) from being used. This can be done by removing the handle of the switch and by placing a warning label for the maintenance personnel.
For information on the external maintenance bypass, see paragraph 4.4.
Page 37
Chapter 4 – ‘1+N’ System Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 4-2 (07/04)
Figure 4-1 '1+N' System block diagram with separate batteries.
(*) See the warning message at the bottom of page 4-1.
Page 38
Installation Manual Liebert Hipulse E Chapter 4 - ‘1+N’ System Single or '1+N' UPS System
(07/04) Page 4-3
4.2 Installation procedure
4.2.1 Preliminary Checks
Be sure that a parallel kit is present and fitted in each of the modules, and that the modules are of the same rating and with the same SW and HW release (See paragraph 8.1.2 of the User Manual The Menu Options).
WARNING
Fitting of the parallel kits and board setting required to convert from Single Module to 1+N
must be made by Liebert Service & Support trained personnel.
4.2.2 Protective Devices
Refer to the instructions supplied in Chapter 2 Electrical Installation - Section 2.1.6.
4.2.3 Power cables
Input Bypass and Rectifier, outputs of modules
For power cabling the installation is the same for each module as described in Chapter 2.
4.2.4 Control cables
Inter-module control
Modules are interconnected as shown in Figure 4-2 using connections to the other UPS modules via the parallel connector board with shielded 34-way cables. These cables are connected between the 'N' modules to pass control signals which govern module synchronization, load sharing, battery charge current sharing (in a common battery installation), load transfer operation and other general control and alarm functions. These signals are necessary to ensure correct system operation, and built-in redundancy allows the system to function if ever one of the 'N' cables becomes disconnected.
Inter-module Parallel Connections
1+N Parallel UPS System: Inside the module there is a parallel connection board (P/N 4590060U) mounted on the right hand side of the Static Switch cabinet. Connect one end of the interconnecting ribbon cable to interface connector (X1) of the first UPS module and the other end to connector (X2) of the second module, and so to the next module until a closed loop is formed.
Cable entry is as identified in the mechanical drawings in Chapter 6.
Figure 4-2 Connection of '1+N' system parallel signal bus cables
Page 39
Chapter 4 – ‘1+N’ System Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 4-4 (07/04)
4.2.5 Battery Control
The system is designed to operate with two different battery configurations: With separate batteries Installation procedure is the same as for single module. With common battery (only for two units)
In order that the battery charge current is shared equally between the modules, a ‘common battery’ option kit is available. (see Figure 4-6).
Figure 4-3 System with common battery
(*) See the warning message at the bottom of page 4-1.
Page 40
Installation Manual Liebert Hipulse E Chapter 4 - ‘1+N’ System Single or '1+N' UPS System
(07/04) Page 4-5
4.2.6 Emergency Stop (EPO)
The external emergency stop facility is identical to that described for the single module installation — that an individual Emergency Stop button is provided for each module. Note that this is a normally closed switch.
Figure 4-4 Connection of EPO push button.
Page 41
Chapter 4 – ‘1+N’ System Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 4-6 (07/04)
4.3 Common battery box (Option)
4.3.1 Common Battery box for two UPS in parallel
A common battery box is available to permit a common battery to be shared between two modules (see fig.4-6). The box, which is used to connect the DC busbar of the two modules to a common battery, should be fitted as close as possible to the UPS modules, with cabling preferably of the same length.
Warning
There is no protection to prevent closing a module's battery isolation switch when its rectifier is shut down. Such operation will trip the battery circuit breaker and rupture the battery fuse in that module.
Before operating the module's battery isolation switch, the operator must first check that the battery voltage and rectifier voltage different by less than 10% — this may be easily achieved by reading the Battery Voltage on the Display Panels of both modules.
Control cable connections are required as shown in Fig. 4-5, this includes an extension of the inter-module cables described in Section 4.2.4. In addition there are other auxiliary connections that are identified in the figure below.
Figure 4-5 -
Common Battery Box - connection details
Cable
A From common battery box (X3) to battery circuit breaker control board (X1) of BCB box B Auxiliary cables for battery sensor C&D Auxiliary cables from UPS terminal block to common battery box F
From common battery box (X1) to parallel connectoring board (X2) of UPS1 (Ribbon cable)
G
From common battery box (X2) to parallel connectoring board (X1) of UPS2 (Ribbon cable)
E
Intermodule cables between parallel connectoring board (X1) of UPS1 and parallel connectoring board (X2) of UPS2 (Ribbon cable)
A
B
C
D
E
F
G
Page 42
Installation Manual Liebert Hipulse E Chapter 4 - ‘1+N’ System Single or '1+N' UPS System
(07/04) Page 4-7
Figure 4-6 Common battery box 800A (300 kVA Hipulse)
Weight: 85 kg.
6
11 12
10
8 9
7
1
3 4 5
2
FUSES TYPE gl - 1 A / 500 V ~ SIZE 10 x 38
Q1
Q2
+
_
+
+
_
_
Page 43
Chapter 4 – ‘1+N’ System Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 4-8 (07/04)
4.3.1.1 Installation Procedure (Common Battery)
WARNING
If differential circuit breakers are used on UPS inputs, be sure to use a common device for all input lines. If the configuration has inputs from separate mains, a common device will also be required for all the System’s bypass mains.
A
t the instant of electrical connection, the current may not be split instantaneously and this may cause the
residual current circuit-breakers to trip separately.
Refer to the general diagram shown in figure 4-3.
The 1+N parallel system with common batteries (only for two units) also uses the ”Common Battery Box” optional kit (box type depends on UPS dimensions). This box uses two isolators to connect the battery to the two UPS modules, and thus individually isolate the two modules from the system. The box is also designed to supply the two UPS modules with a battery current measurement (charge or discharge). The Common Battery includes protection fuses of the DC power supply (F1&2): Type GL = Size 10x38 – 1A\500V.
4.3.1.2 Connection between UPS and “Common battery box”
Refer to the diagram shown in figure 4-5 and the attached table.
1. POWER CABLES:
For the connection between the UPS modules and the common battery box use cables with the section indicated in the Installation Electrical (table 2-1).
2. AUXILIARY CABLES:
The auxiliary cables of the common battery box must be screened and double insulated. The screen is connected to the earth of the common battery box. Use multiple-core shielded cables with a section of 0.5 to 1 mm
2
.
Connect the cables with the Fast-on 6.3x 0.8 mm terminals (female).
The temperature sensor, contained in a bag inside the Common Battery Box, must be mounted in the battery cabinet next to the sensor which was previously installed, and connected to the Common battery box through cable “B” as illustrated in figure 4-5.
Note: Power and auxiliary cables are not included in the supply.
Page 44
Installation Manual Liebert Hipulse E Chapter 4 - ‘1+N’ System Single or '1+N' UPS System
(07/04) Page 4-9
4.4 Maintenance Bypass cabinet (Option)
Bypass cabinet enables maintenance operations and reparations to be performed in full isolation besides allowing the disabling of each UPS without affecting the ordinary operation of the system (depending on the redundancy level). The optional maintenance bypass cabinet must
be used in all configurations where the internal bypass is not
sufficient to guarantee the power requested by the load.
This cabinet comprises:
A cut-off isolator for the direct line, which disconnects the bypass line from the load
Two isolators (see Note 1) to cut-off single UPS outputs
A cut-off isolator for the output of the whole UPS system
A terminal block for the auxiliary connections to the UPS's
Note (1): there are alternative solutions differing from suggested standard for specific installation requirements (i.e. with several UPS cut-off isolators).
Study the reference drawing provided in Chapter 6.
WARNING
Carefully follow the operating procedures provided in this manual to completely disable the UPS. It is useful to remember that all input/output power and battery switches must be open for the UPS to be completely insulated.
The UPS system with external maintenance bypass cabinet offers a standard protection that guarantees the blocking of the inverter and the switching of the load to the bypass line if the maintenance bypass switch is accidentally closed.
4.4.1 Auxiliary connections between the maintenance bypass cabinet and two UPS's
The maintenance bypass box connected to the terminal blocks requires specific control cabling, as described here below.
Maintenance Bypass cabinet
UPS 2
X1-1 Q2-N.O. X4-3 X1-2 Q2-COM X4-4
EXT. SW. OUT
UPS 1
X1-3 Q1-N.O. X4-3 X1-4 Q1-COM X4-4
EXT. SW. OUT
X1-5 Q3/4-N.C. X4-7 X1-6 Q3/4-COM X4-8
EXT. BYP
UPS 1 UPS 2
X4-7 X4-7 X4-8
EXT. BYP
X4-8
EXT. BYP
Table 4-1
Note: All auxiliary cables of terminal block X1 must be double insulated.
The cross-sectional area of the auxiliary cables is from 1 mm
2
. Connect the cables with the Fast-on 6.3x 0.8 mm terminals (female). Power and auxiliary cables are not included in the supply.
Page 45
Chapter 4 – ‘1+N’ System Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 4-10 (07/04)
4.4.2 Castell Interlock
The Castell Interlock enables the operator to close/open the external maintenance bypass switch following the procedure required to release/insert the key. The UPS Liebert Hipulse E system offers two types of Castell Interlock options: mechanical and electromechanical. The type must be selected depending on the configuration of the system installed in the plant.
Castell Interlock
Configuration of the UPS system Type of Castell Interlock
Two UPS's with parallel redundant connection (1+1) Mechanical Castell Interlock
Two UPS's with parallel power or above two UPS's (1+N)
Electromechanical Castell Interlock
The Castell Interlock option is normally used in combination with the power isolators placed inside the external maintenance bypass cabinet.
Note: The Liebert Hipulse E UPS system is already pre-arranged for the installation of this option.
This option comprises:
A Castell Interlock with key (BP1) for each UPS of the system. The key is normally blocked and released only
when the UPS inverter turns off and the load is switched to the static bypass, depending on the active UPS modules.
A Castell key exchange box. This will receive the keys from all the UPS modules, then release another key
(BP2) to use in the Maintenance Bypass isolator.
A Castell Interlock with key (BP2), situated on the external maintenance bypass isolator. As this isolator is
normally open and has no key, it can be closed only with the key (BP2) released by the Castell key exchange box. The key is released only when the isolator is open.
A Castell Interlock with key (BP2), situated on the UPS output isolator within the external maintenance bypass
cabinet. This isolator is normally closed and has a key. The key is released only when the isolator is open.
4.4.2.1 Electromechanical Castell Interlock
This option consists of a Castell key exchange box and of several Castell units with individual key. Their number varies according to the number of UPS's present in the system. The release of a specific key (BP1) occurs only when the inverter turns off. As a consequence thereof, the load is transferred to the internal static bypass line (the switching operation occurs when the number of active UPS's is lower that the number set in the menu of the operator control panel). The key, which is fixed in position by means of an electromechanical device, can only be removed by pressing the energising button of the solenoid and when the green indicator is on. The keys extracted from the UPS's (n BP1) enable to free a second key (BP2) from the Castell key exchange box and to close the external maintenance bypass isolator, enabling the line that directly connects the bypass mains to the load. To isolate the UPS system, it is necessary to open the UPS output isolator of the external bypass cabinet, the protective devices at the input distribution panel and the battery circuit breaker. At this point, the load is supplied by the direct line inside the maintenance bypass cabinet and it is possible to perform maintenance operations or reparations on the UPS as it is completely isolated.
4.4.2.2 Mechanical Castell Interlock
The description above is valid also for this type of Castell unit, with the following exceptions:
The maintenance bypass switch (Q3) of the UPS is closed before the external bypass isolator.
The key (BP1) acts on the maintenance bypass isolator (Q3) blocking (or disengaging) a mechanical stop.
No button needs to be pressed to extract the key (BP1) on the UPS.
The keys symbols of the Castell Interlocks can be customized to suit the needs of the customer.
Page 46
Installation Manual Liebert Hipulse E Chapter 4 - ‘1+N’ System Single or '1+N' UPS System
(07/04) Page 4-11
Figure 4-7 Example of configuration with two redundant UPS's connected in parallel with the external maintenance bypass cabinet.
This drawing should show an external maintenance bypass supply for the system (with two redundant UPS's) as referred to in the warning message at the bottom of page 4-1.
Page 47
Chapter 4 – ‘1+N’ System Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 4-12 (07/04)
Figure 4-8 Example of configuration with three UPS's connected in parallel with the external maintenance bypass cabinet.
This drawing should show an external maintenance bypass supply for the system (with three UPS's) as referred to in the warning message at the bottom of page 4-1.
Page 48
Installation Manual Liebert Hipulse E Chapter 5 – ‘Specification’ Single or '1+N' UPS System
(07/04) Page 5-1
5 Chapter 5 - Specification
This specification describe requirements for an Uninterruptible Power System (UPS).
5.1 Conformity and Standard
The UPS has been designed to conform to the following standards:
Description Year Normative references
General and safety requirements for
UPS used in operator access areas
2002
EN 62040-1-1
IEC 62040-1-1
Emissions requirements 1995
EN 50091-2 (tables 2 and 4)*
Method of specifying the performance
and test requirements
2001
EN 62040-3 identical to
IEC 62040-3 (1999)
* Class ‘A’ compliance if optional RFI filters is fitted (only for 300 kVA UPS)
CCE
E marked
The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety (60950) and construction (60529). For more details, see below:
Description Year Normative references
Information technology equipment 2000 EN 60950
Degrees of protection provided by enclosures (IP code).
1989 EN 60529
5.2 UPS Environmental
The UPS shall be able to operate under the following environmental conditions without damage or degradation in electrical operating characteristics:
ENVIRONMENTAL CHARACTERISTICS
UNITS
Rated power kVA 300 400
Operating Temperature °C 0- 40
Maximal temperature for 8 hr day °C
40°C
de-rate power by 1,5% per °C between +40°C and + 50°C
Mean Temperature for 24 h °C 35 Relative humidity
90% at 20°C
Acoustical noise dBA 70 73 Altitude of operation
1000m asl
de-rate power by 1% per 100m between 1000 and 2000 m
Storage-Transport Temperature °C
-25 ÷ 70
Page 49
Chapter 5 – ‘Specification’ Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 5-2 (07/04)
5.3 UPS Mechanical Characteristics
MECHANICAL
CHARACTERISTICS
UNITS
UPS
300 kVA (6 pulse ) 300 kVA (12 pulse)
400 kVA (6 pulse )
400 kVA
(12 pulse)
Section
UPS 12 pulse Rect./St. Inverter Rect./St Inverter
Height
1900
Width of each section
1640 1640 640 1230
1230
Total width
1640 2280
2460
Total width including top cable entry option
2280 2920
3100
Depth
mm
856
Weight of each section
1810 730
640
1750 1310 1750
Total weight without Input Filter
1850
2540
2390 3060
Total weight with Input Filter
“ “ “ (filter 4%)
2650
3192
“ “ “ (filter 9%)
kg
2010
2574
Ventilation - By internal extract fans
Airflow m
3
/h
4500 5000
8000
Cable entry - Bottom or either side (top optional)
Colour - RAL 7035 (Light grey)
Protection level (with open/closed front doors)
IP 20
Note: Dimensions and weight do not include the pallet and packing material. Actual weight will vary depending on installed options.
OPTION
MAINTENANCE BYPASS CABINET
1+ 1 Configuration (two UPS's with parallel redundant connection)
Height
1900
Width
900
Depth
mm
856
Weight kg
300
Cable entry - Top and bottom or either side
Colour - RAL 7035 (Light grey)
Protection grade
- IP 20
Power isolators
SIRCO 4 poles 630A (at 400 Vca)
Page 50
Installation Manual Liebert Hipulse E Chapter 5 – ‘Specification’ Single or '1+N' UPS System
(07/04) Page 5-3
5.4 UPS Electrical Characteristics (Input Rectifier)
RECTIFIER INPUT MAINS
UNITS
Rated power kVA 300 (6 pulse ) 300 (12 pulse) 400 (6 pulse ) 400 (12 pulse)
Rated mains voltage
Vac 380 - 400 - 415 V
Supply Three phase without neutral
Input voltage tolerance
% -15, +10
Frequency
Hz 50 / 60
Input frequency tolerance
% ± 5
321 304 431 410
Rated input power
with input harmonic filter
kVA
276 with Input Filter
(9%)
304 with Input Filter
(4%)
371 with Input Filter
(9%)
410 with Input Filter
(4%)
463 438 622 591
Rated input current
with input harmonic filter
A
399 with Input Filter
(9%)
439 with Input Filter
(4%)
535 with Input Filter
(9%)
591 with Input Filter
(4%)
405 384 540 520
Maximal input power
with input harmonic filter
kVA
345 with Input Filter
(9%)
384 with Input Filter
(4%)
463 with Input Filter
(9%)
520 with Input Filter
(4%)
600 554 800 751
Maximal input current
with input harmonic filter
A
499 with Input Filter
(9%)
554 with Input Filter
(4%)
669 with Input Filter
(9%)
751 with Input Filter
(4%)
Duration of progressive power
walk-in
sec 2 or 10
Maximal output current
A 750 1000
Note:
= 380V or 415V set changing taps on auxiliary supply transformer. = With mains at –15% and suggested battery elements the UPS maintains the output rated voltage at rated load but
cannot guarantee float charge to battery; the battery does not discharge.
= EN 62040-3 (3.4.5): UPS , rated load, input rated voltage 400V, no current to battery. = EN 62040-3 (3.4.6): UPS , rated load or overload, input rated voltage 400V, battery on boost charge with maximal
allowed current.
= Set with jumper on Rectifier Control Board (slow or fast).
Page 51
Chapter 5 – ‘Specification’ Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 5-4 (07/04)
5.5 UPS Electrical Characteristics (DC Intermediate Circuit)
DC INTERMEDIATE CIRCUIT
UNITS
Rated power kVA 300 400
Voltage range for inverter operation
Vdc 320 – 490
Recommended number of lead-acid cells
-
No
192 ( 380Va.c.)
198 ( 400Va.c.)
204 ( 415Va.c.)
Recommended float charge voltage
2.25 V/el.
Vdc
432 ( 380Va.c.)
446 ( 400Va.c.)
459 ( 415Va.c.)
Recommended boost charge voltage
2.40 V/el.
Vdc
460 ( 380Va.c.)
475 ( 400Va.c.)
490 ( 415Va.c.)
Recommended end of discharge voltage
1.67 V/el.
Vdc
320 ( 380Va.c.)
330 ( 400Va.c.)
340 ( 415Va.c.)
Recommended test voltage
1.90 V/el.
Vdc
365 ( 380Va.c.)
376 ( 400Va.c.)
388 ( 415Va.c.)
Maximum voltage on manual charge
2.45 V/el.
Vdc
480 ( 380Va.c.)
495 ( 400Va.c.)
500 ( 415Va.c.)
Maximum recharge battery current
A 150 200
Battery boost charge cycle
-
Characteristics to DIN 41772 I-U, boost to floating charge switching, with current
measuring criterion plus control of charging time
Maximum boost charge duration
min 0-999
Boost-float threshold current
A 0-99
Temperature voltage compensation
mV/°C 2
Ripple voltage superimposed
%
1
Note:
= (According to rated voltage). = Factory set for rated 400 V, different cells number and voltage per cell may be set by software and/or trimmers on
Rectifier Control Board.
= Set by software. = With external temperature sensor, feature selected on Rectifier Control Board. = Battery disconnected, RMS percentage value referred to DC voltage. = Lead acid (SMF/VRLA and WET cell) and Ni-Cad with constant voltage and current charging for European units.
Page 52
Installation Manual Liebert Hipulse E Chapter 5 – ‘Specification’ Single or '1+N' UPS System
(07/04) Page 5-5
5.6 UPS Electrical Characteristics (Inverter Output)
INVERTER OUTPUT
UNITS
Rated power kVA 300 400
Rated mains voltage
Vac 380 - 400 - 415
Supply Three phase with neutral Frequency
Hz 50 / 60
Rated Power at cos ϕ = 0.8
kVA 300 400
Rated Power at cos ϕ = 1
kW 240 320
Three -phase transient overload
%
110 for 60 minutes 125 for 10 minutes
150 for 1 minute
Single -phase transient overload
sec
I/In
30
2.2
Maximal non linear load allowed
100% Pn
Voltage stability, steady state test
% ± 1
Voltage stability, transient test
% ± 5
Maximum rate of change of frequency
Hz/sec 0.1
Current rating of neutral cable
A
630 (1) 945 (2)
Note:
= Factory set 400V 380 or 415 voltages with software setting. = Factory set at 50Hz; 60 Hz with software setting. = EN 62040-3 (3.5.8). = EN 62040-3 (3.4.14 and annex E) crest factor 3. = EN 62040-3 (6.3.4).
= EN 62040-3 (6.3.7) also for 0-100-0%, load transient, restore time 20 ms to ±1%.
= Factory set at 0.1Hz/sec; 0.5 to 1 Hz/sec with software setting for UPS single module. = (1) refers to the sizing of the UPS power isolators (cut-off neutral).
(2) optional kit to uprate the neutral cut-off current rating where local regulations permit.
Page 53
Chapter 5 – ‘Specification’ Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 5-6 (07/04)
5.7 UPS Electrical Characteristics (Bypass Input Mains)
BYPASS INPUT
UNITS
Rated power kVA 300 400
Rated mains
voltage
Vac 380 - 400 - 415 V
Supply Three phase with neutral
470 627 446 595
Rated Current:
380Vac 400Vac 415Vac
A
430 574
(*) load assumed @ P.F. = 0.8
Bypass voltage tolerance
%
± 10
Delay time to recognise bypass voltage returned to window
sec 10
Inverter output voltage window
% ± 10
Frequency
Hz 50 \ 60
Input frequency tolerance
% ± 2
Maximum frequency slew rate
Hz/sec 0.1
Current rating of neutral cable
630 (1) 945 (2)
Protection, bypass line
To avoid series fuses, the bypass line should be protected using an external device
in the input distribution system. This device should be sized to discriminate with
the load protection.
Transient overload
ms
I/In
10
14.3
20
12.6
50
11.0
100
10.0
200
9.0
500
8.0
1000
7.1
2000
6.6
5000
5.7
Note:
= Factory set 400V 380 or 415 set changing taps on auxiliary supply transformer and with software setting. = Other values 0 –15% with software setting. = Factory set at 50Hz; 60 Hz with software setting. = Other values 1 – 9 % with software setting.
= (1) refers to the sizing of the UPS power isolators (cut-off neutral).
(2) optional kit to uprate the neutral cut-off current rating where local regulations permit.
Page 54
Installation Manual Liebert Hipulse E Chapter 5 – ‘Specification’ Single or '1+N' UPS System
(07/04) Page 5-7
5.8 UPS Electrical Characteristics (System Performance)
SYSTEM PERFORMANCE
UNITS
Rated power kVA
300 (6 pulse ) 300 (12 pulse) 400 (6 pulse ) 400 (12 pulse)
91.3 90.2 91.0 90.7
AC/AC Efficiency at load 25%
with input harmonic filter
91.3 with Input Filter (9%)
90.2 with Input Filter (4%)
91.0 with Input Filter (9%)
90.5 with Input Filter (4%)
94.1 93.3 93.2 92.9
AC/AC Efficiency at load 50%
with input harmonic filter
93.7 with Input Filter (9%)
93.3 with Input Filter (4%)
93.0 with Input Filter (9%)
92.7 with Input Filter (4%)
94.3 93.3 93.4 92.7
AC/AC Efficiency at load 75%
with input harmonic filter
94.0 with Input Filter (9%)
93.1 with Input Filter (4%)
93.2 with Input Filter (9%)
92.5 with Input Filter (4%)
93.6 93.0 93.0 92.1
AC/AC Efficiency at load 100%
with input harmonic filter
93.5 with Input Filter (9%)
92.8 with Input Filter (4%)
92.8 with Input Filter (9%)
91.9 with Input Filter (4%)
ECOMODE
%
97.7 97.4 97.1
5.8.1 Losses
LOSSES
UNITS
Rated power kVA
300 (6 pulse ) 300 (12 pulse) 400 (6 pulse ) 400 (12 pulse)
4.40 5.0 6.6 7.0
No load losses
with input harmonic filter
4.84 with Input Filter (9%)
5.3 with Input Filter (4%)
7.1 with Input Filter (9%)
8.0 with Input Filter (4%)
5.7 6.5 7.9 8.2
Losses at load 25%
with input harmonic filter
4.89 with Input Filter (9%)
5.65 with Input Filter (4%)
7.2 with Input Filter (9%)
7.8 with Input Filter (4%)
7.5 8.6 11.6 12.2
Losses at load 50%
with input harmonic filter
8.21 with Input Filter (9%)
8.62 with Input Filter (4%)
10.8 with Input Filter (9%)
11.3 with Input Filter (4%)
10.9 12.9 17.0 18.9
Losses at load 75%
with input harmonic filter
11.90 with Input Filter (9%)
13.34 with Input Filter (4%)
15.9 with Input Filter (9%)
17.2 with Input Filter (4%)
16.4 18.1 24.1 27.4
Full load losses (100%)
with input harmonic filter
16.79 with Input Filter (9%)
18.9 with Input Filter (4%)
24.8 with Input Filter (9%)
26.7 with Input Filter (4%)
ECOMODE
kW
7.4 8.0 9.9 10.3
Page 55
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-1
6 Chapter 6 - Installation Drawings
6.1 Introduction
The drawings below illustrate the principal mechanical and electrical characteristics of the Liebert Hipulse E and of its various optional cabinets.
In these drawings you will find all information of use for positioning the equipment, determining cable entry, making electrical power and auxiliary connections, determining the position of isolators, determining the physical location of various optional equipment, etc.
Page 56
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-2 (07/04)
6.1.1 300kVA UPS Module with 6 pulse rectifier
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air exhaust
- 800 mm min. clearance above unit required for air exhaust.
4. Operator control and display panel
A
ll dimensions are in mm.
Page 57
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-3
6.1.2 300kVA UPS Module with 6 pulse rectifier – Top and base view
Layout cable entry and floor fixing
B
ase view with panels and doors
5. N°4 holes 14 for securing unit to floor (if required)
- N° 4 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
7. Load supporting feet
A
ll dimensions are in mm.
Page 58
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-4 (07/04)
6.1.3 300kVA UPS Module with 6 pulse rectifier with Top Cable entry option
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air exhaust
- 800 mm min. clearance above unit required for air exhaust.
4. Operator control and display panel
A
ll dimensions are in mm.
Page 59
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-5
6.1.4 300kVA UPS Module with 6 pulse rectifier with Top Cable entry option – Top and base view
Layout cable entry and floor fixing
B
ase view with panels and doors
5. N°8 holes 14 for securing unit to floor (if required)
- N° 8 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
7. Load supporting feet
8. Top cable entry ( user to size and cut holes for the cables to be used)
A
ll dimensions are in mm.
Page 60
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-6 (07/04)
6.1.5 300kVA UPS Module with 12 pulse rectifier
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air exhaust
- 800 mm min. clearance above unit required for air exhaust.
4. Operator control and display panel
A
ll dimensions are in mm.
Page 61
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-7
6.1.6 300kVA UPS Module with 12 pulse rectifier – Top and base view
Layout cable entry and floor fixing
B
ase view with panels and doors
5. N°8 holes 14 for securing unit to floor (if required)
- N° 8 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
7. Load supporting feet
A
ll dimensions are in mm.
Page 62
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-8 (07/04)
6.1.7 300kVA UPS Module with 12 pulse rectifier with Top Cable entry option
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air exhaust
- 800 mm min. clearance above unit required for air exhaust.
4. Operator control and display panel
A
ll dimensions are in mm.
Page 63
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-9
6.1.8 300kVA UPS Module with 12 pulse rectifier with Top Cable entry option - Top and base view
Layout cable entry and floor fixing
B
ase view with panels and doors
5. N°12 holes 14 for securing unit to floor (if required)
- N° 12 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
7. Load supporting feet
8. Top cable entry ( user to size and cut holes for the cables to be used)
A
ll dimensions are in mm.
Page 64
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-10 (07/04)
6.1.9 300kVA UPS Module with 6 pulse rectifier - open door view
1. Auxiliary terminal blocks (X3-X4).
2. Parallel connection board P/N 4590060U (option for multimodule configuration only)
3. Parallel logic P/N 4520075B (option for multimodule configuration only)
4. Alarm interface board P/N 4590055P and extension alarm interface board P/N 4590056Q (Options)
5. Fan failure alarm indicators (Option)
6. Mechanical Castell Interlock option
7. Electromechanical Castell Interlock option
8. Socket (250 Vac max 1A)
9. Battery ground fault detection (Option)
Page 65
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-11
6.1.10 Cable connections for 300 kVA UPS
Note 1: For split Bypass operation ensure that the busbars and cables (*) between Bypass and Rectifier input are removed. Note 2: With a Class ‘A’ EMC filter (optional) and a ‘common’ input configuration, the capacitors on the Rectifier input bars
must be removed.
1. Battery connections (+/-)
2. Main input connections (U1-V1-W1)
3. Bypass connections (U3-V3-W3-N3)
4. Output connections (N2-U2-V2-W2)
5. Earth
6. Auxiliary terminal blocks (X3-X4)
7. Details of bar connections
A
ll dimensions are in mm.
Page 66
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-12 (07/04)
6.1.11 Internal connections between the 300 kVA UPS and the 12 pulse cabinet
Page 67
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-13
6.1.12 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier)
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air exhaust
- 800 mm min. clearance above unit required for air exhaust.
4. Operator control and display panel
A
ll dimensions are in mm.
Page 68
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-14 (07/04)
6.1.13 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier) – base and top view
Layout cable entry and floor fixing
B
ase view with panels and doors
5. N°8 holes 14 for securing unit to floor (if required)
- N° 8 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
7. Load supporting feet
A
ll dimensions are in mm.
Page 69
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-15
6.1.14 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier) with Top Cable entry option
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air exhaust
- 800 mm min. clearance above unit required for air exhaust.
4. Operator control and display panel
A
ll dimensions are in mm.
Page 70
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-16 (07/04)
6.1.15 400kVA UPS Module with 6 pulse rectifier (or 12 pulse rectifier) with Top Cable entry option – base and top view
Layout cable entry and floor fixing
B
ase view with panels and doors
5. N°12 holes 14 for securing unit to floor (if required)
- N° 12 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
7. Load supporting feet
8. Top cable entry ( user to size and cut holes for the cables to be used)
A
ll dimensions are in mm.
Page 71
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-17
6.1.16 400 kVA UPS – Front view open doors
1. Auxiliary terminal blocks (X3-X4).
2. Parallel connection board P/N 4590060U (option for multimodule configuration only)
3. Parallel logic P/N 4520075B (option for multimodule configuration only)
4. Alarm interface board P/
N
4590055P and extension alarm interface board P/N 4590056Q (Options)
5. Fan failure alarm indicators (Option)
6. Mechanical Castell Interlock option
7. Electromechanical Castell Interlock option
8. Socket (250Vac max 1A)
9. Battery ground fault detection (Option)
Page 72
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-18 (07/04)
6.1.17 Cable connections for 400 kVA UPS (Rectifier/Static Switch cabinet)
1. Battery connections (+/-)
2. Main input connections (U1-V1-W1)
3. Bypass connections (U3-V3-W3-N3)
4. Output connections (N2-U2-V2-W2)
5. Earth
6. Auxiliary terminal blocks (X3-X4)
7. Details of bar connections
Page 73
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-19
6.1.18 400 kVA UPS – View of auxiliary, control signals and power connections between the 400 kVA UPS cabinets
Page 74
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-20 (07/04)
6.1.19 Top Cable entry option
1. Main input connections (U1-V1-W1)
2. Battery connections (+/-)
3. Output connections (N2-U2-V2-W2)
4. Bypass connections (U3-V3-W3-N3)
5. Earth
6. Connection from UPS
7. Customer cables
A
ll dimensions are in mm.
a. Removable grille and panels for lifting with fork-lift truck. b. Air inlet grille c. Top cable entry (user to size and cut holes for the cables to be used)
Page 75
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-21
6.1.20 Cable connections for 300 / 400 kVA UPS with Battery Circuit Breaker
Page 76
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-22 (07/04)
6.1.21 Maintenance Bypass cabinet (Option) – general view
1. Removable grille and panels for lifting with fork-lift truck.
2. Air inlet grille
3. Air outlet grille
4. Top cable entry (user to size and cut holes for the cables to be used)
5. N°4 holes 14 for securing unit to floor (if required)
- N°4 rawl plug M14 -
- Mounting feet
6. Bottom cable entry
A
ll dimensions are in mm.
Page 77
Installation Manual Liebert Hipulse E Chapter 6 – Installation Drawing Single or '1+N' UPS System
(07/04) Page 6-23
6.1.22 Maintenance Bypass cabinet (Option) – Front view with open doors
MAINTENANCE BYPASS CABINET
Q1
Q2
Q4
Q3
Q2
ISTRUZIONI PE R
VEDERE LE
TO THE SUPPL Y
CONNECTING
LA ALIMENTACIÓN DE RED
L'ALIMENTAZIONE
PRIMA DI COLLEGARE
INSTRUCTION S
SEE INSTALLATION
L'INSTALLAZIONE
BEFORE
VOIR INSTRUCTIONS
AVANT DE CONNECTER
VOR DEM ANSCHLUSS,
INSTALLATIONSANLEITUNG
UNBEDINGT
VER INSTRUCCIONES
A L'ALIMENTATION
D'INSTALLATION
ANTES DE CONECTAR
DE INSTALACION
LESEN
Q1
WITH UPS SWITCHED
OPERATE ONLY
WARNIN G
TO BYPASS SUPPLY
SU RETE DI SOCCORSO
CON UPS COMMUTATI
MANOVRARE S OLO
ATTENZIONE
Q4
Q3
1. Connections from UPS 1 output
2. Connections from UPS 2 output
3. Maintenance bypass input supply
4. To load supply
5. Auxiliary terminal block (X1)
6. Earth
Page 78
Chapter 6 – Installation Drawing Liebert Hipulse E Installation Manual Single or '1+N' UPS System
Page 6-24 (07/04)
6.1.23 RS232 Communications for 300-400 kVA UPS (Option) – Modem and NIC card locations
1. Kit for modem connection
2. Operator Logic board
3. Customer cable
4. To telephone line
5. Kit for NIC card
6. To Ethernet connection
.
Page 79
User Manual Liebert Hipulse E Chapter 7 - General Description Single or '1+N' UPS System Design Concept
(07/04) Page 7-1
Part II – User Manual
7 Chapter 7 - General Description
7.1 Introduction
The Liebert Hipulse E Uninterruptible Power Supply (UPS) System is connected between a critical load, such as a computer, and its three phase mains power supply. Being designed to furnish a well regulated 3 phase output power supply under all rated load and input supply conditions, the system offers the user the following advantages:
Increased power quality:
The UPS has its own internal voltage and frequency regulators which ensure that its output is maintained within close tolerances independent of voltage and frequency variations on the mains power lines.
Increased noise rejection:
By rectifying the input a.c. power to d.c. power, and then converting it back to a.c., any electrical noise present on the input mains supply line is effectively isolated from the UPS output, therefore the critical load sees only clean power.
Power blackout protection:
If the mains power fails, the UPS continues to power the critical load from its battery source, leaving the load immune from power disturbances.
7.2 Design Concept
7.2.1 Introduction
This section describes an individual module's operating principles. The UPS basically operates as an a.c. -d.c. -a.c. converter (see figure 7-1). The first conversion stage (from a.c. to d.c.) uses a 3 phase, fully-controlled SCR bridge rectifier to convert the incoming mains supply into a regulated d.c. bus-bar.
Figure 7-1 Single Module block diagram
The d.c. bus-bar produced by the rectifier provides both battery charging power - being equipped with a temperature compensated battery charging system, to prolong battery life - and power to the inverter section – which utilizes the latest IGBT switching pulse width modulation ( PWM ) design - and provides the second conversion phase, i.e. reconverting the d.c. bus-bar voltage back into an a.c. voltage waveform.
UPS
Output
a.c.
Bypass a.c. Supply
Rectifier a.c. Supply
RECTIFIER
INVERTER
ST
A
TIC
SWITCH
BATTERY
Page 80
Chapter 7 - General Description Liebert Hipulse E User Manual Design Concept Single or '1+N' UPS System
Page 7-2 (07/04)
During normal operation both the rectifier and inverter sections are active and provide regulated load power whilst simultaneously float charging the battery. In the event of a mains power failure, the rectifier becomes inoperative and the inverter is powered solely from the battery. Critical load power is maintained under these conditions until the battery is fully discharged, whereupon the UPS shuts down. The end of battery discharge is assumed when the battery voltage falls below a preset value (i.e. 330V d.c. for a 400V a.c. system). The period for which the load can be maintained following a mains power failure is known as the system's ‘Autonomy Time' and is dependent upon both the battery A/Hr capacity and the applied percentage load.
7.2.2 Bypass supplies
The circuit block annotated ‘Static Switch' in figure 7-2 contains an electronically controlled switching circuit which enables the critical load to be connected either to the inverter output or to a bypass power source via the `static bypass line'. During normal system operation the load is connected to the inverter and the 'inverter-side' of the Static Switch is closed; but in the event of a UPS overload, or inverter failure, it is automatically transferred to the static bypass line.
Figure 7-2 UPS power switches configuration
To provide a clean ( no-break ) load transfer between the inverter output and static bypass line, the static switch activates connecting the load to the bypass supplies. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics which make the inverter frequency track that of the static bypass supply provided that the bypass remains within an acceptable frequency window. The synchronizing window is pre-selected to 2% of nominal frequency, giving an acceptable frequency window ±1 Hz.
A manually controlled, `maintenance bypass' supply is also incorporated into the UPS design. Its purpose is to enable the critical load to be powered from the mains ( bypass ) supply while the UPS is shut down for routine maintenance.
Note: The load equipment is not protected from normal supply aberrations when operating on Bypass side or in the maintenance bypass mode
DC Bus
RECTIFIER
Bypass Isolator Q2
Maintenance Bypass Isolator Q3
Input Isolator Q1
Output Isolator Q4
Input Mains Supply
Bypass Mains Supply
UPS Output
Battery
Bypass Side
INVERTER STATIC SWITCH
UPS MODULE
C.B.
Battery Circuit Breaker
Page 81
User Manual Liebert Hipulse E Chapter 7 - General Description Single or '1+N' UPS System Design Concept
(07/04) Page 7-3
7.2.3 System Control Philosophy
Normal operation
During normal operation, i.e. when the UPS input supply is present and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical load busbars. The battery circuit breaker is also closed and the battery is therefore permanently float charged at the d.c. busbar voltage level. (1+N Parallel UPS System) Note: As the unit outputs are connected in parallel, the System checks that the inverter control circuits are perfectly synchronised with one another and with the Bypass Mains in terms of both frequency and phase and that they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message appears while synchronisation is in progress.
A module's static switch cannot close until these conditions are satisfied
Mains Failure
If the power mains has a failure or is out of tolerance the rectifier will stop automatically, while the Inverter will continue to operate on power from the battery for a period of time which depends on the load and the capacity of the battery. If the mains supply has not returned within this time, the Inverter will stop automatically and an alarm message will appear on the UPS operator control panel display. Critical load will not be interrupted in the event of a drop or return of the AC power mains.
Return of power mains
When the mains returns within the required tolerance, the Rectifier will start up again automatically and gradually (power walk-in), supplying power to the Inverter and recharging the battery at the same time. There will be no interruption of the critical load.
Input Power Walk-in
The rectifier/charger provides a feature that limits the total initial power requirements to 20% of rated load and gradually increases power up to 100% of full rating over an hardware selectable time (slow or fast).
Off-Battery
If the battery system only is taken out of service for maintenance, it is disconnected from the rectifier/charger and inverters by means of (an) external disconnect breaker(s). The UPS shall continue to function and meet all of the specified steady-state performance criteria, except for the power outage back-up time capability.
Power Walk-in delay timer
On 1+N parallel systems, it is possible to select the start of each UPS after a power failure, by setting a suitable time from the operator's display (ranging between 0 and 120 seconds). This function is particularly useful when a generator is present on the input side because it enables to acquire power gradually.
UPS Module fault
In the event of an Inverter fault, the Static Transfer Switch will automatically transfer the load onto the bypass mains with no interruption. In such an event, request qualified technical assistance. (1+N Parallel UPS System) In the event of a fault in a unit, the unit’s Static Transfer Switch will automatically exclude the unit from the system. If the system is still capable of providing the required load, the remaining units will continue to supply the load with no interruption. When the units still present in the system are no longer capable of fulfilling power requirements, the load will automatically be transferred onto the bypass mains. The load will be transferred with no interruption if the Inverters are synchronised with the network; if this is not the case, there will be an interruption lasting about 20 msec.
Overload
In the event of an overload at the Inverter output which lasts longer than the typical time/current (refer to Installation Manual – Specifications), the Inverter will shut down and the Static Transfer Switch will automatically transfer the load onto the bypass mains with no interruption. If the overload falls within the typical time/current that has been specified, the load will be returned to the inverters when the power drops to a level which can be supported by the number of active units in the system (parallel 1+N). In the event of a short circuit in the output, the load will normally be transferred onto the bypass mains, which will cause the Inverter to shut down; this switch is determined above all by the features of the protective devices in use in the system. In either case, an alarm message will appear on the UPS operator control panel display.
(1+N Parallel UPS System) The control logic system constantly monitors load requirements and controls the power supplied by the UPS modules. In the event that an overload condition is sustained for greater than a preset time, the load will transfer to the mains bypass supply, when the number of active modules are unable to satisfy load
Page 82
Chapter 7 - General Description Liebert Hipulse E User Manual Design Concept Single or '1+N' UPS System
Page 7-4 (07/04)
requirements. The load returns to the inverter supply if the power is reduced to a value that can be sustained by the number of active modules in the system.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the ‘Maintenance Bypass’ line is included to enable a ‘raw’ mains supply to be made available to the load while facilitating a safe working environment for carrying out scheduled UPS system maintenance or trouble shooting. The circuit is manually selected by the Maintenance Bypass Isolator which can be padlocked in the OFF position.
WARNING
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
CAUTION:
If an automatic circuit breaking device is not present in the input distribution panel, there remains a
dangerously high voltage at the output busbars and also on the input busbars of the UPS module that is switched off
7.2.4 ECOMODE (for single UPS only)
In this operating mode the System prefers to put the load on the Bypass Mains, with the Inverter on stand-by. The load is switched over to the Inverter when the mains goes outside of standard frequency and voltage values (or the values as modified using the operator panel when starting up the system). The ECOMODE configuration requires a different set­up in the default menu configuration, which may be prepared in the factory before shipment or during installation by personnel trained in use of the System.
Note: In order to operate in ECOMODE, UPSs must be provided with compatible software versions: The ‘UPS Logic’ card must be release 15.0 or later (the SW release of the cards may be read on the front panel display, referring to Section 8.1.2 Operating Instructions). Operating procedures in ECOMODE are the same as those described in Chapter 9, except that the load is normally on the Bypass Mains, the Load led is normally on Inverter (5), and the corresponding alarm message will be replaced with Load on Mains (6).
WARNING
In ECOMODE the load is not protected against mains distortion.
7.2.5 UPS Power Switch Configuration
Figure 7-2 illustrates the Liebert Hipulse E UPS module in what is known as the “Split Bypass” configuration. In the “Split Bypass” configuration the static bypass line is connected by a separate power switch to a dedicated `bypass'
power source which also feeds the maintenance bypass line. Where a separate power source is not available the Bypass ( Q2 ) and Rectifier input supply connections would be linked together.
With the exception of the maintenance bypass isolator, all the isolators shown must be closed during normal UPS operation.
7.2.6 Battery circuit breaker
The battery should be connected to the d.c. busbar through a circuit breaker fitted inside the battery cabinet –or located adjacent to the batteries where a battery cabinet is not used. This circuit breaker is closed manually, but it contains an undervoltage release coil which enables it to be tripped from the UPS control electronics following certain detected faults. It also has a magnetic trip facility for overload protection.
7.2.7 Battery temperature compensation
Liebert Hipulse E UPS System offers a battery temperature compensation circuit. As the temperature at the battery location rises the d.c. busbar voltage reduces in order to sustain the battery at its optimum charge voltage. This must be used in conjunction with the battery temperature sensor board.
7.2.8 Socket outlet
Socket outlet of 1A current 250 Vca (max) handling capability is provided for the ease of testing, commissioning & servicing of the UPS.
Page 83
User Manual Liebert Hipulse E Chapter 7 - General Description Single or '1+N' UPS System Design Concept
(07/04) Page 7-5
7.2.9 System Expansion
If necessary, a single-module system can be expanded to cater for an increased load requirement by adding additional modules. Such forward planning should also take into account the physical space required by any additional UPS modules, because any such modules must be situated adjacent to the existing system. System expansion requires a change in the SETUP of the display panel.
Note: System expansion should be carried out only by trained service personal.
The individual modules connected to the system must be of the same power rating.
7.2.10 Frequency Converter
Liebert Hipulse E is designed to function with the output AC to your critical load, supplied at a different frequency to the input mains. The following frequency conversions are available:
1. 50 Hz input 60 Hz output
2. 60 Hz input 50 Hz output
When operating a single module as frequency converter the Liebert Hipulse E requires the static bypass operation to be disabled and isolation of the input mains supply from your critical load. These modifications will be carried out by the setting of internal links to inhibit the static switch operation, and isolation of the supply to the bypass isolator. As a bypass is not required, it is easier to implement a frequency converter application by using a Multi Module Unit version (MMU) Liebert Hipulse E module (see Figure 7-1). For requirements with different operating voltages the solution is to use a standard MMU module with external adapter auto-transformer.
Figure 7-1 Example of frequency converter application
Page 84
User Manual Liebert Hipulse E Chapter 8 - Operating Instructions Single or '1+N' UPS System Operator Control and Display Panel
(07/04) Page 8-1
8 Chapter 8 - Operator Control and Display Panel
8.1 Introduction
On the front of the UPS there is a display and control panel, from which it is possible to easily verify the status of the UPS including all the measured parameters and alarms of the UPS and battery discharge status. The operator control panel is divided into three functional areas: * - ‘mimic LED display’ and Inverter control switch * - ‘operator panel ’&‘LCD display’ * - ‘bargraph section’ As can be seen the left section consists of LEDs, which indicate the operational and alarm status of the system by turning ON or OFF or by flashing ON/OFF. The middle section of the operator control and display panel consists of a LCD ( Liquid Crystal Display ) and its associated switches. The following functional area (right section) shows the various UPS load and battery charging conditions.
Figure 8-1 UPS Operator control/display panel
Page 85
Chapter 8- Operating Instructions Liebert Hipulse E User Manual Single or '1+N' UPS System Operator Control and Display Panel
Page 8-2 (07/04)
8.1.1 Operator control panel
The control and display panel LED indications are illustrated in figure 8-2 and described in the following text:
Figure 8-2 Single module operator control panel
Mimic indications
Six LED’s mounted on a single line diagram represent the various UPS power paths and show the current UPS operational status:
1 Bypass supply healthy
This led illuminates when the bypass a.c. input power switch is closed and the input supply is within of set
value nominal voltage ( default ±10% ).
2 Input supply healthy and Rectifier is operative.
3 Battery status healthy.
This LED illuminates when the battery is discharging and flashes when the battery circuit breaker is open.
4 Inverter output healthy.
5 Load on Inverter status.
This led illuminates when the output power switch is closed and the load is connected to the inverter
6 Load on Bypass status.
This led illuminates when the output power switch is closed and the load is connected to the bypass a.c. supply
via the static switch.
Inverter control switch
7 Inverter ON — Manual inverter selection switch.
8 Inverter LED — inverter status indicator contained above the switch icon.
The Inverter Led (yellow) indicates when the Inverter is switched OFF.
Page 86
User Manual Liebert Hipulse E Chapter 8 - Operating Instructions Single or '1+N' UPS System Operator Control and Display Panel
(07/04) Page 8-3
Menu Control switches
Four push button switches ESCape [9], DOWN [10], UP [11], ENTER [12], are located below the LCD display and are used to navigate a menu-driven UPS operating and control system.
Note 1: In addition to entering the day-to-day operating functions, the menu system is also used to set-up various UPS operating parameters during commissioning. A system of password protection is therefore used to limit the control functions accessible to the operator, whilst allowing full access to maintenance personnel. A full description of the available menus is provided in the appropriate User and Commissioning manuals.
Note 2: From the display Panel Menu it possible to select one of the following languages: English (
1
), Italian (1),
French, Spanish and German. The sequence is Default Window
FUNCTION⇒ENTER PASSWORD⇒PANEL
SETUP
LANGUAGE.
Default language is English.
Other languages can be selected as: English (
1
), Italian (1), Dutch, Swedish and Norwegian. It requires a replace of
the programmable component.
Note: (
1
) Base languages are English and Italian.
9 ESC Pressing the ESCAPE cancels the most recent actions;
i.e. when selecting options it returns the previous window to the LCD;
when setting parameters, it exits the window without saving the new settings;
10 MENU
The DOWN push-button moves a cursor down the LCD over the options offered on certain
windows, and changes the highlighted parameter values in others.
11 MENU
The UP push-button moves a cursor up the LCD over the options offered on certain windows, and
moves a rectangular cursor to the next digit on the right when changing parameter values in others;
12 ENTER
Pressing ENTER, when selecting options, displays the next window;
The next window is determined by the option which has been selected in the present window.
When selecting new parameters its saves the new parameters.
13 Warning Indicator — The red LED within the Alarm Silence Switch illuminates when a WARNING alarm is
displayed on the LCD message screen, and is normally accompanied by an audible alarm.
14 Alarm Silence Switch — Pressing the Alarm Silence Switch cancels the audible alarm but leaves the warning
message displayed until the inappropriate condition is rectified.
Page 87
Chapter 8- Operating Instructions Liebert Hipulse E User Manual Single or '1+N' UPS System Operator Control and Display Panel
Page 8-4 (07/04)
Operator Panel & LCD Display
15 LCD Display
The LCD display is capable of showing four rows of 20 characters; the top row displays the UPS warning and alarm messages and the lower row indicate the selected metered parameters.
During normal operation the top line of the LCD panel shows the general UPS Status (e.g. NORMAL OPERATION ) and the bottom line will indicate the current time and date – this is known as the ‘Default Screen’. Pressing the ESCape button [9] changes the displayed information to indicate the Communications Port status (if connected) and the version of the software fitted to the UPS control boards.
Pressing the ENTER button [12] from the Default Screen gives the operator access to the ‘Measurements/Alarm history’ menu which facilitates access to the following measurements:
Output Parameters
– Output Voltage (L-L or L-N for all three phases) – Output Current (all three phase currents displayed in Amperes or as a % Load) – Output Power (for all three phases displayed in kW or kVA) – Output Frequency (of inverter and bypass mains)
Input Parameters
– Input Voltage (L-L for all three phases)
Battery Parameters
– Battery Voltage – Battery Current – Battery Charge (in %) or remaining autonomy time when the battery is discharging.
Temperature
– Battery Temperature (°C)
Alarm History: It provides current and historical events and the alarms, with date stamping. Running Time: It shows the operating hours of the UPS.
Bargraph Section
This following functional area shows the various UPS load and battery charging conditions.
16 Load Battery
The amber LED situated at the beginning of the % Autonomy bargraph illuminates when the battery voltage has
discharged to 1.8V/cell and indicates that the battery is approaching its low voltage cut-off point and the UPS will shortly shut-down.
17 % Battery state Autonomy time bargraph
When the battery is being charged (normal) the five leds illuminate progressively to indicate the state of battery
charge as a percentage of a charge. When the battery is discharging (battery on-load) the bargraph function changes to provide an indication of the remaining battery autonomy time.
With a fully charged battery all five LEDs are illuminated indicating than time remaining is dependent upon both the battery A/Hr capacity and the applied percentuage load. An autonomy is determined from the type of battery used, as the autonomy falls below this time the LEDs will extinguish in steps starting from the right-hand end.
18 % Load bargraph
The five leds illuminate progressively to indicate the applied load as a percentage of the rated maximum current,
increasing in 20% steps to 100% of full load when all five are illuminated.
19 Overload
The amber LED situated at the end of the % Load bargraph illuminates if the applied load exceeds 100% of the
module(s) rated output current. This indication will be accompanied by an audible alarm and an alarm message.
Page 88
User Manual Liebert Hipulse E Chapter 8 - Operating Instructions Single or '1+N' UPS System Operator Control and Display Panel
(07/04) Page 8-5
Figure 8-3 EPO on UPS module
20 Emergency Stop — housed beneath a safety cover to prevent inadvertent operation
When the emergency stop switch is pressed it disables the static switch block entirely (so removing load power). It also disables the rectifier and inverter, and trips the battery circuit breaker. Under normal circumstances it does not remove UPS input power since this is applied through a manually controlled external isolator; however, if the UPS input supply is connected via a circuit breaker having an electrical trip facility, emergency power off can be used to drive the external circuit breaker's trip circuit.
Page 89
Chapter 8- Operating Instructions Liebert Hipulse E User Manual Single or '1+N' UPS System Operator Control and Display Panel
Page 8-6 (07/04)
8.1.2 The Menu Options
A map of the routes to the options offered by the menu is provided in figure below. Options include windows, which show status information and windows which permit data to be entered, or parameters for equipment control to be set. The menu map shows that the routes pass from the main menu through different intermediate windows to reach the option targeted. The diagram shows each of the windows in the format in which it appears on the LCD screen. The initializing, default & main menu windows are described below.
Page 90
User Manual Liebert Hipulse E Chapter 8 - Operating Instructions Single or '1+N' UPS System Operator Control and Display Panel
(07/04) Page 8-7
Figure 8-4 Map of screen display available to operator
ESC
ESC
ESC
ESC
ESC
Page 91
Chapter 8- Operating Instructions Liebert Hipulse E User Manual Single or '1+N' UPS System Operator Control and Display Panel
Page 8-8 (07/04)
LCD Display Panel Messages
Initializing Window.
After first connecting power to the UPS and closing the bypass a.c. input power switch, the INITIALIZATION message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded and the unit performs a self test. It is followed by a window showing various messages with the time and date on the bottom line.
When the power switches and battery circuit breaker have been closed and the inverter has stabilized the window will change to the default window.
Default Window.
The message shown below, will be seen on the default window whenever the UPS is operating normally:
The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.
If the ECOMODE configuration is in effect, the default window will be modified as shown to the side.
Info Window.
From Default Window, pressing the ESC key, information about the modem programmed in memory and its connection are shown on display.
Pressing again the ESC key, software release are shown, both on UPS board and on Panel board: this feature is useful upgrading SW for next versions and to know exactly features of present release.
Pressing again ESC key it goes back to Default Window.
Main Menu Window.
The main menu is selected from the Default Window by pressing the ENTER key:
The four windows accessed from the Main Menu offer further options which are described in the relevant chapters of this manual.
The MEASUREMENT option gives access to windows which show the present values of parameters such as input & output voltages and current, load etc. These parameters are useful when determining the state of the UPS or the causes of alarms, and are described in more detail below.
The ALARM HISTORY window displays detailed current and historical event, warnings and alarm can be scrolled on the UPS display or can be simultaneously gathered through background RS232 port or LAN. The ALARM HISTORY procedure is detailed in Chapter 9.
LIEBERT
UPS
RECTIF. SWITCH OPEN BATTERY C.B. OPEN OUTPUT SWITCH OPEN HH.MM.SS DD.MM.YY
NORMAL OPERATION
HH.MM.SS DD.MM.YY
>MEASUR./ALARM HIST.< FUNCTION MAINTENANCE SETUP
SW VERSION
PANEL V xx.x UPS LOGIC V xx.x
MODEM TYPE 3COM U.S.ROBOTICS MODEM STATUS: NOT CONNECTED
NORMAL OPERATION (ECOMODE) HH.MM.SS DD.MM.YY
Page 92
User Manual Liebert Hipulse E Chapter 8 - Operating Instructions Single or '1+N' UPS System Operator Control and Display Panel
(07/04) Page 8-9
The FUNCTION, MAINTENANCE and SETUP options all require a password, which is set by the commissioning engineer. This manual does not provide servicing instructions and the options accessed from these windows are therefore not shown on the menu map in figure 8-4. Only trained service engineers should be authorized with a password.
In any case FUNCTION, MAINTENANCE and SETUP options can be read but it is not possible to change them without the password.
Option Selection Mode
If a window from which options can be selected is displayed, a pair of indicator arrows appear at the extremities of the line.
The UP/DOWN push buttons move these up and down the screen over the options. When the arrows point at a chosen option, press ENTER to display the next window. Press ESCAPE to return the previous window to the screen.
Alarm/Warning messages
The Alarm and Warning messages are shown on the three upper lines of the display. The ALARM indicator (red) and audible warning accompany all Alarm messages.
There is a default selection for every message and corresponding mode of red indicator ( OFF, ON, FLASHING ) and buzzer sound ( OFF, ON, INTERMITTENT, SINGLE SOUND ).
The default mode can be changed according to particular needs of the plant, a PC and communication program are needed .
The Alarm and Warning messages are detailed in Chapter 10 - Display Panel Interpretation of this manual.
Page 93
User Manual Liebert Hipulse E Chapter 9 - Operating Instructions Single or '1+N' UPS System Procedure
(07/04) Page 9-1
9 Chapter 9 - Operating Instructions
9.1 Introduction
The UPS can be considered to be in one of following operating conditions:
Normal operation - All relevant power switches and circuit breakers closed, the load is powered by the UPS.
On Maintenance Bypass - UPS shut down but the load connected to the unprotected mains via the
Maintenance Bypass Supply line.
Shutdown - All power switches and circuit breakers open - no load power.
On Static Bypass - The load power is supplied though the mains static bypass line. This may be considered as
an intermediate operating condition being utilized for the purpose of load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.
ECOMODE – All relevant power supply switches and the battery switch are on, and the load is fed by the
Bypass Mains through the UPS Static Transfer Switch, while the Inverter remains on stand-by.
This chapter contains instructions which enable you to switch between the above conditions, to carry out a RESET and how to switch ON\OFF the inverter, etc.
9.1.1 General notes
Note 1: All the user controls and indicators (led) mentioned in these procedures are identified in Chapter 8.
Note 2: The audible alarm may annunciate at various points in these procedures. It can be canceled at any time by
pressing the `Alarm Reset' push-button.
Note 3: The Liebert Hipulse E UPS System incorporates an optional automatic boost charge facility which can be
used in systems containing conventional flooded lead-acid batteries. If this type of battery is used in your installation you may notice that the battery charger voltage may be greater than its nominal (432V d.c. for 380V a.c., 446V d.c. for 400V a.c. and 459V d.c. for a 415V a.c. system) when the mains supply returns from a prolonged outage. This is the normal response of the boost charge facility: the charger voltage should return to normal after a few hours.
9.1.2 Power Switches
The UPS can be separated by means of power switches, mounted inside the cabinet and accessible after opening the front door, which has a key. The location of the UPS power switches is shown in Figure 9-1.
The UPS module power switches are: Q1 - Input Isolator: connects the UPS with the mains supply. Q2 - Bypass Isolator: connects the UPS with the bypass supply. Q3 – Maintenance Bypass Isolator (padlocked) permits supply of the load directly by the bypass line for maintenance
of the UPS module.
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules
in parallel.
Q4 - Output Isolator: connects the output of the UPS to the load.
Note : The battery interrupter is not expected inside of the UPS and should be installed in the proximity of the respective battery.
Page 94
Chapter 9 - Operating Instructions Liebert Hipulse E User Manual Procedure Single or '1+N' UPS System
Page 9-2 (07/04)
Figure 9-1 Power Isolator Location
Input Isolator (Q1) Bypass Isolator (Q2) Maintenance Bypass Isolator (Q3) Output Isolator (Q4) Terminal blocks
Page 95
User Manual Liebert Hipulse E Chapter 9 - Operating Instructions Single or '1+N' UPS System Procedure
(07/04) Page 9-3
9.2 Procedure for UPS Start-Up: without interrupting power to the load
This procedure will describe how to start the UPS and the how to transfer the load from the external maintenance bypass to the UPS inverter. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed. Refer to Fig. 9-1 for corresponding isolators Q1 to Q4.
ENSURE CORRECT PHASE ROTATION.
1. Close Q3 Maintenance Bypass switch and external switch (inside Maintenance Bypass) to load.
2. Close the Output power switch Q4 and the Bypass power switch Q2.
Initializing Window: after first connecting power to the UPS and closing the isolator, this message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded. It is followed by a screen showing various messages with the time and date on the bottom line.
The Module Mimic indicators Bypass supply healthy ( 1 ) and after 20 seconds Load on bypass ( 6 ) will flash and red
led (13) will illuminate.
The Display window will show the present status of the UPS:
3. Close the Rectifier input power switch Q1.
Note: In ECOMODE the message ‘LOAD ON BYPASS’ will not appear.
4. Wait for 20 seconds then close the battery circuit breaker. The Module Mimic indicator ( 3 ) Battery unavailable should extinguish. Several LED's on the Battery state of charge bar graph will illuminate showing the battery state of charge.
The rectifier will `walk-in' and stabilize at float the voltage.
5. Open the Maintenance Bypass power switch Q3 and fit lock. The Module mimic indicator Load on bypass ( 6 ) will Flash amber.
The Display window will show the present status of the UPS:
6. After 5 seconds the Module Mimic LED's will change so that the Load on inverter ( 5 ) will light steady green and the Load on bypass ( 6 ) will extinguish.
Note: In ECOMODE the Load on Mains led (6) stays on while the Load on inverter led (5) is off.
LOAD ON BYPASS INV.: OFF
HH.MM.SS DD.MM.YY
RECTIF. SWITCH OPEN BATTERY C.B. OPEN MANUAL BYPASS CLOSED HH.MM.SS DD.MM.YY
LOAD ON BYPASS MANUAL BYPASS CLOSED INV OFF HH.MM.SS DD.MM.YY
LIEBERT
UPS
Page 96
Chapter 9 - Operating Instructions Liebert Hipulse E User Manual Procedure Single or '1+N' UPS System
Page 9-4 (07/04)
The message shown below, will be seen on the default screen whenever the UPS is operating normally:
The UPS is operating normally with its inverter supplying the load.
ECOMODE: The following message will appear in the default screen whenever the UPS is operating in ECOMODE. The load is supplied by the Bypass Mains.
The UPS is operating in ECOMODE with the Bypass Mains supplying the load.
NORMAL OPERATION
HH.MM.SS DD.MM.YY
NORMAL OPERATION (ECOMODE) HH.MM.SS DD.MM.YY
Page 97
User Manual Liebert Hipulse E Chapter 9 - Operating Instructions Single or '1+N' UPS System Procedure
(07/04) Page 9-5
BATTERY C.B. OPEN
HH.MM.S DD.MM.YY
9.3 Procedure for UPS Start-Up: without power initially supplied to the load
This procedure should be followed when turning on the UPS from a fully powered down condition - i.e. where the load is not being initially supplied at all. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed. Refer to Fig. 9-1 for corresponding isolators Q1 to Q4.
1. Open the UPS door(s) to gain access to the main power switches.
2. Close the Rectifier Power Switch Q1. The Module Mimic LED's will indicate input supply a.c. present ( 2 - steady green ) and after approximately 20 seconds the Inverter output healthy ( 4 - steady green ) and Battery unavailable (3) will light and also red led (13) will illuminate. The Display screen will show the following:
Initializing Window: after first connecting power to the UPS and closing the Q1 isolator, this message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded. It is followed by a screen showing various messages with the time and date on the bottom line.
Note: If input power is present but the display remains blank, then the Micro Controller is not working, please contact your dealer for advice.
WARNING
THE FOLLOWING ACTION WILL APPLY POWER TO THE LOAD EQUIPMENT -
ENSURE THAT IT IS SAFE TO DO SO.
3. Close the UPS output power switch Q4. The Module Mimic LED's will change so that the Load on inverter ( 5 - steady green ) and Battery unavailable (3) will light and also red led (13) will illuminate.
Note: In ECOMODE the Load on inverter led (5) is off.
The display window will show:
4. Close the Bypass input power switch Q2. Bypass input Led ( 1 – steady green ) will light, after 20 seconds the inverter synchronises with the mains bypass.
5. Before closing the battery circuit breaker check the d.c. bus-bar voltage. From the above window press the
ENTER key:
LIEBERT
UPS
BYPASS SWITCH OPEN BATTERY C.B. OPEN OUTPUT SWITCH OPEN HH.MM.SS DD.MM.YY
BATTERY C.B. OPEN BYPASS SWITCH OPEN
HH.MM.S DD.MM.YY
Page 98
Chapter 9 - Operating Instructions Liebert Hipulse E User Manual Procedure Single or '1+N' UPS System
Page 9-6 (07/04)
The Main Menu Window will display:
Select MEASUREMENT/ALARM HISTORY and press ENTER key:
Select MEASURES and press ENTER key.
Select BATTERY and the d.c. bus bar voltage will be displayed:
If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system 446V d.c. for 400V a.c. system and 459V d.c for a 415V a.c. system) press the escape key repeatedly until the display returns to the original window.
6. Manually close the battery circuit breaker. The Module Mimic indicator ( 3 ) Battery unavailable should extinguish. Several LED's on the Battery state of
charge bargraph (17) will illuminate showing the battery state of charge.
When the battery circuit breaker has been closed and the inverter has stabilized the screen will change to the default
window.
Default Window.
The message shown below, will be seen on the default screen whenever the UPS is operating normally:
The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.
The UPS is operating normally with its inverter supplying the load.
ECOMODE: The following message will appear in the default screen whenever the UPS is operating in ECOMODE. The load is supplied by the Bypass Mains.
The UPS is operating in ECOMODE with the Bypass Mains supplying the load.
BATTERY: VOLTAGE 446 [V] CURRENT 001 [A] CHARGE 000 [%]
NORMAL OPERATION
HH.MM.SS DD.MM.YY
> MEASUR./ALARM HIST.< FUNCTION MAINTENANCE SETUP
OUTPUT INPUT > BATTERY < TEMPERATURE
NORMAL OPERATION (ECOMODE) HH.MM.SS DD.MM.YY
>MEASURES< ALARM HISTORY RUNNING TIME
Page 99
User Manual Liebert Hipulse E Chapter 9 - Operating Instructions Single or '1+N' UPS System Procedure
(07/04) Page 9-7
9.4 Procedure for Switching the UPS into a Maintenance Bypass condition from normal operation.
The first part of this procedure details how to select the Inverter OFF and power the load from the bypass mains via the Static Switch. This procedure should be followed to transfer the load from the UPS inverter output to the maintenance bypass system. This may be required during UPS maintenance procedures. NORMAL OPERATION: follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass of the UPS.
ECOMODE: follow the procedure below to transfer the load from the output to the Maintenance Bypass of the UPS.
Caution
The following window allows the operator to select the UPS inverter ON or OFF. Before making this operation, read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it, not to risk a short interruption in powering the load.
IF YOU ARE NOT SURE OF WHAT YOU ARE DOING - THEN DO NOT DO IT.
1. Press the INV switch on the left side of the operator control panel.
2. Confirm this operation as instructed at the display:
Press Enter for 1 second to confirm INV OFF Press Esc for 1 second to exit
3. If Enter is pressed: The Module Mimic indicator Load on Inverter ( 5 )will extinguish and the Load on Bypass indicator ( 6 ) will flash amber, and also the red led (13) will flash and normally will accompanied by an audible alarm. Pressing the Alarm Silence Switch cancels the audible alarm but leaves the warning message displayed until the appropriate condition is rectified.
NORMAL OPERATION:
4.a The UPS inverter will now shut down and the load will transfer to the Bypass supply.
The Module Mimic indicator Load on Bypass (6) will flash amber and the Load on Inverter (5) indicator will extinguish.
Your load is now powered via the Static Bypass system.
ECOMODE:
4.b At this point the UPS inverter stops but the load continues to be supplied by the bypass mains.
The Load on Mains indicator light (6) on the unit’s synoptic panel flashes yellow, and the Load on Inverter indicator light (5) goes off.
Your load is now powered via the Static Bypass system.
WARNING! STOP INVERTER REQUESTED ENTER TO CONTINUE ESC TO CANCEL
Page 100
Chapter 9 - Operating Instructions Liebert Hipulse E User Manual Procedure Single or '1+N' UPS System
Page 9-8 (07/04)
5. Unfasten the lock, release the internal safety bar and close the maintenance bypass power switch Q3. Open the
Rectifier input power switch Q1, the Output power switch Q4, the bypass power switch Q2 and the Battery circuit breaker. The unit will power down but the load will continue to be supplied by the manual Maintenance bypass.
WARNING
WARNING: Wait 5 minutes for the internal d.c. bus bar capacitors to discharge.
WARNING
The following points will be live within the UPS:
Bypass a.c. input supply terminals and busbars
Maintenance Bypass power switch
Static Bypass power Switch
UPS output terminals and busbars
Input and output terminals remain protected by a metallic cover.
Your load is now powered from the maintenance bypass system and the UPS is completely shut down.
Caution
The load equipment is not protected from normal supply aberrations when operating in the maintenance bypass mode.
9.5 Procedure for Switching the UPS ON from a Maintenance Power condition.
Follow the procedure for ‘UPS Start-Up: without interrupting power to the load’ referring to the paragraph 9.2, start from point number 2.
Loading...