Liebert GXT2-6000 RT208 User Manual

Page 1
POWER AVAILABILITY
GXT2-6000RT208
USER MANUAL
120/208V 120/240V
Page 2
Page 3
TABLE OF CONTENTS
1.0 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.0 I
3.0 S
3.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 5
3.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.5 DC to DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.7 Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
NTRODUCTION AND SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
YSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.0 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.1 Main Frame and Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Internal Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.0 WHATS INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
6.0 INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
6.1 Install the Main Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.1.1 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.3 Connect Input/Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.3.1 Replacing a power distribution box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.3.2 Distribution Box Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.3.3 PD-HDWR and PD-HDWR-MBS Terminal Block Connections. . . . . . . . . . . . . . . . . . . . . . . . 15
6.3.4 PD-001 Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4 Install the Grounding Electrode Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.5 Install the Internal Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.0 INITIAL STARTUP AND ELECTRICAL CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.1 L14-30P Plug-in Connections—Including the PD-001 Distribution Box . . . . . . . . . . . . . . . 18
i
Page 4
8.0 CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.1 GXT2-6000RT208 Configuration Program Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.1.1 What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2 Configuration Program—Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.3 Establishing Communication Link with the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.4 Configuration Program—Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.4.1 Read/Confirm UPS Configuration Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.4.2 Changing UPS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.4.3 Programming Rejected? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.4.4 Exit Without Changing UPS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.5 UPS Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.5.1 Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.5.2 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.5.3 L-N Reverse Detection (120V UPS Models Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.5.4 Frequency Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.6 Options Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.7 Options Tab Used With Earlier GXT 2U Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.8 Battery Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.8.1 Low Battery Time Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.8.2 Auto Battery Test Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.8.3 Battery Cabinets Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.8.4 Auto Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.9 About Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.0 CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
9.1 ON/Alarm Silence/Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.2 OFF/Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.3 L1 & L2 Load Level Indicators (Two Rows of Indicators: 4 Green, 1 Amber). . . . . . . . . . . . 29
9.4 Battery Level Indicators (5 Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.5 Fault Indicator (Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.6 Bypass Indicator (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.7 UPS ON Indicator (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.8 Battery Indicator (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.9 AC Input Indicator (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ii
Page 5
10.0 MODES OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
10.1 Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.2 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.3 Battery Recharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.1 Communications Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.1.1 DB-9 Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.1.2 Communications SNMP Web Card SNMP Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.2 Pin 4 - Remote Shutdown on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.3 UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.4 Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
12.1 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
12.1.1 Internal Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
12.2 UPS Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
13.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
13.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
14.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
14.1 Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
iii
Page 6
FIGURES
Figure 1 6 kVA Dual Inverter GXT 2U (front and rear views) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 2 Support base and spacers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 3 30A branch circuit breaker connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 4 Factory default settings for 120VAC UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 5 REPO switch connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
TABLES
Table 1 Electrical requirements—PD-HDWR and PD-HDWR-MBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 2 Electrical requirements—PD-001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 3 DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 4 Fault indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 5 Alarm conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 6 Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 7 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 8 UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 9 Battery specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 10 Power distribution box specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 11 External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
iv
Page 7

IMPORTANT SAFETY INSTRUCTIONS

WARNING
!
Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, installation and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Individuals without previous training can install and operate this equipment.
It is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230, 120/208, 120/240 or 127/220 VAC, 50 Hz or 60 Hz supply. The factory default setting is 120/208 VAC, 60 Hz. Installation instructions and warning notices are located in this manual.
This UPS is only for use with a four-wire input (L1, L2, N, G).
This UPS MAY NOT be used with a three-wire, single-phase utility source (L1, N, G).
ELECTROMAGNETIC COMPATIBILITY—The GXT2-6000RT208 Series complies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation. Operat­ing this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F (0°C to +40°C). Install it in a clean environment, free from conductive contaminants, moisture, flam­mable liquids, gases and corrosive substances.
This UPS contains no user serviceable parts except the internal battery pack. The Off/Bypass push button does not electrically isolate internal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. PROPER DIS­POSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other openings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any other appli­ance using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
1
Page 8
When replacing batteries, replace with the same Liebert authorized replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
2
Page 9

1.0 GLOSSARY OF SYMBOLS

Risk of electrical shock
Glossary of Symbols
!
R
i
-
PbH2SO4
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
3
Page 10

2.0 INTRODUCTION AND SYSTEM DESCRIPTION

Congratulations on your choice of the Liebert UPStation GXT2-6000RT208 Uninterruptible Power Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equip­ment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes or complete power failure that may interrupt computer operations, cause data loss or even damage equipment. The UPStation GXT2-6000RT208 protects equipment from these disturbances.
The UPStation GXT2-6000RT208 is a compact, on-line UPS. An on-line UPS continuously conditions and regulates its output voltage whether utility power is present or not. It supplies connected equip­ment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT2-6000RT208 features a light-emitting diode (LED) display to indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combina­tion ON/Alarm Silence/Battery Test button, a Standby button, user configurable program and two levels of alarms when the unit is operating on battery.
The UPStation GXT2-6000RT208 has an interface port for communication between the UPS and a network server or other computer systems. This port provides detailed operating information includ­ing voltages, currents and alarm status to the host system when used in conjunction with Liebert’s MultiLink™ software. MultiLink software can also control UPS operation remotely.
Introduction and System Description
4
Page 11

3.0 SYSTEM DESCRIPTION

System Description
Input Output
L1
L2
N
G G
TVSS & EMI/RFI
Filters
Rectifier
/PFC
Battery
Charger
Dynamic
Bypass
DC to DC
Converter
Battery
Inverter
L1
L2
N

3.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters

These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the util­ity line and keep the sensitive equipment protected.

3.2 Rectifier/Power Factor Correction (PFC) Circuit

In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The utility power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT2-6000RT208.

3.3 Inverter

In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter receives energy from the battery through the DC to DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.

3.4 Battery Charger

The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the UPStation GXT2-6000RT208 is plugged in, even when the UPS is not turned on.
5
Page 12

3.5 DC to DC Converter

The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti­mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti­mum efficiency and voltage, thus increasing reliability.

3.6 Battery

The UPStation GXT2-6000RT208 utilizes valve-regulated, nonspillable, flame retardant, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional external battery cabinets are available to extend battery run times.

3.7 Dynamic Bypass

The UPStation GXT2-6000RT208 provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator (other indicators may be illu­minated to indicate the diagnosed problem).
The user may manually transfer the connected load from the inverter to bypass by pressing the Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances on the utility supply.
System Description
6
Page 13

4.0 MAJOR COMPONENTS

The GXT2-6000RT208 is composed of three major assemblies to provide easier handling, installation and versatility.

4.1 Main Frame and Electronics

This 4U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The UPS is shipped with a basic hardwire distribution box.

Figure 1 6 kVA Dual Inverter GXT 2U (front and rear views)

Major Components
Status Indicators and Controls
Front Bezels (2)
!
UPStation GXT
Battery Compartment (behind bezel); Internal Battery Pack is shipped loose (see Section 4.2)
Output
Circuit
Breaker
External Battery Connector
Hardwire Knockouts
Support Base
REAR VIEWFRONT VIEW
Intellislot
®
Port
DB-9 Communications Port
Cooling Fan (1 of 4)
+
--
Grounding Electrode
+
Conductor
REPO Switch
Input Circuit Breaker
Power Distribution Box Standard Module (See Section 4.3)

4.2 Internal Battery Pack

The front bezels may be pulled forward and removed to reveal the battery access door. The internal battery pack is a compact assembly ready to slide into the battery compartment after the front battery access door has been opened. Electrical connection is automatic upon insertion.
(144V)
12Vx12
9Ahi45W
-
!
+
:
T
N
E
M
E
S
IS
T
R
E
V
A
:
IA
!
C
N
E
T
R
E
V
D
A
:
!
G
IN
N
R
A
W
:
G
IN
N
R
A
W
7
Page 14

4.3 Removable Power Distribution Box

The UPS is shipped with a basic hardwire power distribution pack installed. For maximum flexibility, this may be easily replaced with either of two optional power distribution boxes that provide the ben­efits of hardwire input and output plus manual bypass switch or plug/receptacle convenience with manual bypass switch.
Power Distribution Box With
Hardwire Connections
(Standard - Ships With UPS)
DISCONNECT BYPASS POWER TO
THE MANUAL BYPASS SWITCH.
PD-HDWR
Major Components
PD-HDWR-MBS
Power Distribution Box
With Hardwire Connections
and Manual Bypass Switch
(Optional)
PD-001
Power Distribution Box
With Wired Connections
and Manual Bypass Switch
(Optional)
8
Page 15

5.0 WHATS INCLUDED

The GXT2-6000RT208 is shipped with the following items:
• GXT2-6000RT208 user manual
• Vertical display overlay
• Front bezels - 2
• Top bezels - 2
• Battery cover grille
• MultiLink software CD
• MultiLink serial cable, 10 ft (3m)
• Rack mount handles
• Support base - 2
• GEC ring connector
• Mounting hardware
• Configuration program disk
• Ferrite beads (2)
What’s Included
L1
!
- +
UPStation GXT
Vertical display overlay
Support base
L2
S
S
A
P
Y
B
N
O
S
P
U
Y
R
E
T
T
A
B
T
U
P
IN
C
A
with spacers
!
Front bezels
MultiLink
software CD
GEC connector
Top bezels (tower use)
MultiLink
serial cable
10 ft (3m)
Mounting hardware
Battery cover grille
Rack mount
handles
www.liebert.com
GXT 2U™ Configuration Program
For use with LiebertGXT 2U model UPS systems Versi on 1. 6 For Windows 95/98/NT To Install: Choose the Start button on the Taskbar and select Run
Configuration
disk
Ferrite
beads (2)
9
Page 16

6.0 INSTALLATION AND CONFIGURATION

This section includes instructions on how to install, configure and perform initial electrical checks of your UPS installation.
DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 7.0 - Initial Startup and Electrical Checks.
Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see 14.0 - Specifications). Take proper precautions when lifting or moving it.
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, cor­rosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.
Installation and Configuration

6.1 Install the Main Cabinet

The GXT2-6000RT208 may be installed either as a tower unit or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instruc­tions in either 6.1.1 - Tower UPS Installation or 6.1.2 - Installing the Adjustable Rack-Mount Kit—Sold Separately.

6.1.1 Tower UPS Installation

When using the GXT2-6000RT208 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS.
If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).
Figure 2 Support base and spacers
End Bases
4U Support Base
2U Spacer
Spacers added to support
base to accommodate
additional battery cabinets
Attach Bezels to Top
When used as a tower, the GXT2-6000RT208 requires bezels attached to the top. To connect the bezels:
1. Position the UPS so that the battery compartment is on the bottom.
2. Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.
10
Page 17

6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately

This kit contains parts needed to mount several different models of UPS and external battery cabi­nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per pair of adjustable rack-mounting brackets is 200 pounds (91 kg).
Parts included are:
Item Quantity
Rear bracket members 2
Front bracket members 2
Inner bracket members 2
M4 x 8mm machine screws 16
M4 locking hex nuts 8
M5 x 16 mm machine screws 12
Grease packet. 1
Tools needed for installation are:
• one Phillips screwdriver
• one 7mm wrench
The adjustable rack-mounting brackets feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack.
Installation and Configuration
To install the rack mount brackets:
1. Unpack two (2) rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are interchangeable between left-hand or right-hand.
Remove inner member of each bracket assembly as shown in at right by extending it to its outermost position, depressing the retaining latch and then pulling the inner member out of the bracket assembly.
2. Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet.
CAUTION
!
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.
3. Install the rear member of each bracket assembly into rack enclosure with two (2) M5 screws provided in this kit (see figure at right). The return flanges on the bracket assembly fit to the inside of rack mounting rails. Insert screws loosely (finger-tight) into the top and bottom holes of the return flange on the rear member. Extend the bracket assembly by sliding the front member forward until it touches the front rack mounting rail. Insert two (2) M5 screws loosely (finger­tight) into top and bottom holes of the return flange on each front member. Make sure bracket assemblies are at the same mounting height on all four (4) rack mounting rails.
Retaining Latches
Inner members
Front rack mounting rails
M5 screws
Return flanges
Front members
M5 screws
Rear rack mounting rails
11
Page 18
Installation and Configuration
4. Get eight (8) M4 screws and eight (8) M4 nuts from the hardware pack in this kit. Each nut has a locking, nylon
M4 nuts
M4 screws
insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action.Fasten the rear member and the front member together using (4) screws and (4) nuts per bracket assembly as shown in at right. For maximum support, insert fasteners for each bracket assembly as far apart as possible, depending on rack depth, while still joining both members (see figures at right). Check alignment of bracket assemblies
18" rack depth
M4 nuts
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.
5. Prepare the UPS or battery cabinet (the “equipment”) for rack mounting by following instructions in the equipment’s
M4 nuts
M4 screws
user manual. The equipment may require additional parts to be added or parts to be removed for rack mounting. After it is prepared, lay the equipment in rack-mounting position. Fasten the inner members from Step 1 to the equipment on both sides as shown at right with eight (8) M4 screws provided in the kit. Make sure retaining latch is near the rear
32" rack depth
M4 nuts
of the equipment as shown (see figure at right).
6. Open the grease packet provided in the kit. Apply a 1" long
M4 screws
Retaining latch
bead of grease at four (4) places inside the bottom, curved tracks of the front members as shown below right. The grease will allow the equipment to slide into the bracket assemblies more easily.
CAUTION
!
6.
Lifting equipment into the rack may be a two-person job, depending on the weight of the equipment. See equipment’s user manual.)
Front
UPS or battery cabinet
7. Insert the equipment, with inner members attached in Step 5, into the bracket assemblies by inserting the top and
M4 screws
bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the equipment into the rack (see figure at right). Ends of inner members are tapered to allow the rear of the equipment to be angled upward before insertion, if space allows.
Then the rear, bottom edges of the inner members can be
UPS or battery cabinet
Apply grease
placed into the front edge of the bottom tracks and the front of the equipment can be tipped up so they are level to insert the top edges of the inner members before sliding the equip­ment into the rack (see figure below right). The equipment should move smoothly into the bracket assemblies. If it does
Apply grease (inside)
not, recheck the alignment of the front and rear members from Steps 2 and 3.
8. Secure the front of the equipment to the rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on the front of the equipment
... and push it into the rack.
that align with the center holes on the return flange of the front members, you can use the four (4) extra M5 screws provided in the kit to secure the equipment. Otherwise, the equipment should be secured to the front of the rack with four (4) customer-supplied fasteners.
Insert the UPS into the front members, lift the front .. .
12
Page 19

6.2 External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS.
CAUTION
!
The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.
CAUTION
!
Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the battery cabinet at this time. When installation is complete, you will be instructed to turn on the circuit breaker.
When the external battery cabinet is received, it should be inspected for freight damage. Report dam­age to the carrier and your local dealer or Liebert representative.
To install an external battery cabinet:
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up. Optional rack-mount handles are shipped with the external battery cabinet and may be installed now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed.)
2. Fasten the slides into position with the screws according to the instructions included with the slide rails.
3. Use the enclosed support bases for the tower option to prevent the assembly from tipping over. One additional set of support base extensions ships with each external battery cabinet.
4. Connect the supplied external battery cabinet cable to either of the connectors on the rear of the external battery cabinet, then to the rear of the UPS.
5. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 7 - Battery run times in this manual.
6. Do NOT turn on the battery cabinet circuit breaker at this time. Please complete the remainder of the installation first.
Installation and Configuration
Support Base With Spacers for External Battery Cabinets
NOTE
After installation is complete, you must use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for using the configuration program follow in 8.0 - Configuration Program.
13
+
--
+
UPS and Four External Battery
Cabinets With Support Base
Page 20

6.3 Connect Input/Output Power

The UPS ships with the basic hardwire box attached. If an optional model is to be used, remove the standard box and install the optional box using the three captive mounting screws marked in the illustration, below, right.

6.3.1 Replacing a power distribution box

Whenever a power distribution box is not attached to a UPS, the cover must be slid over the electrical connectors to prevent damage or injury.
Installation and Configuration
Slide cover over connec­tors
1. On the power distribution box attached to the UPS, locate the three captive mounting screws holding the box to the UPS (see illustration above, right).
2. Turn the screws until the box can be pulled away from the UPS. Exercise care to avoid removing screws from the hardwire box.
3. On the replacement power distribution box to be attached to the UPS, loosen the cover over the electrical connectors by backing out the three screws one turn each.
4. Slide the cover open to expose the electrical connectors.
5. Gently retighten the three screws loosened in Step 3.
6. Align the connectors on the box and UPS.
7. Push the box into place.
8. Holding the box firmly against the UPS, tighten the three captive mounting screws until the box is secure. Do not overtighten.

6.3.2 Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.
The installer must provide a 30A branch circuit breaker. The input circuit breaker on the distribution box and the output circuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and the distribution box.
Loosen screws to move cover
Mounting screws
for removable box
DISCONNECT BYPASS POWER TO
THE MANUAL BYPASS SWITCH.
Models equipped with a manual bypass switch pass utility power directly to the bypass switch from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass switch.
Figure 3 30A branch circuit breaker connection diagram
PD-HDWR Distribution Box PD-HDWR-MBS Distribution Box
Breaker
Input
Output
30A Input Circuit Breaker
30A UPS Output Circuit Breaker
UPS - PFC, Battery, Inverter UPS - PFC, Battery, Inverter
14
Utility Utility
30A External
Branch Circuit
Input
30A External
Branch Circuit
Breaker
30A Input Circuit Breaker
30A UPS Output Circuit Breaker
Byp
Output
Inv
Page 21

6.3.3 PD-HDWR and PD-HDWR-MBS Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit.
Table 1 Electrical requirements—PD-HDWR and PD-HDWR-MBS
Input Current
Rating
24A 30A 10 AWG 8 AWG 20 in-lb
Recommended (Max.)
External Overcurrent
Protection
Recommended Wire
(including ground wire)
(75°C copper wire)
The standard PD-HDWR comes installed on the UPS. The PD-HDWR-MBS with manual bypass switch is optionally available. Both have the same hardwire terminal connections.
Maximum Wire
Accepted by
Terminal Block
Installation and Configuration
Terminal
Tightening
Torque
NL2L1
OUTPUT INPUT
8-10 AWG - USE COPPER WIRE ONLY - 20 in-lb - Strip 7mm
NL2L1
120 120
0
Output to Load - See Note 1
208 or 240
Input to UPS - See Note 2
NL2L1
30A Max. Branch
Overcurrent Protection
NL2L1
120 120
0
208 or 240
NOTE
1. The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.
2. The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.
For best performance, distribute all L-N loads evenly between L1 and L2.

6.3.4 PD-001 Power Distribution Box

An optional PD-001 is available to provide the conve­nience of an L14-30P input plug and output receptacles. To use this box, remove the original PD-HDWR hardwire box and install the PD-001.
Table 2 Electrical requirements—PD-001
Input Current
Rating
24A 30A NEMA L14-30R
Recommended (Max.)
External Overcurrent
Protection
Output
Receptacles
Manual Bypass
Switch
Required Utility
Receptacle
15
Page 22

6.4 Install the Grounding Electrode Conductor

A Grounding Electrode Conductor must be attached to the rear panel using the M5x12 Phillips screw provided. This connection is required in addition to the power input ground connection to the remov­able power distribution box.
Install an 8 AWG (10 mm 250-94) grounding electrode conductor to the nearest effectively grounded metal structural member, nearest effectively grounded metal water pipe or other grounding electrode in the grounding electrode system. If the grounding electrode conductor must be protected, non-metal conduit is recommended. If metal conduit must be used, bond both ends of the conduit to the grounding electrode conductor. Con­duit is not an acceptable grounding electrode conductor.
A 5mm ring lug for 8AWG wire lug is provided in the accessory box. Other suitable connectors may be used.
2
) (75°C copper wire) (minimum size, see NEC 250-5d, 250-81, 250-83, table
Installation and Configuration
GROUNDING ELECTRODE CONDUCTOR
+
NOTE
IN BATTERY MODE ONLY, the UPS operates as a separately derived source and contains a neutral to ground bonding jumper. A grounding electrode conductor (GEC) must be installed in accordance with national and local wiring codes and regulations.

6.5 Install the Internal Battery Pack

To facilitate shipping and installation, the GXT2-6000RT208 ships without the internal battery installed. Once the UPS is installed in place, the internal battery pack must be installed.
1. Unpack the internal battery from its shipping container.
2. Lift the battery pack from its container, holding it in the center of the pack. Do NOT lift the battery pack by grasping the connector on the rear.
3. Align the battery pack so that the rear connector is nearest the control panel.
4. Slide in the battery pack until fully inserted.
5. Install the battery door, tightening the two captive screws, finger tight. The battery door will not install if the battery is not fully inserted.
6. For tower installation, place the horizontal overlay over the controls and indicators (see illustration at right).
7. Install the two front bezels.
Ground Electrode System or Protective Earth System
+
Controls and Indicators
Screws for battery door
Battery Compartment
Liebert
V)
144 ( W 2
hi45
!
A 12Vx1 9
-
:
AVERTISSEMENT
+
ADVERTENCIA:
!
!
NING:
WAR
!
Battery
!
Battery cover
Front bezels
16
Back of battery
Battery connector
Page 23

7.0 INITIAL STARTUP AND ELECTRICAL CHECKS

Initial Startup and the Configuration Program—The UPS ships with a default 120 VAC L-N setting. This is also the most robust setting in that it can operate with either input phase angle (120 or 180 degrees). Perform initial system checks first. If the UPS configuration needs to be modified for your application, then go to the next section to review use of the configuration program. Some config­uration changes require that the UPS be in the OFF mode while powered from the utility. Therefore, the installer must confirm that the UPS input has been properly wired. After re-configuring your UPS, the UPS may be put into service with the intended loads.
Hardwire Input Connections (For L14-30P Plug-in Connections, skip to 7.1 - L14-30P Plug-in Con-
nections—Including the PD-001 Distribution Box.)
WARNING
!
Miswiring power to the input terminal block (L1-L2-N-G) or connecting to single phase voltages (L-N-G only) may damage the UPS.
1. Verify that the Input and Output circuit breakers are off.
2. During initial system checks, disconnect all loads (open load disconnects).
3. Inspect all wiring, cables and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets. Turn on the battery cabinet circuit breaker now.
5. If you are using a distribution box that includes a manual bypass switch, place the switch in BYPASS position.
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.
7. Using a voltmeter, verify the expected L1-N, L2-N and L1-L2 voltages. a. If no manual bypass switch is used, there will be no output voltage at this time. If a manual
bypass switch is used, verify that the same voltages appear at the Output terminals. If a manual bypass switch is used, the Bypass lamp will light by the switch. If no manual bypass switch is used, there will be no output voltage at this time.
b. If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the
input phase angle is required to be 180 degrees.
c. If the configuration program as been used to set the L-N voltage at 127 VAC, then the input
phase angle is required to be 120 degrees (leading or lagging).
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power, close all access panels to the distribution box and reapply input power.
9. Close the Input circuit breaker located on the distribution box. The green AC Input indicator should illuminate on the front panel.
10. Press the On button for 1 second. The Bypass indicator will light for several seconds before the UPS ON indicator turns on continuously. If the batteries are determined to charged above 80%, an automatic battery test will run for about 15 seconds.
11. Close the Output circuit breaker on the rear of the UPS. If a manual bypass switch is used, the UPS Available indicator by the switch will light. If a manual bypass switch is used, transfer the switch to the UPS position. The output terminal block will be powered at this time.
12. Perform a Manual Battery Test - Press the On button for one (1) second. The front Battery indicator will light for about 15 seconds and then return to only the UPS ON and AC Input indicators being illuminated.
13. Review all setting option provided by the configuration program. Some changes require that the UPS be OFF. If this is the case, these should be programmed before powering the loads. The configuration program is described in the next section.
14. Connect all loads for normal operation.
Initial Startup and Electrical Checks
17
Page 24
Initial Startup and Electrical Checks

7.1 L14-30P Plug-in Connections—Including the PD-001 Distribution Box

WARNING
!
Miswiring power to the input (L1-L2-N-G) or connecting to single phase voltages (L-N-G only) may damage the UPS. A qualified electrician should verify that the L14-30R is properly wired before attaching the UPS.
If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the input phase angle is required to be 180 degrees.
If the configuration program as been used to set the L-N voltage at 127 VAC, then the input phase angle is required to be 120 degrees (leading or lagging).
1. Verify that the input and output circuit breakers are off.
2. During initial system checks, unplug all loads (or open load disconnects).
3. Inspect all wiring, cables and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets. Turn on the battery cabinet circuit breaker.
5. If you are using a distribution box that includes a manual bypass switch, place the switch in BYPASS position.
6. Plug in the UPS input plug.
7. Turn on the branch circuit disconnect to apply voltage to the UPS input.
8. If no manual bypass switch is used, there will be no output voltage at this time. If a manual bypass switch is used, the Bypass lamp will light by the switch
9. Close the input circuit breaker located on the distribution box. The green Line lamp should illuminate on the front panel.
10. Press the Start button for 1 second. The Bypass lamp will light for several seconds before the Inverter lamp turn on continuously. If the batteries are determined to charged above 80%, an automatic battery test will run for about 15 seconds.
11. Close the output circuit breaker on the rear of the UPS. If a manual bypass switch is used, the Inverter lamp by the switch will light. If a manual bypass switch is used, transfer the switch to the Inverter position. The output terminal block will be powered at this time.
12. Perform a Manual Battery Test by pressing the ON button for 1 second. The front Battery lamp will light for about 15 seconds and then extinguish, leaving only the Inverter and Line lamps illuminated.
13. Review all setting option provided by the configuration program. Some changes require that the UPS be OFF. If this is the case, these should be programmed before powering the loads. The configuration program is described in the next section.
14. Connect all loads for normal operation.
18
Page 25

8.0 CONFIGURATION PROGRAM

The final step of installation may require custom configuration of your UPS using the enclosed config­uration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full time service powering the critical load.
For most users operating with 120 VAC L-N and with no external batteries, the factory default set­tings will be adequate. This manual illustrates the features available for modification, as well as the factory default setting.
The factory default L-N setting is 120 VAC. When first powered by the AC input, the UPS will auto­sense the utility phase angle between L1 and L2, setting the UPS to operate as either a 120/208 VAC system (120 degrees, leading or lagging) or a 120/240 VAC system (180 degrees).
If your application requires that the L1-N, L2-N voltages be set at 100, 110, 115 or 127 VAC, the cor­responding phase angle between L1 and L2 is restricted. The VAC settings of 100, 110 and 115 may work only with a phase angle of 180 degrees. A VAC setting of 127 VAC will work only with a phase angle of 120 degrees (leading or lagging).
To confirm the phase angle of the utility input, measure the L1-N, L2-N and L1-L2 VAC of the utility input that is intended for the UPS. If the measured L1-L2 voltage is equal to the average L-N voltage times 2.0, then the phase angle is 180 degrees and the L-N VAC may be set at 100, 110, 115 or 120 VAC. The nominal L1-L2 voltages for these four settings will be 200, 220, 230 or 240 VAC, respec­tively.
If the measured L1-L2 voltage is equal to the average L-N voltage times 1.73, then the phase angle is 120 degrees and the L-N VAC may be set at either 120 or 127 VAC. The nominal L1-L2 voltages for these two settings will be 208 or 220 VAC, respectively.
Configuration Program
Selecting a L-N nominal voltage that is not compatible with the L1-L2 phase angle detected by the UPS when AC input is applied will result in a fault alarm and the UPS will not operate from utility power.

8.1 GXT2-6000RT208 Configuration Program Features

The configuration program enables the user to perform the following functions:
• Select one of five L-N output voltages to match local voltages
• Enable or disable Auto-Restart
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz
• Set the Low Battery Warning alarm time from 2 to 30 minutes
• Enable or disable the Auto-Battery test
• Set the Auto-Battery test to 7, 14, 21 or 28 days
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert software products
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see 11.0 - Com- munications)

8.1.1 What You Will Need

In addition to the GXT2-6000RT208 UPS, you will need the configuration program diskette and serial cable (beige or tan, three-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A computer—desktop or laptop—running Windows 95 up and run the configuration program.
®
or later is also required to set
!
UPStation GXT
19
Page 26

8.2 Configuration Program—Installation

An easy-to-use installation program will streamline the installation of the configuration program. If you have a previous version of this configuration program installed, it is recommended that it be uninstalled using its Uninstall program before installing this updated version.
Configuration Program
1. Use the Windows Explorer to find and open the
Lbt_gxt2-1.6.exe installation program on the
included software CD.
2. When you see this PreSetup window, select OK. This will open the main installation screen.
3. Click NEXT to continue installing the configuration program.
Liebert recommends using the default installation options, but you will be given the option to make modifications to the standard entries.
The installation program will also install an Uninstaller program along with the UPS configuration program.
20
Page 27

8.3 Establishing Communication Link with the UPS

Use only the serial communication cable supplied with the configuration program. If an accessory communication card has been installed in the UPS’s communication card slot, the option card must be removed while using the configuration program.
Use the serial communication cable to connect your computer’s COM1 port to the DB-9 communica­tion port on the rear of the UPS. COM2 may also be used. If the COM port of the host computer has only a DB-25 pin connector, a DB-25 to DB-9 adapter must be added.
The program may be used while the UPS is on to read and confirm the current settings. The UPS must be off and powered by the AC utility when using the configuration program to change any UPS setting. Any attempt to change a setting while the UPS is on will result in an error message.
Select Lbt_gxt2.exe from the program group to start the configuration program. The program will search COM1 & COM2 for a properly connected GXT 2U™ UPS. When the UPS is found, the opening program window will display the UPS model.
If the configuration program ever fails in its attempt to read data from a UPS, the error message below will be displayed. The program must communicate with the UPS when it first opens, when a new tab is opened and when the REFRESH, APPLY or OK buttons are pressed.
Configuration Program
If this message is displayed, check the following items:
1. Verify that the serial communication cable is connected properly.
2. Verify that the COM port being used is designated COM1 or COM2.
3. Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode or Off with AC power available at the input (AC Input indicator on). In all cases, the rear fan will be running.
4. Verify that the COM port is not in use by other UPS communication software (or non-UPS software). If MultiLink UPS software is installed on the computer, the MultiLink service must be stopped to free the COM port. MultiLink typically restarts automatically whenever the computer restarts.
5. The UPS serial port is in use by an internal, optional communication card in the UPS card slot. Remove the option card.
6. The program is connected to a UPS that was not designed for this program.
21
Page 28

8.4 Configuration Program—Operation

8.4.1 Read/Confirm UPS Configuration Settings

The UPS settings may be monitored, but not changed, using the configuration program while the UPS is operating in any mode. If the program is only used to read the present UPS settings, close the pro­gram using the CANCEL button.
Mistakenly using the APPLY or OK button will attempt to write data to the UPS and will result in the error message shown at right if the UPS is not off.
If this message is displayed and you do not wish to change any settings, close this error message and close the configuration program using the CANCEL button.
If the UPS is off and you do not wish to risk changing any settings, close the program using the CAN­CEL button. Do not use the APPLY or OK buttons in the configuration program.

8.4.2 Changing UPS Settings

UPS SETTINGS MAY ONLY BE CHANGED USING THE CONFIGURATION PROGRAM WHEN THE UPS IS OFF AND NO POWER IS BEING DELIVERED TO THE LOAD. AC input power must be available to power the UPS logic during programming. Only the AC Line indicator will be on indi­cating utility input power.
Configuration Program
To turn the UPS off to change configuration settings, press the UPS OFF/Bypass button twice within four seconds (hold the button one second each time). This will disconnect all power to the load.
Changing any value or selecting/deselecting any setting in the configuration window will not immedi­ately change the settings in the UPS. You may modify the displayed settings until you are satisfied with the new proposed changes. Settings displayed by the configuration program can always be restored to the existing values stored in the UPS by selecting the REFRESH key.
Values displayed will be transmitted to the UPS only when either the APPLY or OK button is selected. The APPLY button sends the new settings to the UPS without closing the program. The OK button sends the new set­tings and closes the program.
Whenever data is successfully transmitted to the UPS, this message shown at right will be displayed.

8.4.3 Programming Rejected?

If the UPS appears to be off but this error message is displayed when the APPLY or OK button is selected to transmit settings, the UPS may be in an intermediate standby con­dition.
To confirm that the UPS is fully off, repeat the turn off procedure. Press the UPS OFF/ Bypass button twice within four seconds (hold the button one second each time).

8.4.4 Exit Without Changing UPS Settings

If you decide not to change the UPS after modifying the displayed settings, close the configuration program using the Cancel button.
22
Page 29

8.5 UPS Tab

When the program starts, the following window will open displaying the UPS model along with the current UPS settings. This information can be updated at any time using the REFRESH button.

Figure 4 Factory default settings for 120VAC UPS

Configuration Program

8.5.1 Output Voltage

The Output Voltage displayed is the nominal input/output voltage. This is not a voltmeter and will display the nominal voltage whether the UPS is on or off. The drop down box will show the alternate voltages available. Select the voltage that matches the nominal utility in your location.

8.5.2 Auto Restart

The UPS will provide computer grade power during power outages. If input power is unavailable for an extended time, the UPS will shut down when batteries are depleted or a shutdown signal is sent by the computer operating system to limit battery depletion (serial data or contact closure). If Auto Restart is enabled (check mark in box), the UPS will restart when input power is restored. If the UPS turns off power to the load for any other reason, manual restart is required (See 8.6 - Options Tab for exceptions). Click on the box to remove the check mark and disable Auto Restart.

8.5.3 L-N Reverse Detection (120V UPS Models Only)

Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression and surge suppression. The UPS checks the outlet when first plugged in. If the Line-Neutral is reversed or the ground is missing, the UPS will not start. If a problem is detected after the UPS is started, the UPS will continue to operate, but the AC Input indicator will flash. In some unique applications the user may wish to disable this alarm. Except for special situations, improperly wired receptacles should be immediately repaired before the UPS is put into service. Click on the box to remove the check mark and disable this alarm.
23
Page 30

8.5.4 Frequency Selection

The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore, for all normal use the Auto Sense button should be selected.
Some special applications require that the UPS be used as a frequency converter. Frequency con­verter 50Hz or frequency converter 60Hz may be selected.
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is unable to power the load, the alternate bypass to utility power will not be available and power will be removed from any load.

8.6 Options Tab

Computer users may choose to use versatile com­puter shutdown software that communicates with the UPS via a serial communications cable. The Options tab should not be used to modify the UPS functions for such applications.
For some industrial applications and special computer applications, the UPS may be moni­tored and controlled using external voltages and relay contact signals. The Options tab expands the UPS versatility for such applications.
Configuration Program
Refer to your UPS manual for a description of the 9-pin communication connector on the rear of the UPS. Pin 6 of the 9-pin communication connector is used for “Any Mode Shutdown” of the UPS out­put. This control input may be used in special applications to disable the UPS output power ­both Inverter and Bypass.
The Options tab allows the behavior of the Any Mode Shutdown feature to be modified.
When the program opens or the REFRESH but­ton is pressed, the UPS setting is read by the configuration program and displayed.
Factory Default Setting Illustrated - This Options tab illustration shows the available function definitions using pin 6 and the factory default settings.
WARNING
!
Auto-Enable Output
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS output can turn on automatically and without warning if the Pin 6 connection is changed.
WARNING
!
Pin 6 Logic
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to install a normally-closed connection between Pins 5 & 6. This connection must be maintained to use the UPS or to use the configuration program again, including the ability to change the UPS setting back to the default setting using the configuration program via a serial communication link.
24
Page 31

8.7 Options Tab Used With Earlier GXT 2U Models

This version of the configuration program will accompany GXT 2U UPS models that support new pro­gramming features accessible using the Options tab.
If version 1.6 (or later) is used with an earlier GXT 2U model (with an earlier UPS firmware version), the Any Mode Shutdown features cannot be changed.
If the configuration program is used with an earlier UPS model (with an earlier UPS firmware ver­sion) that does not support the modification of these settings, the Options tab will display a reminder of the factory default settings, as shown. These cannot be changed.
Configuration Program
25
Page 32

8.8 Battery Tab

Factory default settings illustrated.
The boxes on the right show the available options using the drop-down selection boxes.
Configuration Program

8.8.1 Low Battery Time Warning

The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30 minutes.

8.8.2 Auto Battery Test Time

The UPS performs an automated battery test periodically, if enabled. The user may also select time periods of 7, 14, 21 and 28 days.

8.8.3 Battery Cabinets Number

If additional batteries are attached to the UPS, accurate battery runtime estimates are possible if the battery number and type of batteries are entered here. The new UPS models are designed to operate with up to four external battery packs or four long runtime battery packs (not currently available).

8.8.4 Auto Battery Test

In some applications it may be preferable to disable the automated, periodic battery test. Click on the box to remove the check mark and disable the periodic battery test.
26
Page 33

8.9 About Tab

The version number of the configuration program may be confirmed using the About Tab.
Configuration Program
27
Page 34

9.0 CONTROLS AND INDICATORS

L1
L2
BYPASS
Controls and Indicators
All indicators lit for illustrative purposes.
Vertical overlay for tower installation
!
- +
UPStation GXT
UPS ON
BATTERY
AC INPUT

9.1 ON/Alarm Silence/Battery Test Button

This button controls output power to connected load(s) and has three functions:
•ON
•Alarm Silence
•Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the alarm is silenced, the UPStation GXT2-6000RT208 will reactivate the alarm system to alert of additional problems.
Horizontal overlay for rack mounting
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON/Alarm Silence/Battery Test button for at least one second while operating from utility power with no alarm conditions present.
• If only three of the five Battery indicators illuminate, allow the UPS to recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery indicators illuminate, con­tact your local dealer, Liebert representative or Liebert Worldwide Support Group.

9.2 OFF/Bypass Button

This button controls output power to connected load(s) and has dual functions: OFF and Bypass.
Pressing the OFF/Bypass button twice within 4 seconds shuts off power to the output receptacles and connected loads, but the UPS’s circuits remain live, charging the unit’s battery.
CAUTION
!
Pressing the OFF/Bypass button once will cause the load to be transferred to bypass power. Pressing the OFF/Bypass button a second time within 4 seconds will result in loss of power to the output receptacles and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.
28
Page 35
Controls and Indicators

9.3 L1 & L2 Load Level Indicators (Two Rows of Indicators: 4 Green, 1 Amber)

The Load Level indicators display the approximate electrical load placed upon both output legs of the UPS at all times. Each indicator represents an approximate 25 percent increase in load. For optimum utilization of the UPS, distribute L-N loads to approximately balance the loads on L1 and L2.

9.4 Battery Level Indicators (5 Green)

The Battery Level indicators display approximate battery capacity at all times. Each indicator repre­sents an approximate 20 percent increase in battery capacity.
The UPStation GXT2-6000RT208 is equipped with automatic and remote battery test features. The automatic test occurs every 14 days (this option is user-configurable) if utility has not been inter­rupted. Should the battery fail this test, the red Fault indicator along with the A and C diagnostic indicators will illuminate and an alarm will sound (refer to 13.0 - Troubleshooting). The remote test feature functions with MultiLink 3 software and can remotely initiate the battery test.

9.5 Fault Indicator (Red)

The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the Battery Level indicators may be illuminated (refer to 13.0 - Troubleshooting section).

9.6 Bypass Indicator (Amber)

The Bypass indicator is illuminated when the UPS is operating from bypass power. An alarm will sound indicating the UPS detected a problem or the manual bypass function has been activated.

9.7 UPS ON Indicator (Green)

The UPS ON indicator is illuminated when the UPS inverter is operating and supplying power to your connected loads.

9.8 Battery Indicator (Amber)

The Battery indicator is illuminated when the UPS is operating on battery.

9.9 AC Input Indicator (Green)

The AC Input indicator is illuminated when utility power is available and within the input specifica­tions.
29
Page 36

10.0 MODES OF OPERATION

10.1 Normal Mode Operation

During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green Load Level indica­tors display an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percent­age of load (see example at right) on the UPS output.

10.2 Battery Mode Operation

Battery mode occurs in event of an extreme input voltage condition or complete utility failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input indicator will extinguish and the Battery indicator will illuminate to warn that a utility problem has occurred. Each Battery Level indicator repre­sents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 13.0 - Trouble-
shooting. For approximate battery run times, refer to Table 7 - Battery run times. These times are approximate
based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add the optional external battery cabinet.
Modes of Operation
Normal Mode Operation Batteries at 100% charge L1 Load at 10%, L2 Load at 90%
Battery Mode Operation Batteries at 30% charge L1 Load at 60%, L2 Load at 60%
CAUTION
!
Turning OFF the UPS while in battery mode will result in loss of output power.

10.3 Battery Recharge Operation

Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.
30
Page 37

11.0 COMMUNICATIONS

r

11.1 Communications Interface Port

The UPStation GXT2-6000RT208 UPS has a standard DB-9 serial port female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:

Table 3 DB-9 pin assignment

DB-9
Pin
Assignment Description
1 Low Battery (open collector)
2 UPS TxD (typically RS-232 levels)
3 UPS RxD (typically RS-232 levels)
4 Remote Shutdown (5-12VDC, 10-24mA max; battery operation)
5 Common
6 Remote Shutdown (short to pin 5); all modes of operation
7 Low Battery (open emitter)
8 Utility Fail (open emitter)
9 Utility Fail (open collector)
Communications
Pin Assignment Collector to Emitter*
6789
330 Ohms
54321
* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA

11.1.1 DB-9 Interface Port

Using the following directions to attach the smaller enclosed ferrite bead clamp to the communication cable as shown at right:
1. Open the ferrite bead.
2. Place the communication cable inside the ferrite bead groove.
3. Position the ferrite bead as close as possible to the end of the cable that connects to the DB-9 connector of the UPS.
4. Close the ferrite bead so that the ferrite bead’s case snaps closed with the cable routed through the ferrite bead’s case.

11.1.2 Communications SNMP Web Card SNMP Adapter

Attach the larger enclosed ferrite bead clamp to the network cable, see illustration at right, using the following directions:
1. Open the ferrite bead.
2. Place the network cable inside the ferrite bead groove.
3. Wrap the cable once around the ferrite bead.
4. Position the ferrite cable as close as possible to the end of the cable that connects to the UPS.
5. Close the ferrite bead so that the ferrite bead’s case snaps closed with the cable routed through the ferrite bead’s case.
Open
(+)
Collecto
Open
(-)
Emitter
Wrap network cable around ferrite bead
Run cable through ferrite bead case
31
Page 38

11.2 Pin 4 - Remote Shutdown on Battery

1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds, the command cannot be canceled.
3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.
4. If the utility returns during the 2-minute timer countdown, the shutdown timer will continue until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and restart the server.
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown delay.

11.3 UPS Intelligent Communications

Communications
The UPStation GXT2-6000RT208 is equipped with an Intellislot® port to provide advanced communi­cation and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit. For more information about the Intellislot SNMP/Web Card and MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT2-6000RT208 The Intellislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor­dinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv­ers support for built-in shutdown for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables, where applicable.
32
Page 39

11.4 Remote Emergency Power Off

The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.

Figure 5 REPO switch connections

REPO Connection
Communications
REPO
as shipped
Key to REPO switch connections
1. 24 VDC
2. Sense
3. Sense
4. Ground
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be segregated and run separately from power cables.
REPO connections
for normally open
switch system
12341234
REPO connections
for normally closed
switch system (fail-safe)
1234
33
Page 40

12.0 MAINTENANCE

The UPStation GXT2-6000RT208 requires very little maintenance. The batteries are valve-regulated, non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The UPS continuously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri­odically will permanently degrade battery capacity.
The UPStation GXT2-6000RT208 is designed to allow the user to safely replace the internal batteries. Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing.

12.1 Battery Replacement

CAUTION
!
A battery can present a risk of electrical shock and high short circuit Current. The following precautions should be observed before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
Maintenance

12.1.1 Internal Battery Replacement Procedures

1. Gently remove the front plastic bezels cover from the UPS by pulling forward.
2. Loosen the two captive screws on the front battery door. Lay the battery door aside for reassembly.
3. Grasp the battery pack assembly and pull it out of the front of the UPS. Be prepared to support the weight of the battery as it is withdrawn.
4. Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 6; otherwise STOP and contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
5. Line up and slide in the new replacement battery pack.
6. Reattach the front battery door, tightening the two captive screws finger tight.
7. Reattach the front plastic bezels to the UPS.
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.
Battery
Battery Cover
!
UPS
!
12Vx12(144V) 9Ahi45W
-
:
AVERTISSEMENT
+
ADVERTENCIA:
!
!
NING:
WAR
Front Bezels
Liebert
!
Battery Cover Captive Screws
34
Page 41

12.2 UPS Replacement

When using a power distribution box with bypass, the UPS can be removed while powering the load through the Bypass Switch.
NOTE
During the procedure, the connected load will not be protected from power disturbances, such as spikes, sags and failure.
To remove the UPS without shutting off power to the connected load:
1. Turn the Bypass Switch on the power distribution box to the Utility position.
2. Open the Output circuit breaker (on the UPS rear panel).
3. Open the Input circuit breaker (on the power distribution box).
4. Loosen the three captive mounting screws about 20 turns until the power distribution box can be pulled away from the UPS.
5. Loosen the electrical connector cover by backing out the two screws holding it one turn each. Also loosen the end screw one turn.
6. Slide the cover to reach the end screw and cover the electrical connectors; retighten the three screws gently to hold the cover in place.
7. Replace the UPS.
8. Loosen the three screws holding the electrical connector cover again—one turn each.
9. Slide the cover away from the electrical connectors; gently retighten the three screws.
10. Align the connectors on the power distribution box and the UPS.
11. Push the power distribution box into place.
12. Holding the power distribution box firmly against the UPS, tighten the three captive mounting screws until the box is secure. Do NOT overtighten the screws.
13. Close the Input circuit breaker (on the power distribution box).
14. Close the Output circuit breaker (on the UPS rear panel).
15. Turn the Bypass Switch on the power distribution box back to the UPS position.
Electrical connector cover
DISCONNECT BYPASS POWER TO
THE MANUAL BYPASS SWITCH.
Mounting screws
for removable power
distribution box
Screws securing electrical connector cover
Maintenance
35
Electrical connectors
Page 42

13.0 TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation GXT2-6000RT208 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS has detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional Load Level/Battery Level indicators will be illuminated to provide a diagnostic aid to the operator, as described below:
Troubleshooting
AB C D E
Fault indicator
Battery indicators
Load Level indicators
AC Input indicator
UPS ON indicatorBattery indicator
Bypass indicator

Table 4 Fault indicators

Indicator status
All indicators On bypass due to output overload; beep every half-second
Indicator A
Indicator B
Indicator C
Indicator D
Indicator E
Indicators A&B Inverter-to-Inverter communications failure; half-second beep every 1 second
Indicators A&C UPS failed battery test; 2-second beep every 60 seconds
Indicators A&D L1 to L2 phase angle unacceptable
Indicators B&C REPO is currently activated, UPS output cannot be started by any method
Indicators B&D
Indicators C&E UPS shutdown due to command from communications (RS232 or SNMP); no beep
Indicators D&E UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds
AC Input indicator On & Battery indicator Flashing
Bypass indicator Flashing
On bypass due to overtemperature condition on L1; 1-second beep every 4 seconds On bypass due to overtemperature condition on L2; 2-second beep every 4 seconds
On bypass due to DC bus overvoltage on L1; 1-second beep every 4 seconds On bypass due to DC bus overvoltage on L2; 2-second beep every 4 seconds
On bypass due to control power supply failure on L1; 1-second beep every 4 seconds On bypass due to control power supply failure on L2; 2-second beep every 4 seconds
On bypass due to PFC failure on L1; 1-second beep every 4 seconds On bypass due to PFC failure on L2; 2-second beep every 4 seconds
On bypass due to inverter failure on L1; 1-second beep every 4 seconds On bypass due to inverter failure on L2; 2-second beep every 4 seconds
UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is restored, press the OFF button twice within four seconds (to clear the alarm), then press the ON button to start UPS (Auto-restart is NOT possible).
AC input has been applied to start UPS but the batteries are either missing or below the minimal level to allow the UPS to start; continuous audible alarm
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside acceptable limits
Diagnosis/Audible alarm
Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World­wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.
36
Page 43
Troubleshooting
All audible alarms can be silenced, with the exception of Low Battery, Bypass Reminder and Missing Batteries at Startup alarms. Once silenced, the alarm will not sound again until a new alarm condi­tion is present.

Table 5 Alarm conditions

Condition Alarm
Battery Mode (utility failure) One short beep every 10 seconds; more than 2 minutes of run time remaining
Low Battery Two short beeps every 5 seconds; less than 2 minutes of run time remaining
On Bypass Reminder A one-second beep every 2 minutes
Output Overload (bypass) One short beep every half second
Overtemperature (bypass) A one-second, or two-second, beep every 4 seconds
DC Bus Overvoltage (bypass) A one-second, or two-second, beep every 4 seconds
Control Power Supply Failure (bypass) A one-second, or two-second, beep every 4 seconds
PFC Failure (bypass) A one-second, or two-second, beep every 4 seconds
Inverter Failure A one-second, or two-second, beep every 4 seconds
Inverter-to-Inverter Communications Failure
Battery Test Failure A two-second beep every 1 minute
REPO Activated A one-quarter second beep every half second
A one-half second beep every 1 second

Table 6 Troubleshooting guide

Problem Cause Solution
UPS fails to start when the ON button is pressed.
Battery indicator is illuminated.
UPS has reduced battery time.
Fault and Bypass indicators and all Load Level indicators are illuminated.
Fault and Bypass indicators and diagnostic indicator C are illuminated.
Fault and Bypass indicators and diagnostic indicator D are illuminated.
Fault and Bypass indicators and diagnostic indicator A are illuminated.
UPS is short-circuited or overloaded.
UPS not plugged in.
UPS input protection fuse has blown/opened.
Utility voltage out of UPS input range.
Batteries are not fully charged.
UPS is overloaded. Check load level display and reduce the load on the UPS.
Batteries may not be able to hold a full charge due to age.
UPS overloaded or load equipment is faulty.
UPS control power supply fault.
UPS PFC (Power Factor Correction Circuit) fault.
UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power.
Ensure the UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure the loads are not defective or shorted internally.
UPS is operating in Battery Mode, make certain UPS is securely plugged into the wall receptacle.
UPS is operating in Battery Mode. Save data and close applications. Replace UPS input fuse, then restart UPS.
UPS is operating in Battery Mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group for replacement battery kit.
Check load level display and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load equipment for faults.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Ensure the UPS is not overloaded, ventilation openings are not blocked and room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS does not restart, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
37
Page 44
Table 6 Troubleshooting guide
Problem Cause Solution
Troubleshooting
Fault and Bypass indicators and diagnostic indicator B are illuminated.
Fault and Bypass indicators and diagnostic indicator E are illuminated.
Fault and Bypass indicators and diagnostic indicators A and B are illuminated.
Fault indicator and diagnostic indicators A and C are illuminated.
Fault indicator and diagnostic indicators A and D are illuminated.
Fault indicator and diagnostic indicators B and C are illuminated.
Fault indicator and diagnostic indicators B and D are illuminated.
Fault indicator and diagnostic indicators C and E are illuminated.
Fault indicator and diagnostic indicators D and E are illuminated.
AC Input indicator is On & Battery indicator is flashing.
Bypass indicator is flashing.
UPS internal DC bus overvoltage.
UPS inverter fault.
Inverter-to-Inverter Communications Failure
UPS failed the battery test.
L1 to L2 phase angle unacceptable.
REPO is currently activated.
UPS output is OFF from a previous REPO command. REPO is no longer activated.
UPS shutdown due to a command from the communications port(s).
UPS charger fault.
Battery source is not available; continuous horn.
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside acceptable limits.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Only phase angles of 120, 180 or 240 degrees (±10 degrees) are permitted. These must be compatible with the selections in the configuration program. Or the phase angle has changed while the UPS was running. The phase angle is detected at startup and cannot be changed to a different power source while running. Turn the UPS Off and wait until the fans stop. Apply input AC power. The UPS will reprogram the phase angle to match the utility, if the utility is 120, 180 or 240 degrees between L1 and L2. If this does not resolve the issue, contact a qualified electrician to verify the site wiring.
UPS has shut down due to the REPO (Remote Emergency Power Off). The output cannot be started by any method.
UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is restored, press the OFF button twice within four seconds (to clear the alarm), then press the ON button to start UPS (Auto-restart is NOT possible).
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable.
38
Page 45
Troubleshooting
Using the configuration program, the user may specify the number of GXT2-144VBATT external bat­tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 7 shows estimated run times at different loads.

Table 7 Battery run times

6000VA Run Time
Battery/External Cabinets Load%
10% 75 20% 38 30% 25 40% 18
Internal Battery
Internal Battery + 1 External
Battery Cabinet
Internal Battery + 2 External
Battery Cabinets
Internal Battery + 3 External
Battery Cabinets
Internal Battery + 4 External
Battery Cabinets
50% 14 60% 11 70% 9 80% 7 90% 6
100% 5
10% 156 20% 90 30% 62 40% 44 50% 34 60% 28 70% 23 80% 19 90% 16
100% 14
10% 235 20% 137 30% 99 40% 74 50% 58 60% 47 70% 39 80% 33 90% 28
100% 25
10% 313 20% 183 30% 133 40% 103 50% 82 60% 67 70% 55 80% 47 90% 41
100% 36
10% 391 20% 229 30% 166 40% 129 50% 105 60% 87 70% 73 80% 63 90% 54
100% 47
in Minutes
39
Page 46

13.1 Auto-Learning Battery Run Times

As batteries age, the estimated run times may become less accurate. The GXT2-6000RT208 is pro­grammed to “learn” from a full battery discharge and modify the estimated run time for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-dis­charge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the battery table on the right will be restored. This will override any value that is automatically learned.
Troubleshooting
40
Page 47

14.0 SPECIFICATIONS

Table 8 UPS specifications
Model Number GXT2-6000RT208
4200W/5200VA at 127/220 (120 or 240 degrees only)
4200W/5200VA at 120/208 (120 or 240 degrees)
Model Rating
DIMENSIONS in (mm)
Unit W x D x H in. (mm) 6.9 x 24.2 x 16.9 (176 x 615 x 430)
Shipping W x D x H in. (mm) 13.2 x 27.8 x 20.9 (335 x 705 x 530)
WEIGHT lbs (kg)
Unit 67 (30.3)
Shipping 76.3 (34.6)
INPUT AC PARAMETERS
Nominal Operating Frequency 50 or 60 Hz (Factory Default = 60)
Factory Default VAC 120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase
Allowable Input Phase Angle
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC (May be modified using configuration program)
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)
100% - 90% loading 90 VAC - 140 VAC
90% - 70% loading 80 VAC - 140 VAC 70% - 30% loading 70 VAC - 140 VAC
30% - 0% loading 60 VAC - 140 VAC
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)
100% - 70% loading 80 VAC - 140 VAC
70% - 30% loading 70 VAC - 140 VAC
30% - 0% loading 60 VAC - 140 VAC
L1-N, L2-N Max. Allowable VAC 150 VAC
Input Frequency w/o Battery
Input Power Connection See Distribution Box Options
OUTPUT AC PARAMETERS
Factory Default VAC 120/208 VAC @ 120 degrees
L1-L2 Factory Default
Output Phase Angle
Allowable Output Phase Angle 120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC, ±3%
Output Connections See Distribution Box Options
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Angle
120, 180, 240 degrees, Auto-sensing on application of AC
Operation
Frequency 50 Hz or 60 Hz, Nominal
Waveform Sinewave
4200W/6000VA at 120/240 (180 degrees) 4200W/6000VA at 115/230 (180 degrees only) 3780W/5400VA at 110/220 (180 degrees only) 3360W/4800VA at 100/200 (180 degrees only)
120 degrees
(Restrictions for L-N voltages other than 120 VAC)
40 - 70 Hz
120 degrees
Specifications
41
Page 48
Table 8 UPS specifications (continued)
Model Number GXT2-6000RT208
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A

Table 9 Battery specifications

Model Number GXT2-144BATKIT
DIMENSIONS in (mm)
Shipping W x D x H in. (mm) 13.4 x 27.2 x 13.4 (340 x 690 x 340)
WEIGHT lbs (kg)
Unit 79 (35.8)
Shipping 84 (38.1)
Type Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating 12 x 12V x 9.0 AH
Battery Mfg / Part # Yuasa / REW 45-12 FR
Back-Up Time See Table 7 - Battery run times
Recharge Time 6 Hours to 90% capacity after full discharge into 100% load
Specifications
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides

Table 10 Power distribution box specifications

Model Number PD-HDWR
Amp Rating 24 Amps Input Power Connection 4-Wire Hardwired, 8-10AWG Output Power Connection 4-Wire Hardwired, 8-10AWG Input Branch Circuit Breaker 30 Amp, Supplied by User
Model Number PD-HDWR-MBS
Amp Rating 24 Amps Input Power Connection 4-Wire Hardwired, 8-10AWG Output Power Connection 4-Wire Hardwired, 8-10AWG
Includes: Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker 30 Amp, Supplied by User
Model Number PD-001
Amp Rating 24 Amps Input Power Connections L14-30P on 10 foot cord Output Power Connection
L1-L2-G (1) L6-30R on a 300mm cord
L1-L2-N-G (1) L14-30R on a 300mm cord
L1-N-G (2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers L2-N-G (2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
Includes: Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker 30 Amp, Supplied by User
42
Page 49

Table 11 External battery cabinet specifications

Model Number GXT2-144VBATT
Used w/ UPS Model GXT2-6000RT208
DIMENSIONS in (mm)
Unit (with bezel) W x D x H 3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping W x D x H 10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT lbs (kg)
Unit 93.6 (42.5)
Shipping 105 (47.6)
BATTERY PARAMETERS
Type Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating 12 x 12V x 9.0 AH
Battery Mfg / Part # Yuasa / REW 45-12 FR
Back-Up Time See Table 7 - Battery run times
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000m) maximum
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A
Specifications

14.1 Product Warranty Registration

To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877 Outside the US: 614-841-6755
upstech@liebert.com
43
Page 50
Specifications
44
Page 51
Page 52
POWER AVAILABILITY
GXT2-6000RT208
The Company Behind the Products
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2003 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23170 (8/03) Rev. 0
USER MANUAL
Technical Support/Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@liebert.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
Loading...