LG UU30 INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL

AIR CONDITIONER

Please read this installation manual completely before installing the product.

Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

www.lg.com

P/NO : MFL40910604

<![if ! IE]>

<![endif]>DEUTSCH FRANÇAIS ESPAÑOL ITALIANO ENGLISH

Air Conditioner Installation Manual

TABLE OF CONTENTS

Installation

 

Requirements

 

Safety Precautions .....

3

Installation of Indoor,

Outdoor unit................

6

The indoor unit

 

installation...................

9

Remote controller

 

installation.................

24

Wiring connection ....

25

Connecting Pipes to

 

the Indoor Unit ..........

27

Installation to

 

decorative panel .......

29

Indoor unit drain

 

piping .........................

30

Test running ..............

35

Optional operation....

37

Installation guide at

 

seaside.......................

42

Required Parts

Connecting cable

Four Type "A" Screw

Hanging Bolt

(W 3/8 or M10 length 650mm)

Pipes: Gas side Liquid side

Insulated drain hose

Additional Drain hose Inner Dia

Cassette type.............32mm Duct type....................25mm

Additional drain pipe (Convertible type)

(Outer diameter .....15.5mm)

Required Tools

Level

Screw driver

Electric drill

Hole core drill (ø70mm)

Flaring Tools set

Torque Wrenches

Hexagonal Wrench (4mm, 5mm)

Gas-leak detector

Owner’s Manual

Thermometer

2 Air Conditioner

Safety Precautions

Safety Precautions

or other people and property damage, the following instructions

the air conditioner.

specified here as they include important items related to safety. instruction will cause harm or damage. The seriousness is

.

indicates the possibility of death or serious injury.

indicates the possibility of injury or damage to properties only.

used in this manual are as shown below.

Be sure not to do.

Be sure to follow the instruction.

<![if ! IE]>

<![endif]>ENGLISH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Always perform grounding.

Don’t use a power cord, a

 

 

plug or a loose socket which

 

 

is damaged.

• Otherwise, it may cause

• Otherwise, it may cause a fire

electrical shock.

or electrical shock.

Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.

If the electrical part cover of the indoor unit and the service

Always install an air leakage breaker and a dedicated switching board.

No installation may cause a fire and electrical shock.

For installation of the product, always contact the service center or a professional installation agency.

Otherwise, it may cause a fire, electrical shock, explosion or injury.

Do not keep or use flammable gases or combustibles near the air conditioner.

Otherwise, it may cause a fire or the failure of product.

Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.

• It may cause injury or an accident.

Do not disassemble or repair the product randomly.

• It will cause a fire or electrical shock.

Installation Manual 3

Safety Precautions

Do not install the product at a place that there is concern of falling down.

• Otherwise, it may result in personal injury.

Use caution when unpacking and installing.

• Sharp edges may cause injury.

Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.

• There is the risk of death, injury, fire or explosion.

ν Operation

Do not share the outlet with other appliances.

It will cause an electric shock or a fire due to heat generation.

Do not use the damaged power cord.

Otherwise, it may cause a fire or electrical shock.

Do not modify or extend the power cord randomly.

Otherwise, it may cause a fire or electrical shock.

Take care so that the power cord may not be pulled during operation.

Otherwise, it may cause a fire or electrical shock.

Unplug the unit if strange sounds, smell, or smoke comes from it.

Otherwise, it may cause electrical shock or a fire.

Keep the flames away.

• Otherwise, it may cause a fire.

Take the power plug out if

Do not use the power cord

necessary, holding the head

near the heating tools.

of the plug and do not touch

 

it with wet hands.

 

• Otherwise, it may cause a fire

• Otherwise, it may cause a fire

or electrical shock.

and electrical shock.

Do not open the suction inlet of the indoor/outdoor unit during operation.

Otherwise, it may electrical shock and failure.

Do not allow water to run

Hold the plug by the head

into electrical parts.

when taking it out.

• Otherwise, it may cause the

• It may cause electric shock

failure of machine or electrical

and damage.

shock.

 

Never touch the metal parts of the unit when removing the filter.

They are sharp and may cause injury.

Do not step on the

Do not place a heavy object

indoor/outdoor unit and do

on the power cord.

not put anything on it.

 

• It may cause an injury through

• Otherwise, it may cause a fire

dropping of the unit or falling

or electrical shock.

down.

 

When the product is submerged into water, always contact the service center.

Otherwise, it may cause a fire or electrical shock.

Take care so that children may not step on the outdoor unit.

• Otherwise, children may be seriously injured due to falling down.

4 Air Conditioner

Safety Precautions

Installation

Install the drain hose to ensure that drain can be securely done.

• Otherwise, it may cause water leakage.

Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.

Otherwise, it may cause dispute with the neighbors.

Always inspect gas leakage after the

Keep level parallel in installing the product.

installation and repair of product.

 

• Otherwise, it may cause the failure of product.

• Otherwise, it may cause vibration or water

 

leakage.

Operation

Avoid excessive cooling and perform ventilation sometimes.

• Otherwise, it may do harm to your health.

Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.

The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.

Do not use an appliance for special purposes

Do not place obstacles around the flow inlet

such as preserving animals vegetables,

or outlet.

precision machine, or art articles.

 

• Otherwise, it may damage your properties.

• Otherwise, it may cause the failure of appliance

 

or an accident.

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 5

Installation of Indoor, Outdoor Unit

Installation of Indoor, Outdoor Unit

Selectionofthebestlocation

1. Indoor unit Cassette type

There should not be any heat source or steam near the unit.

There should not be any obstacles to prevent the air circulation.

A place where air circulation in the room will be good.

A place where drainage can be easily obtained.

A place where noise prevention is taken into consideration.

Do not install the unit near the door way.

Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.

The indoor unit must keep the maintenance space.

Ceiling

 

 

 

<![if ! IE]>

<![endif]>more

Ceiling Board

Ceiling Board

 

 

 

<![if ! IE]>

<![endif]>or

 

 

 

 

 

<![if ! IE]>

<![endif]>30

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>less

50 or

 

<![if ! IE]>

<![endif]>or more

 

 

50 or

<![if ! IE]>

<![endif]>30 or

more

<![if ! IE]>

<![endif]>100

<![if ! IE]>

<![endif]>250

<![if ! IE]>

<![endif]>less

more

 

 

 

 

 

<![if ! IE]>

<![endif]>Above

<![if ! IE]>

<![endif]>330 or

 

Unit:cm

 

 

 

 

 

 

 

 

 

 

Floor

 

 

Duct type

The place shall easily bear a load exceeding four times the indoor unit’s weight.

The place shall be able to inspect the unit as the figure.

The place where the unit shall be leveled.

The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)

The place shall easily connect with the outdoor unit.

The place where the unit is not affected by an electrical noise.

The place where air circulation in the room will be good .

There should not be any heat source or steam near the unit

Top view

 

 

 

 

 

 

Inspection hole

 

 

 

 

 

 

 

 

 

 

 

(600X600)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(unit: mm)

 

 

 

 

 

 

Control box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

 

<![if ! IE]>

<![endif]>1000

 

 

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front

Front view

H

6 Air Conditioner

Installation of Indoor, Outdoor Unit

Convertible type

Do not have any heat or steam near the unit.

Select a place where there are no obstacles in front of the unit.

Make sure that condensation drainage can be conveniently routed away.

Do not install near a doorway.

Ensure that the interval between a wall and the left (or right) of the unit is more than 70cm.

Use a stud finder to locate studs to prevent unnecessary damage to the wall.

There should not be any heat source or steam near the unit.

There should not be any obstacles to prevent the air circulation.

A place where air circulation in the room will be good.

A place where drainage can be easily obtained.

A place where noise prevention is taken into consideration.

Do not install the unit near the door way.

Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.

More than 70cm

More than 70cm

More than 20cm

More than 20cm

More than eye-level

(Ceiling installation)

More than 20cm

More than 20cm

(Floor/Wall installation)

2. Outdoor unit

1.If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.

2.Ensure that the spaces indicated by arrows around front, back and side of the unit.

3.Do not place animals and plants in the path of the warm air.

4.Take the air conditioner weight into account and select a place where noise and vibration are minimum.

5.Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

 

More than 60cm

More than

More than 30cm

30cm

 

More than

More

than 60cm

70cm

 

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 7

Installation of Indoor, Outdoor Unit

3. Piping length and the elevation

Capacity

Pipe Size

Length A(m)

Elevation B(m)

*Additional

(Diameter:Ø)

 

 

 

 

 

 

 

 

 

 

 

refrigerant(g/m)

 

Gas

Liquid

Standard

Max.

Standard

Max.

 

 

 

 

 

 

 

 

 

 

24k Btu/h

5/8"(15.88mm)

3/8"(9.52mm)

7.5

40

5

30

45

 

 

 

 

 

 

 

 

30k Btu/h

5/8"(15.88mm)

3/8"(9.52mm)

7.5

50

5

30

45

 

 

 

 

 

 

 

 

36k Btu/h

5/8"(15.88mm)

3/8"(9.52mm)

7.5

50

5

30

45

 

 

 

 

 

 

 

 

Oil trap

Gas piping Liquid piping

Indoor unit

A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

<![if ! IE]>

<![endif]>*15m

* Install trap at each

 

difference in height

Outdoor unit

 

15m

 

 

Outdoor unit

Indoor unit

CAUTION:

Rated performance for refrigerant line length of:7.5m

Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Improper refrigerant charge may result in abnormal cycle.

8 Air Conditioner

 

The indoor unit installation

 

The indoor unit installation

 

 

1. Cassette type

 

<![if ! IE]>

<![endif]>ENGLISH

Ceiling

 

 

Ceiling board

 

Level gauge

 

 

TE Series

 

600 (Ceiling opening)

 

 

39.5

521(Hanging bolt)

39.5

 

 

 

<![if ! IE]>

<![endif]>75

<![if ! IE]>

<![endif]>(Ceiling opening)

 

570 Unit size

<![if ! IE]>

<![endif]>672 (Hanging bolt)

 

<![if ! IE]>

<![endif]>Unit size

 

<![if ! IE]>

<![endif]>570

<![if ! IE]>

<![endif]>75

<![if ! IE]>

<![endif]>600

 

 

 

 

 

Unit:mm

TH/TD Series

 

875 (Ceiling opening)

 

 

45

785(Hanging bolt)

45

 

 

 

<![if ! IE]>

<![endif]>101.5

<![if ! IE]>

<![endif]>(Ceiling opening)

 

840 Unit size

<![if ! IE]>

<![endif]>672 (Hanging bolt)

 

<![if ! IE]>

<![endif]>Unit size

 

<![if ! IE]>

<![endif]>840

<![if ! IE]>

<![endif]>101.5

<![if ! IE]>

<![endif]>875

 

 

Unit:mm

TM/TN/TP Series

 

875(Ceiling opening)

 

 

 

787(Hanging bolt)

 

 

<![if ! IE]>

<![endif]>671

840 Unit size

<![if ! IE]>

<![endif]>684(Hanging bolt)

<![if ! IE]>

<![endif]>(Ceiling opening)

<![if ! IE]>

<![endif]>Unit size

 

<![if ! IE]>

<![endif]>840

 

<![if ! IE]>

<![endif]>875

 

 

Unit:mm

CAUTION :

This air-conditioner uses a drain pump.

Install the unit horizontally using a level gauge.

During the installation, care should be taken not to damage electric wires.

NOTICE

• Avoid the following installation location.

Select and mark the position for fixing bolts and piping hole.

Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.

Drill the hole for anchor bolt on the wall.

1.Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.

In these cases, take the following actions;

Make sure that ventilation fan is enough to cover all noxious gases from this place.

Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

2.Avoid installng air conditioner

in such places where

 

Air conditioner

cooking oil or iron powder is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

generated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Avoid places where

 

 

 

 

 

 

 

 

 

 

 

 

 

Take enough

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inflammable gas is generated.

 

 

 

 

distance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use the ventilation fan

 

 

 

 

 

 

 

 

 

 

4. Avoid place where noxious gas is

 

 

 

 

 

 

 

 

 

 

for smoke-collecting

 

 

 

 

 

 

 

 

 

 

hood with sufficient

generated.

 

 

 

 

 

 

 

 

 

 

capacity.

 

 

 

 

 

 

 

 

Cooking table

 

 

 

 

 

5.Avoid places near high frequency generators.

Installation Manual 9

The Indoor Unit Installation

Hanging bolt (W3/8 or M10)

Nut (W3/8 or M10)

Spring washer (M10)

 

 

 

 

 

 

 

 

 

Ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep the length of the bolt

 

 

 

 

 

Air Conditioner body

 

 

<![if ! IE]>

<![endif]>150mm

Flat washer for M10

 

 

 

 

 

 

 

 

from the bracket to 40mm

 

 

 

 

 

 

 

 

 

 

 

 

(accessory)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling board

 

 

 

 

 

 

 

 

 

Ceiling board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flat washer for M10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(accessory)

 

Paper model

Set screw of

 

 

 

 

Nut

 

 

 

 

 

 

for installation

paper model (4 pieces)

 

 

 

(W3/8 or M10)

 

Adjust the same height

Open the ceiling board

along the outer edge of the

 

 

paper model

• The following parts is option.

Hanging Bolt

- W 3/8 or M10

Nut

- W 3/8 or M10

Spring Washer - M10

Plate Washer

- M10

CAUTION: Tighten the nut and bolt to prevent unit falling.

Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.

 

Wall

Indoor

Outdoor

 

<![if ! IE]>

<![endif]>5~7mm

10 Air Conditioner

The Indoor Unit Installation

2. Duct type

CASE 1

POSITION OF SUSPENSION BOLT

-canvas between the unit and unnecessary vibration.

Accessory at air return hole.

(Unit:mm)

Dimension

 

 

 

 

 

 

 

 

 

Capacity

A

B

C

D

E

F

(G)

H

I

 

 

 

 

 

 

 

 

 

30/36k Btu/hr 1232 1182

355

45.5

450

30

87

830

186

 

 

 

 

 

 

 

 

 

 

24k Btu/h

932

880

355

45.5

450

30

87

750

163

 

 

 

 

 

 

 

 

 

 

A

<![if ! IE]>

<![endif]>ENGLISH

 

B

 

 

<![if ! IE]>

<![endif]>C E

 

<![if ! IE]>

<![endif]>D

(G)

<![if ! IE]>

<![endif]>F

<![if ! IE]>

<![endif]>I

 

H

 

Drainage hole

 

CASE 2

 

 

 

 

unit leaning to a drainage hole

 

 

 

 

figure for easy water drainage.

M10 Nut

X 4

 

 

 

 

 

 

M10 SP. washer X 4

(Local

 

 

supply)

 

 

M10 washer

X 4

 

 

POSITION OF CONSOLE BOLT

 

 

 

 

where the unit will be leveled and

M10 washer

X 4

 

 

support the weight of the unit.

(Local

 

where the unit can withstand its

M10 SP. washer X 4

 

 

M10 Nut

X 4

supply)

 

where service can be easily

 

 

 

 

 

 

 

Installation Manual

11

The Indoor Unit Installation

Select and mark the position for fixing bolts.

Drill the hole for set anchor on the face of ceiling.

Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.

Mount the suspension bolts to the set anchor firmly.

Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

CAUTION: Tighten the nut and bolt top revent unit falling.

Old building

 

New building

1

Set anchor

2

Plate washer

3

Spring washer

4

Nut

 

5 Suspension

 

bolts

 

• Local supply

 

Set anchor

 

Plate washer

- M10

Spring washer

- M10

Nut

 

- W3/8 or M10

Suspension bolt

- W3/8 or M10

12 Air Conditioner

LG UU30 INSTALLATION INSTRUCTIONS

The Indoor Unit Installation

CAUTION

1.Install declination of the indoor unit is very important for the drain of the duct type air conditioner.

2.Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view

The unit must be horizontal or declined to the drain hose connected when finished installation.

 

 

Ceiling

 

 

 

<![if ! IE]>

<![endif]>1~3mm

 

CORRECT

Drainage hole

INCORRECT

Drainage hole

 

 

<![if ! IE]>

<![endif]>ENGLISH

CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING

Lay the drain hose with a downward inclination so water will drain out.

Always lay the drain with downward inclination (1/50 to 1/100).

Prevent any upward flow or reverse flow in any part.

5mm or thicker formed thermal insulator shall always be provided for the drain pipe.

 

Thermal insulator

 

(Local supply)

 

Drainage pipe

Unit

(Local supply)

 

Make sure to be closed.

Drainage hole

• Upward routing not allowed

CORRECT

INCORRECT

Applied U-Trap Dimension

Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.

A

70mm

 

B

2C

 

 

C

2 x SP

B

SP = External Pressure

 

(mmAq)

C

Ex) External Pressure

U-Trap

 

= 10mmAq

 

A

70mm

A

 

B

40mm

 

 

C

20mm

 

Installation Manual 13

Loading...
+ 30 hidden pages