The UPS must be commissioned by a Liebert - approved engineer
before it is put into service. Failure to observe this condition will
invalidate any implied warranty .
Do not apply power to this equipment before it has been
commissioned by a Liebert - approved engineer. He will validate
the installation work and install ' site information ' into the
micro-controller memory. This information is required to
substantiate any warranty claims that might be made.
If you find any problems with the procedures in this manual, seek
immediate assistance from the Liebert distributor or agent from
whom you purchased the equipment.
Do not attempt to service this product yourself .It contains no user
serviceable parts. All servicing must be referred to qualified
personnel.
Qualified personnel should be consulted if liquid spills into the
product.
The UPS is for indoor use only.
It must be protected from rain or excessive moisture and installed
in clean environment , free from flammable liquids, gasses , or
corrosive substances. Do not put drinks, plants, or any other
containers holding liquids, on top of the unit.
Ventilation grills are provided beneath and at the rear of the
cabinet. Do not block or cover these openings otherwise
overheating may occur and UPS operation become unreliable.
Never poke anything through the ventilation holes or openings.
Do not place magnetic storage media on top of the unit as it can
corrupt the data stored on them.
Electromagnetic Compatibility
WARNING
This is a Class A UPS product. In a domestic environment this
product may cause radio interference, in which case the user
may be required to take additional measures.
Limits on use:
WARNING
This UPS should not be supplied from electrical power
systems of the 'IT' (Impedance a Terre ) type.
(IEC 364-ELECTRICAL INSTALLATION OF
BUILDINGS)
Content
Chapter 1 Introduction
1.1 Application
1.3 System Function Block
1.4 Features
Chapter 2 Installation
2.1 Unpacking Inspection
2.2 Outline and Panel Description
2.2.1 Outline
2.2.2 Front Panel
2.2.3 Rear Panel
2.3 Installation
2.3.1 Important Note
2.3.2 Installation Procedure
2.4 Connection of External Batteries
Chapter 3 Operation
3.1 Operating Mode
3.1.1 Normal Mode
3.1.2 Bypass Mode
3.1.3 Battery Mode
3.1.4 ECO Mode
3.1.5 Failure Mode
3.2 Operation
3.2.1 Startup and Initialization
3.2.2 Turn On the Inverter
3.2.3 Manual Battery Self-testing
3.2.4 Turn off the Inverter
3.2.5 Totally Shutdown the System
1
1
1
2
5
5
5
5
7
8
8
8
10
13
17
17
17
18
18
19
20
21
21
22
24
25
26
3.2.6 LCD Panel Operation
Chapter 4 Maintenance and Storage
26
27
I. Battery Maintenance
II. Keep Air Vent Unblocked
III. UPS State Check
IV. Function Inspection
Chapter 5 Troubleshooting
Appendix 1 LCD Panel Displays and Operation
1. Constitution of Display Panel
2. Function of display Panel
3. Menu Operation
4. Information LCD-displaying Priority
Relay Communication Mode
Appendix 2 Product Specification
Appendix 3 Accessories
27
28
28
28
31
35
35
36
39
42
43
46
49
6 Chapter 1 Product Introduction
1.1 Application
GXT2-3X1 Series UPS provides high quality AC power to your precision instrument. It
can be applied in Computer Center , Network Management Center, Communication
System, Automation Control System, precision instrument or other Critical Systems.
1.2 Classification
" GXT2-3X1 " Series include 10kVA, 15kVA and 20kVA UPS products, shown in the
following table:
Capacity 10kVA 15kVA 20kVA
Model GXT2-3X1-0100L GXT2-3X1-0150L GXT2-3X1-0200L
Description Extended Battery
Cabinet is required
Chapter 1 Introduction
Extended Battery
Cabinet is required
Extended Battery
Cabinet is required
1.3 System Function Block
System can run with as a single UPS, or in Hot-standby mode to increase the system
reliability (Refer to figure 1-2).
Short circui t c able
for hot standby
Utility
bypass breaker
Rectifier
Utility Switch
Charger
Battery
Group1
Maintenance bypas s
bypass
Inverter
Battery
Group 2
Figure 1-1 single UPS module
Elec tronic
Transfer
Switch
Maint enance
switch
Load
E1-20010329-C-1.0
Chapter 1 Product Introduction 7
Maint enance bypas s
Utility
1.4 Features
GXT2-3X1 Series Three phase input/Single phase output 10kVA/15kVA /20kVA UPS
is an advanced, intelligent, Online with Sinusoidal waveform output UPS system. The
system adopts high-frequency double conversion topology structure with high input
power factor, wide input voltage range, with the following Key features:
Back up
UPS
bypas s B reaker
Utility Break er
Charger
bypas s
Recti fier
Battery
Battery
Group1
Group 2
Figure 1-2 hot-standby system
Inverter
Elec tronic
Transfer
Switch
Master UPS
Load
Maint enance
switch
UPS can operate with loss of input phases (up to 2 phases)
Digital Signal Processing (DSP) Controlled.
Self- diagnostic
Intelligent battery management
LCD & LED annunciation
Static by pass
Maintenance bypass
Large internal charger
E1-20010329-C-1.0
Chapter 2 Installation
2.1 Unpacking Inspection
1. Unpack the packing box to move the UPS to position , be careful not to drop it as it is
heavy.
2. In the event of product damage due to transportation, please notify Liebert or its
authorized agent.
2.2 Outline and Panel Description
2.2.1 Outline
Chapter 2 Installation 9
LCD Display Panel
Ventilation holes on front panel
Figure 2-1 UPS Front view
Supporting caster
Adjustable Footpad
E1-20010329-C-1.0
10 Chapter 2 Installation
Air-inlet holes on Front Panel
Utility Switch
Bypass Switch
Maintenance Switch
Figure 2-2 Front view without panel
Utility
Fault
On/Silence Key
Off Key
Figure 2-3 LCD display Panel
Scroll Key
Battery
Inverter
Bypass
LCD Display
Enter Key
E1-20010329-C-1.0
Chapter 2 Installation 11
contact closure port
Alarm Relay Port
Ventilation holes
Input/Output Terminals block
Figure 2-4 rear panel
2.2.2 Front Panel
Parts' Function Description
Input Switch Used for controlling the utility input to UPS.
Bypass Switch Used for controlling the bypass input to UPS
Maintenance
switch
Front Panel air
inlet hole
LCD Panel and Description is in Appendix 1 in detail.
2.2.3 Rear Panel
Parts' Function Description
Input/output
terminals
Contact closure port Provide Optical Coupler Dry Contact control
For switching UPS to maintenance bypass.
Note: To be operated by trained technical Personnel only.
for ventilation of UPS
Used for UPS input/output cable connection and
external battery connection for UPS
signal, for OS and UPS shutdown.
bProvide relay Dry Contact alarm/ control signal,
E1-20010329-C-1.0
12 Chapter 2 Installation
Heat Dissipation and
ventilation holes
2.3 Installation
2.3.1 Important Note
1. Please position the UPS on the flat ground/surface ..
2. The distance from the rear and side panels of the UPS to the wall or other equipment
should be greater than 20cm, and the air inlets on the front panel and at the bottom of
the UPS should be kept unobstructed to facilitate ventilation and heat dissipation.
3. Please ensure that the UPS is installed in an environment in compliance with UPS
environmental specification.
4. Avoid using the UPS in dusty or corrosive environment.
It can be included in monitoring system defined
by users .
Used for heat dissipation and ventilation of UPS
5. Even if the UPS is shutdown, there could be high voltage inside, untrained personnel
must not open the UPS as there may be danger of electric shock.
6. Install four-pole or three-pole interactive circuit breaker with capacity higher than
80A(suitable for 10kVA system)or 125A( for 15kVA/20kVA system)on the hot line
of Three-phase utility input to isolate the input source in case of emergency. When
using three-pole interactive circuit breaker, utility neutral line need not go through the
circuit breaker and can be connected with UPS' neutral line directly.
7. Please use right cable connection method to ensure the safety of UPS or customer
equipment::
W
Input hot
U
V
N
line
Input neutral
line
U
P
S
output hot
line
output
neutral line
Load
4-pole Interactive
circ uit break er
E
Figure 2-5(a) right cable connection
E1-20010329-C-1.0
Chapter 2 Installation 13
U
V
W
N/E
Warning
Classified according to European standard EN55022 , this is an A level UPS product.
When it is used in family house, it may generate radio interference, user should take
other measures in this condition.
2.3.2 Installation Procedure
Input hot
line
Input neutral
line
Figure 2-5 (b) wrong cable connection
U
P
S
output hot
line
output
neutral li ne
Load
1. Prior to any wire connection, please confirm that all the input and output circuit
breakers are in “OFF”state;
2. As shown in Figure 2-6, connect the input cables(three hot lines, neutral line and
earth line)to the correspondent terminals and secure the screw;
Note
Please do not reverse connection of the input hot line and neutral line!
Because the input default configuration of system's U phase is bypass input, please
ensure the proper connection of U phase.
Please don't use the power source socket on the wall as the UPS' input source.
3. Connect the input cables (hot lines, neutral line and earth line)of user's equipment
to the correspondent UPS output terminals refer , figure 2-6 .
Note
When connecting the input and output cables, the input hot line and neutral line must
be connected correctly and the UPS must be connected to earth firmly.
E1-20010329-C-1.0
Loading...
+ 29 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.