This Manual Contains Important Safety Instructions. Read all safety and operating instructions
before operating the Uninterruptible Power Supply (UPS). Adhere to all warnings on the unit and in
this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training.
This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS
rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer.
See Limited Warranty.
This UPS is designed for use on a properly earthed (grounded), 220-240 VAC, 50Hz or 60Hz supply,
for installation by qualified personnel. A qualified electrician must review and approve customer supplied wiring, circuit breakers, intended loads, and verify correct input, output and earth connections
to ensure compliance with technical standards and local electrical codes of practice. Installation
instructions and warning notices only for use by qualified personnel are located after the UPS operator instructions in this manual.
WARNING
!
This UPS should not be supplied from electrical power systems of the “IT” (Impédance à
Terre) type. (IEC 364-ELECTRICAL INSTALLATION OF BUILDINGS)
ELECTROMAGNETIC COMPATIBILITY—This UPS complies with the requirements of the EMC
Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
WARNING
!
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C
(32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
This UPS contains no user serviceable parts. The UPS ON/OFF push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions, or the UPS performance alters in use. Refer all faults to your dealer.
Only trained engineers authorized by Liebert should perform troubleshooting. To replace batteries,
refer all servicing to qualified service personnel. Proper disposal of batteries is required. Refer to your
local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,
for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half
wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the off UPS and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol
cleaners.
1
GLOSSARY OF SYMBOLS
Risk of electrical shock
!
R
i
-
PbH2SO4
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
Indicates the position of a fuse
2
1.0INTRODUCTION
Congratulations on your choice of the Liebert UPStation GXT2-6000RT230 and GXT2-4500RT230
Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other
sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it
may be subject to voltage sags, spikes, or complete power failure that may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT2 protects equipment from
these disturbances.
The UPStation GXT2 comes in nominal power ratings of 4500 VA and 6000 VA. Complete model specifications appear at the end of this manual.
The UPStation GXT2 is a compact, on-line UPS. An on-line UPS continuously conditions and regulates its output voltage, whether mains power is present or not. It supplies connected equipment with
clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT2 features a light-emitting diode (LED) display to indicate both
load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm
Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of
alarms when the unit is operating on battery.
The UPStation GXT2 has an interface port for communication between the UPS and a network server
or other computer systems. This port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ software. MultiLink software can also remotely control UPS operation.
Introduction
3
2.0SYSTEM DESCRIPTION
System Description
InputOutput
L1
N
GG
TVSS &
EMI/RFI
Filters
Rectifier
/PFC
DC-to-DC
Converter
Battery
Charger
Dynamic
Bypass
Inverter
Battery
L1
N
2.1Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
These UPS components provide surge protection and filter both electromagnetic interference (EMI)
and radio frequency interference (RFI). They minimize any surges or interference present in the
mains line and keep the sensitive equipment protected.
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to
regulated DC power for use by the inverter while ensuring that the waveshape of the input current
used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The mains power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the mains is reduced.
This results in cleaner power being available to other devices in the building not being protected by
the UPStation GXT2.
2.3Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and
inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter
receives its required energy from the battery through the DC to DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, Regulated Ac Output
Power.
2.4Battery Charger
The battery charger utilizes energy from the mains power and precisely regulates it to continuously
float charge the batteries. The batteries are being charged whenever the UPStation GXT2 is connected to mains power.
4
2.5DC-to-DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
2.6Battery
The UPStation GXT2 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery
design life, operate the UPS
in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery cabinets are
available to extend battery run times.
2.7Dynamic Bypass
The UPStation GXT2 provides an alternate path for mains power to the connected load in the
unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is
indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to
indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass,
press the Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances
in the mains supply.
System Description
5
3.0MAJOR COMPONENTS
The GXT2 is composed of three major assemblies to provide easier handling, installation, and versatility.
3.1Main Frame and Electronics
This 5U cabinet is shipped with internal batteries installed and a basic, hardwire distribution box
attached and ready to install.
Figure 1GXT2, front view
Top Trim
(2 pieces;
tower use
only)
Major Components
Lower Bezel &
Battery Access
Door
Status
Indicators
& Controls
Upper
Bezel
!
UPStation GXT
6
Figure 2GXT2, rear view
Battery
Disconnect
Major Components
External Battery
Connector
UPS Output
Circuit Breaker
DB-9
Communication
Port
Removable Power
Distribution Box
Fans
REPO Connector
Relay Card Slot
Serial Card Slot
(SNMP, OCWEB, USB)
3.2Internal Battery Packs
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each
pack is fitted with a connector to link to the UPS.
Figure 3Internal battery pack with connector
7
3.3Removable Power Distribution Box
The UPS arrives with a basic hardwire power distribution pack installed. This box always contains
the UPS input circuit breaker.
Optional versions may be available to replace the standard box for custom installations.
Major Components
Figure 4
Power distribution boxes, basic, optional
Basic Hardwire Power Distribution Box
PD-CEHDWR
NOTE
Hardwire and hardwire/receptacle boxes that include a manual bypass switch allow
AC power to continue to flow from the mains input to the load while the box is removed
from the UPS. For details, refer to 11.2 - AC Power Connections.
Optional Hardwire Power Distribution
Box with Maintenance Bypass Switch
PD-CEHDWRBYP
8
4.0WHAT’S INCLUDED
The GXT2 are shipped with the following items:
• GXT2-6000RT230 and GXT2-4500RT230 user manual
• Vertical display overlay
• Top bezels - 2
• MultiLink software CD
• MultiLink serial cable, 10 ft (3m)
• Rack mount handles
• Support base - 2
• Mounting hardware
• Configuration program disk
•DB9 port cover
What’s Included
Top bezels
(tower use)
Vertical
display
overlay
Support base
with spacers
Rack mount
handles
MultiLink
software CD
Mounting hardware
DB9 port cover
MultiLink
serial cable
10 ft (3m)
www.liebert.com
GXT2™ Configuration
Program
For use with LiebertGXT 2U model UPS
systems
Versi on 1. 6
For Windows 95/98/NT
To Install:
Choose the Start button on the Taskbar
and select Run
Configuration
disk
9
5.0INSTALLATIONAND CONFIGURATION
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until
instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.
Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer
or Liebert representative.
CAUTION
!
The UPS is heavy (see 13.0 - Specifications). Take proper precautions
when lifting or moving it.
Install the GXT2 indoors in a controlled environment, where it cannot be accidentally turned off.
Place it where air flows unrestricted around the unit. The installation location must be free of water,
flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of
100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to
40°C (32 -104°F).
NOTE
UPS operation in sustained temperatures above 25°C (77°F) reduces battery life.
This device is intended for use in an Installation Category II environment.
Installation and Configuration
5.1Install the Main Cabinet
The GXT2 may be installed in either a tower configuration or in a rack, depending on available space
and use considerations. Determine the type of installation and follow the appropriate instructions in
either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.
5.1.1Tower UPS Installation
When using the GXT2 in a tower configuration, use the included support base (shown below, left) to
stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).
Figure 5Tower-use support bases, spacers for external battery cabinets
3U
5U support base for GXT2
End bases and 3U spacer
5.1.2Rack-Mount UPS Installation
When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed
rails or a shelf.
When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The figures accompanying 5.1.3 - Installing the Adjustable Rack-Mount Kit—Sold Separately shows
the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out
of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.
Spacers added to support base
to accommodate additional battery cabinets
3U
3U
2U
2U
2U
2U
CAUTION
!
Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box
is located. The fourth mounting hole is above the Power Distribution Box and is not used.
10
5.1.3Installing the Adjustable Rack-Mount Kit—Sold Separately
This kit contains parts needed to mount several different models of UPS and external battery cabinets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per
pair of adjustable rack-mounting brackets is 91 kg (200lbs.).
Parts included are:
ItemQuantity
Rear bracket members2
Front bracket members2
Inner bracket members2
M4 x 8mm machine screws16
M4 locking hex nuts8
M5 x 16 mm machine screws12
Grease packet.1
Tools needed for installation are:
• one Phillips screwdriver
• one 7mm wrench
The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent
users from inadvertently sliding the UPS or battery cabinet out of the rack.
Installation and Configuration
To install the rack mount brackets:
1. Unpack two (2) rack-mounting bracket assemblies and
mounting hardware from this kit. Bracket assemblies are
interchangeable between left-hand or right-hand.
Remove inner member of each bracket assembly as shown
at right by extending it to its outermost position, depressing the retaining latch and then pulling the inner member
out of the bracket assembly.
2. Determine the height position inside the rack enclosure
where you want to mount the UPS or battery cabinet.
CAUTION
!
Reduce the risk of tipping the rack enclosure by
placing the UPS or battery cabinet in the lowest
possible rack position.
3. Install the rear member of each bracket assembly into the
rack enclosure with two (2) M5 screws provided in this kit
(see figure at right). The return flanges on the bracket
assembly fit to the inside of rack mounting rails. Insert
screws loosely (finger-tight) into the top and bottom holes of
the return flange on the rear member. Extend the bracket
assembly by sliding the front member forward until it
touches the front rack mounting rail. Insert two (2) M5
screws loosely (finger-tight) into the top and bottom holes of
the return flange on each front member. Make sure that the
bracket assemblies are at the same mounting height on all
four (4) rack mounting rails.
Retaining
Latches
Inner
members
Front rack
mounting rails
M5 screws
Return
flanges
Front
members
M5 screws
Rear rack
mounting
rails
11
Installation and Configuration
4. Get eight (8) M4 screws and eight (8) M4 nuts from the
hardware pack in this kit. Each nut has a locking, nylon
M4 nuts
M4
screws
insert that begins gripping the screw when it is halfway
tight. Make sure to tighten the nut and screw completely to
ensure locking action. Fasten the rear member and the front
member together using (4) screws and (4) nuts per bracket
assembly as shown in at right. For maximum support, insert
fasteners for each bracket assembly as far apart as possible,
depending on rack depth, while still joining both members
(see figures at right). Check alignment of bracket assemblies
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.
5. Prepare the UPS or battery cabinet (the “equipment”) for
rack mounting by following instructions in the equipment’s
457mm
(18")
rack
depth
M4 nuts
M4 nuts
M4
screws
user manual. The equipment may require additional parts to
be added or parts to be removed for rack mounting. After it is
prepared, lay the equipment in rack-mounting position.
Fasten the inner members from Step 1 to the equipment on
both sides as shown at right with eight (8) M4 screws
provided in the kit. Make sure retaining latch is near the rear
813mm
(32") rack
depth
M4 nuts
of the equipment as shown (see figure at right).
6. Open the grease packet provided in the kit. Apply a bead of
M4 screws
Retaining latch
grease 25mm (1") long at four (4) places inside the bottom,
curved tracks of the front members as shown below right. The
grease will allow the equipment to slide into the bracket
assemblies more easily.
CAUTION
!
6.
Lifting equipment into the rack may be a two-person
job, depending on the weight of the equipment.
Liebert recommends taking the internal batteries
Front
UPS or battery
cabinet
out of the UPS during rack installation. This will
make the UPS cabinet lighter and easier to handle.
M4 screws
The GXT2 weighs 67kg (151lb). For the battery
cabinet’s weight, see the unit’s user manual.
7. Insert the equipment, with inner members attached in
Step 5, into the bracket assemblies by inserting the top and
bottom edges of the inner members into the top and bottom
curved tracks of the front members and sliding the
UPS or
battery
cabinet
Apply
grease
equipment into the rack (see figure at right). Ends of inner
members are tapered to allow the rear of the equipment to be
angled upward before insertion, if space allows.
Then the rear, bottom edges of the inner members can be
placed into the front edge of the bottom tracks and the front
Apply
grease
(inside)
of the equipment can be tipped up so they are level to insert
the top edges of the inner members before sliding the equipment into the rack (see figure below right). The equipment
should move smoothly into the bracket assemblies. If it does
not, recheck the alignment of the front and rear members
... and push it
into the rack.
from Steps 2 and 3.
8. Secure the front of the equipment to the rack mounting rails
to prevent the equipment from sliding out of position. If
securing holes are provided on the front of the equipment
that align with the center holes on the return flange of the
front members, you can use the four (4) extra M5 screws
provided in the kit to secure the equipment. Otherwise, the
Insert the UPS into the front
members, lift the front .. .
equipment should be secured to the front of the rack with
four (4) customer-supplied fasteners.
12
5.2External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked
beneath the UPS.
CAUTION
!
The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery
cabinets can be used in rack-mount or tower configuration. Take proper precautions when
lifting them.
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier
and your local dealer or Liebert representative.
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift
up to remove. Optional rack-mount handles are shipped with the external battery cabinet and
may be installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert
representative for these additional options and any assistance needed. Fasten the slides into
position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of
support base extensions ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,
then to the rear of the UPS.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run
times, refer to Table 6.
Installation and Configuration
NOTE
You must use the included configuration program to program the UPS for the number
of external battery cabinets connected. Instructions for the configuration program are in
7.0 - Configuration Program.
3U
2U
Spacers added to support
base to accommodate
additional battery cabinets
2U
13
5.3Connect the Internal Batteries Using the External Connector
The internal connectors of the internal battery packs will be connected when shipped. However, the
internal batteries will be disconnected from the UPS using a rear panel connector. The connector
attaches to the UPS in both the open and closed position using two screws. The picture on the left
shows the connector in the open position, as shipped.
When the UPS is installed, remove the two screws to release the connector. Plug the connector into
the socket. The internal batteries are now connected to the UPS electronics. Install the two screws to
secure the connector in the closed position.
Remove these screws
to release connector
Installation and Configuration
5.3.1Storage
If the UPS is to be shipped or stored for an extended time, the connector should be removed and
attached in the open position, as shown above. This will minimize any standby current drain on the
batteries.
5.4Connect Input/Output Power
The UPS should arrive with the basic hardwire
box attached. If the box needs to be exchanged for
an optional model, remove and install the desired
box using the three captive screws marked in the
illustration at right.
To remove:
Loosen the screws about 20 turns until the box
can be pulled away from the UPS.
To install:
Align the connectors on the box and UPS. Push
the box into place. While holding the box firmly
against the UPS, tighten the three captive screws
until the box is secure. Do not over tighten.
5.4.1Distribution Box Electrical Connections
Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.
The installer must provide a 32A branch circuit breaker. The Input circuit breaker on the distribution
box and the Output circuit breaker on the rear fixed-panel of the UPS disconnect all power between
the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from
the input terminal block. The input circuit breaker on the distribution box does not disconnect power
from the manual bypass switch.
1. Note1 The installer must provide circuit breaker protection according to local codes. The
mains disconnect should be within sight of the UPS or have appropriate an appropriate
lock-out. Maintain service space around the UPS or use flexible conduit.
2. Note 2 The installer must provide output distribution panels, circuit breaker protection, or
emergency disconnects according to local codes. Output circuits must not share a common
conduit with any other wiring.
15
6.0INITIAL START-UPAND ELECTRICAL CHECKS
1. Verify that the Input Output circuit breakers are off.
2. During initial system checks, disconnect all loads (open load disconnects).
3. Inspect all wiring, cables, and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted
in the sockets.
5. If you are using a distribution box that includes a Manual Bypass Switch, place the switch in
BYPASS position.
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.
7. Using a voltmeter, verify the expected L1-N voltage.
If no Manual Bypass Switch is used, there will be no output voltage at this time. If a Manual
Bypass Switch is used, verify that the same voltages appear at the Output terminals. If a Manual
Bypass Switch is used, the Bypass lamp will light by the switch. If no manual bypass switch is
used, there will be no output voltage at this time.
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power,
close all access panels to the distribution box, and reapply input power.
9. Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should
illuminate on the front panel.
10. Press the ON button for 1 second. The BYPASS lamp will light for several seconds before the UPS
ON lamp turn on continuously. If the batteries are determined to charged above 80%, an
automatic battery test will run for about 15 seconds.
11. Close the Output circuit breaker on the rear of the UPS. If a Manual Bypass Switch is used, the
Inverter lamp by the switch will light. If a Manual Bypass Switch is used, transfer the switch to
the Inverter position. The output terminal block will be powered at this time.
12. Perform a Manual Battery Test - Press the ON button for 1 second. The front BATTERY lamp will
light for about 15 seconds and then return to only the UPS ON and AC INPUT lamps being on.
13. Review all setting option provided by the configuration program. Some changes require that the
UPS be OFF. If this is the case, these should be programmed before powering the loads. The
configuration program is described in the next section.
14. Connect all loads for normal operation.
Initial Start-Up and Electrical Checks
16
Configuration Program
7.0CONFIGURATION PROGRAM
The final step of installation may require custom configuration of your UPS using the enclosed configuration program. Some configuration settings may be changed only while the UPS is off. These should
be set before the UPS is put into full-time service powering the critical load.
For most users operating with 230VAC and with no external batteries, the factory default settings
will be adequate.
7.1GXT2-6000RT230 and GXT2-4500RT230 Configuration Program Features
• Select one of three L-N output voltages to match local voltages.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculations reported by Liebert software products.
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see Table 2).
7.1.1What You Will Need
In addition to the GXT2 UPS, you will need the configuration program diskette and serial cable (beige
or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A Windows 95® or later computer, desktop or laptop, is also required to set up and run the configuration
program.
17
8.0CONTROLSAND INDICATORS
Controls and Indicators
All indicators illuminated
for illustration only.
UPStation GXT
BATTERY UPS ONBYPASSAC INPUT
8.1ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
•ON
•Alarm Silence
•Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and
protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the
alarm is silenced, the UPStation GXT2 will reactivate the alarm system to alert of
additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second
while operating from mains power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24
hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact
your local dealer, Liebert representative or Liebert Worldwide Support Group.
8.2Standby/Manual Bypass Button
This button controls output power to connected load(s) and has dual functions:
Standby and Manual Bypass.
CAUTION
!
Pressing the Standby/Manual Bypass button once will transfer the
load to bypass power. Pressing the Standby/Manual Bypass button a
second time within 4 seconds will cut off power to the output sockets
and connected loads. Perform all necessary shutdown procedures on
connected loads before pressing this button twice.
18
8.3Load Level Indicators (4 Green, 1 Amber)
The load level indicators display the approximate electrical load placed upon the UPS at all times.
8.4Battery Level Indicators (5 Green)
The battery level indicators display approximate battery capacity at all times.
The UPStation GXT2 is equipped with automatic and remote battery test features. The automatic
test occurs every 14 days (this option is user configurable) if mains has not been interrupted. Should
the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will
illuminate and an alarm will sound (refer to 12.0 - Troubleshooting). The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery test.
8.5Fault Indicator LED (Red)
The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the
battery level indicators may be illuminated (refer to 12.0 - Troubleshooting).
8.6Bypass Indicator LED (Amber)
The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm
will sound indicating the UPS detected a problem, or the manual bypass function has been activated.
Controls and Indicators
8.7UPS ON Indicator LED (Green)
The UPS ON indicator LED is illuminated when the UPS inverter is operating and supplying power
to the connected loads.
8.8Battery Indicator LED (Amber)
The Battery indicator LED is illuminated when the UPS is operating on battery.
8.9AC Input Indicator LED (Green)
The AC Input indicator LED is illuminated when mains power is available and within the input specifications.
19
9.0OPERATING INSTRUCTIONS
AC I NPUT
9.1Normal Mode Operation
During normal operation, mains power provides energy to the
UPS. The filters, power factor correction circuit and the inverter
process this power to provide computer grade power to connected
loads. The UPS maintains the batteries in a fully charged state.
The four green load level LEDs indicate an approximate level of
load in 25% increments. If the UPS becomes loaded beyond full
rating, the fifth (amber) LED indicator will illuminate and the
UPS will sound an audible alarm. The display template indicates
the percentage of load (10% of load shown in example) on the UPS
output.
9.2Battery Mode Operation
Battery mode occurs in event of an extreme input voltage condition
or complete mains failure. The battery system supplies power
through the DC to DC converter to the inverter to generate power
for the connected load. During battery mode an alarm sounds
every 10 seconds. This will change to two beeps every 5 seconds
when the battery runs low (approximately 2 minutes remaining,
but this is user configurable). The AC Input LED will extinguish,
and the Battery LED will illuminate to warn that a mains problem
has occurred. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 12.0 - Troubleshooting. For approximate battery
run times, refer to Table 6. These times are approximate, based on resistive load and an ambient
temperature of 25°C (77°F). To increase this time, turn off non-essential pieces of equipment (such as
idle computers and monitors) or add the optional external battery cabinet.
Operating Instructions
BATTERY UPS ON BYPASSAC I NPUT
Normal Mode Operation
Batteries at 100% Charge
Load at 10%
Battery Mode Operation
Batteries at 30% Charge
Load at 50%
CAUTION
!
Turning OFF the UPS while in it is battery mode will cut off output power.
9.3Bypass Mode Operation
Bypass mode occurs when the OFF button is pressed once while
the UPS is in Normal Mode. During bypass operation, mains
power provides energy to the UPS. The mains power bypasses the
inverter and provides power for the connected load.
The four green load level LEDs indicate an approximate level of
load in 25% increments. If the UPS becomes loaded beyond full
rating, the fifth (amber) LED indicator will illuminate and the
UPS will sound an audible alarm. The display template indicates
the percentage of load (26-50% of load shown in the example above) on the UPS output.
9.4Battery Recharge Mode
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger
begins recharging.
UPS ON BYPASS
20
10.0 COMMUNICATIONS
r
10.1Communications Interface Port
The UPStation GXT2 UPS has a standard DB-9 serial port female connector located on the rear of the
UPS unit. Several signals are provided on this port and are assigned as follows:
6Remote Shutdown (short to pin 5); all modes of operation
7Low Battery (open emitter)
8Mains Fail (open emitter)
9Mains Fail (open collector)
Communications
Pin Assignment Collector to Emitter*
6789
54321
* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA
10.2Pin 4 - Remote Shutdown on Battery
1. 1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the
mains, Pin 4 will ignore any signal on this pin.
2. 2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using
Liebert's contact closure cable. It cannot be used with just a contact closure unless the relay is
used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal
a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown
signal for 1.5 seconds, the command cannot be canceled.
3. 3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown
signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the
UPS will shut down.
4. 4. If the mains returns during the 2-minute timer countdown, the shutdown timer will continue
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least
10 seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and
restart the server.
330 Ohms
(+)
(-)
Open
Collecto
Open
Emitter
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled
or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown
delay.
21
10.3UPS Intelligent Communications
The UPStation GXT2 is equipped with two Intellislot® ports to provide advanced communication and
monitoring options.
The Intellislot port closer to the corner of the UPS chassis is the serial card slot. This Intellislot port is
used for the OCWEBCARD and the USBCARD. The other Intellislot port is used for
RELAYCARD-INT or the MULTIPORT Card.
Liebert’s OCWEBCARD
Communications
DB9 (RS232) port
covered
NOTE
The OCWEBCARD DB9 serial port cable should be used only for the initial card setup. Remove
the cable after setup is complete.
When the DB9 OCWEBCARD serial port cable is removed, the OCWEBCARD DB9 connector
needs to be covered. The DB9 cover is included with the UPS.
Liebert's MultiLink software continually monitors the UPS and can shut down your computer or
server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the
network with other computers running MultiLink when you purchase a MultiLink License Kit. For
more information about the Intellislot SNMP/Web Card and MultiLink license Kits, visit our Web site
(www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT2. The Intellislot
SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coordinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built-in shutdown for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be segregated and run separate from all other power cables, where applicable.
22
10.4Remote Emergency Power Off
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply
with national and local wiring codes and regulations.
REPO switch connection diagram
UPS ships with REPO jumper
installed allowing the UPS
to operate
Communications
Opening the REPO connection will disable the UPS.
Manual restart using the front panel is required after
the REPO connection is closed again.
12
Normally closed switch system
(fail-safe)
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be segregated and run separately from power cables.
12
23
11.0MAINTENANCE
11.1Internal Battery
The UPStation GXT2 requires very little maintenance. The batteries are valve-regulated, non-spillable, flame retardant, lead acid, and should be kept charged to obtain their designed life. The UPS
continuously charges the batteries when connected to the mains supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries periodically will result in permanent degradation of battery capacity.
UPStation GXT
- +
AC INPUT
Maintenance
!
BATTERY UPS ON BYPASS
The UPStation GXT2 is designed to allow the user to safely replace the internal batteries. Read the
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the
appropriate replacement battery kit part number and pricing.
24
11.1.1 Internal Battery Replacement
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. Observe the
following precautions before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (cross-head) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
Maintenance
1. Remove the 3U battery access panel on the front of
the UPS by loosening the two captive screws
located between the bezels (see illustration at
right).
2. Once the captive screws are loosened, tip the panel
forward and lift to remove it from the main
cabinet.
3. Use a Phillips (cross-head) screwdriver to remove
the screw in the battery retaining bracket on each
battery pack (see illustration at right). Remove the
retaining brackets.
4. Disconnect the battery connectors in the front of
each battery pack.
5. Lift the internal connector out of the way and slide
the battery out of the UPS. Support the weight of
the battery to prevent it from falling.
6. Unpack the new battery assembly, taking care not
to destroy the packing. Compare new and old
battery assemblies to make sure they are the
same. If so, proceed with Step 7; otherwise STOP
and contact your local dealer, Liebert
representative or the Liebert Worldwide Support
Group.
7. Line up and slide in the new replacement battery
pack while holding the internal connector out of
the way.
8. Reconnect the electrical connections for each
battery pack.
9. Install the battery retaining brackets using the
Phillips removed earlier.
10. Install the battery access panel and tighten the
captive screws.
Battery Door Captive Screws
!
3U Battery Access Door and
UPStation GXT
- +
Battery Bezel
AC INPUT
BATTERYUPS ONBYPASS
Retaining screw
!
UPStation GXT
AC OUTPUT BATTERY UPS ON BYPASS
Retaining bracket
!
UPStation GXT
- +
AC INPUT
BATTERY UPS ON BYPASS
NOTE
These are hot-swappable replacement
batteries. However, caution should be
exercised because during this procedure the
load is unprotected from disturbances and
power outages.
25
Battery Connectors
11.2AC Power Connections
Power connections may be disconnected from the UPS cabinet via a removable distribution box. This
may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows
power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to
the UPS to describe these procedures.
Hardwire and Hardwire/Receptacle boxes that include a Manual Bypass Switch allow AC power to
continue to flow from the mains input to the load while the box is removed from the UPS.
11.2.1 PD-CEHDWR—Manual Bypass Switch Available
Disconnect
1. DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect
all power to the load.
2. Ensure that the Maintenance Bypass Lamp is ON.
3. Switch to the maintenance bypass position.
The Load is now unprotected from line disturbances or interruptions.
4. Turn off the UPS using the front panel controls.
a. If needed, push the OFF button for one second once to transfer the load to bypass.
b. Press the OFF button twice within four seconds to turn the UPS off.
5. Turn off the UPS input circuit breaker on the box at the rear of the UPS.
This input circuit breaker only cuts power to the connector between the box and UPS. The input
circuit breaker does not cut power to the manual bypass switch.
6. Turn off the output circuit breaker on the rear of the UPS.
7. Remove the distribution box from the UPS
a. Loosen all three captive screws until box releases.
b. Pull box away from the UPS and set the box aside on a padded surface.
Maintenance
CAUTION
!
Power is still passing through the box from mains to the load.
Reconnect
1. Align connectors and press the box onto the rear of the UPS.
2. 2. Hold the box firmly against the UPS and tighten the captive screws. Do not overtighten.
3. If the Mains branch circuit breaker and load is off, turn the branch breaker on now.
4. Turn on the output circuit breaker on the rear of the UPS.
5. Turn on the input circuit breaker on the box.
6. Start the UPS according to the startup instructions.
Press the ON button for one second.
7. Confirm that the UPS AVAILABLE lamp is lit beside the manual bypass switch.
8. Turn the manual bypass switch to the UPS position.
9. The UPS now protects the load.
26
12.0 TROUBLESHOOTING
AC I NP UT
The information below indicates various symptoms a user may encounter in the event the UPStation
GXT2 develops a problem. Use this information to determine whether external factors caused the
problem and how to remedy the situation.
1. 1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. 2. An alarm will sound, alerting that the UPS requires attention.
3. 3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic
aid to the operator, as described below:
Table 3Indicator meanings
Troubleshooting
Fault
Example shows UPS
on bypass because
of output overload,
signified by amber
load indicator.
LED statusDiagnosis/Audible alarm
All LEDsOn bypass due to output overload; beep every half-second
A LEDOn bypass due to overtemperature condition; beep every 4 sec.
B LEDOn bypass due to DC bus overvoltage; beep every 4 sec.
C LEDDC-DC failure during battery mode; beep every 4 sec.
D LEDOn bypass due to PFC failure; beep every 4 sec.
E LEDOn bypass due to inverter failure; beep every 4 sec.
A&C LEDsUPS failed battery test; long beep every minute
C&E LEDsUPS shutdown due to command from communication port (SNMP); no beep
Battery LED Flashing
A&E LEDsFan locked
B&CREPO active. UPS cannot run with REPO loop open.
B&DUPS is OFF due to previous REPO shutdown. Autorestart disabled.
D&ECharger Malfunction
Internal Battery source not available (continuous horn). Check Battery connection,
completely power down and reboot UPS.
Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is
operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Support Group. Please have the UPS model number and serial number available at the time of
your inquiry.
27
Table 4Troubleshooting guide
Problem
UPS fails to start when the
ON button is pressed.
Battery indicator LED is
illuminated.
UPS has reduced battery
time.
Fault and Bypass indicator
LEDs and all load level LEDs
are illuminated.
Fault and Bypass indicator
LEDs and diagnostic LED A
are illuminated.
Fault and Bypass indicator
LEDs and diagnostic LED B
are illuminated.
Fault indicator LED and
diagnostic LED C are
illuminated.
Fault and Bypass indicator
LEDs and diagnostic LED D
are illuminated.
Fault and Bypass indicator
LEDs and diagnostic LED E
are illuminated.
Fault indicator LED and
diagnostic LEDs A and C are
illuminated.
Fault and Bypass indicator
LEDs and diagnostic LED C
and E are illuminated.
Fault and LEDs A&E are
Illuminated
Fault and LEDs B&C are
Illuminated
Fault and LEDs B&D are
Illuminated
CauseSolution
UPS is short-circuited or
overloaded.
UPS not plugged in.
UPS input protection fuse
has blown/opened.
Mains voltage out of UPS
input range.
Batteries are not fully
charged.
UPS is overloaded.Check load level display and reduce the load on the UPS.
Batteries may not be able to
hold a full charge due to age.
UPS overloaded or load
equipment is faulty.
UPS internal fan has a
problem or UPS shutdown
due to temperature condition.
Load is on bypass power.
UPS internal DC bus
overvoltage.
DC-DC failure during battery
mode.
UPS PFC (Power Factor
Correction Circuit) fault.
UPS inverter fault.
UPS failed the battery test.
UPS shutdown due to a
command from the
communications port(s).
Fan locked
REPO active
UPS is OFF due to previous
REPO shutdown, but the
REPO has been connected
or reset. Autorestart
disabled.
Troubleshooting
Ensure UPS is OFF. Disconnect all loads and ensure nothing is
lodged in output receptacles.
Ensure loads are not defective or shorted internally.
UPS is operating from battery mode, make certain UPS is
securely plugged into the wall receptacle.
UPS is operating from battery mode. Save data and close
applications. Replace UPS input fuse, then restart UPS.
UPS is operating from battery mode. Save data and close
applications. Ensure mains supply voltage is within acceptable
limits for UPS.
Keep UPS plugged in continuously at least 24 hours to
recharge batteries.
Replace batteries. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group for
replacement battery kit.
Check load level display and remove non-essential loads.
Recalculate the load and reduce number of loads connected to
UPS. Check load equipment for faults.
Ensure UPS is not overloaded, ventilation openings not
blocked, or room ambient temperature is not excessive. Wait
30 minutes to allow UPS to cool, then restart UPS. If UPS does
not restart, contact your local dealer, Liebert representative or
the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
Bus voltage under 315VDC(O/P 220VAC) / 330VDC(O/P
230VAC) / 345VDC(O/P 240VAC). UPS requires service.
Contact your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
Representative or the Liebert Worldwide Support Group.
Replace batteries. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
Your UPS has received a signal or command from the attached
computer. If this was inadvertent, ensure the communication
cable used is correct for your system. For assistance, contact
your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
Check for external obstruction entering fan guard. UPS
requires service. Contact your local dealer, Liebert
representative or Liebert Worldwide Support Group.
circuit is closed. If not used, a wire jumper must connect the
REPO terminals.
Start the UPS using the front panel.
28
Troubleshooting
Table 4Troubleshooting guide (cont’d)
Problem
Fault and LEDs D&E are
Illuminated
Battery LED is flashing.
CauseSolution
If the charger is overvoltage, the UPS will shutdown. If the
Charger malfunction
Battery source is not
available; continuous horn.
charger is undervoltage and the batteries are nearly depleted,
this alarm will give a temporary warning before the UPS shuts
down. UPS requires service. Contact your local dealer, Liebert
representative or Liebert Worldwide Support Group.
Check battery connections, completely power down and restart
UPS.
NOTE: If the battery circuit
opens while the UPS is running,
it will be detected when the next
battery test is performed.
Table 5Alarm conditions
ConditionAlarm
Battery Mode (mains failure)One short beep every 10 seconds: more than 2 minutes of run time remaining
Low BatteryTwo short beeps every 5 seconds: less than 2 minutes of run time remaining
Output Overload (Bypass)One short beep every half second
Overtemperature (Bypass)A one-second beep every 4 seconds
DC Bus Overvoltage (Bypass)A one-second beep every 4 seconds
DC-DC failure during battery
mode
PFC Failure (Bypass)A one-second beep every 4 seconds
Inverter FailureA one-second beep every 4 seconds
Battery Test FailureA two-second beep every 1 minute
Fan LockedA one-second beep every 4 seconds
REPO ActiveA 0.25-second beep every 0.25 seconds
UPS OFF; Autorestart disabled
from previous REPO shutdown
Charger MalfunctionA one-second beep every 4 seconds
Using the configuration program, the user may specify the number of GXT2-240VBATT external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 6 above shows the estimated run times at different loads.
30
12.0.1 Auto-Learning Battery Run Times
As batteries age, the estimated runtimes may become less accurate. The GXT2 is programmed to
“learn” from a full battery discharge and modify the estimated runtime for the measured battery
capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at
different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery above table will be restored. This will override any value that is Auto-Learned.
Troubleshooting
31
13.0 SPECIFICATIONS
Table 7UPS specifications
Model NumberGXT2-6000RT230GXT2-4500RT230
Dimensions mm (in.)
Shipping, W x D x H560 x 690 x 500 (22.05 x 27.17 x 19.7)
Weight kg (lbs)
Input AC Parameters
Nominal Operating Frequency50 or 60Hz (Factory Default = 50)
Factory Default VAC230VAC
User Configurable VAC
Operating Voltage Range Without
Battery Operation
Maximum Allowable VAC276VAC
Input Frequency Without Battery
Input Power ConnectionPD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Output AC Parameters
Factory Default VAC230VAC
Output ConnectionsPD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Battery Parameters
Battery Mfr. / Part #Yuasa / REW 28-12
Recharge Time (Internal Batteries)3 hrs. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass operationIf input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operationIf input voltage returns to within ±10% of nominal output voltage
Disable Bypass operationWhen the input frequency prevents synchronous operation
Environmental
Operating Temperature0°C to +40°C (+32°F to +104° F)
Storage Temperature-15°C to +50°C (+5°F to +122° F)
Relative Humidity0-95% non-condensing
Operating Elevation
Storage Elevation
Agency
EMI/EMC/C-Tick EMCEN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive
Radiated SusceptibilityEN61000-4-3, Level 3, Criteria A
Electrical Fast TransientEN61000-4-4, Level 4, Criteria A
Model Rating6KVA / 4,200W4.5KVA / 3,150W
Unit, W x D x H221 x 547 x 430 (8.7 x 21.5 x 16.9)
Unit67 (151)67 (151)
Shipping79.5 (175.3)79.5 (175.3)
(May be modified using configuration program)
Operation
Frequency50Hz or 60Hz, Nominal
WaveformSinewave
Main Mode
Overload
TypeValve-regulated, non-spillable, lead acid
Quantity x V20 x 12V
Back-up TimeSee Table 6 - Battery run times
Audible Noise
SafetyEN62040-1-1; TUV/GS
ESDEN61000-4-2, Level 4, Criteria A
Surge ImmunityEN61000-4-5, Level 3, Criteria A
TransportationISTA Procedure 1B
>200% for 96 milliseconds; 131 - 199% for 2 seconds;
112- 129% for 10 seconds with transfer to bypass
Up to 2000m (6600 ft) at 40°C (104° F) without derating
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
220/230/240VAC
176 – 276VAC
40 - 70Hz
15,000m (50,000 ft.) maximum
Specifications
32
Table 8Power distribution specifications
Model NumberPD-CEHDWRPD-CEHDWRBYP
Amps Rating32 Amps
2
Input Power Connection3-Wire Hardwired, 6-10mm
Output Power Connection3-Wire Hardwired, 6-10mm
Includes: Two IEC320 C19 16A/250V sockets
Manual Bypass Switch with Indicator Lamps
(8-10AWG)
2
(8-10AWG)
Two IEC320 C19 16A/250V sockets
Input Branch Circuit Breaker32A, Supplied by User
Table 9External battery cabinet specifications
Model NumberGXT2-240VBATT
Used w/ UPS modelGXT2-6000RT230, GXT2-4500RT230
Dimensions, W x D x H, mm (in.)
Unit (with bezel)176 x 522 x 430 (6.9 x 20.55 x 16.9)
Shipping560 x 690 x 455 (22 x 27.2 x 17.9)
Weight, kg (lbs)
Unit65 (145)
Shipping78.5 (173.1)
Battery Parameters
TypeValve-regulated, non-spillable, flame retardant, lead acid
Qty x V20 x 12V
Battery Manufacturer, Part #Yuasa / REW 45-12
Backup TimeSee Battery Run Times charts
Environmental
Operating Temp0°C to +40°C (+32°F to +104° F)
Storage Temp-15°C to +50°C (+5°F to +122° F)
Relative Humidity0-95% non-condensing
Operating ElevationUp to 2000m (6600 ft.) at 40°C (104° F) without derating
Storage Elevation15,000m (50,000 ft.) maximum
Agency
SafetyEN62040-1-1; TUV/GS
TransportationISTA Procedure 1B
Specifications
33
Specifications
34
POWER AVAILABILITY
GXT2-6000RT230™ & GXT2-4500RT230
USER MANUAL
The Company Behind the Products
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
•Environmental systems—close-control air
conditioning from 1 to 60 tons
•Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
•Integrated systems that provide both
environmental and power protection in a
single, flexible package
•Monitoring and control—from systems of any
size or location, on-site or remote
•Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SLI-23170 (7/04) Rev. 3
Technical Support/Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@liebert.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
™
Italy
Asia
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.