Liebert GXT3-240TBATTCE Product Data Sheet

LIEBERT® GXT3 10000 VA T MODEL
Reliable On-Line Protection In A Compact Tower Package
Liebert® GXT3 is designed to deliver higher power capacities for applications with limited floor space
This true on-line double conversion UPS system is available in two dierent 10000 VA versions featuring an integrated maintenance bypass, as well as optional extended battery back up time.
Liebert GXT3 T230 is the standard version free of integrated isolation transformer which can be configured as either 1/1 or 3/1, providing increased flexibility.
The Liebert GXT3 range also oers the possibility of integrated full galvanic isolation with the Liebert GXT3 T220 which houses an output isolation transformer allowing it to be used at 110, 120 phase to neutral or 208, 220 phase to phase voltages, for dual input with phases shifted by 180 degrees.
Communications For Power Monitoring And Control:
Liebert GXT3 oers a variety of communications options providing flexible monitoring and control capabilities.
yy Vertiv™ IntelliSlot™ web card
providing SNMP and web-based monitoring and control of the UPS
yy Vertiv MultiLink™ automated system
shutdown software
yy Vertiv Nform™ monitoring system
yy Third-party monitoring systems.
Ideally suited for Mission-Critical Applications such as:
yy LAN & WAN servers
yy Network equipment
yy IP telephony deployments
yy Oice telecommunications systems
yy ISDN & frame relay applications
yy Test and diagnostic equipment
yy Micro Processor-controlled
equipment
yy Finance applications.
Flexibility:
yy Automatic frequency detection
yy User replaceable hot-swappable
internal batteries
yy Extended back up time with
additional battery cabinets
yy Vertiv IntelliSlot communications port
yy Includes Windows-based
configuration program
yy Built-in USB communications for use
with Vertiv MultiLink automated shutdown software
yy Built-in closure signals
yy Emergency power o (EPO)
yy Parallelable up to three units (2+1).
Higher Availability:
yy Wider input voltage window
minimizes battery use
yy Internal automatic and manual
bypass
yy Self-diagnostics.
Reduced Total Cost Of Ownership:
yy Standard two-year warranty
yy Compact footprint
yy Batteries shielded from heat
generating electronic components
yy Battery cuto voltage to prevent
from overdischarge of batteries.
Lieber t GXT3 10000 VA Tower
0.9 PF
More Power
Available!
LIEBERT® GXT3 10000 VA T MODEL
Liebert® GXT3 Specifications
MODEL NUMBER GXT310000T230 GXT310000T220
Power Rating 10000 VA/9000 W
DIMENSIONS, W x D x H - mm
Unit / Shipping 300 x 675 x 80 0 / 426 x 866 x 106 2
WEIGHT  KG
Unit 105 140
INPUT AC PARAMETERS
Voltage Range Without Bat tery Operation
Frequency Range 50 - 60Hz autos election
Input Socket terminal block
Output Sockets terminal block
Voltage 220/230/240VAC 20 8VAC
Waveform Sinewave
BATTERY PARAMETERS
Typ e HR 1234W F12 CSB HR12 34R or Pana sonic UP-RW1245
Quantity x Voltage 20 x 12V
Recharge Time 3 hours to 90% c apacity after full discharge with 100% loa d (Internal B atteries Only)
ENVIRONMENTAL
Operating Temperature
Storage Temperature - 15 to 50 °C
Relative Humidity 0%RH to 95%RH, non-condensing
Operating Altitude Up to 1000m
Audible Noi se
Standards and Certifications CE UL 1778, c -UL
RFI/EMI IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6) FCC Part 15 , Subpar t B, Class A
Surge Immunity EN61000-4-5 , Level 3, Criteria A IEC/EN 61000-4-5 , ANSI C62.41 (for Nor th America )
Transportation ISTA Procedure 1A ISTA Procedure 1B
176-280VAC (for 1/1)
304-485VAC (for 3/1)
0 to 30 °C with 0.9 pf
30 to 40 °C with 0. 8 pf
< 55 dBA, at 1 m eter from the rear
< 50 dBA, at 1 meter from the front or sides
100 - 185 ±5VAC (for 1/1)
Liebert GXT3 Battery Cabinet Specifications
MODEL NUMBER GXT3240TBATT CE DIMENSIONS, W x D x H - mm
Unit / Shipping 300 x 675 x 80 0 / 426 x 866 x 106 2
WEIGHT  KG
Unit / Shipping 110/140
BAT TER IE S
Typ e Valve-regulated, non-spillable, lead acid
Quantity x Voltage 2 x 20 x 1 2V
ENVIRONMENTAL
Operating / Storage Temperature, °C 0 to 40/-15 to 40
Relative Humidity 0% to 95%, non-condensing
Maximum Operating Altitude Up to 10000 m (40ºC)
STANDARDS AND CERTIFICATIONS
Safety / Emis sions CE
Transportation ISTA Procedure 1A
REPO Contacts
Parallel Port
Maintenance
Bypass Switch
Input Breaker
Bypass
Source Input
Circuit Breaker
Output Breaker
Parallel Port
Cooling Fan
External Bat tery Connector Block
Hardwire Input and Output Connector Terminal Block
Liebert GXT3-10000T230 Liebert GXT3-10000T220
Externa l Battery
Connector
Vertiv IntelliSlot Communication
Card Slot
USB Port
Dry Contacts
REPO
Hardwire Input
and Output Connectors
(Protective
Cover Shown)
Maintenance Bypass Switch (cover removed for clarity)
Input Circuit Breaker
Output Circuit Breaker
Bypass Circuit Breaker
Tech Support Always On! Our Commitment to your daily Business, provided by multi language Tech Support.
Toll-free 0080011554499 Toll +39 02 98250222 eoc@VertivCo.com
VertivCo.com | Emerson Network Power Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2016 Vertiv C o. All rights reserve d. Vertiv™, the Vertiv logo , Liebert® GXT3, Ver tiv IntelliSlot™, Vertiv M ultiLink™ and Vertiv Nform™ a re trademarks or regis tered trademarks of Ver tiv Co. All other names a nd logos referred to are t rade names, trademar ks or registered trade marks of their respec tive owners. While eve ry precaution has b een taken to ensure acc uracy and complete ness herein, Vertiv C o. assumes no resp onsibility, and discl aims all liability, for da mages resulting fro m use of this inform ation or for any errors or om issions. Speci fications are subje ct to change without n otice.
MKA4L0UKGXT3T Rev.2-09/2013