Liebert GXT 2U User Manual

Page 1
UPStation GXT 2U™
POWER PROTECTION
USER MANUAL
700-3000VA
120V
Page 2
Page 3
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . . 1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
MAJOR COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters . . . 5
Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . 5
Inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DC to DC Converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GXT 2U (Rear View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Rack-Mount UPS Conversion and Installation. . . . . . . . . . . . . . . . . . . . 9
External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . 13
ON/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . 13
Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Load/Battery Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . 14
Fault Indicator LED (Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Bypass Indicator LED (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
UPS ON Indicator LED (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Battery Indicator LED (Amber). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
AC Input Indicator LED (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Output Voltage Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Battery Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
i
Page 4
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Pin 4 - Remote Shutdown on Battery. . . . . . . . . . . . . . . . . . . . . . . . . . 17
UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . 19
GXT 2U Configuration Program Abilities . . . . . . . . . . . . . . . . . . . . . . . 19
What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Internal Battery Replacement Procedures: . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fuse Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
BATTERY CABINET SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 30
BATTERY RUN TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
ii
Page 5

IMPORTANT SAFETY INSTRUCTIONS

WARNING
!
OPENING OR REMOVING THE COVER MAY EXPOSE YOU TO LETHAL VOLTAGES WITHIN THIS UNIT EVEN WHEN IT IS APPARENTLY NOT OPERATING AND THE INPUT WIRING IS DISCONNECTED FROM THE ELECTRICAL SOURCE. OBSERVE ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO SO MAY RESULT IN SERIOUS INJURY OR DEATH. REFER ALL UPS AND BATTERY SERVICE TO QUALIFIED SERVICE PERSONNEL. DO NOT ATTEMPT TO SERVICE THIS PRODUCT YOURSELF. NEVER WORK ALONE.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, instal­lation, and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this man­ual. Follow all operating and user instructions. Individuals without previ­ous training can install and operate this equipment.
It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 100-127 VAC, 50 Hz or 60 Hz supply.
ELECTROMAGNETIC COMPATIBILITY—The GXT 2U plies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient tempera­ture range of 32°F to +104°F (0°C to +40°C). Install it in a clean environ­ment, free from moisture, flammable liquids, gases and corrosive substances.
Series com-
1
Page 6
This UPS contains no user serviceable parts except the internal battery packs and the rear input line fuses. The UPS ON/Standby push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unautho­rized personnel away from the batteries. PROPER DISPOSAL OF BAT­TERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other open­ings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or cor­ruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
When replacing batteries, replace with the same Liebert authorized replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
2
Page 7

GLOSSARY OF SYMBOLS

Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON
Standby
3
Page 8

INTRODUCTION

Congratulations on your choice of the Liebert UPStation GXT 2U™ Unin­terruptible Power System (UPS). It provides conditioned power to micro­computers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during trans­mission and distribution it may be subject to voltage sags, spikes, or com­plete power failure that may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT 2U protects equip­ment from these disturbances.
The UPStation GXT 2U comes in nominal power ratings of 700, 1000, 1500, 2000 and 3000 VA. Complete model specifications appear at the end of this manual.
The UPStation GXT 2U is a compact, “on-line” UPS. An on-line UPS con­tinuously conditions and regulates its output voltage, whether utility power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT 2U features a light-emitting diode (LED) display to indicate either load percentage or battery capacity depending upon the mode of operation. It also provides self-diagnostic tests, a combination On/Alarm Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of alarms when the unit is operating on battery.
The UPStation GXT 2U has an interface port for communication between the UPS and a network server or other computer systems. This port pro­vides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink
software. MultiLink software can also remotely control UPS
operation.
4
Page 9

MAJOR COMPONENTS

Input Output
TVSS &
L
N
G
EMI/RFI
Filters
Battery
Charger
Rectifier
/PFC
Dynamic
Bypass
DC to DC
Converter
Battery

Inverter

L
N
G

TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS

These UPS components provide surge protection and filter both electro­magnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.

RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT

In normal operation, the rectifier/power factor correction (PFC) circuit con­verts utility AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
The utility power is used as efficiently as possible by the UPS
The amount of distortion reflected on the utility is reduced
This results in cleaner power being available to other devices in the build­ing not being protected by the UPStation GXT 2U.
INVERTER
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter receives its required energy from the battery through the DC to DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
5
Page 10

BATTERY CHARGER

The battery charger utilizes energy from the utility power and precisely regulates it to continuously “float charge” the batteries. The batteries are being charged whenever the UPStation GXT 2U is plugged in, even when the UPS is not turned on.

DC TO DC CONVERTER

The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.

BATTERY

The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame retar­dant, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional exter­nal battery cabinets are available to extend battery run times.

DYNAMIC BYPASS

The UPStation GXT 2U provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass opera­tion is indicated by an alarm and illuminated Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually trans­fer the connected load from the inverter to bypass, press the Standby but­ton once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances on the utility supply.
6
Page 11

GXT 2U (REAR VIEW)

DB-9 Communications Port
Intellislot Port
Cooling Fan
External Battery Connector
Output Receptacles
Input Fuse/ Circuit Breaker
AC Input
Support Base
7
Page 12

INSTALLATION

PREPARATION

1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see Specifications section). Take proper precautions when lifting or moving it.
2. Decide where to place the GXT 2U. Install the UPS indoors in a con­trolled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces battery life.
3. The GXT 2U may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Deter­mine the type of installation and follow the appropriate instructions in either Tower UPS Installation or Rack-Mount UPS Conversion
and Installation.

TOWER UPS INSTALLATION

When using the GXT 2U in a tower configuration, use the included sup­port base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accommo­date the additional cabinets (shown below, right).
Support base Spacers added to support
8
base to accommodate
additional battery cabinets
Page 13

RACK-MOUNT UPS CONVERSION AND INSTALLATION

NOTE
When rack mounted, the UPS must be supported by a shelf, brackets or slide rails on each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack.
1. For slide rail installations, first remove the top/side fin. Slide the top/side fin forward, then lift it up to remove. If desired, install the
optional rack mount handles that were shipped with the UPS.
U
PS
tation
G
XT
+
A
C
I N
P
U
T
B
A
T T
E R
Y
U
P S
O
N
B
Y P
A
S S
Optional rack mount handles
Securing hardware and slide rails are sold separately. Contact your local dealer or Liebert representative for these additional options and any assistance needed.
2. Unpack the two slide assem­blies and mounting hard­ware. The slide assemblies are interchangeable between left-hand or right­hand. Remove the inner member of each slide assembly (as seen at right) by extending it to its outer­most position, depressing the locking mechanism and then pulling the inner mem­ber from the slide assembly.
Locking mechanism
Slide assemblies
Inner members
Outer members
Outer members
Mounting bracket
9
Page 14
3. Fasten the inner members from Step 2 to the UPS on both sides (see below) with eight screws provided in the accessories box of the UPS.
Inner members
A C
I
N P
U T
B
A T
T E
R Y
U P
S
ON
B Y
P
A
S S
4. Attach the two mounting brackets to the rack’s mounting rails. The brackets allow adjustment of up to eight inches of the slide assembly mounting position, front-to-back, on the rack mounting rails. Deter­mine which adjustment holes to use on the bracket, and attach it to the slide assembly on the stationary outer member using the bar nuts and #10-32 binding head screws provided in the slide assembly kit. Insert two screws from the inside of each slide assembly.
NOTE
Bar nuts may not be required on all installations, depending on the type of racks being used.
5. Install the slide assemblies, with brackets attached in Step 4 into the the rack enclosure. The return flanges on the mounting brackets and outer members fit to the inside of the rack mounting rails.
6. Insert the eight screws loosely (finger-tight). Make sure the slide assemblies are in the same alignment position on all four rack mount­ing rails. After checking alignment, TIGHTEN ALL SCREWS.
Bar nuts
Slide assemblies
Rack
U P
S ta
t io
n G
X T
mounting rails
10
Page 15
7. Insert the UPS, with inner members attached from Step 3, into the slide assemblies. You may need to depress the locking mechanisms on the inner and outer members of the slide assemblies to allow the slides to retract. The UPS should move smoothly forward and back­ward on the slide assemblies. If not, recheck alignment.
CAUTION
!
Reduce the risk of tipping the rack enclosure by placing the UPS in the lowest possible rack position.
8. To orient the display for horizon­tal viewing, remove the front plastic bezel by pulling forward evenly on both sides. The unit has two front panel overlays.
Vertical
overlay
for
tower
UPS
Horizontal overlay
for rack UPS
Remove the outer overlay (used for tower installation). This reveals a horizontally oriented front panel overlay for rack mounting. Snap the front bezel back into place.
9. Once the UPS is installed in the rack, the load may be con­nected. Ensure the load equip-
+
UPStation GXT
+
UPStation GXT
AC INPUT BATTERY UPS ON BYPASS
AC INPUT BATTERY UPS ON BYPASS
ment is turned off; plug all loads into the output receptacles on the rear of the UPS.
10. Plug the UPS into a dedicated wall receptacle properly pro­tected by a circuit breaker or fuse in accordance with national and local electrical codes. Use a 15 amp rated device for the 700, 1000, or 1500 VA units, 20 amp for the 2000 VA, and 30 amp for the 3000 VA. The wall receptacle must be grounded.
11. Turn ON the UPS by pressing the ON button; then turn on the con­nected load equipment. The UPS is now providing conditioned power to your equipment.
11
Page 16

EXTERNAL BATTERY CABINET INSTALLATION

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. There is no limit to the number of external battery cabinets that can be used but each cabinet will increase the battery recharge time.
CAUTION
!
The external battery cabinet(s) are heavy (see Specifications section). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Liebert repre­sentative.
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove. Optional rack-mount han­dles are shipped with the external battery cabinet and may be installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base exten­sions ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.
6. Turn the battery breaker on the rear of the external battery cabinet “ON”.
7. The UPS is now equipped with addi­tional backup battery runtime. For approximate battery runtimes refer to the Battery Run Times charts in this manual.
NOTE
You must use the included Configuration Program to program the UPS for the number of external battery cabinets connected.
12
Page 17

CONTROLS AND INDICATORS

for illustrative purposes only.
All LEDs illuminated

ON/Alarm Silence/Manual Battery Test Button

This button controls output power to connected load(s) and has three functions:
•ON
• Alarm Silence
• Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide condi­tioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one sec­ond. After the alarm is silenced, the UPStation GXT 2U will reactivate the alarm system to alert of additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON but­ton for at least one second while operating from utility power with no alarm conditions present.
• If only three of the five battery LEDs illuminate, allow the UPS to recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five battery LEDs illuminate, contact your local dealer, Liebert representative or Liebert Worldwide Support Group.
13
Page 18
Standby/Manual Bypass Button
This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass.
CAUTION
!
Pressing the Standby/Manual Bypass button once will cause the load to be transferred to bypass power.
Pressing the Standby/Manual Bypass button a second time within 4 seconds will result in loss of power to the output receptacles and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.

Load/Battery Level Indicators (4 Green, 1 Amber)

The Load/Battery Level indicators have dual functions. During normal mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote battery test features. The automatic test occurs every 14 days (this option is user configurable) if utility has not been interrupted. Should the battery fail this test, the red fault indicator LED along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to Troubleshooting section).
The remote test feature functions with MultiLink
®
3 software and can
remotely initiate the battery test.

Fault Indicator LED (Red)

The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting section).

Bypass Indicator LED (Amber)

The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm will sound indicating the UPS detected a prob­lem, or the manual bypass function has been activated.

UPS ON Indicator LED (Green)

The UPS ON indicator LED is illuminated when the UPS inverter is oper­ating and supplying power to your connected loads.

Battery Indicator LED (Amber)

The Battery indicator LED is illuminated when the UPS is operating on battery.

AC Input Indicator LED (Green)

The AC Input indicator LED is illuminated when utility power is available and within the input specifications.
14
Page 19

Output Voltage Selection

The Output Voltage is user configurable, and is designed to allow select­ing or changing the desired output voltage to match the utility via the GXT2 Configuration Program provided with the UPS. The settings to choose from are 100, 110, 115, 120, and 127 VAC output. The factory default setting is 120 VAC.
CAUTION
!
Never change the voltage settings while the UPS is ON and powering connected loads.
NOTE
Setting output voltage to 100 VAC will cause the UPS unit to be derated (700/1000 VA to 90%, 1500/2000/3000 VA to 80%) of the VA and Watt ratings listed in the Specifications section.
15
Page 20

OPERATING INSTRUCTIONS

NORMAL MODE OPERATION

During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads.
AC INPUT BATTERY UPS ON BYPASS
The UPS maintains the batter­ies in a fully charged state.
Normal Mode Operation at 50%
The four green LEDs indicate an approximate level of load in 25% incre­ments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and sound an audible alarm. The display template indicates the percentage of load (50% of load shown in exam­ple) on the UPS output.

BATTERY MODE OPERATION

Battery mode occurs in event of an extreme input voltage condition or complete utility failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load.
During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish, and the Battery LED will illuminate to warn that a utility problem has occurred. Each load/battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illumi­nated. Refer to Troubleshooting section.
For approximate battery run times, refer to Battery Run Times charts in this manual. To increase this time, turn off non-essential pieces of equip­ment (such as idle computers and monitors) or add the optional external battery cabinet.
AC INPUT BATTERY UPS ON BYPASS
Battery Mode Operation at 80 - 61%
CAUTION
!
Turning off the UPS while in battery mode will result in loss of output power.

BATTERY RECHARGE MODE

Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging the battery.
16
Page 21
r

COMMUNICATIONS

COMMUNICATIONS INTERFACE PORT

The UPStation GXT 2U UPS contains a standard DB-9 serial port female connector located on the rear of the UPS unit. Several signals are pro­vided on this port and are assigned as follows:
Pin Assignment Description
1 Low Battery (open collector)
2 UPS TxD (typical RS-232 levels)
3 UPS RxD (typical RS-232 levels)
4 Remote Shutdown (5-12VDC, 10-24 mA max); battery operation
5Common
6 Remote Shutdown (short to pin 5); all modes of operation
7 Low Battery (open emitter)
8 Utility Fail (open emitter)
9 Utility Fail (open collector)
Pin Assignment Collector to Emitter*
6789
330 Ohms
54321
(+)
(-)
*Maximum voltage and current on pins 1, 7, 8, and 9 is 60V DC; 10.0 mA.

PIN 4 - REMOTE SHUTDOWN ON BATTERY

1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds, the command cannot be canceled.
17
Open Collecto
Open Emitter
Page 22
3. A battery shutdown signal on Pin 4 will NOT cause an immediate shutdown. A shutdown signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.
4. If the utility returns during the 2-minute timer countdown, the shut­down timer will continue until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power returns before the UPS turns OFF. This serves to reset and restart the server.
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown delay.

UPS INTELLIGENT COMMUNICATIONS

The UPStation GXT 2U is equipped with an Intellislot™ port to provide advanced communication and monitoring options.
Liebert's MultiLink™ software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit. For more information about the Intellislot SNMP/Web Card and MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT 2U. The Intellislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coordinate shutdown in the event of a power failure.
The Intellislot Relay Card provides five dry contact relay outputs for custom wired applications and delivers support for built-in shutdown for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables, where applicable.
18
Page 23

CONFIGURATION PROGRAM

This is a new feature included with the new UPStation GXT 2U line. Sev­eral UPS settings that were previously not available or required custom manufacturing may now be modified using this program. For most users, the factory default settings will be adequate. This manual illustrates the features available for modification, as well as the factory default setting.

GXT 2U CONFIGURATION PROGRAM ABILITIES

Select one of five output voltages to match voltages found around the world.
Enable/Disable Auto-Restart.
Enable/Disable the Line-Neutral-Reversal/Loss-of-Ground recepta­cle wiring alarm.
Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
Set the Low Battery Warning alarm time from 2 to 30 minutes.
Enable/Disable the Auto-Battery test.
Set the Auto-Battery test to 7, 14, 21, or 28 days.
Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Lie­bert software products.
NOTE
This program is compatible with UPS models beginning with “GXT2-”, as in “GXT2-1500RT120”. It is not compatible with earlier versions of UPStation GXT UPS.

What You Will Need

In addition to the GXT 2U UPS, you will need the configuration program diskette and serial cable (Beige or Tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. The BLACK ML9P9S CONTACT CLOSURE communication cable IS NOT compatible with the configuration program. A Windows 95
®
, 98®, or NT® computer— desktop or laptop—is also required to set up and run the configuration program.
19
Page 24

MAINTENANCE

The UPStation GXT 2U requires very little maintenance. The batteries are valve regulated, nonspillable, flame retardant, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is recommended to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries.
The UPStation GXT 2U is designed to allow the user to safely replace the internal batteries. Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing.

BATTERY REPLACEMENT

CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:
• Remove rings, watches, or other metal objects.
• Use a Phillips (crosshead) screwdriver with insu­lated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
20
Page 25

Internal Battery Replacement Procedures:

1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the four screws on the front battery door. Lay the battery door aside for reassembly.
3. Gently pull battery wiring out and disconnect the two slotted battery connectors.
4. Grasp the battery pack assembly, and pull it out of the front of the UPS.
5. Unpack the new battery assembly taking care not to destroy the pack­ing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 6; otherwise STOP and contact your local dealer, Liebert representative, or the Liebert Worldwide Support Group.
6. Line up and slide in the new replacement battery pack.
7. Reconnect the 2 slotted battery connectors and gently push the bat­tery wiring and battery pack assembly back into the UPS.
8. Reattach the front battery door with the four screws.
9. Reattach the front plastic bezel cover to the UPS.
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.
21
Page 26

FUSE REPLACEMENT

CAUTION
!
Before changing the input fuse, turn off the UPS, and unplug the supply lead from the AC input supply. Replace the fuse with the same type and rating.
1. Remove the input fuse from the fuse holder on the rear of the unit.
2. Locate the spare input fuse that is shipped with the UPS.
3. Insert the spare fuse into the fuse holder, and reinstall assem­bly into the UPS. Twist by hand; rotate clockwise until fuse holder locks into position.
4. Reconnect the input power cord to input AC supply.
5. Restart the UPS. The UPS is ready for normal operation.
22
Page 27

TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation GXT 2U™ develops a problem. Use this infor­mation to determine whether external factors caused the problem and how to remedy the situation.
1. The fault indicator will illuminate, indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illumi­nated to provide a diagnostic aid to the operator, as described below:
Fault
E
D
C
B
A
BYPASS
UPS ON
BATTERY
AC INPUT
This example shows UPS on bypass due to output overload.
ABCDEFault
AC INPUT BATTERY UPS ON BYPASS
LOAD/BATTERY
LEVEL INDICATORS
LED status Diagnosis/Audible alarm
All LEDs On bypass due to output overload; beep ever half-second
A LED On bypass due to overtemperature condition; beep every 4 sec.
B LED On bypass due to DC bus overvoltage; beep every 4 sec.
C LED On bypass due to control power supply failure; beep every 4 sec.
D LED On bypass due to PFC failure; beep every 4 sec.
E LED On bypass due to inverter failure; beep every 4 sec.
A&C LEDs UPS failed battery test; long beep every minute
C&E LEDs
Battery
LED Flashing
AC LED
Flashing
Bypass LED
Flashing
UPS shutdown due to command from communication port (SNMP); no beep
Internal Battery source not available (continuous horn). Check battery connection, completely power down and reboot UPS.
Line to neutral reversal in the AC input power supply or a loss of proper grounding; continuous horn and UPS will not start.
Utility power voltage or frequency is out of tolerance; bypass is unavailable.
23
Page 28
Under fault conditions, the fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.
Troubleshooting Guide
Problem Cause Solution
UPS fails to start when the ON button is pressed.
Battery indicator LED is illuminated.
UPS has reduced battery time.
UPS is short circuited or overloaded.
UPS not plugged in. UPS is operating from battery
UPS input protection fuse has blown/opened.
Utility voltage out of UPS input range.
Batteries are not fully charged.
UPS is overloaded. Check load level display and
Batteries may not be able to hold a full charge due to age.
Ensure UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
mode, make certain UPS is securely plugged into the wall receptacle.
UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.
UPS is operating from battery mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
reduce the load on the UPS.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group for replacement battery kit.
Fault and Bypass indicator LEDs and all load level LEDs are illuminated.
UPS overloaded or load equipment is faulty.
24
Check load level display and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load equipment for faults.
Page 29
Troubleshooting Guide (Continued)
Problem Cause Solution
Fault and Bypass indicator LEDs and diagnostic LED A are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED B are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED C are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED D are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED E are illuminated.
UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power.
UPS internal DC bus overvoltage.
UPS control power supply fault.
UPS PFC (Power Factor Correction Circuit) fault.
UPS inverter fault. UPS requires service. Contact
Ensure UPS is not overloaded, ventilation openings not blocked, or room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. IF UPS does not restart, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
Fault and Bypass indicator LEDs and diagnostic LED A and C are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED C and E are illuminated.
UPS failed the battery test.
UPS shutdown due to a command from the communications port(s).
25
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Page 30
Troubleshooting Guide (Continued)
Problem Cause Solution
AC LED is flashing. UPS detected a line-to-
neutral reversal or a loss of proper grounding; continuous horn and UPS will not start.This is active only when power is first applied to the input. Once the UPS is running, the AC LED will not start flashing, even if the input wiring is changed.
Battery LED is flashing.
Bypass LED is flashing.
Battery source is not available; continuous horn.
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside acceptable limits.
Contact a qualified electrician to verify site wiring.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this LED will flash, indicating that the bypass is unavailable.
26
Page 31
Alarm Conditions
Condition Alarm
Battery Mode (utility failure)
Low Battery Two short beeps every 5 seconds; less than
Output overload (bypass)
Overtemperature (bypass)
DC Bus Overvoltage (bypass)
Control power supply failure (bypass)
PFC failure (bypass) A one-second beep every 4 seconds
Inverter failure A one-second beep every 4 seconds
Battery Test failure A 2-second beep every minute
One short beep every 10 seconds; more than 2 minutes of run time remaining
2 minutes of run time remaining
One short beep every half second
A one-second beep every 4 seconds
A one-second beep every 4 seconds
A one-second beep every 4 seconds
27
Page 32
Model Number GXT2-700RT120 GXT2-1000RT120 GXT2-1500RT120 Model Rating 700VA / 490W 1000VA / 700W 1500VA / 1050W
DIMENSIONS in (mm)
Unit W x D x H in. (mm) Shipping W x D x H in. (mm)
WEIGHT lbs (kg)
Unit 48.9 (22.2) 49.1 (22.3) 50.6 (23) Shipping 57.7 (26.2) 57.9 (26.3) 59.5 (27)
INPUT AC PARAMETERS
Voltage Range (typical)
100% - 90% loading 80 VAC / 140 VAC 80 VAC / 140 VAC 90 VAC / 140 VAC 90% -70% loading 80 VAC / 140 VAC 80 VAC / 140 VAC 80 VAC / 140 VAC 70% -30% loading 70 VAC / 140 VAC 70 VAC / 140 VAC 70 VAC / 140 VAC 30% - 0% loading 60 VAC / 140 VAC 60 VAC / 140 VAC 60 VAC / 140 VAC Frequency 40 - 70 Hz; Auto Sensing
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles (4) NEMA 5-15R Voltage 100/ 110/ 115/120/ 127 (user configurable) VAC; ±3% Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, flame retardant, lead acid Qty x V x Rating 4 x 12V x 7.0 or 7.2 AH Battery Mfg / Part # China Storage Battery / CSB FR 1270 F2 Back-up Time See Battery Run Times charts Recharge Time 5 Hours to 95% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C) Storage Temp +5°F to +122°F (-15°C to +50°C) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating Storage Elevation 50,000 ft. (15,000m) maximum
Audible Noise
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications) RFI/EMI FCC Part 15, Subpart B, Class A Surge Immunity IEEE/ANSI C62.41 Category A & B Transportation ISTA Procedure 1A

SPECIFICATIONS

3.5 x 21.5 x 17
(87 x 547 x 430)
10.4 x 27.3 x 22.5 (268 x 692 x 585)
120 VAC nominal; variable based on output load
6 ft. attached
w/ NEMA 5-15 plug
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
<45 dBA, at 1 meter from the front or sides
3.5 x 21.5 x 17
(87 x 547 x 430)
10.4 x 27.3 x 22.5 (268 x 692 x 585)
10 ft. attached
w/ NEMA 5-15 plug
<50 dBA, at 1 meter from the rear
10.4 x 27.3 x 22.5 (268 x 692 x 585)
w/ NEMA 5-15 plug
3.5 x 21.5 x 17
(87 x 547 x 430)
10 ft. attached
28
Page 33
SPECIFICATIONS (CONTINUED)
Model Number GXT2-2000RT120 GXT2-3000RT120 Model Rating 2000VA / 1400W 3000VA / 2100W
DIMENSIONS in (mm)
Unit W x D x H in. (mm) Shipping W x D x H in. (mm)
WEIGHT lbs (kg)
Unit 54 (24) 69 (31) Shipping 62.6 (28.4) 78.0 (35.4)
INPUT AC PARAMETERS
Voltage Range (typical) 100% - 90% loading 90 VAC / 140 VAC 90 VAC / 140 VAC 90% -70% loading 80 VAC / 140 VAC 80 VAC / 140 VAC 70% -30% loading 70 VAC / 140 VAC 70 VAC / 140 VAC 30% - 0% loading 60 VAC / 140 VAC 60 VAC / 140 VAC Frequency 40 - 70 Hz; Auto Sensing
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
Voltage 100/110/ 115/120/ 127 (user configurable) VAC; ±3% Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, flame retardant, lead acid Qty x V x Rating 4 x 12V x 9.0 AH 6 x 12V x 9.0 AH Battery Mfg / Part # Panasonic / UP-VW1245P1
Back-up Time See Battery Run Times charts Recharge Time 5 hours to 95% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C) Storage Temp +5°F to +122°F (-15°C to +50°C) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications) RFI/EMI FCC Part 15, Subpart B, Class A Surge Immunity IEEE/ANSI C62.41 Category A & B Transportation ISTA Procedure 1A
3.5 x 21.5 x 17
(87 x 547 x 430)
10.5 x 27.2 x 23
(268 x 692 x 585)
120 VAC nominal; variable based on output load
10 ft. attached
w/ NEMA 5-20 plug
(4) 5-20R T-Slot,
accepts 15A plug
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Yuasa / REW 45-12 FR
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
(1) NEMA L5-30R on 12 in cord
3.5 x 24.2 x 17
(87 x 618 x 430)
10.5 x 27.2 x 23
(268 x 692 x 585)
10 ft. attached
w/ NEMA L5-30 plug
(4) NEMA 5-15R
29
Page 34

BATTERY CABINET SPECIFICATIONS

Model Number GXT2-48VBATT GXT2-72VBATT
GXT2-700RT120
Used w/ UPS Model
DIMENSIONS in (mm)
Unit W x D x H Shipping W x D x H
WEIGHT lbs (kg)
Unit 65.0 (29.5) 93.6 (42.5) Shipping 71.1 (32.3) 102.5 (46.5)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, flame retardant, lead acid Qty x V x Rating 2 x 4 x 12V x 7.0 or 7.2 AH 2 x 6 x 12V x 9.0 AH Battery Mfg / Part # China Storage Battery /
Back-up Time See Battery Run Times charts
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C) Storage Temp +5°F to +122°F (-15°C to +50°C) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating Storage Elevation 50,000 ft. (15,000 m) maximum
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications) RFI/EMI FCC Part 15, Subpart B, Class A Transportation ISTA Procedure 1A
GXT2-1000RT120 GXT2-1500RT120 GXT2-2000RT120
3.5 x 21.5 x 17
(87 x 547 x 430)
10.5 x 27.2 x 23
(268 x 692 x 585)
CSBFR 1270 F2
GXT2-3000RT120
3.5 x 24.2 x 17
(87 x 618 x 430)
10.5 x 27.2 x 23
(268 x 692 x 585)
Panasonic / UP-VW 245P1
Yuasa / REW 45-12 FR
30
Page 35

BATTERY RUN TIMES

Load% 700VA 1000VA 1500VA 2000VA 3000VA
10% 248 191 144 56 91
Internal Battery (minutes)
Internal Battery + 1 External Battery Cabinet (minutes)
Internal Battery + 2 External Battery Cabinets (minutes)
Internal Battery + 3 External Battery Cabinets (minutes)
Internal Battery + 4 External Battery Cabinets (minutes)
Approximate discharge times are in minutes and at 77°F (25°C) and with a 100% resistive load.
20%11587533346 30% 79 48 38 26 30 40% 58 34 28 19 21 50% 44 25 20 14 16 60% 35 19 15 12 11 70% 29 16 12 10 9 80% 24 13 10 8 8 90% 20 12 8 7 7
100% 17 11 7 6 5
10% 992 764 576 168 364 20% 460 348 212 99 184 30% 316 192 152 78 120 40% 232 136 112 57 84 50% 176 100 80 42 64 60% 140 76 60 36 44 70%11664483036 80% 96 52 40 24 32 90% 80 48 32 21 28
100% 68 44 28 18 20
10% 1984 1528 1152 392 728 20% 920 696 424 231 368 30% 632 384 304 182 240 40% 464 272 224 133 168 50% 352 200 160 98 128 60% 280 152 120 84 88 70% 232 128 96 70 72 80% 192 104 80 56 64 90% 160 96 64 49 56
100% 136 88 56 42 40
10% 2976 2292 1728 560 1092 20% 1380 1044 636 330 552 30% 948 576 456 260 360 40% 696 408 336 190 252 50% 528 300 240 140 192 60% 420 228 180 120 132 70% 348 192 144 100 108 80% 288 156 120 80 96 90% 240 144 96 70 84
100% 204 132 84 60 60
10% 3968 3056 2304 840 1456 20% 1840 1392 848 495 736 30% 1264 768 608 390 480 40% 928 544 448 285 336 50% 704 400 320 210 256 60% 560 304 240 180 176 70% 464 256 192 150 144 80% 384 208 160 120 128 90% 320 192 128 105 112
100% 272 176 112 90 80
31
Page 36
32
Page 37
Page 38
POWER PROTECTION
UPStation GXT 2U
The Company Behind the Products
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2002 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23150 (3/02) Rev. 4
USER MANUAL
Technical Support
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Single-Phase UPS
Outside the United States
Environmental Control
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
FAX: +39 049 5841 257
23F, Allied Kajima Bldg.
800-222-5877
614-841-6755
3-Phase UPS
800-543-2378
800-543-2778
Italy
+39 049 9719 111
Asia
138 Gloucester Road
FAX: +852 2 831 0114
upstech@liebert.com
Wanchai
Hong Kong
+852 2 572 2201
Web Site
www.liebert.com
E-mail
Loading...