LG UV21H INSTALLATION MANUAL

ENGLISH ITALIANO ESPAÑOL FRANCAIS DEUTSCH
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
TYPE : Ceiling Suspended Air Conditioner
P/NO.:MFL6208514
P/NO : MFL40910626
www.lg.com
TIPS FOR SAVING ENERGY
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition­er is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
SAFETY PRECAUTIONS
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
!
It can result in serious injury or death when the directions are ignored
CAUTION
!
It can result in minor injury or product damage when the directions are ignored
WARNING
!
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal­function, property damage, personal injury and/or death.
Installation
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a win­dow is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con-
denser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
3
ENGLISH
4
ENGLISH
• Do not install the product on a defective installation stand.
• Be sure the installation area does not deteriorate with age.
Operation
• Do not store or use flammable gas or combustibles near the product.
!
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
• Install the drain hose to ensure that water is drained away properly.
• Keep level even when installing the product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neigh-
• Use two or more people to lift and transport the product.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
SAFETY PRECAUTIONS
- It may cause injury, accident, or damage to the product.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
- There is risk of fire or failure of product.
CAUTION
- Low refrigerant levels may cause failure of product.
- A bad connection may cause water leakage.
- To avoid vibration or water leakage.
borhoods.
- It may cause a problem for your neighbors.
- Avoid personal injury.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
TABLE OF CONTENTS
TABLE OF CONTENTS
5
ENGLISH
2 TIPS FOR SAVING
ENERGY
3 IMPORTANT SAFETY
INSTRUCTIONS
6 INSTALLATION PLACES
7 THE INDOOR UNIT
INSTALLATION
8 - Open side-cover 9 - Mounting the anchor nut and bolt 11 Indoor Unit Drain Piping 11 Drain piping
11 Drain test
12 Heat insulation 12 - Connecting cables to the indoor unit 12 - Wiring Connection
14 TEST RUNNING
14 - PRECAUTIONS IN TEST RUNNING 14 - Check the following items when instal-
lation is complete
14 - Connection of power supply 14 - Evaluation of the performance
15 - HAND OVER
16 INSTALLATION
INSTRUCTIONS
16 Installer Setting -How to enter installer-
setting mode
17 Installer Setting - Installer Setting Code
Table
17 - Installer Setting Code Table 18 Installer Setting - Setting Address of
Central Control
18 Installer Setting - Checking Address of
Central Control
INSTALLATION PLACES
Indoor unit Ceiling Suspended Type
More than
700mm
More than
300mm
More than
700mm
6
ENGLISH
INSTALLATION PLACES
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
THE INDOOR UNIT INSTALLATION
THE INDOOR UNIT INSTALLATION
Air conditioner
Take enough distance
Cooking table
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
7
ENGLISH
CAUTION
!
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
NOTE
!
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange effi­ciency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
• Make sure that ventilation fan is enough
to cover all noxious gases from this place.
• Ensure enough distance from the cook-
ing room to install the air conditioner in such a place where it may not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
8
ENGLISH
THE INDOOR UNIT INSTALLATION
Open side-cover
- Remove four screws from side-cover.
- Unlock side-cover from side panel slightly (Tap the side-cover with your palm on the backside)
- Knock out the pipe hole from the left side­cover with nipper/plier.
CAUTION
!
Hold the side-cover with other hand while tapping to prevent it to fall down.
Step 1
Step 2
Right side cover
Backside
Left side cover
Backside
Step 3
Mounting the anchor nut and bolt
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut (W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Wall
5~7mm
Indoor Outdoor
- Prepare 4 suspension bolts. (Each bolts length should be same.)
- Measure and mark the position for the Suspension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the suspen­sion bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the anchor­nuts firmly.
- Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, wash­ers and spring washers.
- Adjust a level with a level gauge on the direc­tion of left-right, back-forth by adjusting sus­pension bolts.
- Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be declined to the bottomside so as to drain well.
DIM
MODEL
VL 1655 320 VK 1255 320
VJ 855 320
A B
THE INDOOR UNIT INSTALLATION
- The following parts is option. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10
CAUTION
!
Tighten the nut and bolt to prevent unit falling.
• Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
9
ENGLISH
Anchor nut
Ceiling
Nut
Suspension
bolts
Washer
A
Suspension bolt
Suspension
bolts
Spring washer
Hangen
Max.
12mm
B
Nut
Washer
THE INDOOR UNIT INSTALLATION
10
ENGLISH
CAUTION
!
Installation Information For Declination
- Install declination of the indoor unit is very important for the drain of the convertible type air conditioner.
- Minimum thickness of the insulation for the connecting pipe shall be 10mm.
- If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
Front of view
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain direction as shown in fig.
Ceiling
10~20mm
Side of view
- The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
5~10mm
THE INDOOR UNIT INSTALLATION
Tip of drain hose dipped in water
Water leakage
Ditch
Less than 50mm gap
11
ENGLISH
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
- During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
- Remove the rubber stopple before connecting drain hose.
- Hook on the bracket after connecting the drain hose as below.
Drain hose
Bracket
Drain piping
- The drain hose should point downward for easy drain flow.
Water leakage
Do not raise
Water leakage
Accumulated drain water
Air
Waving
- Be sure to execute heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Drain test
Use the following procedure to test the drain pump operation:
Downward slope
- Do not make drain piping like the following.
- Set the air direction louvers up-and-down to the position(horizontally) by hand.
- Pour a glass of water on the evaporator using a kettle.
- Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
12
Indoor unit
Thermal insulator (accessory)
Fastening band (accessory)
Refrigerant piping
The connecting cable
ENGLISH
THE INDOOR UNIT INSTALLATION
Heat insulation
Use the heat insulation material for the refrig­erant piping which has an excellent heat-resis­tance (over 120°C).
Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point tempera­ture: more than 23°C), water drops are liable to fall. In this case, add heat insulation materi­al according to the following procedure:
- Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm.
- Stick glass wool on all air conditioners that are located in ceiling atmosphere.
Connecting cables to the indoor unit
- Remove the terminal block cover for electri­cal connection between the indoor and out­door unit.
- Use the cord clamper to fix the cord.
Wiring Connection
Connect the wires to the terminals on the control board individually according to the out­door unit connection.
* 48k, 42k, 36k, 18k, 12k
1(L) 2(N) 3
1(L) 2(N) 3
* 24k, 21k
1(L) 2(N) 3
1(L) 2(N) 3(C)
CAUTION
!
• indoor and outdoor unit should be com­plied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
GN/YL
• If the supply cord is damaged, it must be replaced by a special cord or assem­bly available from the manufacturer of its service agent.
connected to the
NORMAL CROSS-SECTIONAL AREA 0.75mm
20mm
2
Terminal block cover
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
THE INDOOR UNIT INSTALLATION
13
ENGLISH
Round pressure terminal
When none are available, follow the instruc­tions below.
- Do not connect wiring of different thickness­es to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
Power wire
WARNING
!
• Make sure that the screws of the termi­nal are free from looseness.
TEST RUNNING
14
ENGLISH
TEST RUNNING
PRECAUTIONS IN TEST RUNNING
- The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated.
CAUTION
!
• For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
• Carry out the test run more than 5 minutes without fail.
- To cancel the test run, press any button.
Check the following items when installation is complete
After completing work, be sure to measure and record trial run properties, and store measured data, etc.
Measuring items are room temperature, out­side temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibra­tion and noise, operating pressure, piping tem­perature, compressive pressure.
As to the structure and appearance, check fol­lowing items.
- Is the circulation of air adequate?
- Is the draining smooth?
- Is the heat insulation complete (refrigerant and drain piping)?
- Is there any leakage of refrigerant?
- Is the remote controller switch operated?
- Is there any faulty wiring?
- Are not terminal screws loosened?
M4......118N.cm{12kgf.cm}
M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm}
M8......588N.cm{60kgf.cm}
Connection of power supply
Connect the power supply cord to the inde­pendent power supply.
- Circuit breaker is required. Operate the unit for fifteen minutes or more.
Evaluation of the performance
Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and the discharge one is more than 8°C (Cooling) or reversely (Heating).
Thermometer
TEST RUNNING
15
ENGLISH
CAUTION
!
After the confirmation of the above condi­tions, prepare the wiring as follows:
• Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
• Provide a circuit breaker switch between power source and the unit.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn­out of the wires.)
• Specification of power source.
• Confirm that electrical capacity is suffi­cient.
• Be sure that the starting voltage is main­tained at more than 90 percent of the rated voltage marked on the name plate.
• Confirm that the cable thickness is as specified in the power sources specifica­tion. (Particularly note the relation between cable length and thickness.)
• Never fail to equip a leakage breaker where it is wet or moist.
• The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage
on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
- Proper starting power is not given to
the compressor.
• Use only 1 remote-controller contained in indoor unit, when you combine to use both cassette type indoor unit and differ­ent Indoor units combinations as shown below.
HAND OVER
Teach the customer the operation and mainte­nance procedures, using the operation manual (air filter cleaning, temperature control, etc.).
INSTALLATION INSTRUCTIONS
Refer to the Installer Setting Code Table
on the next page.
16
ENGLISH
INSTALLATION INSTRUCTIONS
Installer Setting -How to enter installer setting mode
CAUTION
!
Installer setting mode is to set the detail function of the remote controller. If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property damage. This must be set by an certificated installer, and any installation or change that is carried out by a non-certificated person should be responsible for the results. In this case, free service cannot be provided.
1. With the FAN SPEED button pressed,
press the RESET button.
2. By using the TEMPERATURE SETTING
button, set function code and setting value. (Please refer the Installer Setting Code Table.)
3. Press the ON/OFF button toward the
indoor unit 1 time.
4. Reset the remote controller to use the
general operation mode.
R
INSTALLATION INSTRUCTIONS
Mode Override
Ceiling Height Selection
Group Control
Auxiliary heater
No. Function Function Code Setting Value Remote Controller LCD
0
1
2
2
Installer Setting - Installer Setting Code Table
Installer Setting Code Table
17
ENGLISH
0 Mode Override
Ceiling Height
1
Selection
Group Control
2
Auxiliary heater
This Function is only for Non-Auto Changeover H/P model.
0 : Set to Master
1 : Set to Slave
1 : Standard
2 : Low
3 : High
4 : Super High
0 : Set to Master
1 : Set to Slave
2 : Check Master/Slave
3 : Set to Auxiliary heater
4 : Cancel Auxiliary heater
5 :
Check Auxiliary heater Installation
Indoor unit connected to wired remote controller operate as wired remote controller setting.
This function is only for group control. Please don’t set this function in case of non-group control.
After setting Group Control of the product, turn off the power then turn it back on after 1 minute.
This function is only applied to models with Auxiliary Heater function being activated.
INSTALLATION INSTRUCTIONS
18
ENGLISH
Installer Setting - Setting Address of Central Control
1. With the MODE button pressed, press the
RESET button.
2. By using the temperature setting button,
set the indoor unit address.
• Setting range : 00 ~ FF
3. After setting the address, press the
ON/OFF button toward the indoor unit 1 time.
4. The indoor unit will display the set address
to complete the address setting.
• The address display time and method can differ by the indoor uint type.
5. Reset the remote controller to use the
general operation mode.
Installer Setting - Checking Address of Central Control
1. With the PLASMA button pressed, press the RESET button.
2. Press the ON/OFF button toward the indoor unit 1 time, and the indoor unit will display the set
address in the display window.
• The address display time and method can differ by the indoor unit type.
3. Reset the remote controller to use the general operation mode.
MANUALE D’INSTALLAZIONE
ITALIANO
CLIMATIZZATORE
• Leggere questo manuale d’istruzioni prima di installare il condizionatore d’aria.
• Il lavoro d’installazione deve essere eseguito conformemente alla normativa vigente sugli impianti elettrici, solo da personale tecnico autorizzato.
• Dopo averlo letto dettagliatamente, conservare questo manuale come riferi­mento per il futuro
TIPO : Ceiling Suspended Air Conditioner
www.lg.com
CONSIGLI PER IL RISPARMIO ENERGETICO
2
CONSIGLI PER IL RISPARMIO ENERGETICO
Qui sono forniti alcuni consigli per aiutarvi a minimizzare il consumo di energia quando usate il
ITALIANO
condizionatore. Potete usare il condizionatore con maggiore efficienza applicando le istruzioni indicate di seguito:
• Non raffreddare eccessivamente gli ambienti interni. Questo può essere dannoso per la salute e può consumare maggiore quantità di elettricità.
• Boccate la luce solare con schermi o tende mentre usate il condizionatore d'aria.
• Tenete le porte e le finestre chiuse quando usate il condizionatore.
• Regolare la direzione del flusso d'aria verticalmente o orizzontalmente per far circolare l'aria interna.
• Accelerare la ventilatore per raffreddare o riscaldare l'aria interna rapidamente in un breve periodo di tempo.
• Aprire le finestra regolarmente per la ventilazione quando la qualità dell'aria interna può deteriorarsi se il condizionatore viene usato per molte ore.
• Pulire il filtro aria una volta ogni 2 settimane. La polvere e le impurità raccolte nel filtro dell'aria pos­sono bloccare il flusso dell'aria o ridurre le funzioni di raffreddamento/deumidificazione.
Per le vostre registrazioni
Conservare questa pagina in caso che sia necessario provare la data di acquisto o per rivendicazioni di garanzia. Scrivere il numero del modello e il numero di serie qui:
Numero di modello
Nuonero di serie
Portete rilevarli nell'etichetta sul lato di ciascuna unità.
Nome del venditore
Data di acquisto
IMPORTANTI ISTRUZIONI DI SICUREZZA
IMPORTANTI ISTRUZIONI DI SICUREZZA
3
LEGGERE TUTTE LE ISTRUZIONI PRIMA DI USARE L'APPARECCHIO.
Applicare sempre le precauzioni seguenti per evitare situazioni pericolose e assicurare la prestazione di picco del vostro prodotto.
ALLERTA
!
Si può provocare un ferimento grave o la morte quando le istruzioni non sono applicate.
CAUTELA
!
Si può provocare un ferimento minimo o danno al prodotto quando le istruzioni non sono appli­cate.
ALLERTA
!
• L'installazione o le riparazioni fatte da persone non qualificate può provocare pericolo a voi e ad altre persone.
• L'informazione contenuta nel manuale è prevista per l'uso da parte di un tecnico di manuten­zionee qualificato che abbia familiarità con le procedure di sicurezza equipaggiato con gli attrezzi e strumenti di prova adatti.
• Se non si legge con accuratezza e non si applicano tutte le istruzioni di questo manuale si può avere un malfunzionamento dell'apparecchio, danno alla proprietà, ferimento e/o morte delle persone.
Installazione
• Non usare un cordone di alimentazione, una spina o presa allentata che siano danneggiati.
- Altrimenti si può provocare una scossa elettrica.
• Per il lavoro elettrico contattare il fornitore, il venditore, un elettricista qualificato o il centro di
manutenzione autorizzato.
- Non smontare o riparare il prodotto. Esiste il rischio di incendio o di scossa elettrica.
• Collegare sempre a terra il prodotto.
- Esiste il rischio di incendio o di scossa elettrica.
• Installare il pannello e il coperchio della scatola di controllo con sicurezza.
- Esiste il rischio di incendio o di scossa elettrica.
• Installare sempre un circuito dedicato e l'interruttore automatico.
- Il cablaggio o l'installazione non corretti possono provocare incendio o scossa elettrica.
• Usare l'interruttore automatico o il fusibile di tipo adeguato.
- Esiste il rischio di incendio o di scossa elettrica.
• Non modificare o prolungare il cavo di alimentazione.
- Esiste il rischio di incendio o di scossa elettrica.
• Non lasciare il condizionatore d'aria in funzione per un tempo lungo quando l'umidità è molto alta e
una porta o una finestra è lascita aperta.
- L'umidità può condenziare e umidificare o danneggiare l'apparecchio.
• Fare attenzione quando si disimballa e si installa il prodotto.
- I bordi acuti possono provocare ferimenti. Fare molta attenzione ai bordi della confezione e alle alette del condensatore e dell'evaporatore.
• Per l'installazione, contattare sempre il fornitore o un centro di manutenzione autorizzato.
- Esiste il rischio di incendio, scossa elettrica, esplosione, o danno fisico.
ITALIANO
4
ITALIANO
Utilizzo
Installazione
IMPORTANTI ISTRUZIONI DI SICUREZZA
• Non installare il prodotto su un supporto di installazione difettoso.
- Esso può provocare ferimento, incidente, o danno al prodotto.
• Fare attenzione che l'area di installazione non si danneggi con il passare del tempo.
- Se la base si rompe, il condizionatore potrebba cadere, provocando danno alla proprietà, guasto del prodotto o danno alle persone.
• Non conservare né usare gas infiammabile o combustibili vicini al prodotto.
- Esiste il rischio di incendio o di danno del prodotto.
CAUTELA
!
• Controllare sempre la perdita di gas (refrigerante) dopo l'installazione o la riparazione del prodotto.
- I livelli di refrigerante bassi possono provocare un guasto del prodotto.
• Installare il tubo di drenaggio per assicurare che l'acqua sia drenata correttamennte.
- Un collegamento errato può provocare perdita di acqua.
• Mantenere il livello quando si installa il prodotto.
- Per evitare le vibrazioni o la perdita di acqua.
• Non installare il prodotto in posizioni in cui il rumore o l'aria calda dell'unità esterna potrebbero dan­neggiare i vicini di casa.
- Si può produrre un problema per i vostri vicini.
• Usare due o tre persone per sollevare e trasportare il prodotto.
- Evitare i danni alle persone.
• Non installare il prodotto in posizione che sia esposta al vento di mare (spruzzi di sale) in modo diret­to.
- Si può produrre la corrosione del prodotto. La corrosione, in particolare del condensatore e delle
alettae dell'evaporatore, potrebbero provocare malfunzionamento del prodotto o funzionamento non efficiente.
INDICE
INDICE
5
2 CONSIGLI PER
RISPARMIO DI ENERGIA
3 IMPORTANTI ISTRUZIONI
DI SICUREZZA
6 POSIZIONI DI INSTAL-
LAZIONE
7 L'INSTALLAZIONE DEL-
L'UNITÀ INTERNA
8 - Aprire il coperchio laterale 9 - Montaggio del dado e bullone di ancor-
aggio
11 Tubazione drenaggio dell'unità interna 11 Tubazione di drenaggio
11 Test di drenaggio
12 Isolamento termico 12 - Collegamento dei cavi all'unità interna 12 - Collegamento di cablaggio
16 ISTRUZIONI DI INSTAL-
LAZIONE
16 Impostazioni per Installatore - Come
entrare nel modo di installazione
17 Impostazioni per Installatore - Tabella
codici di impostazione per installatore
17 - Tabella codici di impostazione per
installatore
18 Impostazioni per Installatore - Indirizzo di
impostazione per controllo centralizzato
18 Impostazioni per Installatore - Controllo
indirizzo per controllo centralizzato
ITALIANO
14 AVVIO DEL TEST
14 - PRECAUZIONI PER ESECUZIONE DEL
TEST
14 - Controllare le seguenti parti quando l'in-
stallazione è stata completata.
14 - Collegamento dell'alimentazione di
energia
14 - Valutazione della prestazione 15 - UTILIZZO
POSIZIONI DI INSTALLAZIONE
Unità interna Tipo sospeso a soffitto
Maggiore di 700mm
Maggiore di 300mm
Maggiore di 700mm
6
POSIZIONI DI INSTALLAZIONE
ITALIANO
- Vicino all'unità non deve essere presente alcuna sorgente di calore o di vapore.
- Non devono essere presenti ostacoli che impediscano la circolazione dell'aria.
- Una porzionee in cui la circolazione dell'aria dell'ambiente sia corretta.
- Una posizione in cui il drenaggio possa essere realizzato facilmente.
- Una posizione in cui la protezione del rumore sia tenuta presente in modo corretto.
- Non installare l'unità vicino alla porta dell'appartamento.
- Verificare gli spazi indicati dalle frecce rispetto alla parete, al soffitto o ad altri ostacoli.
- L'unità interna deve consentire lo spazio per la manutenzione.
L'INSTALLAZIONE DELL'UNITÀ INTERNA
Tabella per
Condizionatore d'aria
Mantenere una distanza sufficiente
Usare il ventilatore per la cappa di raccolta dei fumi con una capacità sufficiente.
L'INSTALLAZIONE DELL'UNITÀ INTERNA
7
ITALIANO
CAUTELA
!
• Installare l'unità orizzontalmente usando una livella ad acqua.
• Durante l'installazione, si deve fare atten­zione a non danneggiare i fili elettrici.
• Selezionare e marcare la posizione per fis­sare i bulloni e il foro della tubazione.
• Stabilire la posizione dei bulloni di fissaggio leggermente inclinati considerando la direzione del tubo di drenaggio.
• Eseguire il foro del bullone di ancoraggio sulla parete.
NOTA
!
• Evitare la seguente posizione di instal­lazione.
1. Le posizioni come ristoranti e le cucine in
cui viene prodotta una grande quantità di vapore e aromi. Questi possono provo­care la riduzione di efficienza dello scam­bio di calore, gocce di acqua, malfunziona­mento della pompa di drenaggio. In questi casi, eseguire le azioni seguenti.
• Verificare che il ventilatore dell'aria sia suf­ficiente per pompare tutti i gas dannosi da questa posizione.
• Accertare che esita una distanza suffi­ciente dalla stanza di cottura per installare il condizionatore d'aria in posizione tale da non aspirare il vapore contenente gocce di olio.
2. Evitare di installare il condizionatore in
posizione in cui sia generato olio di cot­tura o polvere di ferro.
3. Evitare le posizioni in cui è generato gas
infiammabile.
4. Evitare una posizione in cui sia generato
gas tossico.
5. Evitare le posizioni vicine a generatori ad
alta frequenza.
L'INSTALLAZIONE DELL'UNITÀ INTERNA
8
Aprire coperchio laterale
- Togliere le quattro viti del coperchio laterale.
- Sbloccare il coperchio laterale dal pannello
ITALIANO
laterale con cautela. (Trattenere il coperchio laterale con il palmo della mano sul lato pos­teriore.)
- Aprire il foro della tubazione dal coperchio lat­erale sinistro con tenaglie/pinze.
CAUTELA
!
Sostenere il coperchio con l'altra mano mentre si apre il foro per evitare la sua caduta.
Fase 1
Fase 2
Lato posteriore
Fase 3
Coperchio laterale destro
Coperchio laterale sinistro
Lato posteriore
Montaggio del dado e bullone di
Rondella piatta per M10
(accessorio)
Rondella piatta per M10
(accessorio)
Bullone di sospensione (W3/8 or M10)
Dado (W3/8 or M10)
Dado
(W3/8 or M10)
Rondella elastica
(M10)
Wall
5~7mm
Interno Esterno
ancoraggio
- Preparare 4 bulloni di sospensione. (I bulloni devono avere lunghezza eguale.)
- Misurare e marcare la posizione dei bulloni di sospensione e del foro del tubo.
- Eseguire il foro per il dado di ancoraggio sul soffitto.
- Inserire i dadi e le rondelle nei bulloni di sospensione per bloccare i bulloni di sospen­sione sul soffitto.
- Montare i bulloni di sospensione sui dadi di ancoraggio in modo fisso.
- Fissare i tiranti sui bulloni di sospensione (rego­lare livello corretto) usando dadi, rondelle e ron­delle elastiche.
- Regolare il livello con una livella ad acqua nella direzione sinistra-destra, avanti -indietro regolando i bulloni di sospensione.
- Regolare un livello nella direzione di alto-basso regolando i bulloni di sospensione. Quindi l'u­nità verrà inclinata sul lato di fondo per ottenere un drenaggio corretto.
DIM
MODEL
VL 1655 320 VK 1255 320
VJ 855 320
A B
L'INSTALLAZIONE DELL'UNITÀ INTERNA
- La parte seguente è opzionale. Bullone di sospensione - W 3/8 or M10 Dado - W 3/8 or M10 Rondella elastica - M10 Rondella piatta - M10
CAUTELA
!
Serrare i dadi e bulloni per evitare la cadu­ta dell'unità.
• Eseguire il foro della tubazione sulla parete leggermente inclinata verso il lato esterno usando una punta a tazza Ø 70.
9
ITALIANO
Dado di ancoraggio
Soffitto
Dado
Bullone di
sospensione
rondella
A
Bullone di sospensione
Rondella elastica
Sospensore
Bullone di
sospensione
Max. 12mm
B
Dado
rondella
THE INDOOR UNIT INSTALLATION
10
CAUTELA
!
ITALIANO
Informazioni di installazione per l'inclinazione
- L'inclinazione di installazione dell'unità interna è molto importante per il drenaggio del con­dizionatore del tipo convertibile.
- Lo spessore minimo dell'isolamento del tubo di collegamento deve essere di 10 mm.
- Se le piastre di installazione sono fissate sulla linea orizzontale, l'unità interna dopo l'instal­lazione sarà inclinata sul lato inferiore.
Vista anteriore
- L'unità deve essere orizzontale o inclinata con un certo angolo.
- L'inclinazione dovrebbe essere inferiore o eguale a 1° o inclinata di 10 - 20 mm nella direzione di drenaggio come indicato in Fig.
soffitto
10~20mm
Vista laterale
L'unità deve essere inclinata sul lato inferiore quando l'installazione è terminata.
soffitto
5~10mm