Opening or removing the cover may expose you to lethal voltages within this unit even when
it is apparently not operating and the input wiring is disconnected from the electrical source.
Observe all cautions and warnings in this manual. Failure to do so may result in serious
injury or death. Refer all UPS and battery service to qualified service personnel. Do not
attempt to service this product yourself. Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, installation and operating
instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the
unit and in this manual. Follow all operating and user instructions. Individuals without previous
training can install and operate this equipment.
It is not intended for use with life support and other designated critical devices. Maximum load must
not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If
uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230, 120/208,
120/240 or 127/220 VAC, 50 Hz or 60 Hz supply. The factory default setting is 120/208 VAC, 60 Hz.
Installation instructions and warning notices are located in this manual.
This UPS is only for use with a four-wire input (L1, L2, N, G).
This UPS MAY NOT be used with a three-wire, single-phase utility source (L1, N, G).
ELECTROMAGNETIC COMPATIBILITY—The GXT2-6000RT208 Series complies with the limits
for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference and (2) this device must
accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at
their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F
(0°C to +40°C). Install it in a clean environment, free from conductive contaminants, moisture, flammable liquids, gases and corrosive substances.
This UPS contains no user serviceable parts except the internal battery pack. The Off/Bypass push
button does not electrically isolate internal parts. Under no circumstances attempt to gain access
internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to
use the UPS if the front panel indications are not in accordance with these operating instructions or if
the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the
Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from the batteries. PROPER DISPOSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS
FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other openings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from
the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any other appliance using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol
cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
1
Page 8
When replacing batteries, replace with the same Liebert authorized replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The
following precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
2
Page 9
1.0GLOSSARYOF SYMBOLS
Risk of electrical shock
Glossary of Symbols
!
R
i
-
PbH2SO4
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
3
Page 10
2.0INTRODUCTIONAND SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert UPStation GXT2-6000RT208 Uninterruptible Power
Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is
subject to voltage sags, spikes or complete power failure that may interrupt computer operations,
cause data loss or even damage equipment. The UPStation GXT2-6000RT208 protects equipment
from these disturbances.
The UPStation GXT2-6000RT208 is a compact, on-line UPS. An on-line UPS continuously conditions
and regulates its output voltage whether utility power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT2-6000RT208 features a light-emitting diode (LED) display to
indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm Silence/Battery Test button, a Standby button, user configurable program and two
levels of alarms when the unit is operating on battery.
The UPStation GXT2-6000RT208 has an interface port for communication between the UPS and a
network server or other computer systems. This port provides detailed operating information including voltages, currents and alarm status to the host system when used in conjunction with Liebert’s
MultiLink™ software. MultiLink software can also control UPS operation remotely.
Introduction and System Description
4
Page 11
3.0SYSTEM DESCRIPTION
System Description
InputOutput
L1
L2
N
GG
TVSS &
EMI/RFI
Filters
Rectifier
/PFC
Battery
Charger
Dynamic
Bypass
DC to DC
Converter
Battery
Inverter
L1
L2
N
3.1Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
These UPS components provide surge protection and filter both electromagnetic interference (EMI)
and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to
regulated DC power for use by the inverter while ensuring that the waveshape of the input current
used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The utility power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being protected by
the UPStation GXT2-6000RT208.
3.3Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and
inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter
receives energy from the battery through the DC to DC converter. In both modes of operation, the
UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
3.4Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to continuously
float charge the batteries. The batteries are being charged whenever the UPStation GXT2-6000RT208
is plugged in, even when the UPS is not turned on.
5
Page 12
3.5DC to DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
3.6Battery
The UPStation GXT2-6000RT208 utilizes valve-regulated, nonspillable, flame retardant, lead acid
batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F
(20°C to 25°C). Optional external battery cabinets are available to extend battery run times.
3.7Dynamic Bypass
The UPStation GXT2-6000RT208 provides an alternate path for utility power to the connected load in
the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or UPS
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is
indicated by an audible alarm and illuminated amber Bypass indicator (other indicators may be illuminated to indicate the diagnosed problem).
The user may manually transfer the connected load from the inverter to bypass by pressing the
Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances
on the utility supply.
System Description
6
Page 13
4.0MAJOR COMPONENTS
The GXT2-6000RT208 is composed of three major assemblies to provide easier handling, installation
and versatility.
4.1Main Frame and Electronics
This 4U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the
cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The
UPS is shipped with a basic hardwire distribution box.
Figure 16 kVA Dual Inverter GXT 2U (front and rear views)
Major Components
Status Indicators
and Controls
Front Bezels (2)
!
UPStation GXT
Battery Compartment (behind bezel);
Internal Battery Pack is shipped loose
(see Section 4.2)
Output
Circuit
Breaker
External Battery
Connector
Hardwire
Knockouts
Support Base
REAR VIEWFRONT VIEW
Intellislot
®
Port
DB-9
Communications
Port
Cooling Fan
(1 of 4)
+
--
Grounding
Electrode
+
Conductor
REPO
Switch
Input Circuit
Breaker
Power Distribution Box
Standard Module
(See Section 4.3)
4.2Internal Battery Pack
The front bezels may be pulled forward and removed to
reveal the battery access door. The internal battery pack
is a compact assembly ready to slide into the battery
compartment after the front battery access door has been
opened. Electrical connection is automatic upon
insertion.
(144V)
12Vx12
9Ahi45W
-
!
+
:
T
N
E
M
E
S
IS
T
R
E
V
A
:
IA
!
C
N
E
T
R
E
V
D
A
:
!
G
IN
N
R
A
W
:
G
IN
N
R
A
W
7
Page 14
4.3Removable Power Distribution Box
The UPS is shipped with a basic hardwire power distribution pack installed. For maximum flexibility,
this may be easily replaced with either of two optional power distribution boxes that provide the benefits of hardwire input and output plus manual bypass switch or plug/receptacle convenience with
manual bypass switch.
Power Distribution Box With
Hardwire Connections
(Standard - Ships With UPS)
DISCONNECT BYPASS POWER TO
THE MANUAL BYPASS SWITCH.
PD-HDWR
Major Components
PD-HDWR-MBS
Power Distribution Box
With Hardwire Connections
and Manual Bypass Switch
(Optional)
PD-001
Power Distribution Box
With Wired Connections
and Manual Bypass Switch
(Optional)
8
Page 15
5.0WHAT’S INCLUDED
The GXT2-6000RT208 is shipped with the following items:
• GXT2-6000RT208 user manual
• Vertical display overlay
• Front bezels - 2
• Top bezels - 2
• Battery cover grille
• MultiLink software CD
• MultiLink serial cable, 10 ft (3m)
• Rack mount handles
• Support base - 2
• GEC ring connector
• Mounting hardware
• Configuration program disk
• Ferrite beads (2)
What’s Included
L1
!
- +
UPStation GXT
Vertical
display
overlay
Support base
L2
S
S
A
P
Y
B
N
O
S
P
U
Y
R
E
T
T
A
B
T
U
P
IN
C
A
with spacers
!
Front bezels
MultiLink
software CD
GEC connector
Top bezels
(tower use)
MultiLink
serial cable
10 ft (3m)
Mounting hardware
Battery cover grille
Rack mount
handles
www.liebert.com
GXT 2U™ Configuration
Program
For use with LiebertGXT 2U model UPS
systems
Versi on 1. 6
For Windows 95/98/NT
To Install:
Choose the Start button on the Taskbar
and select Run
Configuration
disk
Ferrite
beads (2)
9
Page 16
6.0INSTALLATIONAND CONFIGURATION
This section includes instructions on how to install, configure and perform initial electrical checks of
your UPS installation.
DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until
instructed to do so in 7.0 - Initial Startup and Electrical Checks.
Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or
Liebert representative.
CAUTION
!
The UPS is heavy (see 14.0 - Specifications). Take proper precautions when lifting or
moving it.
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place
it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front
and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.
Installation and Configuration
6.1Install the Main Cabinet
The GXT2-6000RT208 may be installed either as a tower unit or in a rack, depending on available
space and use considerations. Determine the type of installation and follow the appropriate instructions in either 6.1.1 - Tower UPS Installation or 6.1.2 - Installing the Adjustable Rack-Mount Kit—Sold Separately.
6.1.1Tower UPS Installation
When using the GXT2-6000RT208 in a tower configuration, use the included support base (shown
below, left) to stabilize the UPS.
If any external battery cabinets are added, they will include spacers to accommodate the additional
cabinets (shown below, right).
Figure 2Support base and spacers
End Bases
4U Support Base
2U Spacer
Spacers added to support
base to accommodate
additional battery cabinets
Attach Bezels to Top
When used as a tower, the GXT2-6000RT208 requires bezels attached to the top. To connect the
bezels:
1. Position the UPS so that the battery compartment is on the bottom.
2. Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of
the UPS.
10
Page 17
6.1.2Installing the Adjustable Rack-Mount Kit—Sold Separately
This kit contains parts needed to mount several different models of UPS and external battery cabinets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per
pair of adjustable rack-mounting brackets is 200 pounds (91 kg).
Parts included are:
ItemQuantity
Rear bracket members2
Front bracket members2
Inner bracket members2
M4 x 8mm machine screws16
M4 locking hex nuts8
M5 x 16 mm machine screws12
Grease packet.1
Tools needed for installation are:
• one Phillips screwdriver
• one 7mm wrench
The adjustable rack-mounting brackets feature retaining latches to prevent users from inadvertently
sliding the UPS or battery cabinet out of the rack.
Installation and Configuration
To install the rack mount brackets:
1. Unpack two (2) rack-mounting bracket assemblies and
mounting hardware from this kit. Bracket assemblies are
interchangeable between left-hand or right-hand.
Remove inner member of each bracket assembly as shown
in at right by extending it to its outermost position,
depressing the retaining latch and then pulling the inner
member out of the bracket assembly.
2. Determine the height position inside the rack enclosure
where you want to mount the UPS or battery cabinet.
CAUTION
!
Reduce the risk of tipping the rack enclosure by
placing the UPS or battery cabinet in the lowest
possible rack position.
3. Install the rear member of each bracket assembly into rack
enclosure with two (2) M5 screws provided in this kit (see
figure at right). The return flanges on the bracket assembly
fit to the inside of rack mounting rails. Insert screws loosely
(finger-tight) into the top and bottom holes of the return
flange on the rear member. Extend the bracket assembly by
sliding the front member forward until it touches the front
rack mounting rail. Insert two (2) M5 screws loosely (fingertight) into top and bottom holes of the return flange on each
front member. Make sure bracket assemblies are at the
same mounting height on all four (4) rack mounting rails.
Retaining
Latches
Inner
members
Front rack
mounting rails
M5 screws
Return
flanges
Front
members
M5 screws
Rear rack
mounting
rails
11
Page 18
Installation and Configuration
4. Get eight (8) M4 screws and eight (8) M4 nuts from the
hardware pack in this kit. Each nut has a locking, nylon
M4 nuts
M4
screws
insert that begins gripping the screw when it is halfway
tight. Make sure to tighten the nut and screw completely to
ensure locking action.Fasten the rear member and the front
member together using (4) screws and (4) nuts per bracket
assembly as shown in at right. For maximum support, insert
fasteners for each bracket assembly as far apart as possible,
depending on rack depth, while still joining both members
(see figures at right). Check alignment of bracket assemblies
18" rack
depth
M4 nuts
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.
5. Prepare the UPS or battery cabinet (the “equipment”) for
rack mounting by following instructions in the equipment’s
M4 nuts
M4
screws
user manual. The equipment may require additional parts to
be added or parts to be removed for rack mounting. After it is
prepared, lay the equipment in rack-mounting position.
Fasten the inner members from Step 1 to the equipment on
both sides as shown at right with eight (8) M4 screws
provided in the kit. Make sure retaining latch is near the rear
32" rack
depth
M4 nuts
of the equipment as shown (see figure at right).
6. Open the grease packet provided in the kit. Apply a 1" long
M4 screws
Retaining latch
bead of grease at four (4) places inside the bottom, curved
tracks of the front members as shown below right. The grease
will allow the equipment to slide into the bracket assemblies
more easily.
CAUTION
!
6.
Lifting equipment into the rack may be a two-person
job, depending on the weight of the equipment. See
equipment’s user manual.)
Front
UPS or battery
cabinet
7. Insert the equipment, with inner members attached in
Step 5, into the bracket assemblies by inserting the top and
M4 screws
bottom edges of the inner members into the top and bottom
curved tracks of the front members and sliding the
equipment into the rack (see figure at right). Ends of inner
members are tapered to allow the rear of the equipment to be
angled upward before insertion, if space allows.
Then the rear, bottom edges of the inner members can be
UPS or
battery
cabinet
Apply
grease
placed into the front edge of the bottom tracks and the front
of the equipment can be tipped up so they are level to insert
the top edges of the inner members before sliding the equipment into the rack (see figure below right). The equipment
should move smoothly into the bracket assemblies. If it does
Apply
grease
(inside)
not, recheck the alignment of the front and rear members
from Steps 2 and 3.
8. Secure the front of the equipment to the rack mounting rails
to prevent the equipment from sliding out of position. If
securing holes are provided on the front of the equipment
... and push it
into the rack.
that align with the center holes on the return flange of the
front members, you can use the four (4) extra M5 screws
provided in the kit to secure the equipment. Otherwise, the
equipment should be secured to the front of the rack with
four (4) customer-supplied fasteners.
Insert the UPS into the front
members, lift the front .. .
12
Page 19
6.2External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked
beneath the UPS.
CAUTION
!
The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery
cabinets can be used in rack-mount or tower configuration. Take proper precautions when
lifting them.
CAUTION
!
Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the
battery cabinet at this time. When installation is complete, you will be instructed to turn on
the circuit breaker.
When the external battery cabinet is received, it should be inspected for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
To install an external battery cabinet:
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up.
Optional rack-mount handles are shipped with the external battery cabinet and may be installed
now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or
Liebert representative for these additional options and any assistance needed.)
2. Fasten the slides into position with the screws according to the instructions included with the
slide rails.
3. Use the enclosed support bases for the tower option to
prevent the assembly from tipping over. One additional set
of support base extensions ships with each external battery
cabinet.
4. Connect the supplied external battery cabinet cable to either
of the connectors on the rear of the external battery cabinet,
then to the rear of the UPS.
5. The UPS is now equipped with additional backup battery
run time. For approximate battery run times, refer to Table 7 - Battery run times in this manual.
6. Do NOT turn on the battery cabinet circuit breaker at this
time. Please complete the remainder of the installation first.
Installation and Configuration
Support Base With
Spacers for External
Battery Cabinets
NOTE
After installation is complete, you must use the included
configuration program to program the UPS for the
number of external battery cabinets connected.
Instructions for using the configuration program follow
in 8.0 - Configuration Program.
13
+
--
+
UPS and Four External Battery
Cabinets With Support Base
Page 20
6.3Connect Input/Output Power
The UPS ships with the basic hardwire box attached. If an
optional model is to be used, remove the standard box and
install the optional box using the three captive mounting
screws marked in the illustration, below, right.
6.3.1Replacing a power distribution box
Whenever a power distribution box is not attached to a UPS,
the cover must be slid over the electrical connectors to prevent
damage or injury.
Installation and Configuration
Slide
cover
over
connectors
1. On the power distribution box attached to the UPS,
locate the three captive mounting screws holding the box
to the UPS (see illustration above, right).
2. Turn the screws until the box can be pulled away from the
UPS. Exercise care to avoid removing screws from the
hardwire box.
3. On the replacement power distribution box to be attached to the UPS, loosen the cover over the electrical
connectors by backing out the three screws one turn each.
4. Slide the cover open to expose the electrical connectors.
5. Gently retighten the three screws loosened in Step 3.
6. Align the connectors on the box and UPS.
7. Push the box into place.
8. Holding the box firmly against the UPS, tighten the three
captive mounting screws until the box is secure. Do not
overtighten.
6.3.2Distribution Box Electrical Connections
Electrical connections are made through a removable power distribution box that attaches to the rear
of the UPS.
The installer must provide a 30A branch circuit breaker. The input circuit breaker on the distribution
box and the output circuit breaker on the rear fixed-panel of the UPS disconnect all power between
the main cabinet and the distribution box.
Loosen screws
to move cover
Mounting screws
for removable box
DISCONNECT BYPASS POWER TO
THE MANUAL BYPASS SWITCH.
Models equipped with a manual bypass switch pass utility power directly to the bypass switch from
the input terminal block. The input circuit breaker on the distribution box does not disconnect power
from the manual bypass switch.
6.3.3PD-HDWR and PD-HDWR-MBS Terminal Block Connections
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not
share the same conduit.
Table 1Electrical requirements—PD-HDWR and PD-HDWR-MBS
Input Current
Rating
24A30A10 AWG8 AWG20 in-lb
Recommended (Max.)
External Overcurrent
Protection
Recommended Wire
(including ground wire)
(75°C copper wire)
The standard PD-HDWR comes installed on the UPS. The PD-HDWR-MBS with manual bypass
switch is optionally available. Both have the same hardwire terminal connections.
Maximum Wire
Accepted by
Terminal Block
Installation and Configuration
Terminal
Tightening
Torque
NL2L1
OUTPUTINPUT
8-10 AWG - USE COPPER WIRE ONLY - 20 in-lb - Strip 7mm
NL2L1
120120
0
Output to Load - See Note 1
208 or 240
Input to UPS - See Note 2
NL2L1
30A Max. Branch
Overcurrent Protection
NL2L1
120120
0
208 or 240
NOTE
1. The installer must provide circuit breaker protection according to local codes. The utility
disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain
service space around the UPS or use flexible conduit.
2. The installer must provide output distribution panels, circuit breaker protection or
emergency disconnects according to local codes. Output circuits must not share a common
conduit with any other wiring.
For best performance, distribute all L-N loads evenly between L1 and L2.
6.3.4PD-001 Power Distribution Box
An optional PD-001 is available to provide the convenience of an L14-30P input plug and output receptacles.
To use this box, remove the original PD-HDWR hardwire
box and install the PD-001.
Table 2Electrical requirements—PD-001
Input Current
Rating
24A30ANEMA L14-30R
Recommended (Max.)
External Overcurrent
Protection
Output
Receptacles
Manual
Bypass
Switch
Required Utility
Receptacle
15
Page 22
6.4Install the Grounding Electrode Conductor
A Grounding Electrode Conductor must be attached to the rear panel using the M5x12 Phillips screw
provided. This connection is required in addition to the power input ground connection to the removable power distribution box.
Install an 8 AWG (10 mm
250-94) grounding electrode conductor to the nearest effectively grounded metal structural member,
nearest effectively grounded metal water pipe or other grounding electrode in the grounding electrode
system. If the grounding electrode conductor must be protected, non-metal conduit is recommended. If
metal conduit must be used, bond both ends of the conduit to the grounding electrode conductor. Conduit is not an acceptable grounding electrode conductor.
A 5mm ring lug for 8AWG wire lug is provided in the accessory box. Other suitable connectors may be
used.
2
) (75°C copper wire) (minimum size, see NEC 250-5d, 250-81, 250-83, table
Installation and Configuration
GROUNDING ELECTRODE CONDUCTOR
+
NOTE
IN BATTERY MODE ONLY, the UPS operates as a separately derived source and contains a
neutral to ground bonding jumper. A grounding electrode conductor (GEC) must be installed
in accordance with national and local wiring codes and regulations.
6.5Install the Internal Battery Pack
To facilitate shipping and installation, the GXT2-6000RT208 ships
without the internal battery installed. Once the UPS is installed in
place, the internal battery pack must be installed.
1. Unpack the internal battery from its shipping container.
2. Lift the battery pack from its container, holding it in the center
of the pack. Do NOT lift the battery pack by grasping the
connector on the rear.
3. Align the battery pack so that the rear connector is nearest the
control panel.
4. Slide in the battery pack until fully inserted.
5. Install the battery door, tightening the two captive screws, finger
tight. The battery door will not install if the battery is not fully
inserted.
6. For tower installation, place the horizontal overlay over the
controls and indicators (see illustration at right).
7. Install the two front bezels.
Ground Electrode System
or Protective Earth System
+
Controls
and
Indicators
Screws
for battery
door
Battery
Compartment
Liebert
V)
144
(
W
2
hi45
!
A
12Vx1
9
-
:
AVERTISSEMENT
+
ADVERTENCIA:
!
!
NING:
WAR
!
Battery
!
Battery cover
Front bezels
16
Back of
battery
Battery
connector
Page 23
7.0INITIAL STARTUPAND ELECTRICAL CHECKS
Initial Startup and the Configuration Program—The UPS ships with a default 120 VAC L-N
setting. This is also the most robust setting in that it can operate with either input phase angle (120
or 180 degrees). Perform initial system checks first. If the UPS configuration needs to be modified for
your application, then go to the next section to review use of the configuration program. Some configuration changes require that the UPS be in the OFF mode while powered from the utility. Therefore,
the installer must confirm that the UPS input has been properly wired. After re-configuring your
UPS, the UPS may be put into service with the intended loads.
Miswiring power to the input terminal block (L1-L2-N-G) or connecting to single phase
voltages (L-N-G only) may damage the UPS.
1. Verify that the Input and Output circuit breakers are off.
2. During initial system checks, disconnect all loads (open load disconnects).
3. Inspect all wiring, cables and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted
in the sockets. Turn on the battery cabinet circuit breaker now.
5. If you are using a distribution box that includes a manual bypass switch, place the switch in
BYPASS position.
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.
7. Using a voltmeter, verify the expected L1-N, L2-N and L1-L2 voltages.
a. If no manual bypass switch is used, there will be no output voltage at this time. If a manual
bypass switch is used, verify that the same voltages appear at the Output terminals. If a
manual bypass switch is used, the Bypass lamp will light by the switch. If no manual bypass
switch is used, there will be no output voltage at this time.
b. If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the
input phase angle is required to be 180 degrees.
c.If the configuration program as been used to set the L-N voltage at 127 VAC, then the input
phase angle is required to be 120 degrees (leading or lagging).
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power,
close all access panels to the distribution box and reapply input power.
9. Close the Input circuit breaker located on the distribution box. The green AC Input indicator
should illuminate on the front panel.
10. Press the On button for 1 second. The Bypass indicator will light for several seconds before the
UPS ON indicator turns on continuously. If the batteries are determined to charged above 80%,
an automatic battery test will run for about 15 seconds.
11. Close the Output circuit breaker on the rear of the UPS. If a manual bypass switch is used, the
UPS Available indicator by the switch will light. If a manual bypass switch is used, transfer the
switch to the UPS position. The output terminal block will be powered at this time.
12. Perform a Manual Battery Test - Press the On button for one (1) second. The front Battery
indicator will light for about 15 seconds and then return to only the UPS ON and AC Input
indicators being illuminated.
13. Review all setting option provided by the configuration program. Some changes require that the
UPS be OFF. If this is the case, these should be programmed before powering the loads. The
configuration program is described in the next section.
14. Connect all loads for normal operation.
Initial Startup and Electrical Checks
17
Page 24
Initial Startup and Electrical Checks
7.1L14-30P Plug-in Connections—Including the PD-001 Distribution Box
WARNING
!
Miswiring power to the input (L1-L2-N-G) or connecting to single phase voltages (L-N-G only)
may damage the UPS. A qualified electrician should verify that the L14-30R is properly wired
before attaching the UPS.
If the configuration program has been used to set the L-N voltage at 100, 110 or 115, then the input
phase angle is required to be 180 degrees.
If the configuration program as been used to set the L-N voltage at 127 VAC, then the input phase
angle is required to be 120 degrees (leading or lagging).
1. Verify that the input and output circuit breakers are off.
2. During initial system checks, unplug all loads (or open load disconnects).
3. Inspect all wiring, cables and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted
in the sockets. Turn on the battery cabinet circuit breaker.
5. If you are using a distribution box that includes a manual bypass switch, place the switch in
BYPASS position.
6. Plug in the UPS input plug.
7. Turn on the branch circuit disconnect to apply voltage to the UPS input.
8. If no manual bypass switch is used, there will be no output voltage at this time. If a manual
bypass switch is used, the Bypass lamp will light by the switch
9. Close the input circuit breaker located on the distribution box. The green Line lamp should
illuminate on the front panel.
10. Press the Start button for 1 second. The Bypass lamp will light for several seconds before the
Inverter lamp turn on continuously. If the batteries are determined to charged above 80%, an
automatic battery test will run for about 15 seconds.
11. Close the output circuit breaker on the rear of the UPS. If a manual bypass switch is used, the
Inverter lamp by the switch will light. If a manual bypass switch is used, transfer the switch to
the Inverter position. The output terminal block will be powered at this time.
12. Perform a Manual Battery Test by pressing the ON button for 1 second. The front Battery lamp
will light for about 15 seconds and then extinguish, leaving only the Inverter and Line lamps
illuminated.
13. Review all setting option provided by the configuration program. Some changes require that the
UPS be OFF. If this is the case, these should be programmed before powering the loads. The
configuration program is described in the next section.
14. Connect all loads for normal operation.
18
Page 25
8.0CONFIGURATION PROGRAM
The final step of installation may require custom configuration of your UPS using the enclosed configuration program. Some configuration settings may be changed only while the UPS is off. These should
be set before the UPS is put into full time service powering the critical load.
For most users operating with 120 VAC L-N and with no external batteries, the factory default settings will be adequate. This manual illustrates the features available for modification, as well as the
factory default setting.
The factory default L-N setting is 120 VAC. When first powered by the AC input, the UPS will autosense the utility phase angle between L1 and L2, setting the UPS to operate as either a 120/208 VAC
system (120 degrees, leading or lagging) or a 120/240 VAC system (180 degrees).
If your application requires that the L1-N, L2-N voltages be set at 100, 110, 115 or 127 VAC, the corresponding phase angle between L1 and L2 is restricted. The VAC settings of 100, 110 and 115 may
work only with a phase angle of 180 degrees. A VAC setting of 127 VAC will work only with a phase
angle of 120 degrees (leading or lagging).
To confirm the phase angle of the utility input, measure the L1-N, L2-N and L1-L2 VAC of the utility
input that is intended for the UPS. If the measured L1-L2 voltage is equal to the average L-N voltage
times 2.0, then the phase angle is 180 degrees and the L-N VAC may be set at 100, 110, 115 or 120
VAC. The nominal L1-L2 voltages for these four settings will be 200, 220, 230 or 240 VAC, respectively.
If the measured L1-L2 voltage is equal to the average L-N voltage times 1.73, then the phase angle is
120 degrees and the L-N VAC may be set at either 120 or 127 VAC. The nominal L1-L2 voltages for
these two settings will be 208 or 220 VAC, respectively.
Configuration Program
Selecting a L-N nominal voltage that is not compatible with the L1-L2 phase angle detected by the
UPS when AC input is applied will result in a fault alarm and the UPS will not operate from utility
power.
8.1GXT2-6000RT208 Configuration Program Features
The configuration program enables the user to perform the following functions:
• Select one of five L-N output voltages to match local voltages
• Enable or disable Auto-Restart
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz
• Set the Low Battery Warning alarm time from 2 to 30 minutes
• Enable or disable the Auto-Battery test
• Set the Auto-Battery test to 7, 14, 21 or 28 days
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculations reported by Liebert software products
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see 11.0 - Com-munications)
8.1.1What You Will Need
In addition to the GXT2-6000RT208 UPS, you will need the configuration program diskette and serial
cable (beige or tan, three-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS
accessory box. A computer—desktop or laptop—running Windows 95
up and run the configuration program.
®
or later is also required to set
!
UPStation GXT
19
Page 26
8.2Configuration Program—Installation
An easy-to-use installation program will streamline the installation of the configuration program. If
you have a previous version of this configuration program installed, it is recommended that it be
uninstalled using its Uninstall program before installing this updated version.
Configuration Program
1. Use the Windows Explorer to find and open the
Lbt_gxt2-1.6.exe installation program on the
included software CD.
2. When you see this PreSetup window, select OK. This will open the main installation screen.
3. Click NEXT to continue installing the configuration program.
Liebert recommends using the default installation options, but you will be given the option to make
modifications to the standard entries.
The installation program will also install an Uninstaller program along with the UPS configuration
program.
20
Page 27
8.3Establishing Communication Link with the UPS
Use only the serial communication cable supplied with the configuration program. If an accessory
communication card has been installed in the UPS’s communication card slot, the option card must be
removed while using the configuration program.
Use the serial communication cable to connect your computer’s COM1 port to the DB-9 communication port on the rear of the UPS. COM2 may also be used. If the COM port of the host computer has
only a DB-25 pin connector, a DB-25 to DB-9 adapter must be added.
The program may be used while the UPS is on to read and confirm the current settings. The UPS
must be off and powered by the AC utility when using the configuration program to change any UPS
setting. Any attempt to change a setting while the UPS is on will result in an error message.
Select Lbt_gxt2.exe from the program group to start the configuration program. The program will
search COM1 & COM2 for a properly connected GXT 2U™ UPS. When the UPS is found, the opening
program window will display the UPS model.
If the configuration program ever fails in its attempt to read data from a UPS, the error message
below will be displayed. The program must communicate with the UPS when it first opens, when a
new tab is opened and when the REFRESH, APPLY or OK buttons are pressed.
Configuration Program
If this message is displayed, check the following items:
1. Verify that the serial communication cable is connected properly.
2. Verify that the COM port being used is designated COM1 or COM2.
3. Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode or Off with AC power
available at the input (AC Input indicator on). In all cases, the rear fan will be running.
4. Verify that the COM port is not in use by other UPS communication software (or non-UPS
software). If MultiLink UPS software is installed on the computer, the MultiLink service must be
stopped to free the COM port. MultiLink typically restarts automatically whenever the computer
restarts.
5. The UPS serial port is in use by an internal, optional communication card in the UPS card slot.
Remove the option card.
6. The program is connected to a UPS that was not designed for this program.
21
Page 28
8.4Configuration Program—Operation
8.4.1Read/Confirm UPS Configuration Settings
The UPS settings may be monitored, but not changed, using the configuration program while the UPS
is operating in any mode. If the program is only used to read the present UPS settings, close the program using the CANCEL button.
Mistakenly using the APPLY or OK button
will attempt to write data to the UPS and will
result in the error message shown at right if
the UPS is not off.
If this message is displayed and you do not
wish to change any settings, close this error
message and close the configuration program
using the CANCEL button.
If the UPS is off and you do not wish to risk changing any settings, close the program using the CANCEL button. Do not use the APPLY or OK buttons in the configuration program.
8.4.2Changing UPS Settings
UPS SETTINGS MAY ONLY BE CHANGED USING THE CONFIGURATION PROGRAM WHEN
THE UPS IS OFF AND NO POWER IS BEING DELIVERED TO THE LOAD. AC input power must
be available to power the UPS logic during programming. Only the AC Line indicator will be on indicating utility input power.
Configuration Program
To turn the UPS off to change configuration settings, press the UPS OFF/Bypass button twice within
four seconds (hold the button one second each time). This will disconnect all power to the load.
Changing any value or selecting/deselecting any setting in the configuration window will not immediately change the settings in the UPS. You may modify the displayed settings until you are satisfied
with the new proposed changes. Settings displayed by the configuration program can always be
restored to the existing values stored in the UPS by selecting the REFRESH key.
Values displayed will be transmitted to the UPS only
when either the APPLY or OK button is selected. The
APPLY button sends the new settings to the UPS without
closing the program. The OK button sends the new settings and closes the program.
Whenever data is successfully transmitted to the UPS,
this message shown at right will be displayed.
8.4.3Programming Rejected?
If the UPS appears to be off but this error
message is displayed when the APPLY or OK
button is selected to transmit settings, the
UPS may be in an intermediate standby condition.
To confirm that the UPS is fully off, repeat the
turn off procedure. Press the UPS OFF/
Bypass button twice within four seconds (hold
the button one second each time).
8.4.4Exit Without Changing UPS Settings
If you decide not to change the UPS after modifying the displayed settings, close the configuration
program using the Cancel button.
22
Page 29
8.5UPS Tab
When the program starts, the following window will open displaying the UPS model along with the
current UPS settings. This information can be updated at any time using the REFRESH button.
Figure 4Factory default settings for 120VAC UPS
Configuration Program
8.5.1Output Voltage
The Output Voltage displayed is the nominal input/output voltage. This is not a voltmeter and will
display the nominal voltage whether the UPS is on or off. The drop down box will show the alternate
voltages available. Select the voltage that matches the nominal utility in your location.
8.5.2Auto Restart
The UPS will provide computer grade power during power outages. If input power is unavailable for
an extended time, the UPS will shut down when batteries are depleted or a shutdown signal is sent by
the computer operating system to limit battery depletion (serial data or contact closure). If Auto
Restart is enabled (check mark in box), the UPS will restart when input power is restored. If the UPS
turns off power to the load for any other reason, manual restart is required (See 8.6 - Options Tab
for exceptions). Click on the box to remove the check mark and disable Auto Restart.
8.5.3L-N Reverse Detection (120V UPS Models Only)
Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression and surge
suppression. The UPS checks the outlet when first plugged in. If the Line-Neutral is reversed or the
ground is missing, the UPS will not start. If a problem is detected after the UPS is started, the UPS
will continue to operate, but the AC Input indicator will flash. In some unique applications the user
may wish to disable this alarm. Except for special situations, improperly wired receptacles should be
immediately repaired before the UPS is put into service. Click on the box to remove the check mark
and disable this alarm.
23
Page 30
8.5.4Frequency Selection
The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the
model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically
sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore,
for all normal use the Auto Sense button should be selected.
Some special applications require that the UPS be used as a frequency converter. Frequency converter 50Hz or frequency converter 60Hz may be selected.
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is
unable to power the load, the alternate bypass to utility power will not be available and power will be
removed from any load.
8.6Options Tab
Computer users may choose to use versatile computer shutdown software that communicates
with the UPS via a serial communications cable.
The Options tab should not be used to modify the
UPS functions for such applications.
For some industrial applications and special
computer applications, the UPS may be monitored and controlled using external voltages and
relay contact signals. The Options tab expands
the UPS versatility for such applications.
Configuration Program
Refer to your UPS manual for a description of the
9-pin communication connector on the rear of the
UPS. Pin 6 of the 9-pin communication connector
is used for “Any Mode Shutdown” of the UPS output. This control input may be used in special
applications to disable the UPS output power both Inverter and Bypass.
The Options tab allows the behavior of the Any
Mode Shutdown feature to be modified.
When the program opens or the REFRESH button is pressed, the UPS setting is read by the
configuration program and displayed.
Factory Default Setting Illustrated - This
Options tab illustration shows the available
function definitions using pin 6 and the factory
default settings.
WARNING
!
Auto-Enable Output
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS
output can turn on automatically and without warning if the Pin 6 connection is changed.
WARNING
!
Pin 6 Logic
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to
install a normally-closed connection between Pins 5 & 6. This connection must be maintained
to use the UPS or to use the configuration program again, including the ability to change the
UPS setting back to the default setting using the configuration program via a serial
communication link.
24
Page 31
8.7Options Tab Used With Earlier GXT 2U Models
This version of the configuration program will accompany GXT 2U UPS models that support new programming features accessible using the Options tab.
If version 1.6 (or later) is used with an earlier GXT 2U model (with an earlier UPS firmware version),
the Any Mode Shutdown features cannot be changed.
If the configuration program is used with an earlier UPS model (with an earlier UPS firmware version) that does not support the modification of these settings, the Options tab will display a reminder
of the factory default settings, as shown. These cannot be changed.
Configuration Program
25
Page 32
8.8Battery Tab
Factory default settings illustrated.
The boxes on the right show the available options using the drop-down selection boxes.
Configuration Program
8.8.1Low Battery Time Warning
The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated
if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30
minutes.
8.8.2Auto Battery Test Time
The UPS performs an automated battery test periodically, if enabled. The user may also select time
periods of 7, 14, 21 and 28 days.
8.8.3Battery Cabinets Number
If additional batteries are attached to the UPS, accurate battery runtime estimates are possible if the
battery number and type of batteries are entered here. The new UPS models are designed to operate
with up to four external battery packs or four long runtime battery packs (not currently available).
8.8.4Auto Battery Test
In some applications it may be preferable to disable the automated, periodic battery test. Click on the
box to remove the check mark and disable the periodic battery test.
26
Page 33
8.9About Tab
The version number of the configuration program may be confirmed using the About Tab.
Configuration Program
27
Page 34
9.0CONTROLSAND INDICATORS
L1
L2
BYPASS
Controls and Indicators
All indicators lit for illustrative purposes.
Vertical overlay
for tower
installation
!
- +
UPStation GXT
UPS ON
BATTERY
AC INPUT
9.1ON/Alarm Silence/Battery Test Button
This button controls output power to connected load(s) and has three functions:
•ON
•Alarm Silence
•Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and
protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the
alarm is silenced, the UPStation GXT2-6000RT208 will reactivate the alarm system to
alert of additional problems.
Horizontal overlay for rack mounting
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON/Alarm Silence/Battery Test
button for at least one second while operating from utility power with no alarm conditions present.
• If only three of the five Battery indicators illuminate, allow the UPS to recharge the batteries for
24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery indicators illuminate, contact your local dealer, Liebert representative or Liebert Worldwide Support Group.
9.2OFF/Bypass Button
This button controls output power to connected load(s) and has dual functions: OFF
and Bypass.
Pressing the OFF/Bypass button twice within 4 seconds shuts off power to the output receptacles and
connected loads, but the UPS’s circuits remain live, charging the unit’s battery.
CAUTION
!
Pressing the OFF/Bypass button once will cause the load to be
transferred to bypass power. Pressing the OFF/Bypass button a second
time within 4 seconds will result in loss of power to the output
receptacles and connected loads. Perform all necessary shutdown
procedures on connected loads before pressing this button twice.
The Load Level indicators display the approximate electrical load placed upon both output legs of the
UPS at all times. Each indicator represents an approximate 25 percent increase in load. For optimum
utilization of the UPS, distribute L-N loads to approximately balance the loads on L1 and L2.
9.4Battery Level Indicators (5 Green)
The Battery Level indicators display approximate battery capacity at all times. Each indicator represents an approximate 20 percent increase in battery capacity.
The UPStation GXT2-6000RT208 is equipped with automatic and remote battery test features. The
automatic test occurs every 14 days (this option is user-configurable) if utility has not been interrupted. Should the battery fail this test, the red Fault indicator along with the A and C diagnostic
indicators will illuminate and an alarm will sound (refer to 13.0 - Troubleshooting). The remote
test feature functions with MultiLink 3 software and can remotely initiate the battery test.
9.5Fault Indicator (Red)
The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the Battery
Level indicators may be illuminated (refer to 13.0 - Troubleshooting section).
9.6Bypass Indicator (Amber)
The Bypass indicator is illuminated when the UPS is operating from bypass power. An alarm will
sound indicating the UPS detected a problem or the manual bypass function has been activated.
9.7UPS ON Indicator (Green)
The UPS ON indicator is illuminated when the UPS inverter is operating and supplying power to
your connected loads.
9.8Battery Indicator (Amber)
The Battery indicator is illuminated when the UPS is operating on battery.
9.9AC Input Indicator (Green)
The AC Input indicator is illuminated when utility power is available and within the input specifications.
29
Page 36
10.0 MODESOF OPERATION
10.1Normal Mode Operation
During normal operation, utility power provides energy to
the UPS. The filters, power factor correction circuit and the
inverter process this power to provide computer grade
power to connected loads. The UPS maintains the batteries
in a fully charged state. The four green Load Level indicators display an approximate level of load in 25% increments.
If the UPS becomes loaded beyond full rating, the fifth
(amber) indicator will illuminate and the UPS will sound an
audible alarm. The display template indicates the percentage of load (see example at right) on the UPS output.
10.2Battery Mode Operation
Battery mode occurs in event of an extreme input voltage
condition or complete utility failure. The battery system
supplies power through the DC to DC converter to the
inverter to generate power for the connected load. During
battery mode an alarm sounds every 10 seconds. This will
change to two beeps every 5 seconds when the battery runs
low (approximately 2 minutes remaining, but this is user
configurable). The AC Input indicator will extinguish and
the Battery indicator will illuminate to warn that a utility
problem has occurred. Each Battery Level indicator represents a 20% capacity level. As capacity decreases, fewer
indicators remain illuminated. Refer to 13.0 - Trouble-
shooting. For approximate battery run times, refer to
Table 7 - Battery run times. These times are approximate
based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off
non-essential pieces of equipment (such as idle computers and monitors) or add the optional external
battery cabinet.
Modes of Operation
Normal Mode Operation
Batteries at 100% charge
L1 Load at 10%, L2 Load at 90%
Battery Mode Operation
Batteries at 30% charge
L1 Load at 60%, L2 Load at 60%
CAUTION
!
Turning OFF the UPS while in battery mode will result in loss of output power.
10.3Battery Recharge Operation
Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger
begins recharging.
30
Page 37
11.0COMMUNICATIONS
r
11.1Communications Interface Port
The UPStation GXT2-6000RT208 UPS has a standard DB-9 serial port female connector located on
the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:
6Remote Shutdown (short to pin 5); all modes of operation
7Low Battery (open emitter)
8Utility Fail (open emitter)
9Utility Fail (open collector)
Communications
Pin Assignment Collector to Emitter*
6789
330 Ohms
54321
* Maximum voltage and current on pins 1, 7, 7 and 9 are 60VDC and 10.0 mA
11.1.1 DB-9 Interface Port
Using the following directions to attach the smaller enclosed ferrite
bead clamp to the communication cable as shown at right:
1. Open the ferrite bead.
2. Place the communication cable inside the ferrite bead groove.
3. Position the ferrite bead as close as possible to the end of the cable
that connects to the DB-9 connector of the UPS.
4. Close the ferrite bead so that the ferrite bead’s case snaps closed
with the cable routed through the ferrite bead’s case.
11.1.2 Communications SNMP Web Card SNMP Adapter
Attach the larger enclosed ferrite bead clamp to the network
cable, see illustration at right, using the following directions:
1. Open the ferrite bead.
2. Place the network cable inside the ferrite bead groove.
3. Wrap the cable once around the ferrite bead.
4. Position the ferrite cable as close as possible to the end of
the cable that connects to the UPS.
5. Close the ferrite bead so that the ferrite bead’s case snaps
closed with the cable routed through the ferrite bead’s case.
Open
(+)
Collecto
Open
(-)
Emitter
Wrap network
cable around
ferrite bead
Run cable
through ferrite
bead case
31
Page 38
11.2Pin 4 - Remote Shutdown on Battery
1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the
utility, Pin 4 will ignore any signal on this pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using
Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is
used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal
a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown
signal for 1.5 seconds, the command cannot be canceled.
3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown signal
will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will
shut down.
4. If the utility returns during the 2-minute timer countdown, the shutdown timer will continue
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10
seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and
restart the server.
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled
or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown
delay.
11.3UPS Intelligent Communications
Communications
The UPStation GXT2-6000RT208 is equipped with an Intellislot® port to provide advanced communication and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or
server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the
network with other computers running MultiLink when you purchase a MultiLink License Kit. For
more information about the Intellislot SNMP/Web Card and MultiLink License Kits, visit our Web
site (www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT2-6000RT208
The Intellislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS
across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coordinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built-in shutdown for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be segregated and run separate from all other power cables, where applicable.
32
Page 39
11.4Remote Emergency Power Off
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply
with national and local wiring codes and regulations.
Figure 5REPO switch connections
REPO Connection
Communications
REPO
as shipped
Key to REPO switch connections
1.24 VDC
2.Sense
3.Sense
4.Ground
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be segregated and run separately from power cables.
REPO connections
for normally open
switch system
12341234
REPO connections
for normally closed
switch system (fail-safe)
1234
33
Page 40
12.0 MAINTENANCE
The UPStation GXT2-6000RT208 requires very little maintenance. The batteries are valve-regulated,
non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The
UPS continuously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries periodically will permanently degrade battery capacity.
The UPStation GXT2-6000RT208 is designed to allow the user to safely replace the internal batteries.
Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to
obtain the appropriate replacement battery kit part number and pricing.
12.1Battery Replacement
CAUTION
!
A battery can present a risk of electrical shock and high short circuit Current. The following
precautions should be observed before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
Maintenance
12.1.1 Internal Battery Replacement Procedures
1. Gently remove the front plastic bezels cover
from the UPS by pulling forward.
2. Loosen the two captive screws on the front
battery door. Lay the battery door aside for
reassembly.
3. Grasp the battery pack assembly and pull it out
of the front of the UPS. Be prepared to support
the weight of the battery as it is withdrawn.
4. Unpack the new battery assembly taking care
not to destroy the packing. Compare new and
old battery assemblies to make sure they are the
same. If so, proceed with Step 6; otherwise
STOP and contact your local dealer, Liebert
representative or the Liebert Worldwide
Support Group.
5. Line up and slide in the new replacement
battery pack.
6. Reattach the front battery door, tightening the
two captive screws finger tight.
7. Reattach the front plastic bezels to the UPS.
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages.
Battery
Battery Cover
!
UPS
!
12Vx12(144V)
9Ahi45W
-
:
AVERTISSEMENT
+
ADVERTENCIA:
!
!
NING:
WAR
Front Bezels
Liebert
!
Battery Cover
Captive Screws
34
Page 41
12.2UPS Replacement
When using a power distribution box with bypass, the UPS can be removed while powering the load
through the Bypass Switch.
NOTE
During the procedure, the connected load will not be protected from power disturbances, such
as spikes, sags and failure.
To remove the UPS without shutting off power to the connected load:
1. Turn the Bypass Switch on the power distribution box to the Utility position.
2. Open the Output circuit breaker (on the UPS rear panel).
3. Open the Input circuit breaker (on the power distribution box).
4. Loosen the three captive mounting screws about
20 turns until the power distribution box can be
pulled away from the UPS.
5. Loosen the electrical connector cover by backing
out the two screws holding it one turn each. Also
loosen the end screw one turn.
6. Slide the cover to reach the end screw and cover
the electrical connectors; retighten the three
screws gently to hold the cover in place.
7. Replace the UPS.
8. Loosen the three screws holding the electrical
connector cover again—one turn each.
9. Slide the cover away from the electrical
connectors; gently retighten the three screws.
10. Align the connectors on the power distribution
box and the UPS.
11. Push the power distribution box into place.
12. Holding the power distribution box firmly
against the UPS, tighten the three captive
mounting screws until the box is secure. Do NOT
overtighten the screws.
13. Close the Input circuit breaker (on the power
distribution box).
14. Close the Output circuit breaker (on the UPS
rear panel).
15. Turn the Bypass Switch on the power
distribution box back to the UPS position.
Electrical
connector
cover
DISCONNECT BYPASS POWER TO
THE MANUAL BYPASS SWITCH.
Mounting screws
for removable power
distribution box
Screws securing electrical
connector cover
Maintenance
35
Electrical connectors
Page 42
13.0 TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the UPStation
GXT2-6000RT208 develops a problem. Use this information to determine whether external factors
caused the problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS has detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional Load Level/Battery Level indicators will be illuminated to provide a
diagnostic aid to the operator, as described below:
Troubleshooting
AB C D E
Fault
indicator
Battery
indicators
Load Level
indicators
AC Input
indicator
UPS ON indicatorBattery indicator
Bypass
indicator
Table 4Fault indicators
Indicator status
All indicatorsOn bypass due to output overload; beep every half-second
Indicator A
Indicator B
Indicator C
Indicator D
Indicator E
Indicators A&BInverter-to-Inverter communications failure; half-second beep every 1 second
Indicators A&CUPS failed battery test; 2-second beep every 60 seconds
Indicators A&DL1 to L2 phase angle unacceptable
Indicators B&CREPO is currently activated, UPS output cannot be started by any method
Indicators B&D
Indicators C&EUPS shutdown due to command from communications (RS232 or SNMP); no beep
Indicators D&EUPS is OFF due to charger overvoltage; 1-second beep every 4 seconds
AC Input indicator On &
Battery indicator Flashing
Bypass indicator Flashing
On bypass due to overtemperature condition on L1; 1-second beep every 4 seconds
On bypass due to overtemperature condition on L2; 2-second beep every 4 seconds
On bypass due to DC bus overvoltage on L1; 1-second beep every 4 seconds
On bypass due to DC bus overvoltage on L2; 2-second beep every 4 seconds
On bypass due to control power supply failure on L1; 1-second beep every 4 seconds
On bypass due to control power supply failure on L2; 2-second beep every 4 seconds
On bypass due to PFC failure on L1; 1-second beep every 4 seconds
On bypass due to PFC failure on L2; 2-second beep every 4 seconds
On bypass due to inverter failure on L1; 1-second beep every 4 seconds
On bypass due to inverter failure on L2; 2-second beep every 4 seconds
UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is
restored, press the OFF button twice within four seconds (to clear the alarm), then press the
ON button to start UPS (Auto-restart is NOT possible).
AC input has been applied to start UPS but the batteries are either missing or below the
minimal level to allow the UPS to start; continuous audible alarm
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside
acceptable limits
Diagnosis/Audible alarm
Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger
is operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Support Group. Please have the UPS model number and serial number available at the time of
your inquiry.
36
Page 43
Troubleshooting
All audible alarms can be silenced, with the exception of Low Battery, Bypass Reminder and Missing
Batteries at Startup alarms. Once silenced, the alarm will not sound again until a new alarm condition is present.
Table 5Alarm conditions
ConditionAlarm
Battery Mode (utility failure)One short beep every 10 seconds; more than 2 minutes of run time remaining
Low BatteryTwo short beeps every 5 seconds; less than 2 minutes of run time remaining
On Bypass ReminderA one-second beep every 2 minutes
Output Overload (bypass)One short beep every half second
Overtemperature (bypass)A one-second, or two-second, beep every 4 seconds
DC Bus Overvoltage (bypass)A one-second, or two-second, beep every 4 seconds
Control Power Supply Failure (bypass)A one-second, or two-second, beep every 4 seconds
PFC Failure (bypass)A one-second, or two-second, beep every 4 seconds
Inverter FailureA one-second, or two-second, beep every 4 seconds
Inverter-to-Inverter Communications
Failure
Battery Test FailureA two-second beep every 1 minute
REPO ActivatedA one-quarter second beep every half second
A one-half second beep every 1 second
Table 6Troubleshooting guide
ProblemCauseSolution
UPS fails to start when the
ON button is pressed.
Battery indicator is
illuminated.
UPS has reduced battery
time.
Fault and Bypass indicators
and all Load Level indicators
are illuminated.
Fault and Bypass indicators
and diagnostic indicator C are
illuminated.
Fault and Bypass indicators
and diagnostic indicator D are
illuminated.
Fault and Bypass indicators
and diagnostic indicator A are
illuminated.
UPS is short-circuited or
overloaded.
UPS not plugged in.
UPS input protection fuse
has blown/opened.
Utility voltage out of UPS
input range.
Batteries are not fully
charged.
UPS is overloaded.Check load level display and reduce the load on the UPS.
Batteries may not be able to
hold a full charge due to age.
UPS overloaded or load
equipment is faulty.
UPS control power supply
fault.
UPS PFC (Power Factor
Correction Circuit) fault.
UPS internal fan has a
problem or UPS shutdown
due to temperature
condition. Load is on bypass
power.
Ensure the UPS is OFF. Disconnect all loads and ensure
nothing is lodged in output receptacles.
Ensure the loads are not defective or shorted internally.
UPS is operating in Battery Mode, make certain UPS is
securely plugged into the wall receptacle.
UPS is operating in Battery Mode. Save data and close
applications. Replace UPS input fuse, then restart UPS.
UPS is operating in Battery Mode. Save data and close
applications. Ensure utility supply voltage is within
acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to
recharge batteries.
Replace batteries. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group for
replacement battery kit.
Check load level display and remove non-essential loads.
Recalculate the load and reduce number of loads
connected to UPS. Check load equipment for faults.
UPS requires service. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
Ensure the UPS is not overloaded, ventilation openings
are not blocked and room ambient temperature is not
excessive.
Wait 30 minutes to allow UPS to cool, then restart UPS.
If UPS does not restart, contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
37
Page 44
Table 6Troubleshooting guide
ProblemCauseSolution
Troubleshooting
Fault and Bypass indicators
and diagnostic indicator B are
illuminated.
Fault and Bypass indicators
and diagnostic indicator E are
illuminated.
Fault and Bypass indicators
and diagnostic indicators A
and B are illuminated.
Fault indicator and diagnostic
indicators A and C are
illuminated.
Fault indicator and diagnostic
indicators A and D are
illuminated.
Fault indicator and diagnostic
indicators B and C are
illuminated.
Fault indicator and diagnostic
indicators B and D are
illuminated.
Fault indicator and diagnostic
indicators C and E are
illuminated.
Fault indicator and diagnostic
indicators D and E are
illuminated.
AC Input indicator is On &
Battery indicator is flashing.
Bypass indicator is flashing.
UPS internal DC bus
overvoltage.
UPS inverter fault.
Inverter-to-Inverter
Communications Failure
UPS failed the battery test.
L1 to L2 phase angle
unacceptable.
REPO is currently activated.
UPS output is OFF from a
previous REPO command.
REPO is no longer activated.
UPS shutdown due to a
command from the
communications port(s).
UPS charger fault.
Battery source is not
available; continuous horn.
Bypass voltage is present,
but is disabled for use
because the voltage or
frequency is outside
acceptable limits.
UPS requires service. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
Representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
Representative or the Liebert Worldwide Support Group.
Replace batteries. Contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
Only phase angles of 120, 180 or 240 degrees (±10
degrees) are permitted. These must be compatible with
the selections in the configuration program.
Or the phase angle has changed while the UPS was
running. The phase angle is detected at startup and
cannot be changed to a different power source while
running.
Turn the UPS Off and wait until the fans stop. Apply input
AC power. The UPS will reprogram the phase angle to
match the utility, if the utility is 120, 180 or 240 degrees
between L1 and L2. If this does not resolve the issue,
contact a qualified electrician to verify the site wiring.
UPS has shut down due to the REPO (Remote Emergency
Power Off). The output cannot be started by any method.
UPS is OFF due to previous REPO (REPO is no longer
activated). Once utility power is restored, press the OFF
button twice within four seconds (to clear the alarm), then
press the ON button to start UPS (Auto-restart is NOT
possible).
Your UPS has received a signal or command from the
attached computer. If this was inadvertent, ensure the
communication cable used is correct for your system. For
assistance, contact your local dealer, Liebert
representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert
Representative or the Liebert Worldwide Support Group.
Check battery connections, completely power down and
restart UPS.
NOTE: If the battery circuit opens while the UPS is
running, it will be detected when the next battery test is
performed.
The AC input powers the PFC input and serves as the
bypass source. If the AC is present but the voltage or
frequency exceeds the acceptable range for safe
operation with a load, the bypass will be disabled and this
indicator will flash, indicating that the bypass is
unavailable.
38
Page 45
Troubleshooting
Using the configuration program, the user may specify the number of GXT2-144VBATT external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 7 shows estimated run times at different loads.
As batteries age, the estimated run times may become less accurate. The GXT2-6000RT208 is programmed to “learn” from a full battery discharge and modify the estimated run time for the measured
battery capacity. This can improve accuracy and compensate for aging batteries or batteries that
operate at different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the
battery table on the right will be restored. This will override any value that is automatically learned.
Troubleshooting
40
Page 47
14.0 SPECIFICATIONS
Table 8UPS specifications
Model NumberGXT2-6000RT208
4200W/5200VA at 127/220 (120 or 240 degrees only)
4200W/5200VA at 120/208 (120 or 240 degrees)
Model Rating
DIMENSIONS in (mm)
Unit W x D x H in. (mm)6.9 x 24.2 x 16.9 (176 x 615 x 430)
Shipping W x D x H in. (mm)13.2 x 27.8 x 20.9 (335 x 705 x 530)
WEIGHT lbs (kg)
Unit 67 (30.3)
Shipping76.3 (34.6)
INPUT AC PARAMETERS
Nominal Operating Frequency50 or 60 Hz (Factory Default = 60)
Factory Default VAC120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase
Allowable Input Phase Angle
Factory Default L1-N, L2-N VAC120 VAC nominal
User Configurable L1-N, L2-N VAC100/110/115/120/127 VAC (May be modified using configuration program)
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)
100% - 70% loading80 VAC - 140 VAC
70% - 30% loading70 VAC - 140 VAC
30% - 0% loading60 VAC - 140 VAC
L1-N, L2-N Max. Allowable VAC150 VAC
Input Frequency w/o Battery
Input Power ConnectionSee Distribution Box Options
OUTPUT AC PARAMETERS
Factory Default VAC120/208 VAC @ 120 degrees
L1-L2 Factory Default
Output Phase Angle
Allowable Output Phase Angle120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC120 VAC nominal
User Configurable L1-N, L2-N VAC100/110/115/120/127 VAC, ±3%
Output ConnectionsSee Distribution Box Options
Main Mode Overload200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Bypass Protection Limits
Disable Bypass operationIf input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operationIf input voltage returns to within ±10% of nominal output voltage
Disable Bypass operationWhen the input frequency prevents synchronous operation
Angle
120, 180, 240 degrees, Auto-sensing on application of AC
Operation
Frequency50 Hz or 60 Hz, Nominal
WaveformSinewave
4200W/6000VA at 120/240 (180 degrees)
4200W/6000VA at 115/230 (180 degrees only)
3780W/5400VA at 110/220 (180 degrees only)
3360W/4800VA at 100/200 (180 degrees only)
120 degrees
(Restrictions for L-N voltages other than 120 VAC)
40 - 70 Hz
120 degrees
Specifications
41
Page 48
Table 8UPS specifications (continued)
Model NumberGXT2-6000RT208
ENVIRONMENTAL
Operating Temp+32°F to +104°F (0°C to +40°C)
Storage Temp+5°F to +122°F (-15°C to +50°C)
Relative Humidity0% to 95%, non-condensing
Operating ElevationUp to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation50,000 ft. (15,000 m) maximum
Audible Noise
AGENCY
SafetyUL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMIFCC Part 15, Subpart B, Class A
Surge ImmunityIEEE/ANSI C62.41 Category A & B
TransportationISTA Procedure 1A
Table 9Battery specifications
Model NumberGXT2-144BATKIT
DIMENSIONS in (mm)
Shipping W x D x H in. (mm)13.4 x 27.2 x 13.4 (340 x 690 x 340)
WEIGHT lbs (kg)
Unit 79 (35.8)
Shipping 84 (38.1)
TypeValve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating12 x 12V x 9.0 AH
Battery Mfg / Part #Yuasa / REW 45-12 FR
Back-Up TimeSee Table 7 - Battery run times
Recharge Time6 Hours to 90% capacity after full discharge into 100% load
Specifications
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
Table 10Power distribution box specifications
Model NumberPD-HDWR
Amp Rating24 Amps
Input Power Connection4-Wire Hardwired, 8-10AWG
Output Power Connection4-Wire Hardwired, 8-10AWG
Input Branch Circuit Breaker30 Amp, Supplied by User
Model NumberPD-HDWR-MBS
Amp Rating24 Amps
Input Power Connection4-Wire Hardwired, 8-10AWG
Output Power Connection4-Wire Hardwired, 8-10AWG
Includes:Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker30 Amp, Supplied by User
Model NumberPD-001
Amp Rating24 Amps
Input Power ConnectionsL14-30P on 10 foot cord
Output Power Connection
L1-L2-G(1) L6-30R on a 300mm cord
L1-L2-N-G(1) L14-30R on a 300mm cord
L1-N-G(2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
L2-N-G(2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
Includes:Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker30 Amp, Supplied by User
42
Page 49
Table 11External battery cabinet specifications
Model NumberGXT2-144VBATT
Used w/ UPS ModelGXT2-6000RT208
DIMENSIONS in (mm)
Unit (with bezel) W x D x H3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping W x D x H10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT lbs (kg)
Unit93.6 (42.5)
Shipping105 (47.6)
BATTERY PARAMETERS
TypeValve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating12 x 12V x 9.0 AH
Battery Mfg / Part #Yuasa / REW 45-12 FR
Back-Up TimeSee Table 7 - Battery run times
ENVIRONMENTAL
Operating Temp+32°F to +104°F (0°C to +40°C)
Storage Temp+5°F to +122°F (-15°C to +50°C)
Relative Humidity0% to 95%, non-condensing
Operating ElevationUp to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation50,000 ft. (15,000m) maximum
AGENCY
SafetyUL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMIFCC Part 15, Subpart B, Class A
TransportationISTA Procedure 1A
Specifications
14.1Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
43
Page 50
Specifications
44
Page 51
Page 52
POWER AVAILABILITY
GXT2-6000RT208
The Company Behind the Products
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
•Environmental systems—close-control air
conditioning from 1 to 60 tons
•Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
•Integrated systems that provide both
environmental and power protection in a
single, flexible package
•Monitoring and control—from systems of any
size or location, on-site or remote
•Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SL-23170 (8/03) Rev. 0
™
USER MANUAL
Technical Support/Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@liebert.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114