WARNING: Do not attempt to service this product yourself except to replace
the battery. Opening or removing the cover may expose you to dangerous
voltages, even when the AC cord is disconnected from the electrical outlet.
Refer all servicing to qualified service personnel.
1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS
IMPORTANT INSTRUCTIONS THAT SHOULD BE FOLLOWED
DURING INSTALLATION AND MAINTENANCE OF THE
UNINTERRUPTIBLE POWER SYSTEM (UPS) AND BATTERIES.
CONSERVER CES INSTRUCTIONS. CETTE NOTICE CONTIENT
DES INSTRUCTIONS IMPORTANTES CONCERNANT LA
SÉCURITÉ.
2. This product is not intended for use with life support and other
U.S. FDA designated “critical” devices. See Limited Warranty.
3. CAUTION: A BATTERY PRESENTS A RISK OF ELECTRICAL
SHOCK OR BURN FROM HIGH SHORT CIRCUIT CURRENT.
OBSERVE PROPER PRECAUTIONS.
ATTENTION: UNE BATTERIE PRESENT UN RESQUE DE CHOC
ÉLECTRIQUE OU DE BRÛLURE PAR TRANSFERT D’ÉNERGIE.
SUIVRE LES PRÉCAUTIONS QUI S’IMPOSENT.
4. WHEN REPLACING THE BATTERIES, USE THE SAME NUMBER
AND TYPE OF BATTERIES. PROPER DISPOSAL OF BATTERIES IS
REQUIRED. REFER TO YOUR LOCAL CODES FOR DISPOSAL
REQUIREMENTS.
POUR LE REMPLACEMENT, UTILISER LE MÉME NOMBRE ET
TYPE DE BATTERIES. L’ÉLIMINATION DES BATTERIES EST
RÉGLE-MENTÉE. CONSULTER LES CODES LOCAUX À CER
EFFET.
5. Read all safety and operating instructions before operating the UPS.
Adhere to all warnings on the unit and in this manual. Follow all
operating and user instructions.
6. Turn the UPS off and unplug it before cleaning. Use only a soft cloth,
never liquid or aerosol cleaners.
7. The UPS is designed for data processing equipment. Do not plug
appliances, such as hair dryers, heaters, vacuum cleaners, or electric
drills, into the UPS output receptacles.
8. WARNING: Do not modify input cable. Consult your dealer if
connector does not match the utility receptacle. The UPS must be
grounded at all times while in use. Turn the UPS off before unplugging
2
it, or the safety ground will be removed. Operate UPS only from a
properly grounded 120 VAC outlet (2 wire plus ground).
9. The UPS is equipped with a grounded NEMA 5-15P or L5-30P input
power plug (depending upon model). Do not defeat the safety purpose
of this plug. If unable to fully insert the plug into the wall outlet, contact
a qualified electrician for assistance.
10. Route power supply cords so they are not walked on or pinched.
11. Never block or insert any object into the ventilation holes or other
openings. Maintain a clearance of four (4) inches (102 mm) around the
UPS for proper air flow and cooling.
12. Always turn off the UPS and unplug it before starting the battery
replacement procedure. Servicing of batteries should be performed or
supervised by personnel knowledgeable of batteries and the required
precautions. To replace batteries, refer to the battery replacement
procedure. If you feel unqualified to replace the batteries, do not open
the battery door. Refer all servicing to qualified service personnel.
13. CAUTION: Do not open or mutilate the batteries. Released
electrolyte is harmful to skin and eyes and may be toxic.
3
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure™ Interactive
Uninterruptible Power System (UPS). It provides conditioned power to
microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission it
may be subject to voltage sags, spikes, or complete power failure which may
interrupt computer operations, cause data loss, or even damage equipment. The
PowerSure™ Interactive protects equipment from these disturbances.
The PowerSure™ Interactive comes in nominal power ratings of 700, 1000, 1400,
or 2200 VA. Complete specifications appear near the end of this section.
The PowerSure™ Interactive is a compact, “line interactive” UPS. A “line
interactive” UPS continuously conditions and regulates its output voltage, whether
the utility power is present or not. It supplies connected equipment with clean
sinewave power, to simulate as much as possible, the power generated by the
utility. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the PowerSure™ Interactive contains a light emitting diode (LED)
bar display to indicate “load percentage” or “battery capacity” depending upon the
mode of operation. It also provides self diagnostics, a combination alarm
silence/battery test button, and two levels of alarms when the unit is operating on
battery.
The PowerSure™ Interactive has an interface port for communications between the
UPS and a LAN server or other computer system. This port provides detailed
operating information including voltages, currents, and alarm status to the host
system when used in conjunction with Liebert SiteNet® software. SiteNet®
software can also remotely control UPS operation.
CAUTION: This equipment has been tested and complies with limits for a Class A
digital device, pursuant to Subpart B of Part 15 of FCC rules. These limits provide
reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy. If it is not installed and used in accordance with the
instruction manual, it may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference which the user must correct at his own expense.
4
MAJOR COMPONENTS
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS
These UPS components provide surge protection and filter Electromagnetic
Interference (EMI) and Radio Frequency Interference (RFI). They minimize any
surges or interference present in the utility line and keep the sensitive equipment
protected.
AUTOMATIC VOLTAGE REGULATOR
In normal operation, the Automatic Voltage Regulator (AVR) passes utility AC
power to the connected load. When utility power voltage is outside acceptable
limits, the AVR activates. It raises undervoltage power and lowers overvoltage
power. This keeps the UPS output voltage within the connected equipment’s
tolerances and allows wide utility voltage fluctuations without utilizing battery
power.
BI-DIRECTIONAL CONVERTER
In normal operation, the bi-directional converter “converts” utility AC power into
regulated DC power to “float” charge the battery system. Upon a utility power
failure, the bi-directional converter receives its required energy from the battery and
“inverts” it into precise, regulated sinewave AC power. Charging takes place
whenever the UPS is plugged into the wall outlet whether it is ON or OFF and utility
power is within acceptable limits.
BATTERY
The PowerSure™ Interactive utilizes valve regulated, nonspillable, lead acid
batteries. At typical room temperatures and with the UPS float charging, the
battery system will last many years. For battery run times, refer to the Typical
Battery Discharge Curves.
INPUTOUTPUT
L
and
EMI/RFI Filters
Battery
N
G
TVSS
Automatic
Voltage
Regulator
Bi-Directional
Converter
L
N
G
5
MINI-TOWER INSTALLATION
1. Unpack the UPS carefully noting the packing method. Retain the box and
packing material for possible future shipment.
CAUTION: The UPS is heavy (see specifications). Take proper precautions
when lifting or moving it.
2. Visually inspect the UPS for freight damage. Report damage to the carrier and
your dealer.
3. Locate the UPS indoors where it cannot be accidentally disconnected. Locate
it in an area with unrestricted airflow, away from water, flammable liquids,
gases, corrosives, or conductive contaminants. Maintain a minimum of four (4)
inches (102 mm) clearance around the UPS. Maintain an ambient temperature
range of 32° to 104° F (0° to 40° C).
NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery
life.
4. Ensuring load equipment is turned off, plug all loads into the UPS output
receptacles.
5. Plug the UPS into a dedicated wall receptacle properly protected by a circuit
breaker or fuse in accordance with the National Electric Code (ANSI/NFPA 70)
or local codes. Use a 15 amp rated device for the 700, 1000, or 1400 VA
units, and a 30 amp device for the 2200 VA unit. The wall receptacle must be
grounded.
6. Turn on the UPS, by pressing the On/Off button, then turn on the connected
load equipment. The UPS is ready for normal operation.
6
RACKMOUNT INSTALLATION
1. Unpack the UPS carefully noting the packing method. Retain box and packing
material for possible future shipment.
CAUTION: The UPS is heavy (see specifications). Take the proper
precautions when lifting or moving the UPS.
2. Visually inspect the UPS for freight damage. Report any damage to the carrier
and your dealer.
3. Locate the UPS indoors where it cannot be accidentally disconnected. Locate
it in an area with unrestricted airflow, away from water, flammable liquids,
gases, corrosives, or conductive contaminants. Maintain a minimum of four (4)
inches (102 mm) clearance in front and rear of the UPS. Maintain an ambient
temperature range of 32° to 104° F (0° to 40° C).
NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery
life.
4. Gently lay UPS on its bottom side so that the front bezel is facing you.
5. The Rackmount UPS must be supported by a shelf or rails. The front bezel will
not support the weight of the UPS.
CAUTION: To increase the stability of the rack enclosure, place the UPS in the
lowest possible rack position.
6. Refer to the Installation instructions supplied with the Rack Slide or Shelf Kits
to complete the installation procedures.
7. After the UPS has been installed in the Rack enclosure, plug the UPS into a
dedicated wall receptacle properly protected by a circuit breaker or fuse in
accordance with the National Electric Code (ANSI/NFPA 70) or local codes.
Use a 15 amp rated device for the 700, 1000, or 1400 VA units, and a 30 amp
device for the 2200 VA unit. The wall receptacle must be grounded.
8. Ensuring load equipment is turned off, plug all loads into the UPS output
receptacles.
9. Turn on the UPS, by pressing the On/Off button, then turn on the connected
load equipment. The UPS is ready for normal operation.
7
CONTROLS AND INDICATORS
On/Off Button
The On/Off button controls output power to connected load(s).
CAUTION: Pressing the On/Off button when AC utility is not present will cause the
UPS to begin operating from battery. This should not be performed unless the UPS
input is connected to a properly grounded receptacle.
Load/Battery Level Indicators (ALL GREEN)
The Load/Battery Level Indicators have dual functions. During normal mode
operation, LED indicators display electrical load placed upon the UPS; and during
battery mode operation, LED indicators display battery capacity remaining. Each
LED designates a 25% load or battery capacity increment. All four LED indicators
illuminate at full load/battery capacity. If the UPS becomes loaded beyond full
rating, the top LED indicator will flash continuously while an alarm sounds.
Utility/Battery Status Indicator (GREEN)
An illuminated LED indicates the power button is on and utility power is available.
A flashing LED along with an alarm signifies utility voltage is out of specification
and UPS is operating in battery mode.
Utility High/Low Indicator (AMBER)
An illuminated LED indicates the UPS is correcting utility power, due to a utility
overvoltage or undervoltage condition.
Fault Indicator (GREEN)
The Fault indicator is the second uppermost LED (contained in load/battery level
indicators). A flashing LED indicates the UPS has detected a problem. An alarm
sounds to alert that the UPS requires attention. Refer to Troubleshooting Guide.
Alarm Silence/Battery Test Button
The Alarm Silence/Battery Test button serves a dual purpose. During normal mode
operation, press button for at least one half second to test capacity of the battery
system. The UPS will operate in battery mode for approximately 15 seconds. The
illuminated LED indicators in Load/Battery Level determine battery mode capacity
in 25% increments.
During battery mode operation or active alarm condition, this button functions as
the alarm silence feature. Pressing this button for at least one half second will
silence the alarm. After the alarm is silenced, the PowerSure™ Interactive will
reactivate the alarm system to alert of additional problems. The low battery alarm
is the single alarm that cannot be silenced.
During a Battery Test, if the top two LEDs do not illuminate allow the UPS to
recharge the batteries for 24 hours. After 24 hours, retest the batteries. If the
batteries have been retested and the top two LEDs still do not illuminate, contact
your dealer or Liebert Technical Support (LTS) for a battery replacement kit.
Site Wiring Fault Indicator (RED)
An illuminated LED indicates the UPS has detected a miswired utility receptacle.
Contact a qualified electrician for assistance.
8
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.