Liebert GXT5-16KIRT9UXLE Product Data Sheet

Vertiv™ Liebert
®
GXT5 UPS
5 - 20 kVA 230V
Intelligent and Eicient UPS for Protection of Your Mission-Critical Applications
Vertiv™ Liebert® GXT5 | 5 - 20 kVA UPS
Largest Rack Mount Capacity Available in an Intelligent,

The Vertiv™ Liebert® GXT5 UPS is an online double conversion UPS solution which oers premium power outage protection and continuous power conditioning in a compact and flexible rack/tower form factor.
The Liebert GXT5 single-phase UPS operates with high power eiciency, making it ideally suited to protect critical infrastructure in both centralized and edge network applications.
Now available in higher capacity ratings of 16 and 20 kVA the GXT5 UPS allows for highly reliable single UPS installations minimizing required rack space and supporting more IT equipment loads.
Scalable runtime options with matching external battery cabinets oer additional flexibility when extended uninterrupted
power is required. Plus, the Liebert GXT5 provides battery health status and replacement date prediction for intelligent battery health management.
The UPS system is easy to deploy and maintain due to its user-friendly LCD interface and remote management capabilities supported by the Vertiv RDU101 communications card which makes the Liebert GXT5 compatible with Vertiv infrastructure management solutions such as LIFE™ Services, environmental sensors, Trellis™ Power Insight, and more.
With market leading eiciency and unity power factor operation, the Liebert GXT5 will meet your critical application needs. And you can rest assured that your business is protected with this Vertiv solution that includes a standard, two-year advanced exchange product warranty.
What's in the box
y UPS
y Tower Stand
y USB Cable
y Quick Start Guide
y Safety Manual
y Power Insight Management
Software (free download from Vertiv.com)
Liebert GXT5 Features
Leading UPS Technology
y High output power factor up to 1.0
y Full-color graphic LCD
with gravity sensing orientation
y External battery cabinets with
auto-detection
y Parallel or redundant
operation capability
y Battery health status and
replacement date prediction
y Remote management, update,
and configuration capabilities
y Optimized thermal management
and variable speed fan for peak eiciency and noise reduction
Eicient and Green Product
y High eiciency in online mode
y Energy Star® 2.0 certified
y Even higher eiciency (up to 98%) in
Active ECO mode
y Compliance with Restriction of
Hazardous Substances (RoHS) directive and the Registration, Evaluation, Authorization and Restriction of Chemicals (REACH) regulation
Solutions Wide
y Compact rack/tower design
y Broad range of services and
extended warranty
y Easy to install, configure and operate
y Vertiv RDU101 network
communications card with advanced features
y Compatibility with SN series
environmental sensors
y Integrated dry-contacts with
selectable definition
y Free Trellis™ Power Insight
management software
y Serial port for out-of-band
management with Avocent® serial consoles
y Automatic internal bypass and
external maintenance bypass options
2
Vertiv™ Liebert® GXT5 Features
A
B
LCD
COLOR
LCD
COLOR
LCD
COLOR
B
LCD
COLOR
B
LCD
COLOR
LCD
COLOR
ECO
A
B
LCD
COLOR
B
2+1
High power factor (1.0)
1.0
Compact rack/ tower design
Space-saving UPS provides rack space optimization and flexible installation.
PF
More usable power enables more connected loads saving space and costs.
Eiciency (up to 95%)
in online mode
Energy Star 2.0 certification. Higher
eiciency means an optimized energy
management and lower heat
dissipation, for energy savings and
improved reliability.
Parallel/redundant
operation capability
For 10, 16 or 20 kVA
models, configurations
up to 2+1 redundancy
support maximum
availability and enables
growth as load demand
increases.
2+1
ECO
Eiciency (up to 98%) in Active ECO mode
Superior protection with maximum eiciency.
Product warranty
Comprehensive coverage
B
through a standard two-year advanced exchange warranty.
Colored graphic
LCD with gravity
sensitive orientation
User-friendly interface
provides insight to
UPS status for easy
installation, configuration
and operation.
Integrated Battery
With self-test and
detection capability
Battery Cabinets
with auto-detection
Be confident the UPS is set
up correctly to report
available runtime when used
with external battery cabinets.
COLOR
LCD
3
Vertiv™ Liebert® GXT5 | 5 - 20 kVA UPS
How You Benefit from the Vertiv™ Liebert® GXT5 UPS
Designed for high availability
y Higher power factor (1.0) ensures the connection of more loads and IT equipmenty Available rack mount maintenance bypass solution eliminates the need to
power down connected equipment (16-20) kVA
y Device can be swapped during operation without powering down connected equipment thanks to manual
bypass pod integrated in the device (removable connetion box), (5-10) kVA
y Optional output distribution POD for flexibility of connected equipment needsy Hot-swappable, user-replaceable battery modules minimize downtimey LIFE™ Services helps to enhance uptime, as well as operational eiciency with
continuous remote monitoring, expert analysis, and proactive response
y Automatic programmable battery self-test
User-friendly installation and operation
y Easy-to-read, gravity-sensing graphical color displayy Intuitive user interface for local configuration and managementy Support for the Vertiv suite of remote management tools
(Trellis™ Power Insight, RDU101 network interface card, and serial connectivity support)
y Auto-detection of external battery cabinets enables faster deployment and accurate runtime informationy Remote UPS firmware upgrade capability ensures the UPS has the latest features and enhancements
Longer service life and runtime of the batteries
y Extended runtimes provided by the addition of external battery cabinetsy Improved battery care by temperature-compensated battery chargingy Intelligent battery health management ensures a longer service life
(optimized battery maintenance and replacement when needed)
Optimized energy and capacity management
y Active ECO operating mode with up to 98% eiciencyy Eiciency in online double conversion mode up to 95%y Energy Star 2.0 certified
Seamless connectivity
y Four onboard, user-definable dry contact I/O for integration of support management systemsy Supports SNMP, web, and environmental sensors with the optional RDU101 communications cardy Serial connection for integration of Avocent® ACS product or direct serial management and
control of the UPS
4
Vertiv™ LIFE™ Services Remote Diagnostic and Preventive Monitoring
Vertiv's service program is designed to ensure that your critical power protection system is maintained in an optimum state of readiness at all times.
The Vertiv LIFE™ remote diagnostic and preventive monitoring service provides early warning of UPS conditions and out of tolerances. This allows eective proactive maintenance,fast incident response and remote trouble shooting, giving customers complete security and peace of mind.
With Vertiv LIFE Services you will benefit from:
Uptime Assurance
Constant monitoring of UPS parameters, thus maximizing the availability of your critical infrastructure.
First Time Fix Rate
Pro-active monitoring and data measuring ensure that when our customer engineers are dispatched on-site, they arrive prepared for first time resolution.
Proactive Analysis
From Vertiv LIFE Services centers, our experts proactively analyze the data and trends of your equipment, to recommend actions to ensure their best performance.
Minimized Total Cost of Ownership of Your Equipment
The continuous monitoring of all relevant parameters in turn maximizes unit performance, reduces on-site maintenance and extends the life of your equipment.
Fast Incident Response
Vertiv LIFE Services allow for immediate definition of the best course of action, as a result of the regular communication between your Liebert GXT5 system and our Vertiv LIFE Services centers.
Reporting
You will receive a comprehensive report detailing the working order of your equip mentand its operational performance.
Remote Diagnostic Services for Rapid Response
Uptime assurance
y Continuous monitoring for early
detection of trends and operating anomalies
y Analysis and interpretation of alarm
and status messages
Rapid incident response
y Automatic transmission of data for
analysis
y Concurrent diagnosis and dispatch of
engineer to site
y Shipment of parts for corrective
maintenance
Increased insight and ease of management
y Notification of operating conditions
that may impact system health
y Periodic trend and analysis reports
Refer to page 11 for service oerings' SKUs
y Integration of remote and on-site
services to ensure business continuity
5
Vertiv™ Liebert® GXT5 | 5 - 20 kVA UPS
Technical Specifications 5-10 kVA
GXT5-5000IRT5UXLE GXT5-6000IRT5UXLE GXT5-8000IRT5UXLE GXT5-10KIRT5UXLE
Ratings (VA/ W) 5000 VA / 5000 W 6000 VA / 6000 W 8000 VA / 8000 W 10,000 VA / 10,000 W
Dimensions, inches (mm)
Unit W x D X H
16.9×24.8×8.5
(430×630×394)
Weight, pounds (kg)
Unit 156 (70.8) 298 (135.2) 298 (135.2) 298 (135.2)
Input AC Parameters
Operating Frequency, Nominal
Voltage Range 230 VAC 230 VAC 230 VAC 230 VAC
Input Wiring Hardwire Hardwire
50 or 60Hz
(Factory D efault is 50)
Output AC Parameters
Output Receptacles
Factory-default VAC Frequency
Waveform (On Battery) Sinewave Sinewave Sinewave Sinewave
Utility (AC) Mode Overload
>150% for Minimum 200mS; 125 - 150% for 60
seconds; 105-125% 5 Minutes; ≤105 % Continuous
Hardwire
2 (C19), 6 (C13)
230 VAC
50Hz or 60Hz, Nominal
>150% for Minimum 200mS; 125 - 150% for 60
seconds; 105-125% 5 Minutes; ≤105 % Continuous
Battery
16.9×24.8×8.5
(430×630×394)
50 or 60Hz
(Factory D efault is 50)
Hardwire
2 (C19), 6 (C13)
230 VAC
50Hz or 60Hz, Nominal
16.9×24.8×8.5
(430×630×394)
50 or 60Hz
(Factory D efault is 50)
Hardwire
(common or split bypass)
Hardwire
4 (C19), 4(C13)
230 VAC
50Hz or 60Hz, Nominal
>150% for Minimum 200mS; 125 - 150% for 60
seconds; 105-125% 5 Minutes; ≤105 % Continuous
16.9×24.8×8.5
(430×630×394)
50 or 60 Hz
(factory- default is 50 Hz)
Hardwire
(common or split bypass)
Hardwire
4 (C19), 4(C13)
230 VAC
50Hz or 60Hz, Nominal
>150% for Minimum 200mS; 125 - 150% for 60
seconds; 105-125% 5 Minutes; ≤105 % Continuous
Typ e Valve-regulated, non-spillable, lead acid Valve-regulated, non-spillable, lead acid Valve-regulated, non-spillable, lead acid Valve-regulated, non-spillable, lead acid
Backup Tim e (100% Load )
Backup Tim e (50% Load)
+1 External Battery Cabinet (100% Load)
+1 External Battery Cabinet (5 0% Load)
7 Minutes 5.5 Minutes 3.5 Minutes 2 Minutes
18.5 Minutes 14.5 Minutes 9.5 Minutes 7 Minutes
19 Minutes 14.5 Minutes 9.5 Minutes 7 Minutes
48 Minutes 38.5 Minutes 26 Minutes 19 Minutes
Environmental Requirements
Operating Temperature, °F (°C)
Storage Temperature, °F (°C )
Relative Humidity
Operating Elevation
Audible Noi se
+32 to +104 (0 to 40) (no derating) +32 to +104 (0 to 40) (no derating) +32 to +104 (0 to 40) (no derating) +32 to +104 (0 to 40) (no derating)
+5 to +122 (-15 to 50) +5 to +122 (-15 to 50) +5 to +122 (-15 to 50) +5 to +122 (-15 to 50)
0% to 95%,
non-condensing
Up to 10,000 ft (3,000 m) at 77°F (25°C)
without derating
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
Up to 10,000 ft (3,000 m) at 77°F (25°C)
<50 dBA, at 1 meter from the front or sides
0% to 95%,
non-condensing
without derating
<55 dBA, at 1 meter from the rear
0% to 95%,
non-condensing
Up to 10,000 ft (3,000 m) at 77°F (25°C)
without derating
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
0% to 95%,
non-condensing
Up to 10,000 ft (3,000 m) at 77°F (25°C)
without derating
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
Agency
Surge Immunity
Transportation ISTA Procedure 1E ISTA Procedure 1E ISTA Procedure 1E ISTA Procedure 1E
Safety IEC62040-1:2008 version, GS mark IEC62040-1:2008 version, GS mark IEC62040-1:2008 version, GS mark IEC62040-1:2008 version, GS mark
Emissions IEC/EN/AS 62040-2 2nd Ed (Cat 2) IEC/EN/AS 62040-2 2nd Ed (Cat 2) IEC/EN/AS 62040-2 2nd Ed (Cat 2) IEC/EN/AS 62040-2 2nd Ed (Cat 2)
IEC/EN EN61000-4-5, Level 3, Criteria A IEC/EN EN61000-4-5, Level 3, Criteria A IEC/EN EN61000-4-5, Level 3, Criteria A IEC/EN EN61000-4-5, Level 3, Criteria A
Warranty
6
Std. 2 year; Opt. 1 and 3 year extension Std. 2 year; Opt. 1 and 3 year extension Std. 2 year; Opt. 1 and 3 year extension Std. 2 year; Opt. 1 and 3 year extension
Technical Specifications 16-20 kVA
16KIRT9UXLE 20KIRT9UXLE
Ratings (VA/ W) 16000 VA/16000 W 20000 VA/20000 W
Dimensions, inches (mm)
Unit W x D X H
16.9×24.8×15.5
(430×630×394)
Weight, pounds (kg)
Unit 298 (135.2) 298 (135.2)
Input AC Parameters
Operating Frequency, Nominal
Voltage Range 288 VAC 288 VAC
Input Wiring Input terminal block Input terminal block
50 or 60 Hz
(factory- default is 50 Hz)
Output AC Parameters
Output Receptacles Output terminal block Output terminal block
Factory-default VAC Frequency
Waveform (On Battery) Sinewave Sinewave
Utility (AC) Mode Overload
230 VAC, 50 Hz 230 VAC, 50 Hz
> 150% minimum 200 ms > 150% minimum 200 ms
Battery
16.9×24.8×15.5
(430×630×394)
50 or 60 Hz
(factory- default is 50 Hz)
Typ e Valve-regulated, non-spillable, lead acid Valve-regulated, non-spillable, lead acid
Backup Tim e (100% Load )
Backup Tim e (50% Load)
+1 External Battery Cabinet (100% Load)
+1 External Battery Cabinet (5 0% Load)
3.5 Minutes 2.5 Minutes
9.5 Minutes 7 Minutes
10 Minutes 7 Minutes
26.5 Minutes 19.5 Minutes
Environmental Requirements
Operating Temperature, °F (°C)
Storage Temperature, °F (°C )
Relative Humidity
Operating Elevation
Audible Noi se <58 dBA, at 1 meter from the front <58 dBA, at 1 meter from the front
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating
+32 to +104 (0 to 40) (no derating) +32 to +104 (0 to 40) (no derating)
+5 to +104 (-15 to 40) +5 to +104 (-15 to 40)
0% to 95%,
non-condensing
0% to 95%,
non-condensing
Agency
Surge Immunity
Transportation ISTA Procedure 1E ISTA Procedure 1E
Safety UL1778, c-UL listed UL1778, c-UL listed
Emissions FCC Part 15 (Class A) FCC Part 15 (Class A)
IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62 41 Category B IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62 41 Category B
Warranty
Std. 2 year; Opt. 1 and 3 year extension Std. 2 year; Opt. 1 and 3 year extension
7
Vertiv™ Liebert® GXT5 | 5 - 20 kVA UPS
Accessories
Vertiv™ VR Rack
Supports a wide variety of equipment and gives you the flexibility you need with easy installation
Vertiv™ Geist™ rPDU
Reliably distributes power to the rack, supporting dynamic data center operations and DCIM
Vertiv™ SwitchAir
Prevents overheating of network switches by directing cool air to switch intakes, keeping hot exhaust air out
Vertiv™ ACS Console
Enables integrated remote monitoring, out-of-band management, and IoT connectivity
Vertiv™ KVM Switch
Enables single-point access for switching between multiple computers
Racks and enclosures: Support a
wide variety of equipment with the Vertiv™ VR Rack including servers, storage, switches, routers, PDUs, UPS units, console port servers, and KVM switches.
Rails and mounting hardware:
Install equipment with a four-post rail kit and hardware for mounting in a 19- or 23-inch rack or choose a two-post telecom rack for front- or mid-chassis, wall, or Zero U configuration.
Rack mount PDUs: For basic or
intelligent power distribution that helps prevent overloaded circuits in the data center, choose from products such as upgradable PDUs, inline power meters, transfer switches, and monitoring sensors.
Extended battery modules:
Enable scalable runtime for support during extended power outage situations by adding reliable power and protection to new or existing deployments.
Environmental sensor: Maintain
knowledge of remote environments
Vertiv™ Rack Cooling
Provides energy-eicient cooling close to the IT equipment and UPS units
with temperature, humidity and leak detection, or monitor available dry-contact sensors for security access control or smoke detection.
Vertiv™ Liebert® GXT5
Helps protect mission­critical equipment from all power disturbances due to blackouts, brownouts, sags, surges or noise interference
8
Available Accessories for the Vertiv™ Liebert® GXT5 UPS
External battery cabinets and replacement battery kits
UPS External battery cabinets Replacement battery kits
GXT5-5000IRT5UXLE GXT5-EBC192VRT3U GXT5-9A96BATKIT (x 2pcs)
GXT5-6000IRT5UXLE GXT5-EBC192VRT3U GXT5-9A96BATKIT (x 2pcs)
GXT5-8000IRT5UXLE GXT5-EBC192VRT3U GXT5-9A96BATKIT (x 2pcs)
GXT5-10000IRT5UXLE GXT5-EBC192VRT3U GXT5-9A96BATKIT (x 2pcs)
GXT5-16kRT9UXLE GXT5-EBC384VRT6U GXT5-9A96BATKIT (x 4pcs)
GXT5-20kRT9UXLE GXT5-EBC384VRT6U GXT5-9A96BATKIT (x 4pcs)
Network communications and environmental sensors
Network Communications
Environmental Sensors (Compatible with optional Liebert® network card RDU 101)
UPS manageability options Trellis™ Power Insight Software Management
RDU101
IS-RELAY Intellislot Interface Kit for Relay Contacts
SN-Z01 Integrated cable with single temperature sensor
SN-Z02 Integrated cable with three temperature sensors
SN-Z03 Integrated cable with three temperature and one humidity sensors
SN-T Modular with single temperature sensor
SN-TH Modular with single temperature and single humidity sensor
SN-2D Modular with two door contact inputs
SN-3C Modular with three dry contact inputs
SN-L20 Modular leak zone sensor with 20 foot cable (Liebert RDU-S only)
Intellislot web card for SNMP and web management. Supports environmental sensors.
Trellis™ Power Insight is a complimentary web-based software designed to monitor up to 100 Vertiv™ UPSs and rPDUs
9
Vertiv™ Liebert® GXT5 | 5 - 20 kVA UPS
Liebert® GXT5 Rear Panel (5-6 kVA)
Vertiv IntelliSlot for
optional SNMP/webcard
Terminal block
communication
power receptacles
REPO
C19 Output
C13 output receptacles
Output circuit breakers
External battery connector
Detachable Pod with integrated maintenance bypass
Input circuit breaker
Liebert® GXT5 Rear Panel (8-10 kVA)
Vertiv IntelliSlot for
optional SNMP/webcard
External Battery Connector
Detachable Pod with integrated maintenance bypass
C13 Output Receptacles
10
Output circuit breakers
Input circuit breaker
Liebert® GXT5 Rear Panel (16-20 kVA)
*Optional RDU101 Network Communication
Local Web and SNMP interface. Management and notification across networks.
Output Protection
UPS and POD output circuit breaker protection.
Communications
Multiple management options for local and remote setup configuration and control of the UPS any time.
Optional Output POD
Multiple options for local receptacles C13/C19 options.
Input Protection
Prevent equipment damage from a short circuit of overload.
External Battery Cabinet Connector
Scalable runtime in rack mount configurations. Longer runtimes for critical work completion, work load migration and critical equipment shutdown.
Hardwire Output Connection
Output to panel board distribution or rack PDU for management and control to rack level equipment.
Hardwire Input Connection
For easy installation and reach to available power source.
11
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2019 Vertiv G roup Corp. All right s reserved. Verti v™ and the Vertiv logo are tr ademarks or regis tered trademarks of Ver tiv Group Corp. All o ther names and log os referred to are trad e names, tradema rks or registered tra demarks of their res pective owners . While every precauti on has been taken to en sure accuracy and c ompleteness he re, Vertiv Group Cor p. assumes no resp onsibility, and dis claims all liabili ty, for damages resu lting from use of this inf ormation or for any erro rs or omissions . Specificatio ns, rebates and oth er promotional oers are su bject to change at Ver tiv’s sole discret ion upon notice.
SL-70564 (R1/20)
Loading...