LG URNU96GB8A2 INSTALLATION MANUAL

System
Indoor Unit (2 Series)
INSTALLATION MANUAL
LG
Type: Ceiling Concealed Duct - High Static
IMPORTANT
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
ENGLISH ESPAÑOL
2 Indoor Unit
Ceiling Concealed Duct - High Static Type Indoor Unit Installation Manual
TABLE OF CONTENTS
Four type "A" screws Connecting cable
Pipes: Gas side
Liquid side (Refer to Product Data)
Insulation materialsAdditional drain pipe
Level gaugeScrew driverElectric drillHole core drill
Flaring tool setSpecified torque wrenches
(different depending on model No.)
Spanner .......Half union
A glass of waterScrew driver
Hexagonal wrenchGas-leak detectorVacuum pumpGauge manifold
Owner's manualThermometer
Features ...................................3
Safety Precautions.................4
Installation
Selection the best location ....7
Ceiling opening dimension
and hanging bolt location ......8
Indoor Unit Installation...........9
Wiring Connection .................9
Checking the Drainage........10
Installation of Remote con-
troller.....................................13
Optional Operation of Wired
Remote Controller ...............15
How to Set E.S.P? ................16
Installation Requirements
Required Parts Required Tools
Installation Manual 3
Feature
ENGLISH
Air filters
Wired Remote Controller
Air intake vents
Air outlet vents
R em
o te C
ont ro
ller
T E
M P
Features
4 Indoor Unit
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the
following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Installation
Do not use a defective or under­rated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electri­cian, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or elec­tric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated cir­cuit and breaker.
• Improper wiring or installation may cause fire or electric shock.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Installation Manual 5
Safety Precautions
ENGLISH
Operation
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air condi­tioner could fall with it, causing prop­erty damage, product failure, and personal injury.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Gasolin
6 Indoor Unit
Safety Precautions
Always check for gas (refriger­ant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away prop­erly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the out­door unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the con­denser and evaporator fins, could cause product malfunction or inefficient operation.
Installation
If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.
90˚
Installation Manual 7
Installation
ENGLISH
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
Read completely, then follow step by step.
Top view
(unit: mm)
H
Front view
600600
Front
Inspection hole
(600X600)
Control box
1000
Installation
Selection of the best location
CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt, The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
8 Indoor Unit
Installation
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as a fig­ure for easy water drainage.
• A place where the unit will be leveled and that can support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
Drainage hole
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
A
B
CD
(G)
H
I
EF
B8 Chassis
BH/BG/BR Chassis
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
NOTICE
Ceiling dimension and hanging bolt location
(Unit:mm)
ABCDEFGH I JKL
76/96k
1680 1565 1160 330 460 580 700 1400 1635 390 445 15
Dimension
Capacity(Btu/h)
(Unit:mm)
A B C D E F (G) H I
7/9/12/15/18/24k
932 882 355 47 450 30 87 750 158
28/36/42k
1232 1182 355 47 450 30 87 830 186
48k 1282 1230 477 56 590 30 120 1006 294
Dimension
Capacity(Btu/h)
Installation Manual 9
Installation
ENGLISH
• Select and mark the position for fixing bolts.
• Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspen­sion bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension bolts
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0 75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
Terminal Block Indoor
1(L) 2(N) 3 4
INDOOR POWER INPUT
IDU IDU
Outdoor unit
Indoor unit
Central controller
SODU SODU
DRY1
DRY2
GND
INTERNET
12V
Outdoor unit
Wiring Connection
Indoor Unit Installation
CAUTION : Tighten the nut and bolt to prevent unit falling.
WARNING : Make sure that the screws of the terminal are free from looseness.
,
10 Indoor Unit
Installation
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon the evaporator.
• Ensure that water flows drain hose of indoor unit without any leakage.
Checking the Drainage
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
THERMAL INSULATION
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for refrigerant pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose crip for thermal insulator(Local supply)
Union for liquid pipe
Refrigerant pipe and thermal insulator(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe (Local supply)
Hose crip for thermal insulator (Local supply)
Installation Manual 11
Installation
ENGLISH
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A 70mm B 2C C 2 x SP SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq A 70mm B 40mm C 20mm
A
Make sure to be closed.
Unit
Drainage pipe (Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Lay the drain hose with a downware inclination so water will drain out.
Front of view
• Alway lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part.
• 5mm or thicker formed thermal insulator shall always be provided for the drain pipe.
CORRECT
• Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.
Applied U-Trap Dimension
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
• The unit must be horizontal or declined to the drain hose connected when finished installation.
Drain Pump
unuse
INCORRECT
Drain Pump
use
• Upward routing not allowed