LG UU37W INSTALLATION INSTRUCTIONS

Page 1
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
INSTALLATION MANUAL
AIR CONDITIONER
TYPE : Standard inverter
www.lg.com
Copyright © 2015 - 2019 LG Electronics Inc. All Rights Reserved.
MFL69190205
Rev.01_051719
ENGLISH
РУССКИЙ ЯЗЫК
УКРАÏНСЬКА
ҚАЗАҚ ТІЛІ
беларуская мова
OZBEK TILI
Page 2
Table of contents
TABLE OF CONTENTS
3 SAFETY PRECAUTIONS
6 INSTALLATION OF OUTDOOR UNIT
9 Night Silent Operation setting
10 WIRING CONNECTION
10 Electrical Wiring
10 Connecting Cables between Indoor Unit and Outdoor Unit
12 Connecting the cable to Outdoor Unit
13 CONNECTING PIPES
13 Preparation of Piping
14 Connecting the pipes to the Outdoor unit
16 Forming the piping
17 LEAKAGE TEST AND EVACUATION
17 Preparation
17 Leakage test
18 Evacuation
19 TEST RUNNING
21 FUNCTION
21 Forced Cooling Operation
22 SELF-DIAGNOSIS FUNCTION
22 Error Indicator (Outdoor)
23 INSTALLATION GUIDE AT THE SEASIDE
2 Air Conditioner
Page 3
Safety Precautions
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions must be followed.
n Be sure to read before installing the air conditioner. n Be sure to observe the cautions specified here as they include important items related to safety. n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
ENGLISH
!
WARNING
!
CAUTION
n The meanings of the symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
!
WARNING
Installation
• Always perform grounding.
- Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation agency.
- Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not
attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board.
- No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner.
- Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly.
- It will cause a fire or electrical shock.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
Installation Manual 3
Page 4
Safety Precautions
- There is the risk of death, injury, fire or explosion.
• Do not install the product at a place that there is concern of falling down.
- Otherwise, it may result in personal injury.
• Use caution when unpacking and installing.
- Sharp edges may cause injury.
Operation
• Do not share the outlet with other appliances.
- It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord.
- Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation.
- Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell or smoke comes from it.
- Otherwise, it may cause electrical shock or a fire.
• Keep the flames away.
- Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools.
- Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation.
- Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts.
- Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out.
- It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter.
- They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it.
- It may cause an injury through dropping of the unit or falling down.
• Do not place a heavy object on the power cord.
- Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit.
- Otherwise, children may be seriously injured due to falling down.
4 Air Conditioner
Page 5
Safety Precautions
!
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done.
- Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
- Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product.
- Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product.
- Otherwise, it may cause vibration or water leakage.
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
Operation
• Avoid excessive cooling and perform ventilation sometimes.
- Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner or a strong detergent.
- The appearance of the air conditioner may deteriorate, change color or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine or art articles.
- Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet.
- Otherwise, it may cause the failure of appliance or an accident.
ENGLISH
Installation Manual 5
Page 6
More than 300 mm
Installation of Outdoor Unit
Installation of Outdoor Unit
1. Installation Places
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
• Ensure that the spaces indicated by arrows around front, back and side of the unit.
More than 300 mm
• Do not place animals and plants in the path of the warm air.
• Take the air conditioner weight into account
Fence or
obstacles
and select a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
2. Piping length and the elevation
n Single Operation
Pipe Size
Model Capacity
UU18W 5 kW Ø 12.7(1/2) Ø 6.35(1/4) 7.5 40 5 30 20 UU24W 7 kW Ø 15.88(5/8) Ø 9.52(3/8) 7.5 50 5 30 40
UU30W 8 kW Ø 15.88(5/8) Ø 9.52(3/8) 7.5 50 5 30 40 UU36W/UU37W 10 kW Ø 15.88(5/8) Ø 9.52(3/8) 7.5 50 5 30 40 UU42W/UU43W 12.5 kW Ø 15.88(5/8) Ø 9.52(3/8) 7.5 75 5 30 40 UU48W/UU49W 14 kW Ø 15.88(5/8) Ø 9.52(3/8) 7.5 75 5 30 40 UU60W/UU61W 15 kW Ø 15.88(5/8) Ø 9.52(3/8) 7.5 75 5 30 40
mm(inch)
Gas Liquid Standard Max. Standard Max.
Length A(m) Elevation B(m)
Sunroof
More than 700 mm
More than
More than 300 mm
300 mm
More than 600 mm
Unit : mm
Additional refrigerant
(g/m)
If installed tube is shorter than 7.5 m, additional charging is not necessary. Additional Refrigerant = (A-7.5)xAdditional refrigerant (g)
6 Air Conditioner
Indoor unit
B
A
Outdoor unit
Indoor unit
Outdoor unit
A
B
Page 7
Installation of Outdoor Unit
Indoor Unit Refrigerant Additional charging (g)
Duo
Trio
Quartet
Refrigerant = (L1-b)xB+(L2+L3)xC
Refrigerant = (L1-b)xB+(L2+L3+L4)xC
Refrigerant = (L1-b)xB+(L2+L3+L4+L5)xC
C
(g/m)
Pipe Size mm(inch)
Ø 6.35(1/4)
Ø 9.52(3/8)
35
40
b
(m)
Model
UU42W/UU43W UU48W/UU49W UU60W/UU61W
B
(g/m)
7.5 40
n Synchro Operation
Install the branch pipe so that pipe length and difference between high and low will not exceed below Spec.
L2
L3
L4
L5
H1
Remote
Controller
L1
Branch
A
A
Pipe Length & Height
Total(L1+L2+L3+L4+L5)
Main Pipe(L1)
H2
Branch Pipe (L2+L3+L4+L5)
Each
Indoor-Outdoor (H1)
Indoor-Indoor (H2)
(L1+L2),(L1+L3),(L1+L4),(L1+L5)
A
[Unit : m]
Spec(MAX.)
80
45
40
15
30
1
70
10
• When installing the branch pipe, direction and angle of installation is not limited.
• Take care so that burrs and foreign material may not enter into the cutting surface when connecting.
• Connect remaining those by cutting or direct insertion to the diameter of pipe.
n Refrigerant Additional Charging Method
For additional charging method, see below table.
ENGLISH
NOTICE
b : Rated performance for refrigerant line length. C : Additional charging Refrigerant of Branch Liquid Pipe. B : Additional charging Refrigerant of Main Liquid Pipe.
!
CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of
• Improper refrigerant charge may result in abnormal cycle.
reliability.
Installation Manual 7
Page 8
Installation of Outdoor Unit
SW01B
LED01H
DIP SW2
A
B
MAIN PCBMAIN PCB
UU42W/48W/60W UU43W/49W/61W
LED01G LED02G
SW02N
SW01N
B
A
LED01M LED02M
6
ODU
BD
IDU IDU
REMO
ODU
BD
IDU IDU IDU
REMO
BD
IDU IDU IDU IDU
ODU
REMO
3. Synchro Combination table
Possible combination of indoor units
Synchro
Duo Trio Quartet
IDU : INDOOR UNIT ODU : OUTDOOR UNIT BD : BRANACH
DISTRIBUTOR UNIT
REMO : WIRED
REMOTE CONTROLLER
MODEL
UU42W/UU43W UU48W/UU49W UU60W/UU61W
Bdunit PMUB11A PMUB111A PMUB1111A
Applied
Accessi
ries
NOTICE
Simple central controller**
Cassette
CT24 NP2R0 CB24 NH2R0 CV24 NJ2R0 CT18 NQ2R0 CB18 NH2R0 CV18 NJ2R0 CT12 NR2R0 - ­CT24 NP2R0 CB24 NH2R0 CV24 NJ2R0 CT18 NQ2R0 CB18 NH2R0 CV18 NJ2R0 CT12 NR2R0 - -
UT30W NP2R0
UB30 NG2R0 UV30 NJ2R0 CT18 NQ2R0 CB18 NH2R0 CV18 NJ2R0 CT12 NR2R0 - -
** When using synchro operation,
- Do not use wireless remote controller.
- Use only one wired remote controller in the indoor units.
- Use Simple central controller "PQCSZ250S0" only.
Duct
Ceiling
Cassette
Suspended
Duct
PQCSZ250S0
Ceiling
Suspended
Cassette
Duct
Ceiling
Suspended
4.
Outdoor Unit PCB Setting Procedure For Simultaneous Operation System
1. SW01N (PIP SW2) Setting
Set the SW01N (PIP SW2) as below Table (Ⓐ)
2. Auto Addressing Method Addressing work assigns address to each indoor unit. When firstly installing product or replacing the indoor unit PCB. Auto Addressing work should be done for simultaneous operation.
h Work procedure
1) Set SW01N (PIP SW2) correctly.
2) Turn on main power.
3) Press the SW02N (SW01B) for about 3 seconds within 3 minutes After main power on.(Ⓑ)
8 Air Conditioner
Page 9
Installation of Outdoor Unit
SW01N (PIP SW2)
Indoor Unit No.
2(Duo)
1(Single) : Default
3(Trio)
4(Quartet)
Table SW01N (PIP SW2) Setting
DIP SW2
6
SW01N
SW01N
6
4) After step 3), the LED01M/G (red LED) and LED02M/G (green LED) rapidly flickers. When Addressing work is done, green LED is off, else LED (LED01M/G) stops flickering and lights continuously. Address of indoor unit is indicated on the wired remote control display window. (CH01, CH02, CH03, CH04)
5) Press button to turn on the indoor.
6) If you fail to perform the Addressing work, repeat step 2)~5).
Night Silent Operation setting
1. Open the Side panel or Top Cover of outdoor unit.
2. Set the SW01N (PIP SW2).
UU18W UU24W UU30W
UU36W UU42W UU48W UU60W
ENGLISH
UU37W UU43W UU49W UU61W
3. Close the Side panel or Top Cover.
UU18W UU24W UU30W
UU36W UU42W UU48W UU60W
UU37W UU43W UU49W UU61W
Installation Manual 9
Page 10
Wiring Connection
Outdoor
Indoor
Main power source
Switch box
ELCB
2(N)31(L)S CN-REMO
CN-REMO
CN-REMO
Terminals on the indoor unit 4
2(N)31(L)S
Terminals on the indoor unit 3
2(N)31(L)S
Terminals on the indoor unit 2
2(N)31(L)M
Terminals on the indoor unit 1
Terminals on the Outdoor unit
2(N)31(L)
Remote Controller
CN-REMO
2(N)31(L)
2(N)31(L)
2(N)31(L)
2(N)
3
4
4
4
4
5
5
5
5
1(L)
• When using simultaneous Operation System, use only one wired remote controller in the indoor units
Simultaneous Operation Unit 2, 3, 4
Main Unit1
POWER INPUT
(220 V-240 V~)
LN
2(N)31(L)
CSTDUCT, CVT
1(L) 2(N) 1(L) 2(N) 31(L) 2(N) 1(L) 2(N) 3 RS TN 1(L) 2(N) 3
POWER SUPPLY TO INDOOR UNITPOWER SUPPLY TO INDOOR UNIT POWER SUPPLY TO INDOOR UNIT
UU18W UU24W/30W/36W/42W/48W/60W UU37W/43W/49W/61W
Wiring Connection
Electrical Wiring
Perform the electrical wiring work according to the electrical wiring connection.
• All wiring must comply with local requirements. Select a power source that is capable of
• supplying the current required by the air conditioner.
• Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
• Model of circuit breaker recommended by authorized personnel only
Model Phase(Ø ) ELCB UU18W UU24W UU30W UU36W
UU42W/UU48W/UU60W
UU37W
UU43W/UU49W/UU61W
1 20 A 1 30 A 1 30 A 1 40 A 1 40 A 3 20 A 3 20 A
Connecting Cables between Indoor Unit and Outdoor Unit
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
10 Air Conditioner
Page 11
The power cord
connected to the outdoor unit should be complied withIEC 60245 or HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national regulation.
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national regulation.)
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
NORMAL CROSS-SECTIONAL AREA 0.75 mm
2
When the connection line between the indoor unit and outdooor unit is over 40 m, connect the telecommunication line and power line separately.
20 mm
GN/YL
35±5 mm
10±3 mm
GN/YL
20 mm
35±5 mm
10±3 mm
Round pressure terminal
Power wire
Outdoor
unit
Indoor
unit
1
2
3
1
2
3
!
CAUTION
Model Phase(Ø ) Area(mm2)
UU18W/24W/30W
UU36W/UU42W /UU48W/UU60W
UU37W/UU43W /UU49W/UU61W
u
Precautions when laying power wiring
12.5
16
32.5
Use round pressure terminals for connections to the power terminal block.
Wiring Connection
ENGLISH
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
• For wiring, use the designated power wire and connect firmly, then secure to prevent outside
pressure being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head
will strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
Installation Manual 11
Page 12
Wiring Connection
* Make sure the rubber bushes are
properly used in knock-out holes after connecting main power.
Connecting cable terminal
Power cord terminal
Cord clamp
Cord clamp
Connecting the cable to Outdoor Unit
• Remove the side panel for wiring connection.
• Use the cord clamp to fix the cord.
• Earthing work
- Connect the cable of diameter more to the earthing terminal provided in the control box and do earthing.
!
CAUTION
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
!
CAUTION
The Power cord connected to the unit should be selected according to the following specifications.
12 Air Conditioner
Page 13
Connecting Pipes
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.
• Use the accessory piping kit or the pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured distance.
Cut the cable 1.5 m longer than the pipe length.
Burrs removal
• Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
Putting nut on
• Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
Flaring work
Carry out flaring work using dedicated flaring tool for R-410A as shown below.
Pipe diameter
Inch (mm) Ø 1/4 (Ø 6.35) Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
Ø 5/8 (Ø 15.88) Ø 3/4 (Ø 19.05)
0.04~0.05 (1.1~1.3)
0.06~0.07 (1.5~1.7)
0.06~0.07 (1.6~1.8)
0.06~0.07 (1.6~1.8)
0.07~0.08 (1.9~2.1)
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
A inch (mm)
Wing nut type Clutch type
0~0.02
(0~0.5)
Copper
tube
Point down
Copper tube
<Wing nut type> <Clutch type>
Smooth all round
Inside is shining without scratches
Slanted Uneven Rough
90°
Pipe
Flare nut
Bar
Copper pipe
= Improper flaring =
Connecting Pipes
ENGLISH
Reamer
"A"
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section and do flaring work again.
Even length
all round
Inclined
Surface
Cracked Uneven
damaged
Installation Manual 13
thickness
Page 14
Continuous
Torque wrench
Connecting Pipes
Forward
Sideways
Backward
Downward
<Figure 1>
Connecting the pipes to the Outdoor unit
• Align the center of the piping and sufficiently tighten the flare nut by hand.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening follows the arrow on the wrench.
Outside diameter Torque
mm inch N.m Ø 6.35 1/4 16±2 Ø 9.52 3/8 38±4 Ø 12.7 1/2 55±6
Ø 15.88 5/8 75±7
h When tighten the pipe, hold the haxagonal
body.
14 Air Conditioner
Page 15
Connecting Pipes
Knock-out Base pan
Gas side piping
Liquid side piping
Drain hose
Connecting wire
Connection pipe
<Figure 3>
Putty or insulating material (produced locally)
<Figure 2>
• When connecting in a downward direction, knock out the knock-out hole of the base pan. (refer to figure 2)
Preventing foreign objects from entering (Figure3)
• Plug the pipe through-holes with putty or insulation material(procured locally)to stop up all gaps,as shown in the figure 3.
!
CAUTION
Insects or small animals entering the outdoor unit may cause a short circuit in the electrical box.
ENGLISH
Installation Manual 15
Page 16
Connecting Pipes
Trap
Plastic band
Seal a small opening around the pipings with gum type sealer.
TrapTrapTrap
Seal a small opening Seal a small opening around the pipings around the pipings with gum type sealer.with gum type sealer.
Seal a small opening around the pipings with gum type sealant.
• Trap is required to prevent water from entering into electrical parts.
Taping
Drain hose
Pipings
Connecting cable
Power supply cord
PlasticPlastic bandband
Plastic band
Seal a small Seal a small opening around opening around the pipings with the pipings with gum type sealer.gum type sealer.
Seal a small opening around the pipings with gum type sealant.
Forming the piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
• If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1. Tape the piping, drain hose and connecting
cable from down to up.
2. Secure the tapped piping along the
exterior wall using saddle or equivalent.
In cases where the outdoor unit is installed above the indoor unit perform the following.
1. Tape the piping and connecting cable from
down to up.
2. Secure the taped piping along the exterior
wall. Form a trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or
equivalent.
16 Air Conditioner
Page 17
Leakage test and Evacuation
Charge hose
Indoor unit
Outdoor unit
Manifold valve
Lo Hi
Pressure gauge
Nitrogen gas cylinder(in vertical standing position)
ENGLISH
Leakage test and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system. Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.
Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
!
CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
• Pressurize the system to no more than 3.0
MPa with dry nitrogen gas and close the cylinder valve when the gauge reading reached 3.0 MPa Next, test for leaks with liquid soap.
!
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1. Do a leakage test of all joints of the
tubing(both Indoor unit and outdoor unit) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Installation Manual 17
Page 18
Leakage test and Evacuation
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Open
Open
Pressure gauge
Gas pipe
Evacuation
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo and Hi" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
Required time for evacuation when 30 gal/h
If tubing length is less
than 10 m(33 ft)
30 minutes or more 60 minutes or more
2. When the desired vacuum is reached, close the "Lo and Hi" knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter­clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
vacuum pump is used
If tubing length is longer
than 10 m(33 ft)
0.07 kPa or less
18 Air Conditioner
Page 19
Test running
Test running
1. PRECAUTIONS IN TEST RUNNING
• The initial power supply must provide at least 90 % of the rated voltage. Otherwise, the air conditioner should not be operated.
!
CAUTION
For test run, carry out the cooling operation firstly even during heating season. If
heating operation is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
• To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured data, etc.
• Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure.
• As to the structure and appearance, check following items.
Is the circulation of air adequate?Is the draining smooth?Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is the remote controller switch operated?Is there any faulty wiring?Are not terminal screws loosened?
M4......118 N.cm{12 kgf.cm} M5......196 N.cm{20 kgf.cm}
M6......245 N.cm{25 kgf.cm} M8......588 N.cm{60 kgf.cm}
ENGLISH
2. Connection of power supply
1. Connect the power supply cord to the independent power supply.
• Circuit breaker is required.
2. Operate the unit for fifteen minutes or more.
3. Evaluation of the performance
1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is more than 8 °C (Cooling) or reversely (Heating).
Thermometer
Installation Manual 19
Page 20
Test running
!
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of fuse breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
10) Use only 1 remote-controller contained in indoor unit, when using simultaneous operation system as shown below. After setting the ESP value in the Ceiling Concealed Duct Type Indoor Unit, the main power turns off and then remove the remote controller.
11) It is possible to connect (install) same type of indoor units only and also with in a single room.
Connecting cable
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).
20 Air Conditioner
Page 21
6
Function
Forced Cooling Operation
• Adding the refrigerant in winter.
Setting Procedure
1) Set the DIP Switch as follow after shutting the power source down.
Function
ENGLISH
UU18W UU24W UU30W
2) Reset the power.
3) Red LED and Green LED of PCB lights during work. (The indoor unit is operated by force.)
4) If operation is done, Red LED will be turned off. If operation is not done normally, Red LED will blink.
5) Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine). Then close the gas valve after Green LED on.
!
WARNING
• When the green LED of PCB is on, compressor is going to be off because of low pressure.
• You should return the DIP Switch to operate normally after finishing the operation.
• Improper Pump down will lead to product turn off along with LED (green &red) off with in 20 minutes from the initial start.
UU36W UU42W UU48W UU60W
Pump Down DIP S/W Setting
Power on
(Red LED On, Green LED Off)
Comp on
(Red LED On, Green LED On)
UU37W UU43W UU49W UU61W
Pump Down Start
(Red LED On, Green LED Off)
Pump Down Complete
(Red LED Off, Green LED On)
Power off
(Red LED Off, Green LED On)
Liquid Valve Closed
Gas Valve Closed
Installation Manual 21
Page 22
Self-diagnosis Function
1 Time 1 Time 1 Time
2 Times2 Times2 Times
1 Seconds
2 seconds 2 seconds
1 Seconds 1 Seconds
LED01G
(RED)
LED02G
(GREEN)
Self-diagnosis Function
Error Indicator (Outdoor)
Outdoor Error Ex) Error 21 (DC Peack)
UU18W/24W/30W UU37W/43W/49W/61WUU36W/42W/48W/60W
Error Code
Description
21 DC Peak(IPM Fault)
22 Max. CT(CT2)
23 DC Link Low Volt.
24 Pressure switch/Heater Sink.
26 DC Comp Position Error
27 PFC Fault Error
29 Comp Over Current
32 D-Pipe High(Inv.)
40 CT Sensor(Open/Short)
41 Inv. D-Pipe Th Error(Open/Short)
43 High Pressure Sensor(Open/Short)
44 Outdoor air Th Error(Open/Short)
45 Cond. Middle Pipe Th Error(Open/Short)
46 Suction Pipe Th Error(Open/Short)
48 Cond. Out-Pipe Th Error(Open/Short)
51 Capacity over
53 Communication Error(Indoor ÷ Outdoor)
60 EEPROM Error(Outdoor)
61 Cond. Middle Pipe High
62 Heatsink Error(High)
65 Heatsink Th Error(Open/Short)
67 BLDC motor fan lock(Outdoor)
If abnormal voltage is supplied, the protection circuits will turn off the product in order to prevent the component damage. The product will automatically restart after 3 minutes.
LED 1
(Red)
2 times 1 time OFF
2 times 2 times OFF
2 times 3 times OFF
2 times 4 times OFF
2 times 6 times OFF
2 times 7 times OFF
2 times 9 times OFF
3 times 2 times OFF
4 times 0 OFF
4 times 1 time OFF
4 times 3 times OFF
4 times 4 times OFF
4 times 5 times OFF
4 times 6 times OFF
4 times 8 time OFF
5 times 1 times OFF
5 times 3 times OFF
6 times 0 OFF
6 times 1 times OFF
6 times 2 times OFF
6 times 5 times OFF
6 times 7 times OFF
LED 2
(Green)
Indoor
status
22 Air Conditioner
Page 23
Installation Guide at the Seaside
Sea wind Sea wind
Installation Guide at the Seaside
!
CAUTION
1.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc­tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
ENGLISH
Windbreak
Sea wind
3) Select a well-drained place.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
• It should be strong enough like concrete to prevent the sea wind from the sea.
• The height and width should be more than 150 % of the outdoor unit.
• It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
Installation Manual 23
Page 24
24 Air Conditioner
Page 25
Loading...