Opening or removing the cover may expose you to lethal
voltages within this unit even when it is apparently not
operating and the input wiring is disconnected from the
electrical source. Observe all cautions and warnings in this
manual. Failure to do so MAY result in serious injury or
death. Refer all UPS and battery service to qualified service
personnel. Do not attempt to service this product yourself.
Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety,
installation, and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and
in this manual. Follow all operating and user instructions. Individuals
without previous training can install and operate this equipment.
It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS
rating label. The UPS is designed for data processing equipment. If
uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 50 Hz
or 60Hz, 120V supply (programmable for 100, 110, 115, 120 and
127VAC output). Installation instructions and warning notices are
located in this manual.
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT2U™
Series complies with the limits for a CLASS A DIGITAL DEVICE,
PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation. Operating
this device in a residential area is likely to cause harmful interference
that users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F (0°C to +40°C). Install it in a clean
environment, free from moisture, flammable liquids, gases and corrosive substances.
1
DISCONTINUED
PRO DU C T
This UPS contains no user serviceable parts except the internal battery pack. The UPS ON/Standby push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access
internally other than to replace the batteries due to risk of electric
shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or if
the UPS performance alters in use. Refer all faults to your local
dealer, Liebert representative or the Liebert Worldwide Support
Group.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. PROPER DISPOSAL OF
BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND
REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other
openings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or
demand half-wave rectification from the UPS, for example: electric
drills, vacuum cleaners, laser printers or hairdryers.
Storing magnetic media on top of the UPS may result in data loss or
corruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft
cloth, never liquid or aerosol cleaners. Keep the front and rear vents
free of dust accumulation that could restrict airflow.
When replacing batteries, replace with the same Liebert authorized
replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery
may explode.
Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
2
DISCONTINUED
PRO DU C T
1.0GLOSSARYOF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
Glossary of Symbols
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid
battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON
Standby
3
DISCONTINUED
PRO DU C T
Introduction
2.0INTRODUCTION
Congratulations on your choice of the Liebert GXT2U™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during
transmission and distribution it may be subject to voltage sags,
spikes, or complete power failure that may interrupt computer operations, cause data loss, or even damage equipment. The Liebert GXT2U
protects equipment from these disturbances.
The Liebert GXT2U comes in nominal power ratings of 500, 700, 1000,
1500, 2000 and 3000 VA. Complete model specifications appear at the
end of this manual.
The Liebert GXT2U is a compact, “on-line” UPS. An on-line UPS continuously conditions and regulates its output voltage, whether utility
power is present or not. It supplies connected equipment with clean
sinewave power. Sensitive electronic equipment operates best from
sinewave power.
For ease of use, the Liebert GXT2U features a light-emitting diode
(LED) display to indicate either load percentage or battery capacity
depending upon the mode of operation. It also provides self-diagnostic
tests, a combination ON/Alarm Silence/Manual Battery Test button, a
Standby button, user configurable program, and two levels of alarms
when the unit is operating on battery.
The Liebert GXT2U has an interface port for communication between
the UPS and a network server or other computer systems. This port
provides detailed operating information including voltages, currents,
and alarm status to the host system when used in conjunction with
Liebert MultiLink™ software. Liebert MultiLink software can also
remotely control UPS operation.
4
DISCONTINUED
PRO DU C T
3.0MAJOR COMPONENTS
Major Components
InputOutput
L1
L2
G
TVSS &
EMI/RFI
Filters
Battery
Charger
Rectifier
/PFC
Dynamic
Bypass
DC to DC
Converter
Battery
Inverter
L1
L2
G
3.1TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS)
AND EMI/RFI FILTERS
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference
(RFI). They minimize any surges or interference present in the utility
line and keep the sensitive equipment protected.
In normal operation, the rectifier/power factor correction (PFC) circuit
converts utility AC power to regulated DC power for use by the
inverter while ensuring that the waveshape of the input current used
by the UPS is near ideal. Extracting this sinewave input current
achieves two objectives:
• The utility power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the
building not being protected by the Liebert GXT2U.
3.3INVERTER
In normal operation, the inverter utilizes the DC output of the power
factor correction circuit and inverts it into precise, regulated sinewave
AC power. Upon a utility power failure, the inverter receives its
required energy from the battery through the DC to DC converter. In
both modes of operation, the UPS inverter is on-line and continuously
generating clean, precise, regulated AC output power.
5
DISCONTINUED
PRO DU C T
Major Components
3.4BATTERY CHARGER
The battery charger utilizes energy from the utility power and precisely regulates it to continuously “float charge” the batteries. The batteries are being charged whenever the Liebert GXT2U is plugged in,
even when the UPS is not turned on.
3.5DC TO DC CONVERTER
The DC to DC converter utilizes energy from the battery system and
raises the DC voltage to the optimum operating voltage for the
inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
3.6BATTERY
The Liebert GXT2U utilizes valve-regulated, nonspillable, lead acid
batteries. To maintain battery design life, operate the UPS in an
ambient temperature of 68°F to 77°F (20°C to 25°C). Optional external
battery cabinets are available to extend battery run times.
3.7DYNAMIC BYPASS
The Liebert GXT2U provides an alternate path for utility power to the
connected load in the unlikely event of a UPS malfunction. Should the
UPS have an overload, overtemperature, or UPS failure condition, the
UPS automatically transfers the connected load to bypass. Bypass
operation is indicated by an audible alarm and illuminated amber
Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the
inverter to bypass, press the Standby button once.
NOTE
The bypass power path does NOT protect the connected
equipment from disturbances on the utility supply.
6
DISCONTINUED
PRO DU C T
3.8LIEBERT GXT2U, REAR VIEW
Major Components
DB-9
Communications Port
External Battery
Connector
Rev.USBCARD
USB card being fitted
in Liebert IntelliSlot
®
Port
Cooling Fan
Input Fuse/ Circuit
Breaker
Output
Receptacles
Support Base
7
AC Input
DISCONTINUED
PRO DU C T
Installation
4.0INSTALLATION
4.1PREPARATION
1. Visually inspect the UPS for freight damage. Report damage to
the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see 11.0 - Specifications). Take proper
precautions when lifting or moving it.
2. Decide where to place the Liebert GXT2U. Install the UPS indoors
in a controlled environment, where it cannot be accidentally
turned off. Place it in an area of unrestricted airflow around the
unit, away from water, flammable liquids, gases, corrosives, and
conductive contaminants. Maintain a minimum clearance of 4 in.
(100mm) in the front and rear of the UPS. Maintain an ambient
temperature range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
3. The Liebert GXT2U may be installed in either a tower
configuration or in a rack, depending on available space and use
considerations. Determine the type of installation and follow the
appropriate instructions in either 4.2 - Tower UPS Installation
or 4.3 - Rack-Mount UPS Conversion and Installation.
4.2TOWER UPS INSTALLATION
When using the Liebert GXT2U in a tower configuration, use the
included support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).
Support baseSpacers added to support
8
base to accommodate
additional battery cabinets
DISCONTINUED
PRO DU C T
Installation
4.3RACK-MOUNT UPS CONVERSIONAND INSTALLATION
NOTE
When rack mounted, the UPS must be supported by a shelf,
brackets or slide rails on each side. The rack mount handles
WILL NOT support the weight of the UPS. They are used to
move the UPS into and out of the rack.
1. For slide rail installations, first remove the top/side fin. Slide the
top/side fin forward, then lift it up to remove. If desired, install the
optional rack mount handles that were shipped with the UPS.
UPStation GXT
–
+
AC INPUT BATTERY UPS ON BYPASS
Optional rack mount handles
Securing hardware and slide rails are sold separately. Contact
your local dealer or Liebert representative for these additional
options and any assistance needed.
2. Unpack the two (2) rack-
mounting bracket assemblies
and mounting hardware
from the rack-mounting kit
(P/N: RMKIT18-32). Bracket
assemblies are
interchangeable between
left-hand or right-hand.
Remove inner member of
each bracket assembly as
shown at right by extending
it to its outermost position,
depressing the retaining
latch and then pulling inner
member from bracket
assembly.
Retaining
latches
Inner
members
Return
flanges
Rear
members
Front
members
9
DISCONTINUED
PRO DU C T
Installation
3. Determine the height position inside the rack enclosure where you
want to mount the UPS or battery cabinet.
CAUTION
!
Reduce risk of tipping the rack enclosure by placing UPS or
battery cabinet in the lowest possible rack position.
Install rear member of each
bracket assembly into rack
enclosure with two (2) M5
Front rack
mounting rails
M5 screws
screws provided in this kit.
(See figure at right.) Return
flanges on bracket assembly
fit to the inside of rack
mounting rails. Insert screws
loosely (finger-tight) into top
and bottom holes of return
flange on rear member.
Extend bracket assembly by
sliding front member for-
M5 screws
Rear rack
mounting
rails
ward until it touches the front rack mounting rail. Insert two (2) M5
screws loosely (finger-tight) into top and bottom holes of return
flange on each front member. Make sure bracket assemblies are at
the same mounting height on all four (4) rack mounting rails.
4. Locate eight (8) M4 screws
and eight (8) M4 nuts from
M4 nuts
M4
screws
hardware pack in this kit.
Each nut has a locking, nylon
insert that begins gripping
the screw when it is halfway
tight. Make sure to tighten
nut and screw completely to
assure locking action. Fasten
rear member and front
member together using four
(4) screws and four (4) nuts
18" rack
depth
M4 nuts
M4 nuts
per bracket assembly as
shown in the figures at right.
For maximum support,
locate fasteners for each
bracket assembly as far
apart as possible, depending
on rack depth, while still
32" rack
depth
joining both members (See
figures at right). Check alignment of bracket assemblies and
TIGHTEN ALL SCREWS FROM STEPS 3 and 4.
M4
screws
M4 nuts
10
DISCONTINUED
PRO DU C T
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.