Liebert GXT3-5000RT208, GXT3-6000RT208, GXT3-10000RT208, GXT3-8000RT208 Specifications

Page 1
Liebert® GXT3, 5kVA-10kVA UPS
Compact UPS Systems For High Power Network Rack Applications
AC Power For Business-Critical Continuity™
Page 2
Liebert GXT3, 5kVA-10kVA UPS Systems: Big Protection, Small Package
Today’s converged networks require increased availability and reliability. This has created a need for higher density power protection systems that adapt to mixed load voltages and plug types, while remaining easy to install and maintain.
New IT technologies, such as VoIP and PoE, have greatly increased power demands. Unfortunately, as these requirements have risen, the amount of space available for your protected equipment and related power support systems has not.
Liebert IntelliSlot Webcard provides SNMP and web-based management
The Liebert Solution
Liebert GXT3 UPS meets the need for higher power capacities in small spaces. This true on-line double conversion UPS system is available in 5kVA – 10kVA models, and features integrated maintenance bypass, as well as optional extended battery runtime. Add support — Emerson Network Power Service — and it all equals greater power assurance and reliability.
Designed for use in either rack or
tower congurations, all units offer
the smallest available solutions for these power capacities — the 5 & 6kVA model at 120/208V output in 4U size, or the 8 & 10kVA unit 120/208V output in a 6U package. A 6kVA 208V output 5U size model is also available.
To help meet the need for choosing a single supplier for global applications, 220V, 230V and 240V 50/60 Hz models are offered with CE and C-tick markings.
Dual Voltages For Multiple Applications
Simultaneous output voltages of 240/120, 208/120, 230/115, 220/110,
or 200/100 VAC provide the exibility
to adapt to multiple load requirements without the need to add additional transformers that take up extra space and add weight. Input power factor correction to 0.99 reduces current harmonics and their heating effects.
Liebert GXT3 UPS offers a variety of communications options to provide the monitoring and control capabilities demanded by today’s network computing systems. Operation can be monitored using:
Liebert IntelliSlot Web Card provides
SNMP and web-based monitoring and control of your UPS.
Liebert MultiLink™ Automated
System Shutdown Software
Liebert Nform™ Monitoring System
Liebert Universal Monitor And
Remote Power Monitor Panels
Third-Party Monitoring Systems
On Line UPS
Surge
Suppression
Dynamic
Bypass
Power Factor
Correction/Rectifier
Charger
Battery
Inverter
OutputUtility
2
Page 3
UPS operation and display panel can rotate 90 degrees, which provides upright viewing for users.
Liebert GXT3 UPS Includes These Outstanding Features:
Flexibility:
Rack/tower configuration. The
versatile unit installs in either
conguration, and includes a rotating
LED display panel that conforms to the desired orientation.
Automatic frequency detection.
Detects and matches line input frequencies of either 60 or 50 Hz.
User replaceable hot-swappable
internal batteries. Provide four minutes of runtime at full load.
Additional runtime with additional
battery cabinets. UPS cabinet includes rear panel plug-and-play connections for optional battery cabinets. Cabinet sizes: 5-6kVA – 2U, 8-10kVA – 4U, 6kVA 208V– 3U
Liebert IntelliSlot™ communications
port. Utilizes Liebert IntelliSlot Web Card to provide SNMP and web-based monitoring and control of your UPS.
Includes Windows-based
configuration program. Allows various operating parameters to be adjusted and tests to be scheduled.
Built-in USB communications for use
with Liebert MultiLink™ Automated Shutdown Software. Allows you to
monitor communication between the UPS and a server, and ensures a graceful unattended shutdown.
Built-in closure signals. Provides
notication to monitoring systems of
operating conditions including: on battery, low battery, battery mode shutdown and any mode shutdown.
Emergency Power Off (EPO).
Terminal connections for a normally open or normally closed emergency power off switch.
Higher Availability:
Wider input voltage window
minimizes battery use. Features a
wide input voltage window that allows the UPS to support the critical load without having to transfer to batter y, extending system availability for when battery back-up is truly needed.
Internal automatic and manual
bypass. Assures continuity of power to critical loads during system maintenance or in case of internal fault.
Self-diagnostics. Automatically tests
unit electronics and batteries. Designed to simplify maintenance and troubleshooting.
Lowest Total Cost Of Ownership:
Standard two-year replacement
warranty. No-hassle warranty
provides paid shipping both ways. Optional one-year and three year extensions available.
Uses less rack space. Leaves more
room for network equipment.
For longer service life. Shields
batteries from heat generating electronic components, enhancing battery life.
Battery cutoff voltage Automatically
adjusts based on load, extending battery life by preventing over­discharge of batteries.
Liebert Power Assurance Package Offers A Worry-Free UPS Solution For Your Network
Liebert GXT3 5-10kVA UPS systems may be purchased as part of the Liebert Power Assurance Package. While today’s smaller, rack-based UPS systems offer relatively trouble-free operation, the growing criticality of the systems they support has increased the cost of downtime. As a result, the need to maintain these smaller UPS systems is increasingly important.
This all-inclusive package offers you complete peace-of-mind for
ve years including:
UPS — A compact, high quality on-line Liebert GXT3 UPS (5, 6, 8 or 10kVA).
Start-up — On-site system
start-up by a certied Emerson
Network Power Customer Engineer, scheduled anytime, 24 x 7. This includes removal and disposal of your existing UPS.
Preventive maintenance — One preventive maintenance visit completed in year 3 by a
certied Emerson Network Power
Customer Engineer includes 100% Parts Coverage — even internal batteries.
Full parts coverage — Your
on-line Liebert UPS benets
from 100% parts coverage for
ve years, including all internal
batteries.
On-site service — Should you experience a problem, we will
dispatch a certied Emerson
Network Power Customer Engineer to repair or replace your equipment — with 4-hour response guaranteed.
3
Page 4
5 Or 6kVA Of True On-Line Power In A Compact 4U Package
Liebert GXT3 5 & 6kVA models are true on-line UPS systems that provide internal batteries and dual output voltage. They are an ideal fit for applications where the power requirements are demanding — but rack space is limited — delivering 5kVA (4kW) or 6kVA (4.8kW) of power in a single 4U size cabinet. This cabinet size is well suited for installations such as network closets or small data centers.
Adaptable Design
For installation exibility, the
Liebert GXT3 5 & 6kVA models allow you to choose from several
different wiring congurations
made possible by the use of removable power distribution boxes that simply plug into the rear of the UPS. The standard box provides terminal blocks for hardwired input and output connections. An optional hardwire version that includes a maintenance bypass is also available.
When the ease of plug-and-play power connections is desired, optional versions of the power distribution box convert Liebert GXT3 5 & 6kVA units to a cord­type input with receptacles for output distribution, and also offers maintenance bypass capability that allows hot-swapping of the entire UPS. The UPS has as adaptable dual inverter design, capable of providing simultaneous output voltages of 240/120, 208/120, 230/115, 220/110, or 200/100 and an output power factor of 0.8.
PD2-HDWR ships standard with the unit and is hardwire input/output
PD2-HDWR-MBS is an optional hardwire input/output POD with maintenance bypass
5 & 6 kVA Model shown in rack mount position
6 kVA Model shown in tower position with optional battery cabinet
Pluggable input/output PODs available with maintenance bypass
4
Page 5
8kVA And 10kVA Of Power In Just 6U Of Space
The internal battery packs are hot-swappable, and user repleaceable. The unit also supports up to four external battery cabinets for extended run time.
This Liebert GXT3 8 & 10kVA units offer a flexible solution for protecting rack-mount equipment, including VoIP and PoE. Especially designed for use with the new generation of high power switches, these compact UPS systems pack 8kVA (7.2kW) or 10kVA (9kW) of power into a 6U rack/tower package with flexible output voltage and optional output distribution. The UPS includes built-in, user­replaceable batteries for up to four minutes of runtime at full load.
8 & 10 kVA Model shown in rack mount position
10 k VA Model shown in tower position with optional battery cabinet
UPS is hardwire input/output with maintenance bypass and includes no POD standard.
Optional PODs available
Adaptable Design
The UPS has a dual inverter design, capable of providing simultaneous output voltages of 240/120, 208/120, 230/115, 220/110, or 200/100 and an output power factor of 0.9. The new 6U cabinet is the smallest for 208/120 selectable voltage in the 8-10kVA size. The unit features integrated internal manual and automatic maintenance bypass, power module, battery modules, auto detection of extended battery cabinets and optional plug-and­play distribution plates.
The standard 8 & 10kVA models include terminal blocks for hardwired connections of both input and output. Optional power distribution modules are available to add output receptacles to the rear panel of the unit.
Hot-Swappable Operation
Liebert GXT3 8 & 10kVA units feature three bays for one power module and two battery modules. The chassis contains a bypass switch that allows all modules to be removed without powering down the connected load.
5
Page 6
Product specications
UPS specifications—5, 6, 8 and 10 kVA models
Model Number GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208
Model Rating 4000W/5000VA 4800W/6000VA 7200W/8000VA 9000W/10000VA
Dimensions, Rack Mount, W x D x H Unit in. (mm) 16.9 x 26.1 x 6.8 (430 x 662 x 173) 16.9 x 26.5 x 10.3 (430 x 672 x 261)
Weight Unit, lb (kg) 56.2 (25.5) 78.3 (35.5)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default is 60Hz)
Factory Default VAC 120/208VAC
Factory Default L1-N, L2-N VAC 120 VAC nominal
Input Frequency w/o Battery Operation 40 - 70 Hz
Input Power Connection Hardwire Terminal Block 3W + G (L-L-N-G)
L1-N, L2-N Maximum Allowable VAC 150VAC
Output AC Parameters
Factory Default VAC 120/208V AC
Factory Default L1-N, L2-N VAC 120VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127VAC, ±2%
Overload Rating
105% to 130% 1 Minute
131% to 150% 10 seconds
151% to 200% 1 second
>200% (impact load) At least 5 cycles
Environmental
Operating Temp, °F (°C) 32 to 104 (0 to 40)
Storage Temp, °F (°C) 5 to 122 (-15 to 50)
Audible Noise Less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Relative Humidity 0% to 95%, non-condensing
Agency
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A, FCC Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A
Internal battery specifications
Model Number GXT3-144BATKIT GXT3-288RTBKIT
Used with UPS Model GXT3-5000RT208 / GXT3-6000RT208 GXT3-8000RT208 / GXT3-10000RT208
Dimensions, W x D x H, Unit in (mm) 8.1 x 19.3 x 2.8 (206 x 490 x 70) 8.1 x 19.7 x 5.3 (207 x 500 x 135)
Weight, Unit lb (kg) 75.8 (34.4) 71.2 (32.3)
Battery Parameters
Typ e Valve-regulated, non-spillable, lead acid
Kit Quantity x Battery Quantity x V x Rating 2 x 6 x 12V x 9.0 AH 2 x 12 x 12V x 9.0 AH
Battery Mfr / Part # Yuasa / REW 45-12
Recharge Time 3 hours to 90% capacity after full discharge into 100% load
Environmental Operating Temp, Storage Temp, Operating Elevation, and Relative Humidity: Same as UPS
6
Page 7
External battery cabinet specifications
Model Number GXT3-144VBATT GXT3-240VBATTUL GXT3-288RTBATT
Used w/UPS Model GXT3-5000 & GXT3-6000RT208 GXT3-6000RTL630 GXT3-8000 & GXT3 10000RT208
Dimensions, W x D x H, Unit (with bezel) in. (mm)
Weight, Unit lb (kg) 99.9 (45.3) 94.8 (43) 29.8 (13.5)
Battery Parameters
Typ e Valve-regulated, non-spillable, lead acid
Kit Quantity x Battery Quantity x Rating 2 x 6 x 12V x 9.0 AH 2 x 10 x 12V x 9.0 AH 2 x 12 x 12V x 9.0 AH
Battery Mfr., Part # Yuasa / REW 45-12
Environmental Operating Temp, Storage Temp, Operating Elevation, and Relative Humidity: Same as UPS
16.9 x 26.1 x 3.3 (430 x 662 x 85)
16.9 x 22.6 x 5.1
(430 x 574 x 130)
16.9 x 26.5 x 6.8
(430 x 672 x 173)
Power distribution box specifications: GXT3-5000RT208, GXT3-6000RT208 and GXT3-6000RTL630
Power Distribution Box Model Number
Dimensions, W x D x H, Unit in (mm)
Weight, lb (kg) 5.1 (2.3) 6 (2.7) 8.8 (4) 8.6 (3.9) 8.6 (3.9) 9.9 (4.5) 10.6 (4.8) 9.5 (4.3) 8.8 (4)
Electrical Specifications
Amp Rating 30A 2-pole input breaker for UPS input power
Input Power
Connections
Output Power
Connection
PD2-HDWR PD2-HDWR-MBS PD2-001 PD2-002 PD2-003 PD2-004 PD2-005 PD2-006 PD2-L630
5.2x15.5x3.5
(132x393x88)
Hardwire Terminal Block
3W + G (L-L-N-G)
Hardwire Terminal Block
3W + G (L-L-N-G)
5.2x15.5x3.5
(132x393x88)
(4) 5-20R (1) L14-30 (1) L6-30R
(2) 5-20R
(2) L6-20R
5.2x15.5x3.5
(132x393x88)
[1] L14-30P on a 3.2m cord (1) L6-30P
(4) 5-20R (2) L6-30
(4) L5-20R (2) L5-30R
5.2x15.5x3.5
(132x393x88)
(4) L5-20R (2) L6-30R
(4) L6-20R
4.7x13.2x4.1
(119x335x105)
(2) L6-20R (2) L6-30R
Power distribution box specifications for GXT3-8000RT208 and GXT3-10000RT208
Power Distribution Box
Model Number
Dimensions, W x H, Unit in. (mm)
Weight, Unit lb (kg) 4.4 (2) 6.6 (3) 6.6 (3) 6.6 (3) 4.4 (2) 6.6 (3)
Electrical Specifications
Amp Rating 2-pole 60A Input Breaker
Input Power
Connections
Output Power
Connection
PD2-101 PD2-102 PD2-103 PD2-104 PD2-105 PD2-106
7.4 x 5.7(188 x 145) 7.4 x 5.7(188 x 145) 7.4 x 5.7(188 x 145) 7.4 x 5.7(188 x 145) 7.4 x 5.7(188 x 145) 7.4 x 5.7(188 x 145)
Hardwire Terminal Block 3W + G (L-L-N-G) to Chassis
(2) L6-30 (8) 5-20R
(4) L6-20R
(4) 5-20R
(4) 5-20R
(4) L6-30R
(4) 5-20R (2) L6-30R (2) L6-20R
(4) 5-20R (2) L5-30R (2) L5-20R
(4) L6-20R (4) L5-20R
Battery run time, minutes
Run Time, Minutes
Load GXT3-5000RT208 GXT3-6000RT208 GXT3-6000RTL630 GXT3-8000RT208 GXT3-10000RT208
10% 105 100 >90 150 90
20% 50 41 60 57 42
30% 30 23 40 34 26
40% 22 17 27 25 18
Internal
Battery
50% 16 12 21 18 13.5
60% 12 10 16 14 11
70% 10 7 13 12 8
80% 8 5.5 11 9 7
90% 6 4.5 9 8 6
100% 5 4 8 7 4.5
7
Page 8
Emerson Network Power, a business of Emerson (NYSE:EMR), delivers software, hardware and services that maximize availability, capacity and efficiency for data centers, healthcare and industrial facilities. A trusted industry leader in smart infrastructure technologies, Emerson Network Power provides innovative data center infrastructure management solutions that bridge the gap between IT and facility management and deliver efficiency and uncompromised availability regardless of capacity demands. Our solutions are supported globally by local Emerson Network Power service technicians. Learn more about Emerson Network Power products and services at www.EmersonNetworkPower.com
Emerson Network Power. The global leader in enabling Business-Critical Continuity
AC Power
Connectivity DC Power
Embedded Computing Embedded Power Monitoring
.
Outside Plant Power Switching & Controls Precision Cooling
Emerson Network Power
Liebert Corporation World Headquarters 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 United States Of America 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX
Emerson Network Power European Headquarters Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 +63 2 730 9572 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone 614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2011 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-23184 (R11/11) Printed in USA
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2011 Emerson Electric Co.
Loading...