• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : Ceiling Suspended Air Conditioner
P/NO.:MFL6208514
P/NO : MFL40910626
www.lg.com
TIPS FOR SAVING ENERGY
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
SAFETY PRECAUTIONS
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
WARNING
!
It can result in serious injury or death when the directions are ignored
CAUTION
!
It can result in minor injury or product damage when the directions are ignored
WARNING
!
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con-
denser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
3
ENGLISH
4
ENGLISH
• Do not install the product on a defective installation stand.
• Be sure the installation area does not deteriorate with age.
Operation
• Do not store or use flammable gas or combustibles near the product.
!
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
• Install the drain hose to ensure that water is drained away properly.
• Keep level even when installing the product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neigh-
• Use two or more people to lift and transport the product.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
SAFETY PRECAUTIONS
- It may cause injury, accident, or damage to the product.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,
and personal injury.
- There is risk of fire or failure of product.
CAUTION
- Low refrigerant levels may cause failure of product.
- A bad connection may cause water leakage.
- To avoid vibration or water leakage.
borhoods.
- It may cause a problem for your neighbors.
- Avoid personal injury.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation.
TABLE OF CONTENTS
TABLE OF CONTENTS
5
ENGLISH
2TIPS FOR SAVING
ENERGY
3IMPORTANT SAFETY
INSTRUCTIONS
6INSTALLATION PLACES
7THE INDOOR UNIT
INSTALLATION
8- Open side-cover
9- Mounting the anchor nut and bolt
11Indoor Unit Drain Piping
11Drain piping
11Drain test
12Heat insulation
12- Connecting cables to the indoor unit
12- Wiring Connection
14 TEST RUNNING
14- PRECAUTIONS IN TEST RUNNING
14- Check the following items when instal-
lation is complete
14- Connection of power supply
14- Evaluation of the performance
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
THE INDOOR UNIT INSTALLATION
THE INDOOR UNIT INSTALLATION
Air conditioner
Take enough
distance
Cooking table
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
7
ENGLISH
CAUTION
!
• Install the unit horizontally using a level
gauge.
• During the installation, care should be
taken not to damage electric wires.
• Select and mark the position for fixing
bolts and piping hole.
• Decide the position for fixing bolts
slightly tilted to the drain direction after
considering the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
NOTE
!
• Avoid the following installation location.
1. Such places as restaurants and kitchen
where considerable amount of oil
steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain
pump mal-function.
In these cases, take the following
actions;
• Make sure that ventilation fan is enough
to cover all noxious gases from this
place.
• Ensure enough distance from the cook-
ing room to install the air conditioner in
such a place where it may not suck oily
steam.
2. Avoid installng air conditioner
in such places where
cooking oil or iron powder is
generated.
3. Avoid places where
inflammable gas is generated.
4. Avoid place where noxious gas is
generated.
5. Avoid places near high frequency
generators.
8
ENGLISH
THE INDOOR UNIT INSTALLATION
Open side-cover
- Remove four screws from side-cover.
- Unlock side-cover from side panel slightly
(Tap the side-cover with your palm on the
backside)
- Knock out the pipe hole from the left sidecover with nipper/plier.
CAUTION
!
Hold the side-cover with other hand while
tapping to prevent it to fall down.
Step 1
Step 2
Right side cover
Backside
Left side
cover
Backside
Step 3
Mounting the anchor nut and bolt
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Wall
5~7mm
IndoorOutdoor
- Prepare 4 suspension bolts. (Each bolts
length should be same.)
- Measure and mark the position for the
Suspension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on
the ceiling.
- Mount the suspension bolts to the anchornuts firmly.
- Secure the hangers onto the Suspension
bolts (adjust level roughly.) using nuts, washers and spring washers.
- Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
- Adjust a level on the direction of top-bottom
by adjusting supension bolts. Then the unit
will be declined to the bottomside so as to
drain well.
DIM
MODEL
VL1655320
VK1255320
VJ855320
AB
THE INDOOR UNIT INSTALLATION
- The following parts is option.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
CAUTION
!
Tighten the nut and bolt to prevent unit
falling.
• Drill the piping hole on the wall slightly
tilted to the outdoor side using a Ø 70
hole-core drill.
9
ENGLISH
Anchor nut
Ceiling
Nut
Suspension
bolts
Washer
A
Suspension bolt
Suspension
bolts
Spring
washer
Hangen
Max.
12mm
B
Nut
Washer
THE INDOOR UNIT INSTALLATION
10
ENGLISH
CAUTION
!
Installation Information For Declination
- Install declination of the indoor unit is very important for the drain of the convertible type
air conditioner.
- Minimum thickness of the insulation for the connecting pipe shall be 10mm.
- If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be
declined to the bottomside.
Front of view
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain
direction as shown in fig.
Ceiling
10~20mm
Side of view
- The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
5~10mm
THE INDOOR UNIT INSTALLATION
Tip of drain hose
dipped in water
Water
leakage
Ditch
Less than
50mm gap
11
ENGLISH
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- Remove the rubber stopple before
connecting drain hose.
- Hook on the bracket after connecting the
drain hose as below.
Drain hose
Bracket
Drain piping
- The drain hose should point downward for
easy drain flow.
Water
leakage
Do not raise
Water
leakage
Accumulated
drain water
Air
Waving
- Be sure to execute heat insulation on the
drain piping.
Heat insulation material: Polyethylene
foam with thickness more than 8 mm.
Drain test
Use the following procedure to test the drain
pump operation:
Downward slope
- Do not make drain piping like the following.
- Set the air direction louvers up-and-down to
the position(horizontally) by hand.
- Pour a glass of water on the evaporator
using a kettle.
- Ensure the water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
12
Indoor unit
Thermal insulator
(accessory)
Fastening band
(accessory)
Refrigerant piping
• The connecting cable
ENGLISH
THE INDOOR UNIT INSTALLATION
Heat insulation
Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
Precautions in high humidity circumstance:
This air conditioner has been tested according
to the "KS Standard Conditions with Mist" and
confirmed that there is not any default.
However, if it is operated for a long time in
high humid atmosphere (dew point temperature: more than 23°C), water drops are liable
to fall. In this case, add heat insulation material according to the following procedure:
- Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to
20mm.
- Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
Connecting cables to the indoor unit
- Remove the terminal block cover for electrical connection between the indoor and outdoor unit.
- Use the cord clamper to fix the cord.
Wiring Connection
Connect the wires to the terminals on the
control board individually according to the outdoor unit connection.
* 48k,42k,36k,18k,12k
1(L) 2(N) 3
1(L) 2(N) 3
* 24k, 21k
1(L) 2(N) 3
1(L) 2(N) 3(C)
CAUTION
!
•
indoor and outdoor unit should be complied with the following specifications
(Rubber insulation, type H05RN-F
approved by HAR or SAA).
GN/YL
• If the supply cord is damaged, it must
be replaced by a special cord or assembly available from the manufacturer of
its service agent.
connected to the
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
20mm
2
Terminal block cover
Precautions when laying power wiring
Use round pressure terminals for connections
to the power terminal block.
THE INDOOR UNIT INSTALLATION
13
ENGLISH
Round pressure terminal
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the
power wiring may cause abnormal heat.)
- When connecting wiring which is the same
thickness, do as shown in the figure below.
Power wire
WARNING
!
• Make sure that the screws of the terminal are free from looseness.
TEST RUNNING
14
ENGLISH
TEST RUNNING
PRECAUTIONS IN TEST RUNNING
- The initial power supply must provide at least
90% of the rated voltage.
Otherwise, the air conditioner should not be
operated.
CAUTION
!
• For test run, carry out the cooling
operation firstly even during heating
season. If heating operation is carried
out firstly, it leads to the trouble of
compressor. Then attention must be
paid.
• Carry out the test run more than 5
minutes without fail.
- To cancel the test run, press any button.
Check the following items when
installation is complete
After completing work, be sure to measure
and record trial run properties, and store
measured data, etc.
Measuring items are room temperature, outside temperature, suction temperature, blow
out temperature, wind velocity, wind volume,
voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure.
As to the structure and appearance, check following items.
- Is the circulation of air adequate?
- Is the draining smooth?
- Is the heat insulation complete
(refrigerant and drain piping)?
- Is there any leakage of refrigerant?
- Is the remote controller switch operated?
- Is there any faulty wiring?
- Are not terminal screws loosened?
M4......118N.cm{12kgf.cm}
M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm}
M8......588N.cm{60kgf.cm}
Connection of power supply
Connect the power supply cord to the independent power supply.
- Circuit breaker is required.
Operate the unit for fifteen minutes or more.
Evaluation of the performance
Measure the temperature of the intake and
discharge air.
Ensure the difference between the intake
temperature and the discharge one is more
than 8°C (Cooling) or reversely (Heating).
Thermometer
TEST RUNNING
15
ENGLISH
CAUTION
!
After the confirmation of the above conditions, prepare the wiring as follows:
• Never fail to have an individual power
specialized for the air conditioner. As for
the method of wiring, be guided by the
circuit diagram pasted on the inside of
control box cover.
• Provide a circuit breaker switch between
power source and the unit.
• The screw which fasten the wiring in
the casing of electrical fittings are liable
to come loose from vibrations to which
the unit is subjected during the course
of transportation. Check them and make
sure that they are all tightly fastened. (If
they are loose, it could give rise to burnout of the wires.)
• Specification of power source.
• Confirm that electrical capacity is sufficient.
• Be sure that the starting voltage is maintained at more than 90 percent of the
rated voltage marked on the name plate.
• Confirm that the cable thickness is as
specified in the power sources specification.
(Particularly note the relation between
cable length and thickness.)
• Never fail to equip a leakage breaker
where it is wet or moist.
• The following troubles would be caused
by voltage drop-down.
- Vibration of a magnetic switch, damage
on the contact point there of, fuse
breaking, disturbance to the normal
function of a overload protection
device.
- Proper starting power is not given to
the compressor.
• Use only 1 remote-controller contained
in indoor unit, when you combine to use
both cassette type indoor unit and different Indoor units combinations as shown
below.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual
(air filter cleaning, temperature control, etc.).
INSTALLATION INSTRUCTIONS
Refer to the Installer Setting Code Table
on the next page.
16
ENGLISH
INSTALLATION INSTRUCTIONS
Installer Setting -How to enter installer setting mode
CAUTION
!
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user
injury or property damage. This must be set by an certificated installer, and any installation
or change that is carried out by a non-certificated person should be responsible for the
results. In this case, free service cannot be provided.
1. With the FAN SPEED button pressed,
press the RESET button.
2. By using the TEMPERATURE SETTING
button, set function code and setting value.
(Please refer the Installer Setting Code
Table.)
This Function is only for Non-Auto Changeover H/P model.
0 : Set to Master
1 : Set to Slave
1 : Standard
2 : Low
3 : High
4 : Super High
0 : Set to Master
1 : Set to Slave
2 : Check Master/Slave
3 : Set to Auxiliary heater
4 : Cancel Auxiliary heater
5 :
Check Auxiliary heater Installation
Indoor unit connected to wired remote controller operate as wired remote controller setting.
This function is only for group control. Please don’t set this function in case of non-group
control.
After setting Group Control of the product, turn off the power then turn it back on after 1
minute.
This function is only applied to models with Auxiliary Heater function being activated.
INSTALLATION INSTRUCTIONS
18
ENGLISH
Installer Setting - Setting Address of Central Control
1. With the MODE button pressed, press the
RESET button.
2. By using the temperature setting button,
set the indoor unit address.
• Setting range : 00 ~ FF
3. After setting the address, press the
ON/OFF button toward the indoor unit 1
time.
4. The indoor unit will display the set address
to complete the address setting.
• The address display time and method can
differ by the indoor uint type.
5. Reset the remote controller to use the
general operation mode.
Installer Setting - Checking Address of Central Control
1. With the PLASMA button pressed, press the RESET button.
2. Press the ON/OFF button toward the indoor unit 1 time, and the indoor unit will display the set
address in the display window.
• The address display time and method can differ by the indoor unit type.
3. Reset the remote controller to use the general operation mode.
MANUALE D’INSTALLAZIONE
ITALIANO
CLIMATIZZATORE
• Leggere questo manuale d’istruzioni prima di installare il condizionatore d’aria.
• Il lavoro d’installazione deve essere eseguito conformemente alla normativa
vigente sugli impianti elettrici, solo da personale tecnico autorizzato.
• Dopo averlo letto dettagliatamente, conservare questo manuale come riferimento per il futuro
TIPO : Ceiling Suspended Air Conditioner
www.lg.com
CONSIGLI PER IL RISPARMIO ENERGETICO
2
CONSIGLI PER IL RISPARMIO ENERGETICO
Qui sono forniti alcuni consigli per aiutarvi a minimizzare il consumo di energia quando usate il
ITALIANO
condizionatore. Potete usare il condizionatore con maggiore efficienza applicando le istruzioni
indicate di seguito:
• Non raffreddare eccessivamente gli ambienti interni. Questo può essere dannoso per la salute e
può consumare maggiore quantità di elettricità.
• Boccate la luce solare con schermi o tende mentre usate il condizionatore d'aria.
• Tenete le porte e le finestre chiuse quando usate il condizionatore.
• Regolare la direzione del flusso d'aria verticalmente o orizzontalmente per far circolare l'aria interna.
• Accelerare la ventilatore per raffreddare o riscaldare l'aria interna rapidamente in un breve periodo di
tempo.
• Aprire le finestra regolarmente per la ventilazione quando la qualità dell'aria interna può deteriorarsi
se il condizionatore viene usato per molte ore.
• Pulire il filtro aria una volta ogni 2 settimane. La polvere e le impurità raccolte nel filtro dell'aria possono bloccare il flusso dell'aria o ridurre le funzioni di raffreddamento/deumidificazione.
Per le vostre registrazioni
Conservare questa pagina in caso che sia necessario provare la data di acquisto o per rivendicazioni
di garanzia. Scrivere il numero del modello e il numero di serie qui:
Numero di modello
Nuonero di serie
Portete rilevarli nell'etichetta sul lato di ciascuna unità.
Nome del venditore
Data di acquisto
IMPORTANTI ISTRUZIONI DI SICUREZZA
IMPORTANTI ISTRUZIONI DI SICUREZZA
3
LEGGERE TUTTE LE ISTRUZIONI PRIMA DI USARE L'APPARECCHIO.
Applicare sempre le precauzioni seguenti per evitare situazioni pericolose e assicurare la
prestazione di picco del vostro prodotto.
ALLERTA
!
Si può provocare un ferimento grave o la morte quando le istruzioni non sono applicate.
CAUTELA
!
Si può provocare un ferimento minimo o danno al prodotto quando le istruzioni non sono applicate.
ALLERTA
!
• L'installazione o le riparazioni fatte da persone non qualificate può provocare pericolo a voi e
ad altre persone.
• L'informazione contenuta nel manuale è prevista per l'uso da parte di un tecnico di manutenzionee qualificato che abbia familiarità con le procedure di sicurezza equipaggiato con gli
attrezzi e strumenti di prova adatti.
• Se non si legge con accuratezza e non si applicano tutte le istruzioni di questo manuale si può
avere un malfunzionamento dell'apparecchio, danno alla proprietà, ferimento e/o morte delle
persone.
Installazione
• Non usare un cordone di alimentazione, una spina o presa allentata che siano danneggiati.
- Altrimenti si può provocare una scossa elettrica.
• Per il lavoro elettrico contattare il fornitore, il venditore, un elettricista qualificato o il centro di
manutenzione autorizzato.
- Non smontare o riparare il prodotto. Esiste il rischio di incendio o di scossa elettrica.
• Collegare sempre a terra il prodotto.
- Esiste il rischio di incendio o di scossa elettrica.
• Installare il pannello e il coperchio della scatola di controllo con sicurezza.
- Esiste il rischio di incendio o di scossa elettrica.
• Installare sempre un circuito dedicato e l'interruttore automatico.
- Il cablaggio o l'installazione non corretti possono provocare incendio o scossa elettrica.
• Usare l'interruttore automatico o il fusibile di tipo adeguato.
- Esiste il rischio di incendio o di scossa elettrica.
• Non modificare o prolungare il cavo di alimentazione.
- Esiste il rischio di incendio o di scossa elettrica.
• Non lasciare il condizionatore d'aria in funzione per un tempo lungo quando l'umidità è molto alta e
una porta o una finestra è lascita aperta.
- L'umidità può condenziare e umidificare o danneggiare l'apparecchio.
• Fare attenzione quando si disimballa e si installa il prodotto.
- I bordi acuti possono provocare ferimenti. Fare molta attenzione ai bordi della confezione e alle
alette del condensatore e dell'evaporatore.
• Per l'installazione, contattare sempre il fornitore o un centro di manutenzione autorizzato.
- Esiste il rischio di incendio, scossa elettrica, esplosione, o danno fisico.
ITALIANO
4
ITALIANO
Utilizzo
Installazione
IMPORTANTI ISTRUZIONI DI SICUREZZA
• Non installare il prodotto su un supporto di installazione difettoso.
- Esso può provocare ferimento, incidente, o danno al prodotto.
• Fare attenzione che l'area di installazione non si danneggi con il passare del tempo.
- Se la base si rompe, il condizionatore potrebba cadere, provocando danno alla proprietà, guasto del
prodotto o danno alle persone.
• Non conservare né usare gas infiammabile o combustibili vicini al prodotto.
- Esiste il rischio di incendio o di danno del prodotto.
CAUTELA
!
• Controllare sempre la perdita di gas (refrigerante) dopo l'installazione o la riparazione del prodotto.
- I livelli di refrigerante bassi possono provocare un guasto del prodotto.
• Installare il tubo di drenaggio per assicurare che l'acqua sia drenata correttamennte.
- Un collegamento errato può provocare perdita di acqua.
• Mantenere il livello quando si installa il prodotto.
- Per evitare le vibrazioni o la perdita di acqua.
• Non installare il prodotto in posizioni in cui il rumore o l'aria calda dell'unità esterna potrebbero danneggiare i vicini di casa.
- Si può produrre un problema per i vostri vicini.
• Usare due o tre persone per sollevare e trasportare il prodotto.
- Evitare i danni alle persone.
• Non installare il prodotto in posizione che sia esposta al vento di mare (spruzzi di sale) in modo diretto.
- Si può produrre la corrosione del prodotto. La corrosione, in particolare del condensatore e delle
alettae dell'evaporatore, potrebbero provocare malfunzionamento del prodotto o funzionamento
non efficiente.
INDICE
INDICE
5
2CONSIGLI PER
RISPARMIO DI ENERGIA
3IMPORTANTI ISTRUZIONI
DI SICUREZZA
6POSIZIONI DI INSTAL-
LAZIONE
7L'INSTALLAZIONE DEL-
L'UNITÀ INTERNA
8- Aprire il coperchio laterale
9- Montaggio del dado e bullone di ancor-
aggio
11Tubazione drenaggio dell'unità interna
11Tubazione di drenaggio
11Test di drenaggio
12Isolamento termico
12- Collegamento dei cavi all'unità interna
12- Collegamento di cablaggio
16 ISTRUZIONI DI INSTAL-
LAZIONE
16Impostazioni per Installatore - Come
entrare nel modo di installazione
17Impostazioni per Installatore - Tabella
codici di impostazione per installatore
17- Tabella codici di impostazione per
installatore
18Impostazioni per Installatore - Indirizzo di
impostazione per controllo centralizzato
18Impostazioni per Installatore - Controllo
indirizzo per controllo centralizzato
ITALIANO
14 AVVIO DEL TEST
14- PRECAUZIONI PER ESECUZIONE DEL
TEST
14- Controllare le seguenti parti quando l'in-
stallazione è stata completata.
14- Collegamento dell'alimentazione di
energia
14- Valutazione della prestazione
15- UTILIZZO
POSIZIONI DI INSTALLAZIONE
Unità interna
Tipo sospeso a soffitto
Maggiore di 700mm
Maggiore di 300mm
Maggiore di 700mm
6
POSIZIONI DI INSTALLAZIONE
ITALIANO
- Vicino all'unità non deve essere presente alcuna sorgente di calore o di vapore.
- Non devono essere presenti ostacoli che impediscano la circolazione dell'aria.
- Una porzionee in cui la circolazione dell'aria dell'ambiente sia corretta.
- Una posizione in cui il drenaggio possa essere realizzato facilmente.
- Una posizione in cui la protezione del rumore sia tenuta presente in modo corretto.
- Non installare l'unità vicino alla porta dell'appartamento.
- Verificare gli spazi indicati dalle frecce rispetto alla parete, al soffitto o ad altri ostacoli.
- L'unità interna deve consentire lo spazio per la manutenzione.
L'INSTALLAZIONE DELL'UNITÀ INTERNA
Tabella per
Condizionatore d'aria
Mantenere una
distanza sufficiente
Usare il ventilatore per la
cappa di raccolta dei fumi
con una capacità
sufficiente.
L'INSTALLAZIONE DELL'UNITÀ INTERNA
7
ITALIANO
CAUTELA
!
• Installare l'unità orizzontalmente usando
una livella ad acqua.
• Durante l'installazione, si deve fare attenzione a non danneggiare i fili elettrici.
• Selezionare e marcare la posizione per fissare i bulloni e il foro della tubazione.
• Stabilire la posizione dei bulloni di fissaggio
leggermente inclinati considerando la
direzione del tubo di drenaggio.
• Eseguire il foro del bullone di ancoraggio
sulla parete.
NOTA
!
• Evitare la seguente posizione di installazione.
1. Le posizioni come ristoranti e le cucine in
cui viene prodotta una grande quantità di
vapore e aromi. Questi possono provocare la riduzione di efficienza dello scambio di calore, gocce di acqua, malfunzionamento della pompa di drenaggio. In questi
casi, eseguire le azioni seguenti.
• Verificare che il ventilatore dell'aria sia sufficiente per pompare tutti i gas dannosi da
questa posizione.
• Accertare che esita una distanza sufficiente dalla stanza di cottura per installare
il condizionatore d'aria in posizione tale da
non aspirare il vapore contenente gocce di
olio.
2. Evitare di installare il condizionatore in
posizione in cui sia generato olio di cottura o polvere di ferro.
3. Evitare le posizioni in cui è generato gas
infiammabile.
4. Evitare una posizione in cui sia generato
gas tossico.
5. Evitare le posizioni vicine a generatori ad
alta frequenza.
L'INSTALLAZIONE DELL'UNITÀ INTERNA
8
Aprire coperchio laterale
- Togliere le quattro viti del coperchio laterale.
- Sbloccare il coperchio laterale dal pannello
ITALIANO
laterale con cautela. (Trattenere il coperchio
laterale con il palmo della mano sul lato posteriore.)
- Aprire il foro della tubazione dal coperchio laterale sinistro con tenaglie/pinze.
CAUTELA
!
Sostenere il coperchio con l'altra mano
mentre si apre il foro per evitare la sua
caduta.
Fase 1
Fase 2
Lato posteriore
Fase 3
Coperchio laterale destro
Coperchio
laterale
sinistro
Lato posteriore
Montaggio del dado e bullone di
Rondella piatta per M10
(accessorio)
Rondella piatta per M10
(accessorio)
Bullone di sospensione
(W3/8 or M10)
Dado
(W3/8 or M10)
Dado
(W3/8 or M10)
Rondella elastica
(M10)
Wall
5~7mm
Interno Esterno
ancoraggio
- Preparare 4 bulloni di sospensione. (I bulloni
devono avere lunghezza eguale.)
- Misurare e marcare la posizione dei bulloni di
sospensione e del foro del tubo.
- Eseguire il foro per il dado di ancoraggio sul
soffitto.
- Inserire i dadi e le rondelle nei bulloni di
sospensione per bloccare i bulloni di sospensione sul soffitto.
- Montare i bulloni di sospensione sui dadi di
ancoraggio in modo fisso.
- Fissare i tiranti sui bulloni di sospensione (regolare livello corretto) usando dadi, rondelle e rondelle elastiche.
- Regolare il livello con una livella ad acqua nella
direzione sinistra-destra, avanti -indietro
regolando i bulloni di sospensione.
- Regolare un livello nella direzione di alto-basso
regolando i bulloni di sospensione. Quindi l'unità verrà inclinata sul lato di fondo per ottenere
un drenaggio corretto.
DIM
MODEL
VL1655320
VK1255320
VJ855320
AB
L'INSTALLAZIONE DELL'UNITÀ INTERNA
- La parte seguente è opzionale.
Bullone di sospensione - W 3/8 or M10
Dado - W 3/8 or M10
Rondella elastica - M10
Rondella piatta - M10
CAUTELA
!
Serrare i dadi e bulloni per evitare la caduta dell'unità.
• Eseguire il foro della tubazione sulla
parete leggermente inclinata verso il lato
esterno usando una punta a tazza Ø 70.
9
ITALIANO
Dado di ancoraggio
Soffitto
Dado
Bullone di
sospensione
rondella
A
Bullone di sospensione
Rondella elastica
Sospensore
Bullone di
sospensione
Max.
12mm
B
Dado
rondella
THE INDOOR UNIT INSTALLATION
10
CAUTELA
!
ITALIANO
Informazioni di installazione per l'inclinazione
- L'inclinazione di installazione dell'unità interna è molto importante per il drenaggio del condizionatore del tipo convertibile.
- Lo spessore minimo dell'isolamento del tubo di collegamento deve essere di 10 mm.
- Se le piastre di installazione sono fissate sulla linea orizzontale, l'unità interna dopo l'installazione sarà inclinata sul lato inferiore.
Vista anteriore
- L'unità deve essere orizzontale o inclinata con un certo angolo.
- L'inclinazione dovrebbe essere inferiore o eguale a 1° o inclinata di 10 - 20 mm nella direzione
di drenaggio come indicato in Fig.
soffitto
10~20mm
Vista laterale
L'unità deve essere inclinata sul lato inferiore quando l'installazione è terminata.
soffitto
5~10mm
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.