LG UU30W INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL

AIR

CONDITIONER

Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

Standard inverter

Original instruction

[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands [Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-

gu, Changwon-si, Gyeongsangnam-do, KOREA

For more information, Refer to the CD or LG Web site (www.lg.com).

www.lg.com

<![if ! IE]>

<![endif]>ROMÂNĂ LIMBA POLSKI NEDERLANDS ČEŠTINA ΕΛΛΗΝΙΚΆ DEUTSCH FRANÇAIS ESPAÑOL ITALIANO ENGLISH

P/NO : MFL67855411

Single A Air Conditioner Installation Manual

CONTENTS

Safety Precautions ..............................................................................................

3

Installation of Outdoor Unit................................................................................

7

Wiring Connection.............................................................................................

11

Connecting Pipes ..............................................................................................

14

Leakage test and Evacuation ...........................................................................

18

Test running .......................................................................................................

20

Function..............................................................................................................

22

Self-diagnosis Function....................................................................................

23

Installation Guide at the Seaside.....................................................................

24

2

Safety Precautions

Safety Precautions

To prevent the injury of the user or other people and property damage, the following instructions must be followed.

νBe sure to read before installing the air conditioner.

νBe sure to observe the cautions specified here as they include important items related to safety.

νIncorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.

WARNING This symbol indicates the possibility of death or serious injury.

CAUTION This symbol indicates the possibility of injury or damage to properties only.

ν The meanings of the symbols used in this manual are as shown below.

Be sure not to do.

Be sure to follow the instruction.

WARNING

ν Installation

 

 

Always perform

Don’t use a power

grounding.

cord, a plug or a loose

 

 

socket which is dam-

 

 

aged.

• Otherwise, it may cause

• Otherwise, it may cause

electrical shock.

a fire or electrical shock.

For installation of the product, always contact the service center or a professional installation agency.

Otherwise, it may cause a fire, electrical shock, explosion or injury.

Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.

If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.

Always install an air leakage breaker and a dedicated switching board.

No installation may cause a fire and electrical shock.

Do not keep or use flammable gases or combustibles near the air conditioner.

Otherwise, it may cause a fire or the failure of product.

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 3

Safety Precautions

Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.

Do not disassemble or repair the product randomly.

• It may cause injury or an

• It will cause a fire or

accident.

electrical shock.

Do not install the product at a place that there is concern of falling down.

Otherwise, it may result in personal injury.

Use caution when unpacking and installing.

• Sharp edges may cause injury.

ν Operation

Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.

There is the risk of death, injury, fire or explosion.

Do not share the outlet with other appliances.

It will cause an electric shock or a fire due to heat generation.

Do not use the damaged power cord.

Otherwise, it may cause a fire or electrical shock.

Do not modify or extend the power cord randomly.

Otherwise, it may cause a fire or electrical shock.

Take care so that the power cord may not be pulled during operation.

Otherwise, it may cause a fire or electrical shock.

Unplug the unit if

Keep the flames away.

strange sounds,

 

smell, or smoke

 

comes from it.

 

• Otherwise, it may

• Otherwise, it may

cause electrical shock

cause a fire.

or a fire.

 

4

Safety Precautions

Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.

Do not use the power cord near the heating tools.

Do not open the suction inlet of the indoor/outdoor unit during operation.

• Otherwise, it may

• Otherwise, it may

• Otherwise, it may elec-

cause a fire or electri-

cause a fire and electri-

trical shock and failure.

cal shock.

cal shock.

 

Do not allow water to run into electrical parts.

Otherwise, it may cause the failure of machine or electrical shock.

Hold the plug by the head when taking it out.

It may cause electric shock and damage.

Never touch the metal parts of the unit when removing the filter.

They are sharp and may cause injury.

Do not step on the

Do not place a heavy

indoor/outdoor unit

object on the power

and do not put any-

cord.

thing on it.

 

• It may cause an injury

• Otherwise, it may

through dropping of the

cause a fire or electri-

unit or falling down.

cal shock.

When the product is submerged into water, always contact the service center.

Otherwise, it may cause a fire or electrical shock.

Take care so that children may not step on the outdoor unit.

• Otherwise, children may be seriously injured due to falling down.

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 5

Safety Precautions

CAUTION

ν Installation

Install the drain hose to ensure that drain can be securely done.

Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.

• Otherwise, it may cause

• Otherwise, it may cause

water leakage.

dispute with the neigh-

 

bors.

Always inspect gas leakage after the installation and repair of product.

Otherwise, it may cause the failure of product.

Keep level parallel in installing the product.

Otherwise, it may cause vibration or water leakage.

Please install safely at a place that can sufficiently endure the weight of the product.

If the strength is not sufficient, the product may fall and cause injury.

ν Operation

Avoid excessive cooling and perform ventilation sometimes.

Otherwise, it may do harm to your health.

Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.

Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles.

• The appearance of the

• Otherwise, it may dam-

air conditioner may dete-

age your properties.

riorate, change color, or

 

develop surface flaws.

 

Do not place obstacles around the flow inlet or outlet.

• Otherwise, it may cause the failure of appliance or an accident.

6

Installation of Outdoor Unit

Installation of Outdoor Unit

You need to select adequate installation location considering the following conditions, and make sure to acquire the consent of the user.

1.Installation Places

If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.

Ensure that the spaces indicated by arrows around front, back and side of the unit.

Do not place animals and plants in the path of the warm air.

Take the air conditioner weight into account and select a place where noise and vibration are minimum.

Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

Place that can sufficiently endure the weight and vibration of the outdoor unit and where even installation is possible

Place that has no direct influence of snow or rain

Place with no danger of snowfall or icicle drop

Place without weak floor or base such as decrepit part of the building or with a lot of snow accumulation

 

Sunroof

More than

 

300mm

 

Fence

More than

300mm

 

obstacles

 

or

 

More than 600mm

More than 700mm

Unit : mm

2. Piping length and the elevation

ν Single Operation

 

 

Pipe Size

Length A(m)

Elevation B(m)

Additional

Model

Capacity

mm(inch)

refrigerant

 

 

 

 

 

 

Gas

Liquid

Standard

Max.

Standard

Max.

(g/m)

 

 

 

 

 

 

 

 

 

UU18W

5kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

40

5

30

20

UU24W

7kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

UU30W

8kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

UU36W/UU37W

10kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

UU42W/UU43W

12.5kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

75

5

30

40

UU48W/UU49W

14kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

75

5

30

40

 

 

 

 

 

 

 

 

 

UU60W/UU61W

15kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

75

5

30

40

If installed tube is shorter than 7.5 m, additional charging is not necessary.

Additional Refrigerant = (A -7.5) x Additional refrigerant (g)

Indoor unit

Outdoor unit

 

A

 

A

 

 

 

B

Outdoor unit

Indoor unit

B

 

 

 

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 7

LG UU30W INSTALLATION INSTRUCTIONS

Installation of Outdoor Unit

ν Synchro Operation

Install the branch pipe so that pipe length and difference between high and low will not exceed below Spec.

 

L2

Branch

 

[Unit : m]

 

L3

 

Pipe Length & Height

Spec(MAX.)

 

 

A

Total(L1+L2+L3+L4+L5)

80

 

 

 

 

L4

 

Main Pipe(L1)

45

 

 

H2

 

 

 

 

40

H1

L5

 

Branch Pipe (L2+L3+L4+L5)

 

 

A

Each

15

 

 

 

 

 

 

 

Indoor-Outdoor (H1)

30

 

Remote

 

Indoor-Indoor (H2)

1

 

Controller

 

 

 

 

 

 

(L1+L2),(L1+L3),(L1+L4),(L1+L5)

70

 

L1

 

A

10

 

 

 

When installing the branch pipe, direction and angle of installation is not limited.

Take care so that burrs and foreign material may not enter into the cutting surface when connecting.

Connect remaining those by cutting or direct insertion to the diameter of pipe.

ν Refrigerant Additional Charging Method

For additional charging method, see below table.

Indoor Unit

Refrigerant Additional charging (g)

Duo

Refrigerant = (L1-b) x B + (L2 + L3) x C

Trio

Refrigerant = (L1-b) x B + (L2 + L3 + L4) x C

Quartet

Refrigerant = (L1-b) x B + (L2 + L3 + L4 + L5) x C

Model

b

B

(m)

(g/m)

 

UU42W/UU43W

 

 

UU48W/UU49W

7.5

40

UU60W/UU61W

 

 

Pipe Size

C

mm(inch)

(g/m)

Ø6.35(1/4)

35

Ø9.52(3/8)

40

NOTICE

b : Rated performance for refrigerant line length.

C : Additional charging Refrigerant of Branch Liquid Pipe. B : Additional charging Refrigerant of Main Liquid Pipe.

CAUTION:

Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Improper refrigerant charge may result in abnormal cycle.

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation of Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Synchro Combination table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible combination of indoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchro

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duo

 

 

 

 

 

 

 

 

Trio

 

 

 

 

 

 

 

 

 

 

 

 

Quartet

 

 

 

 

 

IDU : INDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ODU : OUTDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BD : BRANACH

 

 

 

 

 

ODU

 

 

 

 

 

 

 

 

 

ODU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ODU

 

 

 

 

 

 

DISTRIBUTOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BD

 

 

 

 

 

REMO : WIRED

 

IDU

 

 

 

 

 

IDU

 

 

IDU

 

IDU

 

IDU

 

 

 

 

 

IDU

 

 

IDU

 

IDU

 

 

IDU

 

REMOTE

 

REMO

 

 

 

 

 

 

 

 

 

REMO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLLER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

Cas-

 

 

Duct

 

Ceiling

Cas-

 

Duct

Ceiling

 

 

Cas-

 

 

 

Duct

 

Ceiling

sette

 

 

Suspended

sette

 

Suspended

 

 

sette

 

 

 

Suspended

UU42W/UU43W

CT24 NP2*2

 

CB24 NH2*2

 

CV24 NJ2*2

CT18 NQ2*3

CB18 NH2*3

CV18 NJ2*3

CT12 NR2*4

-

 

-

 

UU48W/UU49W

CT24 NP2*2

 

CB24 NH2*2

 

CV24 NJ2*2

CT18 NQ2*3

CB18 NH2*3

CV18 NJ2*3

CT12 NR2*4

-

 

-

 

UU60W/UU61W

UT30 NP2*2

 

UB30 NG2*2

 

UV30 NJ2*2

CT18 NQ2*3

CB18 NH2*3

CV18 NJ2*3

CT12 NR2*4

-

 

-

 

Applied

Bdunit

 

 

PMUB11A

 

 

 

 

PMUB111A

 

 

 

 

 

 

 

 

 

PMUB1111A

 

Acces-

Simple central

 

 

 

 

 

 

 

 

 

 

 

 

 

PQCSZ250S0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

siries

controller**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTICE

**When using synchro operation,

-Do not use wireless remote controller.

-Use only one wired remote controller in the indoor units.

-Use Simple central controller "PQCSZ250S0" only.

4. Outdoor Unit PCB Setting Procedure For Simultaneous Operation System

1.SW01N (PIP SW2) Setting

Set the SW01N (PIP SW2) as below Table ( )

2.Auto Addressing Method

Addressing work assigns address to each indoor unit. When firstly installing product or replacing the indoor unit PCB. Auto Addressing work should be done for simultaneous operation.

η Work procedure

1)Set SW01N (PIP SW2) correctly.

2)Turn on main power.

3)Press the SW02N (SW01B) for about 3 seconds within 3 minutes After main power on.( )

B SW02N

<![if ! IE]>

<![endif]>SW01N6

LED01M LED02M

A LED01H

<![if ! IE]>

<![endif]>SW01B SW2DIP

LED01G LED02G

A

MAIN PCB

B

MAIN PCB

 

 

 

 

UU42W/48W/60W

 

UU43W/49W/61W

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 9