Liebert GXTTM User Manual

English
UPStation GXT™
6 & 10 kVA
230V
USER MANUAL
IMPORTANT SAFETY INSTRUCTIONS
1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training.
2. This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer. See Limited Warranty.
3. This UPS is designed for use on a properly earthed (grounded), 208-240 VAC, 50Hz or 60Hz supply, for installation by qualified personnel. A qualified electrician must review and approve customer supplied wiring, circuit breakers, intended loads, and verify correct input, output and earth connections to ensure compliance with technical standards and local electrical codes of practice. Installation instructions and warning notices only for use by qualified personnel are located after the UPS operator instructions in this manual.
WARNING: This UPS should not be supplied from electrical power systems of the “IT” (Impédance à Terre) type. (IEC 364-ELECTRICAL INSTALLATION OF BUILDINGS)
4. ELECTROMAGNETIC COMPATIBILITY- This UPS complies with the
requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
WARNING: This is a CLASS A – Uninterruptible Power System Product. In a domestic environment, this may cause radio interference, in which case the user may be required to take additional measures.
5. Operate the UPS in an indoor environment only in an ambient temperature
range of 0°C to +40°C (32°F to +104°F). Install it in a clean environment, free from moisture, flammable liquids, gasses, or corrosive substances.
6. This UPS contains no user serviceable parts. The UPS ON/OFF pushbuttons
do not electrically isolate internal parts. Under no circumstances attempt to gain access internally, due to the risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions, or the UPS performance alters in use. Refer all faults to your dealer.
7. Only trained engineers authorised by Liebert should perform troubleshooting.
To replace batteries, refer all servicing to qualified service personnel. PROPER DISPOSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR DISPOSAL REQUIREMENTS.
8. Never block or insert any object into the ventilation holes or other openings.
9. DO NOT CONNECT equipment that could overload the UPS or demand DC
current from the UPS, for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half wave rectification.
1
10. Storing magnetic media on top of the UPS may result in data loss or
corruption.
11. Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth,
never liquid or aerosol cleaners.
GLOSSARY OF SYMBOLS
Indicates AC Input
Indicates AC Output
Indicates Caution: Note the accompanying instruction
Indicates the position of a fuse
Requests the user to consult the manual for additional information
Indicates that the unit contains a valve regulated lead acid battery
2
INTRODUCTION AND SYSTEM DESCRIPTION
Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure, which may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT protects equipment from these disturbances.
The UPStation GXT is a compact, “on-line” UPS. An “on-line” UPS continuously conditions and regulates its output voltage, whether the mains power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power. The GXT 6000/10000T-230X models have an additional output isolation transformer.
For ease of use, the UPStation GXT contains a light emitting diode (LED) display to indicate either “load percentage” or “battery capacity” depending upon the mode of operation. It also provides self-diagnostics, a combination On/Alarm Silence/Manual Battery Test button, a combination Off/Bypass button, and two levels of alarms when the unit is operating on battery.
The UPStation GXT has an interface port for communications between the UPS and a LAN server or other computer system. This port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with the SiteNet® 2 software. SiteNet® 2 software can also remotely control UPS operation.
MAJOR COMPONENTS
Rectifier/PFC
INPUT
EMI/RFI
Filter
Battery
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS
These UPS components provide surge protection, and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected.
Battery
Charger
Inverter
EMI/RFI
Static Bypass
Output Transformer
GXT 230X models only
Filter
OUTPUT
3
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to regulated DC power for use by the inverter, while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives: the mains power is used as efficiently as possible by the UPS, and the amount of distortion reflected on the mains is reduced. This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT.
INVERTER
In normal operation, the inverter utilises the DC output of the power factor correction circuit and “inverts” it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required energy from the battery through the rectifier / PFC. In both modes of the operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
BATTERY CHARGER
The battery charger utilises energy from the Rectifier / PFC and precisely regulates it to continuously “float” charge the battery system. The battery system charges whenever the UPStation GXT is connected to mains power.
BATTERY
The UPStation GXT employs valve regulated, non-spillable, lead acid batteries. At typical room temperatures and with the UPS float charging, the battery system will last many years. Optional external battery cabinets are available to provide extended run times.
STATIC BYPASS
The UPStation GXT provides an alternate path for mains power to the connected load, in the unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature, or UPS failure condition, the UPS automatically transfers the connected load to BYPASS providing the bypass voltage is within specification. BYPASS operation is indicated by an alarm and an illuminated BYPASS LED (other LED’s may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to BYPASS power, press the output OFF button once. NOTE: The BYPASS power path does NOT protect the connected equipment from disturbances on the mains supply and its range of operation is limited to +/­15% of the nominal input supply voltage.
AUTO RE-START
Upon restoration of the mains AC power after a mains power outage and complete battery discharge, the UPS will automatically restart and supply power to the critical load and the battery charger automatically recharges the battery.
4
CONTROLS AND INDICATORS
Fault Indicator
UPS ON /
Alarm Silence /
Manual Battery Test
Output OFF /
Bypass
Load / Battery Level
Indicators
BYPASS
UPS ON
BATTERY
AC INPUT
Fault Indicator (Red)
The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting Guide).
BYPASS Indicator (Amber) The BYPASS indicator is illuminated when the UPS is operating from BYPASS power. An alarm will sound indicating the UPS detected a problem, or manually set to BYPASS.
UPS ON Indicator (Green) The UPS On indicator is illuminated when the UPS inverter is operating and supplying power to your connected loads.
Battery Indicator (Amber) The Battery indicator is illuminated when the UPS is operating from the battery system.
AC Input Indicator (Green) The AC Input indicator is illuminated when mains power is available and within the input specification.
Load/Battery Level Indicators (4 Green, 1 Amber) The Load/Battery Level indicators have dual functions. During NORMAL mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity.
5
The UPStation GXT is equipped with automatic and remote battery test features. The automatic test occurs every 14 days if a manual battery test has not been performed or if mains has not been interrupted (14 day timer resets if unit goes to battery). Should the battery fail this test, the fault indicator along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to Troubleshooting Guide). The remote test feature functions with either SiteNet® 2 or SiteNet® SNMP Manager software and can remotely initiate the battery test.
UPS ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions: UPS ON, Alarm Silence, and Manual Battery Test. To start the UPS, while in the BYPASS mode, press this button until the command is acknowledged by a beep from the audible alarm. This will provide conditioned and protected power into the output terminal block. To silence alarms, press this button for at least one half second while alarm conditions are present. After the alarm is silenced, the UPStation GXT will reactivate the alarm system to alert of additional problems. NOTE: The low battery and BYPASS reminder alarms cannot be silenced. BATTERY TESTING- To initiate a manual battery test, press this button for at least one half second while operating in normal UPS mode power and no alarm conditions are present. If the bottom two LED's do not illuminate during a Battery Test, allow the UPS to recharge the batteries for 24 hours. After 24 hours, retest the batteries. If the batteries have been re-tested and the bottom two LED's still do not illuminate, contact your dealer or Global Services for a battery replacement.
OUTPUT OFF/BYPASS Button
This button controls output power to connected load(s) and has dual functions: OUTPUT OFF and Bypass. CAUTION: Pressing this button once during normal operation will cause the load to be transferred to BYPASS power. Pressing this button a second time within 4 seconds will result in loss of power to the output and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.
6
GXT 6 & 10 kVA
Component Diagram
230 & 230X Models Shown
TM
DB-9 Communications Port
Intellislot Communications Port
TM
Intellislot Communications Port
DB-9 Communications Port
Output Voltage Selector Switches
Output Voltage Selector Switches
Input
Breaker
Hardwire
Terminal Blocks
Battery
Breaker
Battery
Breaker
Output
Breaker
Terminal Blocks
Adjustable levels
Breakers
Input Output
Hardwire
7
OPERATING MODES
NORMAL MODE OPERATION- UPS mode
During normal operation, mains power provides energy to the UPS. The filters, the power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state.
The four green LED’s indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and sound an alarm.
The display template indicates the percentage of load on the UPS output.
BATTERY MODE OPERATION
Battery mode occurs in event of an extreme input voltage condition or complete mains failure. The battery system supplies power through the DC-DC converter to the inverter to generate power for the connected load.
During battery mode an alarm sounds every 10 seconds. This will change to 2 beeps every 5 seconds when battery runs low (approximately 2 minutes remaining). The AC Input LED will extinguish, and the Battery LED will illuminate to warn that a mains problem has occurred. Each load/battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to the Troubleshooting Guide.
To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add an optional external battery cabinet.
CAUTION: Turning off the UPS while in battery mode will result in loss of output power.
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging the battery.
Normal Mode Operation at
51-75% loading
Battery Mode Operation at
81-100% battery capacity
Loading...
+ 21 hidden pages